Understanding Vector Group of Transformer
Understanding Vector Group of Transformer
Introduction
Three phase transformer consists of three sets of primary windings, one for each phase, and three sets of secondary windings wound on the same iron core. Separate single-phase transformers can be used and externally interconnected to yield the same results as a 3-phase unit. The primary windings are connected in one of several ways. The two most com-
mon configurations are the delta, in which the polarity end of one winding is connected to the non-polarity end of the next, and the star, in which all three non-polarities (or polarity) ends are connected together. The secondary windings are connected similarly. This means that a 3-phase transformer can have its primary and secondary windings connected the same (delta-delta or star-star), or differently (delta-star or star-delta). Its important to remember that the secondary voltage waveforms are in phase with the primary waveforms when the primary and secondary windings are connected the same way. This condition is called no phase shift. But when the primary and secondary windings are connected differently, the secondary voltage waveforms will differ from the corresponding primary voltage waveforms by 30 electrical degrees. This is called a 30 degree phase shift. When two transformers are connected in parallel, their phase shifts must be identical; if not, a short circuit will occur when the transformers are energized.
Polarity
An AC voltage applied to a coil will induce a voltage in a second coil where the two are linked by a magnetic path. The phase relationship of the two voltages depends upon which way round the coils are connected. The voltages will either be in-phase or displaced by 180 deg. When 3 coils are used in a 3 phase transformer winding a number of options exist. The coil voltages can be in phase or displaced as above with the coils connected in star or delta and, in the case of a star winding, have the star point (neutral) brought out to an external terminal or not.
When Pair of Coil of Transformer have same direction than voltage induced in both coil are in same direction from one end to other end. When two coil have opposite winding direction than Voltage induced in both coil are in opposite direction.
Transformer has a delta connected primary winding (D) a star connected secondary (y) with the star point brought out (n) and a phase shift of 30 deg leading (11). The point of confusion is occurring in notation in a step-up transformer. As the IEC60076-1 standard has stated, the notation is HV-LV in sequence. For example, a step-up transformer with a delta-connected primary, and star-connected secondary, is not written as dY11!, but Yd11!. The 11 indicates the LV winding leads the HV by 30 degrees. Transformers built to ANSI standards usually do not have the vector group shown on their nameplate and instead a vector diagram is given to show the relationship between the primary and other windings.
placement of the vectors of other windings from the reference vector, with anticlockwise rotation, is represented by the use of clock hour figure. IS: 2026 (Part 1V)-1977 gives 26 sets of connections star-star, star-delta, and star zigzag, delta-delta, delta star, delta-zigzag, zigzag star, zigzag-delta. Displacement of the low voltage winding vector varies from zero to -330 in steps of -30, depending on the method of connections. Hardly any power system adopts such a large variety of connections. Some of the commonly used connections with phase displacement of 0, -300, -180" and 330 (clock-hour setting 0, 1, 6 and 11). Symbol for the high voltage winding comes first, followed by the symbols of windings in diminishing sequence of voltage. For example a 220/66/11 kV Transformer connected star, star and delta and vectors of 66 and 11 kV windings having phase displacement of 0 and -330 with the reference (220 kV) vector will be represented As Yy0 Yd11. The digits (0, 1, 11 etc) relate to the phase displacement between the HV and LV windings using a clock face notation. The phasor representing the HV winding is taken as reference and set at 12 oclock. Phase rotation is always anti-clockwise. (International adopted). Use the hour indicator as the indicating phase displacement angle. Because there are 12 hours on a clock, and a circle consists out of 360, each hour represents 30.Thus 1 = 30, 2 = 60, 3 = 90, 6 = 180 and 12 = 0 or 360. The minute hand is set on 12 oclock and replaces the line to neutral voltage (sometimes imaginary) of the HV winding. This position is always the reference point. Example Digit 0 =0 that the LV phasor is in phase with the HV phasor Digit 1 =30 lagging (LV lags HV with 30) because rotation is anti-clockwise. Digit 11 = 330 lagging or 30 leading (LV leads HV with 30) Digit 5 = 150 lagging (LV lags HV with 150) Digit 6 = 180 lagging (LV lags HV with 180)
When transformers are operated in parallel it is important that any phase shift is the same through each. Paralleling typically occurs when transformers are located at one site and connected to a common bus bar (banked) or located at different sites with the secondary terminals connected via distribution or transmission circuits consisting of cables and overhead lines. Phase Shift (Deg) 0 30 lag 60 lag 120 lag 150 lag 180 lag 150 lead 120 lead 60 lead 30 lead Connection Yy0 Yd1 Dd0 Dy1 Dd2 Dd4 Dy5 Dd6 Dy7 Dd8 Dd10 Dy11 Dz0 Yz1 Dz2 Dz4 Yz5 Dz6 Yz7 Dz8 Dz10 Yz11
Yd11
The phase-bushings on a three phase transformer are marked either ABC, UVW or 123 (HV-side capital, LV-side small letters). Two winding, three phase transformers can be divided into four main categories Group Group I TC delta/delta, star/star Group II 6 oclock, 180 delta/delta, star/star Group III 1 oclock, -30 star/delta, delta/star Group IV 11 oclock, star/delta, +30 delta/star Minus indicates LV lagging HV, plus indicates LV leading HV Clock Notation 0 (Phase Shift 0) Oclock 0 oclock, 0
Clock Notation 1 (Phase Shift -30) Clock Notation 2 (Phase Shift -60)
Clock Notation 2 (Phase Shift -60) Clock Notation 4 (Phase Displacement -120)
Clock Notation 4 (Phase Displacement -120) Clock Notation 5 (Phase Displacement -150)
Clock Notation 5 (Phase Displacement -150) Clock Notation 6 (Phase Shift +180)
Clock Notation 6 (Phase Shift +180) Clock Notation 7 (Phase Shift +150)
Clock Notation 7 (Phase Shift +150) Clock Notation 11 (Phase Shift +30)
To be continued