3AH3
3AH3
3AH3
03 2007
R-HG11-172.tif
Contents
Contents
Page
Description
General Construction and mode of operation, standards Ambient conditions, current carrying capacity and dielectric strength Product range overview and basic equipment
5
6 7 9 10
Equipment Selection
Ordering data and configuration example Selection of basic types, circuit-breakers Selection of secondary equipment Selection of additional equipment Accessories and spare parts
11
12 13 16 23 24
Technical Data
Electrical data, dimensions and weights Circuit diagrams Operating times, short-circuit protection of motors, consumption data of releases
29
30 38 40
Annex
Inquiry form Configuration instructions Configuration aid
41
42 43 Foldout page
Siemens AG 2007
R-HG11-173.tif
Description
Contents
Contents
Page
Description
General Construction and mode of operation: Switching medium Pole assemblies Operating mechanism box Operating mechanism Trip-free mechanism Releases Closing Circuit-breaker tripping signal Interlocking
R-HG11-174.tif
5
6
7 7 7 7 7 8 8 8 8 8 9 9 9 10 10
Standards Ambient conditions Current carrying capacity Dielectric strength Product range overview Basic equipment
Description
General
Circuit-breakers must make and break all currents within the scope of their ratings: From small inductive and capacitive load currents up to high short-circuit currents,
controlling all fault conditions in the power system at the same time.
R-HG11-060a.eps
The 3AH1 vacuum circuit-breaker is the universal circuitbreaker: It combines all system and product advantages of the 3AH series, which are decisive for most applications. With 10,000 operating cycles it covers the customary medium-voltage range from 7.2 to 24 kV and is maintenance-free throughout its entire service life. Due to its compact design, panel widths of 600 mm are possible at 12 kV. The clear layout of the operating mechanism enables fast access to all components. Therefore, retrofitting of secondary equipment is also possible. Note: The 3AH1 vacuum circuit-breaker will be discontinued by December 31, 2007. As of January 1, 2008, Siemens will offer this circuit-breaker type for another 10 years for replacement purposes only. We recommend to design new switchgear with circuit-breaker types SION or 3AH5.
The 3AH3 vacuum circuit-breaker is maintenance-free throughout its entire service life. It is extremely powerful and controls up to 10,000 operating cycles. This circuitbreaker is used for high load currents up to 6300 A and high short-circuit currents up to 72 kA as well as for rated voltages up to 36 kV. Due to its high capacity, the circuit-breaker is especially suitable for generator operation and industrial applications. Just like 3AH1, the type 3AH3 meets the requirements of medium-voltage switchgear according to IEC.
R-HG11-204.tif
Description
Construction and mode of operation
The vacuum circuit-breaker consists of the pole assemblies (1) and the operating mechanism box (2). The pole assemblies are fixed to the operating mechanism box via post insulators (3). The switching movement is transferred by means of operating rods (4) and levers. Switching medium The vacuum switching technology, proven and fully developed for more than 30 years, serves as arc-quenching principle by using vacuum interrupters. Pole assemblies The pole assemblies consist of the vacuum interrupters (6) and the interrupter supports. The vacuum interrupters are air-insulated and freely accessible. This makes it possible to clean the insulating parts easily in adverse ambient conditions. The vacuum interrupter is mounted rigidly to the upper interrupter support (5). The lower part of the interrupter is guided in the lower interrupter support (7), allowing axial movement. The braces absorb the external forces resulting from switching operations and the contact pressure.
HG11-2557 eps HG11-2556 eps
3 2 1
1
5
Operating mechanism box The whole operating mechanism with releases, auxiliary switches, indicators and actuating devices is accommodated in the operating mechanism box. The extent of the secondary equipment depends on the case of application and offers a multiple variety of options in order to meet almost every requirement. Operating mechanism The operating mechanism is a stored-energy mechanism. The closing spring is charged either electrically or manually. It latches tight at the end of the charging process and serves as an energy store. The force is transmitted from the operating mechanism to the pole assemblies via operating levers. To close the breaker, the closing spring can be unlatched either mechanically by means of the local ON pushbutton or electrically by remote control. The closing spring charges the opening or contact pressure springs as the breaker closes. The now discharged closing spring will be charged again automatically by the mechanism motor or manually. Then the operating sequence OPEN-CLOSE-OPEN is stored in the springs. The charging state of the closing spring can be checked electrically by means of a position switch. Trip-free mechanism 3AH1/3AH3 vacuum circuit-breakers have a trip-free mechanism according to IEC 62271-100. In the event of an opening command being given after a closing operation has been initiated, the moving contacts return to the open position and remain there even if the closing command is sustained. This means that the contacts of the vacuum circuit-breakers are momentarily in the closed position, which is permissible according to IEC 62271-100.
Circuit-breaker structure
Front view
R-HG11-192.tif
R-HG11-191.tif
Description
Construction and mode of operation, standards
Releases A release is a device which transfers electrical commands from an external source, such as a control room, to the latching mechanism of the vacuum circuit-breaker so that it can be opened or closed. The maximum possible equipment is one shunt release and two other releases. For release combinations, refer to page 16.
The closing solenoid unlatches the charged closing spring of the vacuum circuit-breaker, closing it by electrical means. Shunt releases are used for automatic tripping of vacuum circuit-breakers by suitable protection relays and for deliberate tripping by electrical means. They are intended for connection to an external power supply (DC or AC voltage) but, in special cases, may also be connected to a voltage transformer for manual operation. Current-transformer operated releases comprise a storedenergy mechanism, an unlatching mechanism and an electromagnetic system. They are used when there is no external source of auxiliary power (e.g. a battery). Tripping is effected by means of a protection relay (e.g. overcurrent-time protection) acting on the current-transformer operated release. Undervoltage releases comprise a stored-energy mechanism, an unlatching mechanism and an electromagnetic system which is permanently connected to the secondary or auxiliary voltage while the vacuum circuit-breaker is closed. If the voltage falls below a predetermined value, unlatching of the release is enabled and the circuit-breaker is opened via the stored-energy mechanism. The deliberate tripping of the undervoltage release generally takes place via an NC contact in the tripping circuit or via an NO contact by shortcircuiting the magnet coil. With this type of tripping, the short-circuit current is limited by the built-in resistors. Undervoltage releases can also be connected to voltage transformers. When the operating voltage drops to impermissibly low levels, the circuit-breaker is tripped automatically.
In this way, switchgear-related interlocks can also be considered for local operation in order to prevent involuntary closing. If constant CLOSE and OPEN commands are present at the vacuum circuit-breaker at the same time, the vacuum circuit-breaker will return to the open position after closing. It remains in this position until a new CLOSE command is given. In this manner, continuous closing and opening (= pumping) is prevented. Circuit-breaker tripping signal The NO contact makes brief contact while the vacuum circuit-breaker is opening, and this is often used to operate a hazard-warning system which, however, is only allowed to respond to automatic tripping of the circuit-breaker. Therefore, the signal from the NO contact must be interrupted when the circuit-breaker is being opened intentionally. This is accomplished under local control with the cut-out switch that is connected in series with the NO contact. Interlocking Electrical interlocking The circuit-breakers can be integrated in electromagnetic feeder or switchgear interlocks. In case of electrical interlocking, the disconnector or its operating mechanism is equipped with a magnetic lock-out mechanism. This mechanism is controlled by an auxiliary contact of the circuit-breaker, so that the disconnector can only be operated when the circuitbreaker is open. On the other hand, the circuit-breaker is also controlled by the disconnector or its operating mechanism, so that it can only be closed when the disconnector in an end position. For this purpose, manual electrical closing must be provided in the circuit-breaker operating mechanism (see Closing). Mechanical interlocking To interlock circuit-breaker trucks, withdrawable parts or disconnectors according to the switch position, the circuitbreakers can be equipped with a mechanical interlocking. A sensor at the switchgear checks the position of the circuitbreaker and prevents the open circuit-breaker in a reliable way from being closed mechanically and electrically. Standards 3AH1 and 3AH3 vacuum circuit-breakers conform to the following standards:
For delayed tripping, the undervoltage release can be combined with energy stores. Closing In the standard version, 3AH1/3AH3 vacuum circuit-breakers can be remote-closed electrically. They can also be closed locally by mechanical unlatching of the closing spring via pushbutton. Instead of this manual mechanical closing, manual electrical closing is also available. In this version, the closing circuit of the circuit-breaker is controlled electrically by an electrical pushbutton instead of the mechanical button.
IEC 62271-100 (former IEC 60056) IEC 60694 (in future IEC 62271-1) VDE 0671 (former VDE 0670) IEEE Std C37.013 (only generator circuit-breaker)
Description
Ambient conditions, current carrying capacity and dielectric strength
Ambient conditions The vacuum circuit-breakers are designed for the normal operating conditions defined in IEC 62271-100. Condensation can occasionally occur under the ambient conditions shown opposite. 3AH1/3AH3 vacuum circuitbreakers are suitable for use in the following climatic classes according to IEC 60721, Part 3-3: Climatic ambient conditions: Biological ambient conditions: Mechanical ambient conditions: Chemically-active substances: Mechanically-active substances:
1) Low temperature limit: 5 C 2) Without icing and wind-driven precipitation 3) Restriction: Clean insulation parts
40C
1
max. 95% per day max. 90% per month
HG11-2515a_en eps
Class 3K4 1) Class 3B1 Class 3M2 Class 3C2 2) Class 3S2 3)
-5C
Current carrying capacity The rated normal currents specified in the opposite diagram have been defined according to IEC 62271-100 for an ambient temperature of + 40 C and apply to open switchgear. For enclosed switchgear the data of the switchgear manufacturer applies. At ambient temperatures below + 40 C, higher normal currents can be carried (see diagram): Characteristics curve 1 = Rated normal current 1250 A Characteristics curve 2 = Rated normal current 2000 A Characteristics curve 3 = Rated normal current 2500 A Characteristics curve 4 = Rated normal current 3150 A Characteristics curve 5 = Rated normal current 4000 A Characteristics curve 6 = Rated normal current 5000 A Characteristics curve 7 = Rated normal current 6300 A Dielectric strength The dielectric strength of air insulation decreases with increasing altitude due to low air density. According to IEC 60694, the rated lightning impulse withstand voltage values specified in the chapter Technical Data apply to a site altitude of 1000 m above sea level. For an altitude above 1000 m, the insulation level must be corrected according to the opposite diagram.
Altitude correction factor
7000 A Rated normal current 6000 5000 4000 3000 4 2000 1000 0
HG11-2558b_en eps HG11-2517c_en eps
7 6 5
3 2 1
10
20
30
40 50 60 C 70 Ambient temperature
1.50
The characteristic shown applies to the rated short-duration power-frequency withstand voltage and the rated lightning impulse withstand voltage. To select the devices, the following applies: U W U0 x Ka
U Rated withstand voltage under standard reference atmosphere U0 Rated withstand voltage requested for the place of installation Ka Altitude correction factor according to the opposite diagram
1.40
1.30
1.20
1.10
Example For a requested rated lightning impulse withstand voltage of 75 kV at an altitude of 2500 m, an insulation level of 90 kV under standard reference atmosphere is required as a minimum: 90 kV W 75 kV x 1.2
1.00 1000 1500 2000 2500
Description
Product range overview and basic equipment
kV 7.2
kA 40 50 63 40 50 63 40 50 63 31.5 40 50 63 72 40 31.5 40
12
15
17.5
24 36
3AH11)
3AH3
1) The 3AH1 vacuum circuit-breaker will be discontinued by December 31, 2007, and will then only be available as spare circuit-breaker
Basic equipment
Features Operating mechanism Closing 1st release 2nd release 3rd release Varistor circuit Auxiliary switch Plug connector Anti-pumping Circuit-breaker tripping signal Operating cycle counter Spring charged signal and indication Interlocking Minimum equipment Electrical operating mechanism Closing solenoid and manual mechanical closing Shunt release Without Without Installed for 60 V DC 6 NO + 6 NC 24-pole terminal strip Available Available Available Available Without Alternative equipment Manual operating mechanism (hand crank included in the scope of supply) Manual electrical closing None Shunt release, undervoltage release, c.t.-operated release Undervoltage release, c.t.-operated release None 12 NO + 12 NC 24-pole plug, 64-pole plug None None None None Mechanical interlocking Remarks Hand crank also available as accessory Max. 3 releases can be combined (for possible combinations, refer to page 16) Max. 3 releases can be combined (for possible combinations, refer to page 16) For limiting switching overvoltages due to inductive loads 12 NO + 12 NC not available with 24-pole plug 24-pole plug not together with 12 NO + 12 NC
10
Equipment Selection
Contents
Contents
Page
Equipment Selection
Ordering data and configuration example Selection of basic types, circuit-breakers: Voltage level 7.2 kV Voltage level 12 kV Voltage level 15 kV Voltage level 17.5 kV Voltage level 24 kV Voltage level 36 kV High-current and generator circuit-breakers: Voltage level 17.5 kV
R-HG11-193.eps
11
12
13 13 14 14 15 15 15
Selection of secondary equipment: Release combination Operating voltage, closing solenoid Operating voltage, Operating voltage, 1st shunt release release 2nd 16 17 18 19 20 21 22 22 23 24
Operating voltage, 3rd release Operating voltage of the operating mechanism Auxiliary switch, secondary connection, interlocking Languages and frequency Selection of additional equipment Accessories and spare parts
R-HG11-194.eps
11
Equipment Selection
Ordering data and configuration example
Order number structure The vacuum circuit-breakers consist of a primary and a secondary part. The relevant data make up the 16-digit order number. The primary part covers the main electrical data of the circuit-breaker poles. The secondary part covers the auxiliary devices which are necessary for operating and controlling the vacuum circuit-breaker. Order codes Individual equipment versions, marked with 9 or Z in the 9th or 16th position, are explained more in detail by a 3-digit order code. Several order codes can be added to the order number in succession and in any sequence.
Special versions ( ) In case of special versions, -Z is added to the order number and a descriptive order code follows. If several special versions are required, the suffix -Z is listed only once. If a requested special version is not in the catalog and can therefore not be ordered via order code, it has to be identified with Y 9 9 after consultation. The agreement hereto is made between your responsible sales partner and the order processing department (PTD M C S) in our Switchgear Factory in Berlin.
2
1st position 2nd position 3rd position 4th to 8th position Primary part Superior group Switching devices Main group Circuit-breaker Subgroup Circuit-breaker type series Basic equipment Design and ratings primary part
a: alphabetical
Position: 1 2 3 4 5
n: numerical
6 7 8 9 10 11 12 13 14 15 16 Order codes
Order No.:
3 A H n
Secondary part Secondary equipment Operating mechanism, releases, operating voltages and further auxiliary equipment Order codes Group of 3 after the Order No. Format: a n a Special versions ( ) Initiated with -Z Group of 3 after the Order No. Format: a n n
Configuration example In order to simplify the selection of the correct order number for the requested circuit-breaker type, you will find a configuration example on each side of the chapter Equipment Selection. For the selection of the secondary part, always the last example of the primary part was taken over and continued, so that at the end of the equipment selection (page 23) a completely configured circuit-breaker results as an example.
On the foldout page we offer a configuring aid. Here you can fill in the order number you have determined for your circuit-breaker.
3 A H 3
12
Equipment Selection
Selection of basic types, circuit-breakers
7.2 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance
Position:
10 11 12
13 14 15 16
Order codes
3 A H
Rated voltage
See page 16
See page 17
See page 18
See page 19
See page 20
See page 21
See page 22
See page 22
Ur kV 7.2
Up kV 60
Ud kV 20
Isc kA 40
Ir A 1250 2000 2500 3150 1250 2500 3150 4000 1) 1250 2500 3150 4000 1) 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A H H H H H H H H H H H H 1 1 1 1 3 3 3 3 3 3 3 3 0 0 0 0 0 0 0 0 0 0 0 0 5 5 5 5 5 5 5 7 7 7 7 7 6 6 6 6 7 7 7 7 8 8 8 8 2 4 6 7 2 6 7 8 2 6 7 8 Z E 1 6
50
125/130
210
See page 23
63
160/164
275 275
12 kV
50/60 Hz Ur kV 12 Up kV 75 Ud kV 28 Isc kA 40 Ima kA 100/104 mm 210 Ir A 1250 2000 2500 3150 1250 2500 3150 4000 1) 1250 2500 3150 4000 1) 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A H H H H H H H H H H H H 1 1 1 1 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 6 6 6 6 7 7 7 7 8 8 8 8 2 4 6 7 2 6 7 8 2 6 7 8 Z Z E Y 1 0 3 3
50
125/130
210
63
160/164
275 275
Special versions Ud = 42 kV (not for 3AH1 116-. circuit-breaker) Isc = 57.8 kA Ima = 145 kA (for 3AH3 117-. circuit-breaker) 1) With the supplement -Z Y04, the circuit-breaker can also be used for Ir = 4500 A under the following conditions: Ambient air temperature 40 C, free air circulation and painted conductor bars of 4 x 100 x 10 mm per phase as a minimum
Configuration example Vacuum circuit-breaker Rated voltage Ur = 12 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 75 kV Rated short-circuit breaking current Isc = 50 kA Pole-center distance = 210 mm Rated normal current Ir = 1250 A Example for Order No.: Order codes:
3 A H
3 3 A H 3
1 1
1 1
7 7
2 2
13
Equipment Selection
Selection of basic types, circuit-breakers
15 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance
Position:
10 11 12
13 14 15 16
Order codes
3 A H
Rated voltage
See page 16
See page 17
See page 18
See page 19
See page 20
See page 21
See page 22
See page 22
Ur kV 15
Up kV 95
Ud kV 36
Isc kA 40
Ir A 1250 2000 2500 3150 1250 2500 3150 4000 1) 1250 2500 3150 4000 1) 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A H H H H H H H H H H H H 1 1 1 1 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 6 6 6 6 6 6 6 7 7 7 7 7 6 6 6 6 7 7 7 7 8 8 8 8 2 4 6 7 2 6 7 8 2 6 7 8 Z E 1 3
50
125/130
210
2
63 160/164 Special version (available for all 15 kV circuit-breakers) Ud = 42 kV
275 275
17.5 kV
50/60 Hz Ur kV 17.5 Up kV 95 Ud kV 38 Isc kA 31.5 40 Ima kA 80/82 100/104 mm 210 210 Ir A 3150 1250 2000 2500 3150 1250 2500 3150 4000 1) 1250 2500 3150 4000 1) 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A H H H H H H H H H H H H H 1 1 1 1 1 3 3 3 3 3 3 3 3 2 2 2 2 2 2 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1 2 2 2 2 2 5 6 6 6 6 7 7 7 7 8 8 8 8 7 2 4 6 7 2 6 7 8 2 6 7 8
50
125/130
210
63
160/164
275 275
Special version (available for all 17.5 kV circuit-breakers) Ud = 42 kV 1) With the supplement -Z Y04, the circuit-breaker can also be used for Ir = 4500 A under the following conditions: Ambient air temperature 40 C, free air circulation and painted conductor bars of 4 x 100 x 10 mm per phase as a minimum Configuration example Vacuum circuit-breaker Rated voltage Ur = 17.5 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 95 kV Rated short-circuit breaking current Isc = 63 kA Pole-center distance = 275 mm Rated normal current Ir = 4000 A Example for Order No.: Order codes:
See page 23 Z E
3 A H
3 3 A H 3
2 2
2 2
8 8
8 8
14
Equipment Selection
Selection of basic types, circuit-breakers
24 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance
Position:
10 11 12
13 14 15 16
Order codes
3 A H
Rated voltage
See page 16
See page 17
See page 18
See page 19
See page 20
See page 21
See page 22
See page 22
Ur kV 24
Up kV 125
Ud kV 50
Isc kA 40
Ir A 2500 3 A H 3 2 6 6 6
36 kV
50/60 Hz Ur kV 36 Up kV 170 Ud kV 70 Isc kA 31.5 Ima kA 80/82 mm 350 Ir A 1250 2000 2500 2500 3 3 3 3 A A A A H H H H 3 3 3 3 3 3 3 3 0 0 0 0 5 5 5 6 2 4 6 6 Z E + E Z E + E 1 1 2 2 4 5 4 5
See page 23
40 100/104 350 Special versions (available for all 36 kV circuit-breakers): Up = 185 kV (only possible together) and Ud = 85 kV Up = 195 kV (only possible together) and Ud = 95 kV
17.5 kV
50/60 Hz/generator circuit-breaker acc. to IEEE Std C37.013 Ur kV 17.5 Up kV 110 Ud kV 50 Isc kA 50 Ima kA 137 mm 275 300 63 173 275 300 72 198 275 300 1) With the supplement -Z Y04, the circuit-breaker can also be used for Ir = 4500 A under the following conditions: Ambient air temperature 40 C, free air circulation and painted conductor bars of 4 x 100 x 10 mm per phase as a minimum 2) Higher rated normal currents on request Configuration example Vacuum circuit-breaker Rated voltage Ur = 36 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 170 kV Rated short-circuit breaking current Isc = 40 kA Pole-center distance = 350 mm Rated normal current Ir = 2500 A Example for Order No.: Order codes: 3 A H Ir A 3150 4000 5000 6300 2) 3150 4000 1) 5000 6300 2) 3150 4000 1) 5000 6300 2) 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A H H H H H H H H H H H H 3 3 3 3 3 3 3 3 3 3 3 3 8 8 7 7 8 8 7 7 8 8 7 7 1 1 1 1 1 1 1 1 1 1 1 1 7 7 2 2 8 8 3 3 9 9 4 4 7 8 4 5 7 8 4 5 7 8 4 5
G 1 G 1
A A
3 3 A H 3
3 3
0 0
6 6
6 6
15
Equipment Selection
Selection of secondary equipment
Position:
10 11 12
13 14 15 16
Order codes
Order No.:
3 A H
Closing solenoid
See page 17
See page 18
See page 19
See page 20
See page 21
See page 22
See page 22
M N T P P R S S U U V V
See page 23 Z A
Z Z Z
A A A
4 4 4
6 6 5
Configuration example Vacuum circuit-breaker (Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A, pole-center distance = 350 mm) Closing solenoid, 1st shunt release, undervoltage release and c.t.-operated release with a rated normal current of 1 A Example for Order No.: Order codes:
3 A H 3 3 0 6 6 S 3 A H 3 A 4 6 3 0 6 6 S Z Z A 4 6
16
Equipment Selection
Selection of secondary equipment
Position:
10 11 12
13 14 15 16
Order codes
Order No.:
3 A H
See page 23 K K K K K K K K K
Standard voltages
Special voltages
Mechanical closing at the circuit-breaker 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50/60 Hz 1) 110 V AC 50/60 Hz 1) 230 V AC 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC Manual electrical closing at the circuit-breaker 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50/60 Hz 1) 110 V AC 50/60 Hz 1) 230 V AC 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC
B C D E F H J K Z Z Z Z Z Z Z Z Z M N P Q R T U V Z Z Z Z Z Z Z Z Z
With order code With order code With order code With order code With order code With order code With order code With order code With order code
1 A 1 B 1 C 1 D 1 E 1 F 1 K 1 L 1 M
With order code With order code With order code With order code With order code With order code With order code With order code With order code
K K K K K K K K K
2 A 2 B 2 C 2 D 2 E 2 F 2 K 2 L 2 M
1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 22)
Configuration example Vacuum circuit-breaker (Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A, pole-center distance = 350 mm) Manual electrical closing at the circuit-breaker, operating voltage of the closing solenoid 32 V DC Example for Order No.: Order codes:
17
Equipment Selection
Selection of secondary equipment
Position:
10 11 12
13 14 15 16
Order codes
Order No.:
3 A H
See page 19
See page 23 L L L L L L L L L
Standard voltages
Special voltages
50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC
1 2 3 4 5 6 7 8 9 9 9 9 9 9 9 9 9
With order code With order code With order code With order code With order code With order code With order code With order code With order code
1 A 1 B 1 C 1 D 1 E 1 F 1 K 1 L 1 M
1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 22)
Configuration example Vacuum circuit-breaker (Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A, pole-center distance = 350 mm) Operating voltage of the 1st shunt release 48 V DC Example for Order No.: Order codes:
3 A H 3 3 0 6 6 S Z 2 3 A H 3 A 4 6 + 3 K 0 2 6 B 6 S Z 2 Z
18
Equipment Selection
Selection of secondary equipment
12th position Position: Operating voltage of the 2nd release Order No.: Shunt release, undervoltage release or c.t.-operated release
10 11 12
13 14 15 16
Order codes
3 A H
See page 23 M M M M M M M M M
Standard voltages
Special voltages
Without or c.t.-operated release 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50/60 Hz 1) 110 V AC 50/60 Hz 1) 230 V AC 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC
0 1 2 3 4 5 6 7 8 9 9 9 9 9 9 9 9 9
With order code With order code With order code With order code With order code With order code With order code With order code With order code
1 A 1 B 1 C 1 D 1 E 1 F 1 K 1 L 1 M
Special versions To operate the 2nd release as an undervoltage release on an energy store type AN 1902- (for DC) or AN 1901-2 (for AC), both make Bender, the operating voltage must be defined and whether the energy store will be provided by the customer or included in the scope of supply. Energy store Type 60 V DC 110 V DC 220 V DC 100/110/230 V AC 60 V DC 110 V DC 220 V DC 100/110/230 V AC AN 1902AN 1902AN 1902AN 1901-2 AN 1902AN 1902AN 1902AN 1901-2
9 9 9 9 9 9 9 9
With order code With order code With order code With order code With order code With order code With order code With order code
M M M M M M M M
2 D 2 E 2 F 2 G 3 D 3 E 3 F 3 G
1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 22)
Configuration example Vacuum circuit-breaker (Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A, pole-center distance = 350 mm) 2nd release as undervoltage release with operating voltage 32 V DC Example for Order No.: Order codes:
+ M 1
19
Equipment Selection
Selection of secondary equipment
13th position Operating voltage of the 3rd release Undervoltage release or c.t.-operated release
Position:
10 11 12
13 14 15 16
Order codes
Order No.:
3 A H
See page 23 N N N N N N N N N
Standard voltages
Special voltages
Without or c.t.-operated release 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50/60 Hz 1) 110 V AC 50/60 Hz 1) 230 V AC 50/60 Hz 1)
0 1 2 3 4 5 6 7 8 9 9 9 9 9 9 9 9 9
With order code With order code With order code With order code With order code With order code With order code With order code With order code
1 A 1 B 1 C 1 D 1 E 1 F 1 K 1 L 1 M
Special versions To operate the 3rd release as an undervoltage release on an energy store type AN 1902- (for DC) or AN 1901-2 (for AC), both make Bender, the operating voltage must be defined and whether the energy store will be provided by the customer or included in the scope of supply. Energy store Type 60 V DC 110 V DC 220 V DC 100/110/230 V AC 60 V DC 110 V DC 220 V DC 100/110/230 V AC AN 1902AN 1902AN 1902AN 1901-2 AN 1902AN 1902AN 1902AN 1901-2
9 9 9 9 9 9 9 9
With order code With order code With order code With order code With order code With order code With order code With order code
N N N N N N N N
2 D 2 E 2 F 2 G 3 D 3 E 3 F 3 G
1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 22)
Configuration example Vacuum circuit-breaker (Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A, pole-center distance = 350 mm) 3rd release as c.t.-operated release Example for Order No.: Order codes:
3 A H 3 3 0 6 6 S Z 2 9 0 3 A H 3 A 4 6 + 3 K 0 2 6 B 6 S Z B 2 9 0 Z
+ M 1
20
Equipment Selection
Selection of secondary equipment
Position:
10 11 12
13 14 15 16
Order codes
Order No.:
3 A H
See page 23 P P P P P P P P P
Standard voltages
Special voltages
Manual operating mechanism (hand crank included in the scope of supply) 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50/60 Hz 1) 110 V AC 50/60 Hz 1) 230 V AC 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 50/60 Hz 1) 125 V AC 50/60 Hz 1) 240 V AC 50/60 Hz 1) 1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 22)
A B C D E F H J K Z Z Z Z Z Z Z Z Z
With order code With order code With order code With order code With order code With order code With order code With order code With order code
1 A 1 B 1 C 1 D 1 E 1 F 1 K 1 L 1 M
Configuration example Vacuum circuit-breaker (Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A, pole-center distance = 350 mm) Operating voltage of the operating mechanism 230 V AC, 50 Hz Example for Order No.: Order codes:
+ M 1
21
Equipment Selection
Selection of secondary equipment
15th position Position: Auxiliary switch, secondary connection, interlocking Order No.:
10 11 12
13 14 15 16
Order codes
3 A H
Auxiliary switch 6 NO + 6 NC
Auxiliary switch 12 NO + 12 NC
64-pole plug 1)
24-pole plug
Mechanical interlocking
A E G C M B F H D N Special versions gold-plated contacts and pins Auxiliary switch 6 NO + 6 NC and 24-pole terminal strip (G or H) Auxiliary switch 12 NO + 12 NC and 24-pole terminal strip (M or N) Auxiliary switch 6 NO + 6 NC and 64-pole plug (A or B) Auxiliary switch 12 NO + 12 NC and 64-pole plug (C or D) 1) Depending on the equipment, some connections of the 64-pole plug connector remain free. These can be connected to free auxiliary switch contacts by the customer. Prefabricated wires are available as accessories. 2) Auxiliary switch contacts are not wired to the terminal strip and must therefore be connected directly. Z Z Z Z A A A A 1 1 2 2 7 8 0 1
16th position AC frequency of operating voltages and languages of operating instructions and rating plate
Language
Frequency
50 Hz or DC 60 Hz 50 Hz or DC 60 Hz 50 Hz or DC 60 Hz 50 Hz or DC 60 Hz
0 1 2 3 4 5 6 7
Other languages on request Special versions Additional information on the rating plate (only after consultation with Dept. PTD M C S, Berlin). Information in clear text.
See page 23 Z Y
Configuration example Vacuum circuit-breaker (Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A, pole-center distance = 350 mm) Auxiliary switch 6 NO + 6 NC, 64-pole plug and with mechanical interlocking Auxiliary switch contacts and pins of the plug connector gold-plated Frequency 50 Hz or DC, operating instructions and rating plate in English Example for Order No.: Order codes:
3 A H 3 3 0 6 6 S Z 2 9 0 K B 2 3 A H 3 A 4 6 + 3 K 0 2 6 B 6 S Z B 2 + 9 A 2 0 0 K B 2 Z Z A 2 0
+ M 1
22
Equipment Selection
Selection of additional equipment
Additional equipment
Position:
10 11 12
13 14 15 16
Order codes
Order No.:
3 A H
Options
Wiring cables, halogen-free and flame-retardant Condensation protection, heating for 230 V AC, 50 W Silicone-free design Vacuum circuit-breaker for horizontal installation (only for 3AH3 standard circuit-breakers) Additional rating plate, loose delivery Primary conductor bars silver-plated for external connections and internal interconnection on both sides (standard for 4000 A circuit-breakers and type 3AH381) Routine test certificate enclosed Hand crank (also for motor operating mechanism) for manual charging of the closing spring Circuit-breaker can also be used for 4500 A (applicable to circuit-breaker types 3AH3077-8, 3AH3078-8, 3AH3127-8, 3AH3128-8, 3AH3177-8, 3AH3178-8, 3AH3227-8, 3AH3228-8, 3AH3818-8, 3AH3819-8) Further, non-listed special versions (only after consultation with Dept. PTD M C S, Berlin). Information additionally in clear text.
Z Z Z Z Z Z Z Z Z Z
A A A A B D F F Y Y
1 3 3 7 0 1 2 3 0 9
0 0 1 0 0 0 0 0 4 9
Configuration example Vacuum circuit-breaker Rated voltage Ur = 36 kV (50/60 Hz) Rated lightning impulse withstand voltage Up = 170 kV Rated short-circuit breaking current Isc = 40 kA Pole-center distance = 350 mm Rated normal current Ir = 2500 A Closing solenoid, 1st shunt release, undervoltage release and c.t.-operated release with a rated normal current of 1 A Manual electrical closing at the circuit-breaker, operating voltage of the closing solenoid 32 V DC Operating voltage of the 1st release 48 V DC 2nd release as undervoltage release with operating voltage 32 V DC 3rd release as c.t.-operated release Operating voltage of the operating mechanism 230 V AC, 50 Hz Auxiliary switch 6 NO + 6 NC, 64-pole plug and with mechanical interlocking Auxiliary switch contacts and pins of the plug connector gold-plated Frequency 50 Hz or DC, operating instructions and rating plate in English Routine test certificate enclosed Example for Order No.: Order codes:
3 A H
6 S Z 2 9 0 K B 2 Z Z F 2 0 Z A 2 0 M 1 B Z A K 4 2 6 B
3 A H 3 A 4 6 +
3 K
0 2
6 B
Z B
2 +
9 A
0 0
K +
B F
2 2
+ M 1
23
Equipment Selection
Accessories and spare parts
Retrofitting When releases/solenoids are retrofitted, the order numbers of the mounting parts must also be specified. For other additional equipment, the required mounting parts are included in the delivery. Spare parts When releases/solenoids are required as spare parts, the order number and the type of construction of the associated standard circuit-breaker must also be specified. Remark for orders The order numbers are applicable to standard circuitbreakers of current manufacture. When mounting parts or spare parts are being ordered for an existing standard circuit-breaker, always quote the type designation, serial number, design code and the year of manufacture of the circuit-breaker to be sure to get the correct delivery.
Accessories for the plug connector Included in the scope of supply of the basic equipment for standard circuit-breakers: For 24-pole plug connector Lower part of plug Crimp sockets according to number of contacts Upper part of plug with screwed contacts (no crimp sockets required) For 64-pole plug connector Lower part of plug Upper part of plug Crimp sockets according to number of contacts Vacuum interrupters and other spare parts must only be replaced by instructed personnel.
Designation
Remarks
Operating voltage
Order No.
3AX15 30-2B (for special application conditions) 180 g Klber-Isoflex Topas L32N 1 kg Klber-Isoflex Topas L32N 1 kg Shell Tellus oil 32 (special oil) Used as closing solenoid or 1st shunt release From 60 V DC with integrated varistor From rated voltage 110 V with integrated rectifier and varistor for operation with AC or DC voltage 3AX11 33-3H 3AX11 33-3E 3AX11 33-2D 3AY15 10-5B 3AY15 10-5M 3AY15 10-5C 3AY15 10-5D 3AY15 10-5E 3AY15 10-5N 3AY15 10-5F 3AX11 01-2B 3AX11 01-2C 3AX11 01-2E 3AX11 01-2F 3AX11 01-2G 3AX11 01-2J 3AX11 01-3G 3AX11 01-3J 3AX11 02-2A 3AX11 02-2B 3AX11 04-0B 3AX11 04-2B
Operating solenoid
24 V DC 30/32 V DC 48 V DC 60 V DC 110 V AC/DC 125 V AC/DC 220 V AC/DC 24 V 32 V DC 48 V 60 V DC 110 V 127 V DC 220 V 240 V DC 100 V 125 V AC, 50 Hz 230 V 240 V AC, 50 Hz 100 V 125 V AC, 60 Hz 230 V 240 V AC, 60 Hz
Rated normal current 0.5 A , including varistor and rectifier Rated normal current 1 A, including varistor and rectifier Tripping pulse 0.1 Ws (10 c), for protection relay 7SJ41 Tripping pulse 0.1 Ws (20 c), for protection relay 7SJ45 and SEG WIP1
24
Equipment Selection
Accessories and spare parts
Designation
Remarks
Operating voltage
Order No.
Undervoltage release
Mounting parts
Digital, c.t.-operated overcurrent-time relay make SEG Drive motor For 3AH1
24 V DC 30/32 V DC 48 V DC Including varistor 60 V DC 110 V DC 120 V 127 V DC 220 V DC 240 V DC Including varistor and rectifier 100 V AC, 50 Hz 110 V 125 V AC, 50 Hz 230 V AC, 50 Hz 100 V AC, 60 Hz 110 V 125 V AC, 60 Hz 230 V AC, 60 Hz In combination with energy store AN 1902-, 60 V DC specified voltage corresponds to the input voltage 110 V DC of the energy store 220 V DC In combination with energy store AN 1901-2, 100 V AC, 50/60 Hz specified voltage corresponds to the input voltage 110 V AC, 50/60 Hz of the energy store 230 V AC, 50/60 Hz For 2nd shunt release or c.t.-operated release or undervoltage release With 1 existing shunt release For 3AH1 For 3AH3 With 2 existing releases (shunt release, For 3AH1 c.t.-operated release or undervoltage release) For 3AH3 For 3AH1 For 3AH3 With 2 varistors For delayed tripping of the undervoltage release Type AN 1901-2B, Input voltage with dropout delay of approx. 1/1.8/2.5 s 100/110/230 V AC, 50/60 Hz, output voltage 220 V DC Type AN 1902-1B, Input and output voltage with dropout delay of approx. 0.5/0.9/1.5 s 220 V DC Type AN 1902-2B, Input and output voltage with dropout delay of approx. 0.5/0.9/1.5 s 110 V DC Type AN 1902-3B, Input and output voltage with dropout delay of approx. 0.5/0.9/1.5 s 60 V DC As release Type WIP1 For overcurrent For earth fault 24/30/32 V DC 48 V DC 60 V DC 100/110/126 V AC/DC 220 V DC/230 V AC 24/30/32 V DC 48 V DC 60 V DC 100/110/126 V AC/DC 220 V DC/230 V AC 100 V 250 V AC
3AX11 03-2B 3AX11 03-2L 3AX11 03-2C 3AX11 03-2D 3AX11 03-2E 3AX11 03-2N 3AX11 03-2F 3AX11 03-2P 3AX11 03-2G 3AX11 03-2H 3AX11 03-2J 3AX11 03-3G 3AX11 03-3H 3AX11 03-3J 3AX11 03-2D 3AX11 03-2E 3AX11 03-2F 3AX11 03-3K 3AX11 03-3K 3AX11 03-3K 3AX17 11-2A 3AX17 11-3A 3AX17 11-2B 3AX17 11-3B 3AX17 20-2A 3AX15 20-3C 3AX15 26-0F
3AX11 35-1A 3AX11 35-1B 3AY17 11-2B 3AY17 11-2C 3AY17 11-2D 3AY17 11-2E 3AY17 11-2F 3AY15 11-2B 3AY15 11-2C 3AY15 11-2D 3AY15 11-2E 3AY15 11-2F 3AX15 25-1F
From 60 V DC with integrated varistor For AC, rectifier required For 3AH3 From 60 V DC with integrated varistor For AC, rectifier required Rectifier module For drive motor with AC operation
25
Equipment Selection
Accessories and spare parts
Designation
Remarks
Operating voltage
Order No.
Auxiliary contactor
24/30/32 V DC 48 V DC 60 V DC 110/120 V DC 125 V DC 220 V 240 V DC 100 V 125 V AC, 50 Hz 230 V 240 V AC, 50 Hz 100 V 125 V AC, 60 Hz 230 V 240 V AC, 60 Hz Nos. 1 2 1 2 1
SWB: 48683 SWB: 48687 SWB: 48684 SWB: 48685 SWB: 47730 SWB: 48686 SWB: 48680 SWB: 49906 SWB: 48679 SWB: 49907 SWB: 46677
Position switch
2
Auxiliary switch (-S1) Wire bundle Accessories for plug connector
Type 3SE4 (as spare part), without installation accessories Used for: Electrical anti-pumping (-S3) Motor control (-S21, -S22) Closing spring charged (-S4) Circuit-breaker tripping signal (-S6, -S7) Electrical closing lock-out (-S5) 6 NO + 6 NC 12 NO + 12 NC With 10 wires for connection of auxiliary switch to 64-pole plug connector 24-pole plug connector 24-pole terminal strip (for wire cross-section 1.5 mm2) Crimp pins for lower part of plug 24-pole 64-pole Crimp sockets for upper part of plug 64-pole Crimping pliers Disassembly tool
3SV92 73-2AA0 3SV92 74-2AA0 3AX11 34-4F 3AX11 34-2B 3AX11 34-2C 3AX11 34-3A 3AX11 34-4B 3AX11 34-4C 3AX11 34-4D 3AX11 34-4G
26
Equipment Selection
Accessories and spare parts
Designation
Remarks
Design code
For 3AH1 circuit-breakers 3AH1 056- , 3AH1 116- , 3AH1 166- , 3AH1 215- , 3AH1 216For 3AH3 circuit-breakers 3AH3 057- , 3AH3 117- , 3AH3 167- , 3AH3 2173AH3 078-2, 3AH3 078-6, 3AH3 078-7, 3AH3 128-2, 3AH3 128-6, 3AH3 128-7, 3AH3 178-2, 3AH3 178-6, 3AH3 178-7, 3AH3 228-2, 3AH3 228-6, 3AH3 228-7 3AH3 078-8, 3AH3 128-8, 3AH3 178-8, 3AH3 228-8 3AH3 266-6 3AH3 3053AH3 3063AH3 71 3AH3 818-7 3AH3 818-8 3AH3 818-7 3AH3 818-8 1J 1J 1J 2M 1L 1M 3P 1N 1N 1F 1F 3AY17 15-1J 3AY17 15-1J 3AY17 15-4J 3AY17 15-2M 3AY17 15-1L 3AY17 15-1M 3AY17 15-1N 3AY17 15-2N 3AY17 15-1P 3AY17 15-2P 1G 3AY17 12-1F
As spare parts, the vacuum interrupters are always supplied with adapter. To select the correct spare interrupter, please specify the type designation, serial number, design code and year of manufacture of the circuit-breaker. All data is given on the rating plate. Vacuum interrupters and other spare parts must only be replaced by instructed personnel.
Data on the rating plate Note: For any query regarding spare parts, subsequent deliveries, etc. the following four details are necessary: Type designation Serial No. Design code Year of manufacture
HG11-2588b_en eps
27
28
R-HG11-205.tif
Technical Data
Contents
Contents
Page
Technical Data
Electrical data, dimensions and weights: Voltage level 7.2 kV Voltage level 12 kV Voltage level 15 kV Voltage level 17.5 kV Voltage level 24 kV Voltage level 36 kV Electrical data, dimensions and weights of high-current and generator circuit-breakers Circuit diagrams
R-HG11-196.tif
29
30 30 32 32 34 34
36 38 40 40 40
Vacuum interrupter
R-HG11-197.tif
29
Technical Data
Electrical data, dimensions and weights
7.2 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO
Ir A 3AH1 056-2 3AH1 056-4 3AH1 056-6 3AH1 056-7 3AH3 057-2 3AH3 057-6 3AH3 057-7 3AH3 077-8 mm
tk s 3 3 3 3 3 3 3 3 3 3 3 3
Isc kA 40 40 40 40 50 50 50 50 63 63 63 63 % 36 36 36 36 36 36 36 36 36 36 36 36 kA 44.9 44.9 44.9 44.9 56.1 56.1 56.1 56.1 70.7 70.7 70.7 70.7
Ima kA 100/ 104 100/ 104 100/ 104 100/ 104 125/ 130 125/ 130 125/ 130 125/ 130 160/ 164 160/ 164 160/ 164 160/ 164
Up kV 60 60 60 60 60 60 60 60 60 60 60 60
Ud kV 20 20 20 20 20 20 20 20 20 20 20 20 mV 2.0 1.8 1.5 1.5 1.8 1.8 1.8 1.4 1.8 1.8 1.8 1.4 mm mm mm mm 140 170 140 170 140 170 140 170 160 230 160 230 160 230 160 170 160 170 160 170 160 170 160 170 92 92 92 92 80 80 80 71 71 71 71 71 130 130 130 130 130 130 130 130 130 130 130 130 kg 125 125 130 130 180 180 180 308 196 196 196 308 3M 425 00389 3M 425 00388 3M 425 00375 3M 425 00375 3M 325 00001 3M 325 00001 3M 325 00001 3M 325 00004 3M 325 00003 3M 325 00003 3M 325 00003 3M 325 00004 1 1 1 1 2 2 2 2 3 3 3 3 1 1 1 1 2 2 2 4 3 3 3 4
1250 210 2000 210 2500 210 3150 210 1250 210 2500 210 3150 210 4000 275 1250 275 2500 275 3150 275 4000 275
12 kV
50/60 Hz 3AH1 116-2 3AH1 116-4 3AH1 116-6 3AH1 116-7 3AH3 117-2 3AH3 117-6 3AH3 117-7 3AH3 127-8 3AH3 128-2 3AH3 128-6 3AH3 128-7 3AH3 128-8
Ir A mm
tk s 3 3 3 3 3 3 3 3 3 3 3 3
Isc kA 40 40 40 40 50 50 50 50 63 63 63 63 % 36 36 36 36 36 36 36 36 36 36 36 36 kA 44.9 44.9 44.9 44.9 56.1 56.1 56.1 56.1 70.7 70.7 70.7 70.7
Ima kA 100/ 104 100/ 104 100/ 104 100/ 104 125/ 130 125/ 130 125/ 130 125/ 130 160/ 164 160/ 164 160/ 164 160/ 164
Up kV 75 75 75 75 75 75 75 75 75 75 75 75
Ud kV 28 28 28 28 28 28 28 28 28 28 28 28 mV 2.0 1.8 1.5 1.5 1.8 1.8 1.8 1.4 1.8 1.8 1.8 1.4 mm mm mm mm 140 170 140 170 140 170 140 170 160 230 160 230 160 230 160 170 160 170 160 170 160 170 160 170 92 92 92 92 80 80 80 71 71 71 71 71 130 130 130 130 130 130 130 130 130 130 130 130 kg 125 125 130 130 180 180 180 308 196 196 196 308 3M 425 00389 3M 425 00388 3M 425 00375 3M 425 00375 3M 325 00001 3M 325 00001 3M 325 00001 3M 325 00004 3M 325 00003 3M 325 00003 3M 325 00003 3M 325 00004 1 1 1 1 2 2 2 2 3 3 3 3 1 1 1 1 2 2 2 4 3 3 3 4
1250 210 2000 210 2500 210 3150 210 1250 210 2500 210 3150 210 4000 275 1250 275 2500 275 3150 275 4000 275
30
O - 0.3 s - CO- 15 s - CO
Pole-center distance
Order No.
Weights
Technical Data
Electrical data, dimensions and weights
20 000
Operating cycles
Operating cycles
is shown as a function of the breaking current (r.m.s. value). All vacuum circuit-breakers fulfil the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve shape beyond the parameters defined in IEC 62271-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application.
50 20 10 1 2 5 1
20 10 1 2 5
100
3
HG11-2560 eps
211 668
HG11-2559 eps
109
550/565 1)
604
70
571
610
Dimension drawing 1
1) from Ir = 2500 A
591 275 105 680 275
Dimension drawing 2
750 275
211 733
HG11-2561 eps
105
170
601
776
694
776
Dimension drawing 3
Dimension drawing 4
HG11-2562 eps
31
Technical Data
Electrical data, dimensions and weights
15 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO
Ir A 3AH1 166-2 3AH1 166-4 3AH1 166-6 3AH1 166-7 3AH3 167-2 3AH3 167-6 3AH3 167-7 3AH3 177-8 mm
tk s 3 3 3 3 3 3 3 3 3 3 3 3 tk mm s 3 3 3 3 3 3 3 3 3 3 3 3 3
Isc kA 40 40 40 40 50 50 50 50 63 63 63 63 Isc kA 31.5 40 40 40 40 50 50 50 50 63 63 63 63 % 36 36 36 36 36 36 36 36 36 36 36 36 36 kA 35.4 44.9 44.9 44.9 44.9 56.1 56.1 56.1 56.1 70.7 70.7 70.7 70.7 % 36 36 36 36 36 36 36 36 36 36 36 36 kA 44.9 44.9 44.9 44.9 56.1 56.1 56.1 56.1 70.7 70.7 70.7 70.7
Ima kA 100/ 104 100/ 104 100/ 104 100/ 104 125/ 130 125/ 130 125/ 130 125/ 130 160/ 164 160/ 164 160/ 164 160/ 164 Ima kA 80/ 82 100/ 104 100/ 104 100/ 104 100/ 104 125/ 130 125/ 130 125/ 130 125/ 130 160/ 163.8 160/ 163.8 160/ 163.8 160/ 163.8
Up kV 95 95 95 95 95 95 95 95 95 95 95 95 Up kV 95 95 95 95 95 95 95 95 95 95 95 95 95
Ud kV 36 36 36 36 36 36 36 36 36 36 36 36 Ud kV 38 38 38 38 38 38 38 38 38 38 38 38 38 mV 1.5 2.0 1.8 1.5 1.5 1.8 1.8 1.8 1.4 1.8 1.8 1.8 1.4 mm mm mm mm 140 170 140 170 140 170 140 170 140 170 90 90 90 90 90 130 130 130 130 130 kg 135 130 130 135 135 184 184 184 310 198 198 198 310 3M 425 00378 3M 425 00387 3M 425 00380 3M 425 00378 3M 425 00378 3M 325 00002 3M 325 00002 3M 325 00002 3M 325 00006 3M 325 00005 3M 325 00005 3M 325 00005 3M 325 00006 7 4 4 4 4 8 8 8 8 9 9 9 9 5 5 5 5 5 6 6 6 8 7 7 7 8 mV 2.0 1.8 1.5 1.5 1.8 1.8 1.8 1.4 1.8 1.8 1.8 1.4 mm mm mm mm 140 170 140 170 140 170 140 170 90 90 90 90 130 130 130 130 kg 130 130 135 135 184 184 184 310 196 196 196 308 3M 425 00387 3M 425 00380 3M 425 00378 3M 425 00378 3M 325 00002 3M 325 00002 3M 325 00002 3M 325 00006 3M 325 00003 3M 325 00003 3M 325 00003 3M 325 00004 4 4 4 4 5 5 5 5 6 6 6 6 5 5 5 5 6 6 6 8 7 7 7 8
1250 210 2000 210 2500 210 3150 210 1250 210 2500 210 3150 210 4000 275 1250 275 2500 275 3150 275 4000 275 Ir A
160 230 110 130 160 230 110 130 160 230 110 130 160 170 135 130 160 170 160 170 160 170 160 170 71 71 71 71 130 130 130 130
17.5 kV
50/60 Hz 3AH1 215-7 3AH1 216-2 3AH1 216-4 3AH1 216-6 3AH1 216-7 3AH3 217-2 3AH3 217-6 3AH3 217-7 3AH3 227-8 3AH3 228-2 3AH3 228-6 3AH3 228-7 3AH3 228-8
3150 210 1250 210 2000 210 2500 210 3150 210 1250 210 2500 210 3150 210 4000 275 1250 275 2500 275 3150 275 4000 275
160 230 110 130 160 230 110 130 160 230 110 130 160 170 135 130 160 170 145 130 160 170 145 130 160 170 145 130 160 170 135 130
Possible
32
O - 0.3 s - CO- 15 s - CO
Pole-center distance
Order No.
Weights
Technical Data
Electrical data, dimensions and weights
20 000
Operating cycles
Operating cycles
10 000
is shown as a function of the breaking current (r.m.s. value). All vacuum circuit-breakers fulfil the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve shape beyond the parameters defined in IEC 62271-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application.
20 10 1 2 5
5 4 6
3
HG11-2560 eps
211 668
HG11-2559 eps
109
550/565 1)
604
70
571
610
Dimension drawing 5
1) from Ir = 2500 A
591 275 105 680 275
Dimension drawing 6
750 275
211 733
HG11-2561 eps
105
170
601
776
694
776
Dimension drawing 7
Dimension drawing 8
HG11-2562 eps
33
34
36 kV
50/60 Hz Order No.
24 kV
50/60 Hz
3AH3 305-6 3AH3 305-2 3AH3 266-6 3AH3 305-4 Ir Ir A A Rated normal current Pole-center distance Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO- 15 s - CO s s 3 3 3 tk tk 2500 350 1250 350 2500 275 2000 350 mm mm
Technical Data
Siemens HG 11.03 2007 3 3 Possible Rated short-circuit duration Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asymmetrical breaking current Ima Rated short-circuit making current (at 50/60 Hz) Rated lightning impulse withstand voltage Ud Rated short-duration power-frequency withstand voltage kV 50 2.0 mV Voltage drop U between connections (according to IEC 60694 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth 170 168 175 Weights kg kg 360 226 245 173 mm mm mm mm Isc Isc 40 kA kA 31.5 31.5 31.5 % % 36 36 36 36 kA kA 35.4 35.4 35.4 44.9 100/ 104 Ima kA kA Up Up kV kV 170 170 125 170 Ud kV 70 70 70 2.3 2.3 2.3 mV 40 36 44.9 80/ 82 80/ 82 80/ 82 100/ 104 170 70 2.0 360 330 314 260 360 330 314 260 mm mm mm mm 360 330 314 260 360 330 314 260 175 175 3M 325 00009 3M 325 00008 3M 325 00007 3M 325 00009 3M 325 00008 11 11 10 11 11 9 11 10 11 10 Rated operating sequence possible up to Isc = 31.5 kA Detailed dimension drawing (can be ordered) Operating cycle diagram No. (see page 35) Catalog dimension drawing No. (see page 35)
Technical Data
Electrical data, dimensions and weights
Operating cycles
105
194
20 10 1 2 5
10 11
645
704
Dimension drawing 9
The permissible number of electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All vacuum circuit-breakers fulfil the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve shape beyond the parameters defined in IEC 62271-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application.
494 105
820 350
HG11-2568 eps
50
494
778 1030
210
3
853
HG11-2569 eps
234
737
Dimension drawing 10
820 350
105
234
737
853
Dimension drawing 11
HG11-2570 eps
35
Technical Data
Electrical data, dimensions and weights of high-current and generator circuit-breakers
17.5 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO
Ir A 3AH3 712-4 3AH3 712-5 3AH3 713-4 3AH3 713-5 3AH3 714-4 3AH3 714-5 3AH3 817-7 3AH3 817-8 mm
tk s 3 3 3 3 3 3 3 3 3 3 3 3
Isc kA 50 50 63 63 72 72 50 50 63 63 72 72 % 75 75 65 65 65 65 75 75 65 65 65 65 kA 73 73 86 86 96 96 73 73 86 86 96 96
Ima kA 137 137 173 173 198 198 137 137 173 173 198 198
Up kV 110 110 110 110 110 110 110 110 110 110 110 110
Ud kV 50 50 50 50 50 50 50 50 50 50 50 50 mV 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 mm mm mm mm 160 230 230 230 160 230 230 230 160 230 230 230 160 230 230 230 160 230 230 230 160 230 230 230 160 170 145 130 160 170 135 130 160 170 145 130 160 170 135 130 160 170 145 130 160 170 135 130 kg 470 500 470 500 470 500 230 320 230 320 250 320 3M 325 00587 3M 325 00587 3M 325 00588 3M 325 00588 3M 325 00589 3M 325 00589 3M 325 00592 3M 325 00593 3M 325 00019 3M 325 00030 3M 325 00019 3M 325 00030 14 14 14 14 14 14 12 13 15 13 15 13
5000 300 6300 300 5000 300 6300 300 5000 300 6300 300 3150 275 4000 275 3150 275 4000 275 3150 275 4000 275
36
Pole-center distance
O - 30 min - CO
Order No.
Weights
Technical Data
Electrical data, dimensions and weights of high-current and generator circuit-breakers
Number of operating cycles The maximum permissible number of mechanical operating cycles is 10,000. Short-circuit breaking operations have been tested and proved under various conditions according to IEEE C37.013. As regards the electrical service life, values ranging beyond this depend on the specific case of application.
80
80
104
104
HG11-2571_en eps
668 900
668 900
max.70
119
59
119
Dimension drawing 12
271.5 211 ca.90 600 211 275 275
Dimension drawing 15
HG11-2574_en eps
494
494
80
494
733 1000
Dimension drawing 13
840 356 211 104 410 300 300
494
915 1180
HG11-2572_en eps
max.70
Dimension drawing 14
HG11-2573 eps
max.60
37
Technical Data
Circuit diagrams
Basic equipment
-S10 HE -S21 -S22 -M1 M P
HG11-2575_en eps
-S11
-Y9
-X0
-S3
-S41
-S42
-S1
-S7 -S6
OPEN release -Y1
11 12
13 14
21 22
23 24
31 32
33 34
41 42
43 44
51 52
53 54
61 62
63 64
HA
-X0
Contacts available for customer with basic circuitbreaker equipment and auxiliary switch 6 NO + 6 NC
-S15
-Y9
-X0 -S14
14 13 11 12 21 22 31 32
-S3
-S41
-S42
-S1 -K1
-S3
13 14
22 21
-S7
-S6
OPENrelease -Y1
-Y9
A2
1 2
-K1
A2
-X0
-X0
-X0
43 44
-S1
-S1 -Y7
-Y2
A1
HG11-2583 eps
HG11-2584 eps
HG11-2585 eps
-X0
-X0
-X0
-X0
Undervoltage release
The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring
38
HG11-2586 eps
A2
-Y4
A1 A2
-Y6
A1 A2
-R1
1 2
HG11-2580a eps
HA
A1
A1
HG11-2579a eps
Technical Data
Circuit diagrams
-X0
22 21
-S1
2
-S3
13 14
22 21
-S1
23 24
-S7
M -M1 1 =
D2 21 22 22 21
-S6
1 2
14 13
-S41
13 14
-S42
21 22
-S22 -X0
-K1
A2
-Y1 -X0
A2
1 2
-X0
-S21
M -M1 1 =
D2 22 21
-S1
11 12
13 14
21 22
23 24
31 32
33 34
41 42
43 44
51 52
53 54
61 63 62 64
71 72
73 74
81 82
83 84
91 92
93 101 103 111 113 121 123 94 102 104 112 114 122 124
HG11-2578b eps
-S11
A1
A1
-X0
-X0
Contacts available for customer with basic circuit-breaker equipment Auxiliary switch S1 (12 NO + 12 NC) instead of auxiliary switch 6 NO + 6 NC
Legend
HA HE K1 M1 P R1 S1 S10, S11 Manual opening Manual closing Contactor (anti-pumping) Motor operating mechanism Energy store Resistance Auxiliary switch Anti-pumping for manual closing S14, S15 S21, S22 Anti-pumping Position switches (to de-energize the motor operating mechanism after charging) Position switch (opens when closing spring is charged) S41, S42 S6 S7 X0 Position switches (to indicate the charging state) Circuit-breaker tripping signal Cutout switch for circuitbreaker tripping signal Lower part of plug/ terminal strip Y1 Y2 Y4 Y6 Y7 Y9 1st shunt release 2nd shunt release Current-transformer operated release Low-energy currenttransformer operated release Undervoltage release Closing solenoid
S3
The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring
HG11-2582a eps
-S22
HG11-2581a eps
39
Technical Data
Operating times, short-circuit protection of motors, consumption data of releases
Operating times
Operating times at rated voltage of the secondary circuit Equipment of circuit-breaker Operating time of circuit-breaker
3AH1 Closing time Opening time Arcing time Opening time Dead time CLOSE/OPEN contact time Minimum command duration 1st shunt release 2nd and 3rd release 1st shunt release 2nd and 3rd release 1st shunt release 2nd and 3rd release Closing solenoid 1st shunt release 2nd and 3rd release 1st shunt release 2nd and 3rd release < 75 ms < 65 ms < 50 ms < 15 ms < 80 ms < 65 ms 300 ms < 80 ms < 65 ms 45 ms 40 ms 20 ms > 15 ms > 10 ms < 15 s w 2 ms
3AH3 < 80 ms < 65 ms < 50 ms < 15 ms < 80 ms < 60 ms 300 ms < 90 ms < 70 ms 45 ms 40 ms 20 ms > 15 ms > 10 ms < 15 s w 2 ms
Pulse time for circuit-breaker tripping signal Charging time for electrical operation Synchronism error between the poles
1) The current inrush in the drive motor can be neglected due to its very short presence 2) Values are valid for 3AH1/3AH3, 3AH37, 3AH38
3) Consumption at pickup current (90 % of the rated normal current) and open armature
40
Annex
Contents
Contents
Page
Annex
Inquiry form Configuration instructions Configuration aid
41
42 43 Foldout page
R-HG11-181.tif
4
R-HG11-180.eps
41
Annex
Inquiry form
Please copy and return to your Siemens partner or you can use our prompted online configurator under www.siemens.com/energy
Inquiry concerning
Technical Data
Rated voltage 7.2 kV 17.5 kV 60 kV 125 kV 20 kV 50 kV 31.5 kA 63 kA 1250 A 4000 A 210 mm 12 kV 24 kV 75 kV 170 kV 32 kV 70 kV 40 kA 72 kA 2000 A 5000 A 275 mm 15 kV 36 kV 95 kV 195 kV 36 kV 95 kV 50 kA
Rated lightning impulse withstand voltage Rated short-duration power-frequency withstand voltage
Please
Pole-center distance
Mechanical interlocking
Siemens AG
Dept. Name Street Postal code/city Fax
Operating instructions
English
German
French
Spanish
_ _ _ Please fill in
42
9 10 11 12
13 14 15 16
Instruction for configuration of the 3AH1 and 3AH3 vacuum circuit-breakers 1st step: Definition of the primary part (see pages 13 to 15)
3 A H
See page 13
See page 20
Possible options:
Rated voltage (Ur) Rated lightning impulse withstand voltage (Up) Rated short-duration power-frequency withstand voltage (Ud) Rated short-circuit breaking current (Isc) Rated normal current (Ir) Pole-center distance These ratings define the positions 4 to 8 of the order number.
3 A H + + 3 A H +
+ + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + +
Release combination (position 9) Closing solenoid (position 10) Operating voltage of the releases (positions 11/12) Type of local closing (position 10) Type of operating mechanism and operating voltage of a motor, if available (position 14) Number of auxiliary contacts (position 15) Design of the secondary connection (position 15) Language of the documentation (position 16) Frequency of the operating voltage of the secondary equipment at AC (position 16) These equipment features define the positions 9 to 16 of the order number.
Shunt release, current-transformer operated release and undervoltage release Operating voltages from 24 V DC to 240 V AC Operating voltages from 24 V DC to 240 V AC Mechanical closing, manual electrical closing Manual operating stored-energy mechanism, motor operating stored-energy mechanism with operating voltages from 24 V DC to 240 V AC 6 NO + 6 NC, 12 NO + 12 NC 24-pole terminal strip, 24-pole plug connector, 64-pole plug connector English, German, French, Spanish 50 Hz/60 Hz 3 A H 3 A H
3 A H
3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 23) Should you still need more options than the possible special equipment like halogen-free and flame-retardant or silicone-free version, condensate protection or an additional rating plate, etc., please contact your responsible sales partner.
3 A H
3 A H
3 A H
43
See page 23
page 15
to
If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm.
Siemens AG Power Transmission and Distribution Medium Voltage Division Nonnendammallee 104 13623 Berlin Germany www.siemens.com/energy
For questions concerning Power Transmission and Distribution: You can contact our Customer Support Center 24 hours a day, 365 days a year. Tel.: +49 180/524 70 00 Fax: +49 180/524 24 71 (Calls charged: e.g. 12 Ct/min) E-Mail: [email protected] www.siemens.com/energy-support
Subject to change without notice Order No. E50001-K1511-A031-A1-7600 Printed in Germany Dispo 31601 KG 04.07 5.0 40 En 102412 6101/C6150
Responsible for Technical contents: Siemens AG, Dept. PTD M C PPM Berlin General editing: Siemens AG, Dept. PTD CC M Erlangen
R-HG11-182.tif
The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases. The required features should therefore be specified in each individual case at the time of closing the contract.