100% found this document useful (2 votes)
1K views1 page

CT Calculation P541

This document discusses the calculation of current transformers for a substation project in Sabah, Malaysia. It outlines the required knee point voltage calculation to select an appropriate current transformer according to the manufacturer's specifications. It then shows the calculations for the lead burden and secondary winding resistance and determines that a 600/1A current transformer with a knee point voltage greater than or equal to 197.4V and secondary winding resistance less than or equal to 2.4 ohms would be sufficient for the project.

Uploaded by

Srf Saharin
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
1K views1 page

CT Calculation P541

This document discusses the calculation of current transformers for a substation project in Sabah, Malaysia. It outlines the required knee point voltage calculation to select an appropriate current transformer according to the manufacturer's specifications. It then shows the calculations for the lead burden and secondary winding resistance and determines that a 600/1A current transformer with a knee point voltage greater than or equal to 197.4V and secondary winding resistance less than or equal to 2.4 ohms would be sufficient for the project.

Uploaded by

Srf Saharin
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

TENDER NO CONTRACT NO PROJECT:

: KKLW.T2/2011 :

DEPARTMENT DOCUMENT PAGE Prepared


SAHARIN

ENGINEERING 2 Checked
MAZLAN

OF

REV NO : PAGES

SUBSTATION: BAY NAME:

BEKALAN ELEKTRIK LUAR BANDAR (BELB) SAMBUNGAN GRID ZON DUA (4) NEGERI SABAH TAHUN 2012-2013 SECARA REKA DAN BINA TUNGKU STATION 33KV INCOMER

Verified

Approved

Date: 18/10/2012 Date: 18/10/2012 Date :

Date :

CURRENT TRANSFOMER CALCULATION CT Core Duty COP Relay Designation Relay Manufacturer Relay Model Core CT Ratio Class : Current Differential Protection : 87CD : Schneider : MiCOM P541 : 1 : 600/1A : X

According to manufacturer Schneider manual P54x/EN AP/H53 page 118/138, required knee point voltage:

Vk

K.In (Rct + 2RL)

...(1)

where, In Rct RL K K is dependent on: If = maximum value of through fault current for stability =25000A/600=41.67A X/R = Primary system X/R ratio = 10 (TNB CT Application Guide) If x X/R = 41.67A x 10 = 416.7A K is determined as follow: For relay set at Is1 = 20%, Is2 = 2In, k1=30%, k2=150% (manufacturer recommended setting for two terminal application) K
40 + (0.07 x (If x X/R)) 40 + (0.07 x (416.7)) 69.17 69

= = = =

rated line CT secondary current (1A or 5A) resistance of line CT secondary wiring resistance of singlelead from line CT to relay Dimensioning factor

Calculation of Lead burden : ( Multicore cable resistance per km for 4mm sq conductor ) Cable Length, L C = Cable Resistance (per km), RL = RL = 50 m 4.61 ohm/km 0.2305 Ohm = 0.05 km

RCT = The secondary winding resistance of The CT = 2.4 Ohm @ 600/1A (0.4Ohm per 100 turns as per TNB standard)

for CT ratio 1000/1A, Vk K. In (Rct + 2Rl) 69 x 1 x (2.4+ (2x0.2305)) 197.4 V

Therefore proposed CT as below is sufficient: 600/1A, Vk 197.4V, Rct 2.4 Ohm