Udc 230
Udc 230
Udc 230
51-52-25-73C 4/00
Warranty/Remedy
Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective. The foregoing is Buyers sole remedy and is in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular purpose. Specifications may change without notice. The information we supply is believed to be accurate and reliable as of this printing. However, we assume no responsibility for its use. While we provide application assistance personally, through our literature and the Honeywell web site, it is up to the customer to determine the suitability of the product in the application.
UDC 2300 is a U.S. registered trademark of Honeywell Other brand or product names are trademarks of their respective owners.
ii
4/00
Contacts
World Wide Web
The following lists Honeywells World Wide Web sites that will be of interest to our customers.
Honeywell Organization Corporate Sensing and Control International WWW Address (URL) http://www.honeywell.com http://www.honeywell.com/sensing http://www.honeywell.com/Business/global.asp
Telephone
Contact us by telephone at the numbers listed below.
Organization United States and Canada Honeywell Phone Number 1-800-423-9883 1-888-423-9883 1-800-525-7439 Asia Pacific Europe Latin America Honeywell Asia Pacific Hong Kong Honeywell PACE, Brussels, Belgium Honeywell, Sunrise, Florida U.S.A. (852) 2829-8298 [32-2] 728-2111 (954) 845-2600 Tech. Support Q&A Faxback (TACFACS) Service
4/00
iii
Symbol Definitions
The following table lists those symbols used in this document to denote certain conditions.
Symbol Definition This CAUTION symbol on the equipment refers the user to the Product Manual for additional information. This symbol appears next to required information in the manual. WARNING PERSONAL INJURY: Risk of electrical shock. This symbol warns the user of a potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms, 42.4 Vpeak, or 60 VDC may be accessible. Failure to comply with these instructions could result in death or serious injury. ATTENTION, Electrostatic Discharge (ESD) hazards. Observe precautions for handling electrostatic sensitive devices
Protective Earth (PE) terminal. Provided for connection of the protective earth (green or green/yellow) supply system conductor.
Functional earth terminal. Used for non-safety purposes such as noise immunity improvement. NOTE: This connection shall be bonded to protective earth at the source of supply in accordance with national local electrical code requirements. Earth Ground. Functional earth connection. NOTE: This connection shall be bonded to Protective earth at the source of supply in accordance with national and local electrical code requirements. Chassis Ground. Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements.
iv
4/00
Contents
1
1.1 1.2
INTRODUCTION ................................................................................................... 1
Overview ........................................................................................................................................ 1 CE Conformity (Europe) ................................................................................................................ 2
2
2.1 2.2 2.3 2.4 2.5 2.6 2.7
INSTALLATION..................................................................................................... 3
Overview ........................................................................................................................................ 3 Model Number Interpretation......................................................................................................... 5 Preliminary Checks ........................................................................................................................ 6 Control and Alarm Relay Contact Information .............................................................................. 8 Mounting ........................................................................................................................................ 9 Wiring........................................................................................................................................... 11 Wiring Diagrams .......................................................................................................................... 12
3
3.1 3.2 3.3 3.4
4
4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9
CONFIGURATION .............................................................................................. 23
Overview ...................................................................................................................................... 23 Configuration Prompt Hierarchy.................................................................................................. 24 Configuration Procedure .............................................................................................................. 25 Timer Set Up Group ..................................................................................................................... 26 Tuning Set Up Group ................................................................................................................... 27 SP Ramp Set Up Group................................................................................................................ 29 Accutune Set Up Group ............................................................................................................... 31 Algorithm Set Up Group .............................................................................................................. 32 Input 1 Set Up Group ................................................................................................................... 33
4.10 Input 2 Set Up Group ................................................................................................................... 35 4.11 Control Set Up Group................................................................................................................... 36 4.12 Options Set Up Group .................................................................................................................. 38 4.13 Communications Set Up Group.................................................................................................... 39 4.14 Alarms Set Up Group ................................................................................................................... 41 4.15 Configuration Record Sheet ......................................................................................................... 43
4/00
5
5.1 5.2 5.3 5.4 5.5
6
6.1 6.2 6.3 6.4
OPERATION ....................................................................................................... 53
Overview ...................................................................................................................................... 53 Single Display Functionality........................................................................................................ 54 Start Up Procedure for Operation................................................................................................. 56 Control Modes.............................................................................................................................. 57 6.4.1 Mode Definitions .................................................................................................................. 57 6.4.2 What happens when you change modes................................................................................ 58 Setpoints ....................................................................................................................................... 58 Timer ............................................................................................................................................ 59 Accutune II ................................................................................................................................... 61 Fuzzy Overshoot Suppression ...................................................................................................... 64 Using Two Sets of Tuning Constants........................................................................................... 64
6.10 Alarm Setpoints............................................................................................................................ 66 6.11 Three Position Step Control Algorithm ....................................................................................... 67 6.12 Setting a Failsafe Output Value for Restart After a Power Loss ................................................. 68 6.13 Setting Failsafe Mode................................................................................................................... 69
7
7.1 7.2 7.3 7.4
8
8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8
vi
4/00
9
9.1 9.2 9.3 9.4
10
11
12
4/00
vii
12.2.24 12.2.25 12.2.26 12.2.27 12.2.28 12.2.29 12.2.30 12.2.31 12.2.32 12.2.33 12.2.34 12.2.35 12.2.36 12.2.37 12.2.38 12.2.39 12.2.40 12.2.41 12.2.42 12.2.43 12.2.44 12.2.45 12.2.46 12.2.47 12.2.48 12.2.49 12.2.50 12.2.51 12.2.52 12.2.53 12.2.54 12.2.55 12.2.56 12.2.57 12.2.58 12.2.59 12.2.60 12.2.61 12.2.62 12.2.63 12.2.64 12.2.65 12.2.66 12.2.67 12.2.68 12.2.69 12.2.70 12.2.71 12.2.72 12.2.73
viii
CSRATO (COMPUTER SETPOINT RATIO) ........................................................... 129 CYC T1 or CT1 X3 (CYCLE TIME - HEAT)............................................................ 129 CYC2T2 or CT2 X3 (CYCLE TIME2 - COOL)......................................................... 130 DBAND (DEADBAND) ............................................................................................. 130 DECMAL (DECIMAL POINT LOCATION)............................................................. 130 DI COM (DIGITAL INPUT COMBINATIONS) ....................................................... 131 DIG IN (DIGITAL INPUT)......................................................................................... 131 DISPLAY (SINGLE DISPLAY DEFAULT).............................................................. 133 EMISS (EMISSIVITY) ............................................................................................... 133 ENDSEG (END SEGMENT)...................................................................................... 133 EUHRDN (RATE DOWN VALUE)........................................................................... 133 EUHRUP (RATE UP VALUE) .................................................................................. 133 FAILSF (FAILSAFE OUTPUT VALUE) .................................................................. 134 FILTR1 (INPUT 1 FILTER) ....................................................................................... 134 FILTR2 (INPUT 2 FILTER) ....................................................................................... 134 FINLSP (SINGLE SETPOINT RAMP FINAL SETPOINT)...................................... 134 FREQ (POWER LINE FREQUENCY) ...................................................................... 135 FSMODE ( FAILSAFE MODE) ................................................................................. 135 FUZZY (FUZZY OVERSHOOT SUPPRESSION).................................................... 135 HYST (HYSTERESIS - OUTPUT RELAY ONLY) .................................................. 135 I MIN or I RPM (RESET - INTEGRAL TIME) ......................................................... 136 I2 MIN or I2 RPM (RESET2 - INTEGRAL TIME) ................................................... 136 INCRMT (TIME COUNT INCREMENT) ................................................................. 136 IN1 HI (INPUT 1 HIGH RANGE VALUE) ............................................................... 137 IN1 LO (INPUT 1 LOW RANGE VALUE) ............................................................... 137 IN1TYP (INPUT 1 ACTUATION TYPE).................................................................. 138 IN2 HI (INPUT 2 HIGH RANGE VALUE) ............................................................... 139 IN2 LO (INPUT 2 LOW RANGE VALUE) ............................................................... 139 IN2TYP (INPUT 2 ACTUATION TYPE).................................................................. 140 L DISP (DISPLAY FOR TIMER OPTION) ............................................................... 140 LNGUAG (LANGUAGE)........................................................................................... 140 LOCK (LOCKOUT) ................................................................................................... 141 LOOPBACK (LOCAL LOOPBACK TEST).............................................................. 141 LSPS (LOCAL SETPOINT SOURCE) ..................................................................... 141 MANRST (MANUAL RESET) .................................................................................. 142 MINRPM (RESET UNITS) ........................................................................................ 142 OUTALG (OUTPUT ALGORITHM) ........................................................................ 142 OUT Hi (HIGH OUTPUT LIMIT).............................................................................. 143 OUT Lo (LOW OUTPUT LIMIT) .............................................................................. 143 PARITY (PARITY)..................................................................................................... 143 PB or GAIN (PROPORTIONAL BAND or GAIN).................................................... 144 PB 2 or GAIN 2 (PROPORTIONAL BAND 2 or GAIN 2)........................................ 144 PBorGN (PROPORTIONAL BAND UNITS) ............................................................ 145 PERIOD (TIMEOUT PERIOD).................................................................................. 145 PG END (PROGRAM TERMINATION STATE) ..................................................... 145 PIDSET (NUMBER OF TUNING PARAMETER SETS) ......................................... 146 PVSTRT (PV START)................................................................................................ 147 PWROUT (THREE POSITION STEP CONTROL OUTPUT START-UP MODE) . 147 PWR UP (POWER UP CONTROLLER MODE RECALL) ...................................... 148 RATE T (RATE TIME) .............................................................................................. 148
UDC 2300 Controller Product Manual 4/00
12.2.74 12.2.75 12.2.76 12.2.77 12.2.78 12.2.79 12.2.80 12.2.81 12.2.82 12.2.83 12.2.84 12.2.85 12.2.86 12.2.87 12.2.88 12.2.89 12.2.90 12.2.91 12.2.92 12.2.93 12.2.94 12.2.95 12.2.96 12.2.97 12.2.98 12.2.99 12.2.100 12.2.101 12.2.102 12.2.103 12.2.104 12.2.105 12.2.106 12.2.107 12.2.108 12.2.109 12.2.110
RATE2T (RATE2 TIME) ........................................................................................... 148 RATIO1 (INPUT 1 RATIO) ....................................................................................... 149 RATIO2 (INPUT 2 RATIO) ....................................................................................... 149 RECYCL (RECYCLES) ............................................................................................. 149 RLY TY (RELAY CYCLE TIME INCREMENT)..................................................... 149 RESET (TIMER RESET CONTROL)........................................................................ 150 RN HLD (RUN/HOLD KEY LOCKOUT)................................................................. 150 RPUNIT (ENGINEERING UNITS FOR RAMP SEGMENTS) ................................ 150 RSPSRC (REMOTE SETPOINT SOURCE).............................................................. 150 SECUR (SECURITY CODE) ..................................................................................... 151 SGx RP (SEGMENT RAMP - x = Segment Number 1 THROUGH 12) ................... 151 SGx SP (SEGMENT SETPOINT - x = Segment Number 1 THROUGH 12) ............ 151 SGx TI (SEGMENT DURATION - x = Segment Number 1 THROUGH 12) ........... 152 SDMODE (SHED MODE) ......................................................................................... 152 SHD_SP (SHED SETPOINT RECALL) .................................................................... 152 SHDTIM (SHED TIME) ............................................................................................. 152 SOKDEV (GUARANTEED SOAK DEVIATION) ................................................... 153 SP Hi (SETPOINT HIGH LIMIT) .............................................................................. 153 SP Lo (SETPOINT LOW LIMIT)............................................................................... 153 SPPROG (SETPOINT RAMP/SOAK PROGRAM).................................................. 154 SPRAMP (SINGLE SETPOINT RAMP) ................................................................... 154 SPRATE (SETPOINT RATE) .................................................................................... 154 SP SEL (SETPOINT SELECT FUNCTION LOCKOUT) ......................................... 155 SP TRK (SETPOINT TRACKING)............................................................................ 155 START (TIMER START SELECTION) .................................................................... 155 STATE (PROGRAM STATE AT PROGRAM END)................................................ 155 STRSEG (START SEGMENT) .................................................................................. 156 SW VAL (AUTOMATIC SWITCHOVER VALUE)................................................. 156 TI MIN (SINGLE SETPOINT RAMP TIME) ............................................................ 156 TIMER (TIMER OPTION) ........................................................................................ 156 ToBEGN (RESET PROGRAMMING TO BEGINNING) ......................................... 156 TUNE (ACCUTUNE - DEMAND TUNING) ............................................................ 157 TX DLY (RESPONSE DELAY) ................................................................................ 157 UNITS (COMMUNICATION OVERRIDE UNITS) ................................................. 157 UNITS (TEMPERATURE UNITS) ............................................................................ 157 XMITR1 (TRANSMITTER CHARACTERIZATION) ............................................. 158 XMITR2 (TRANSMITTER CHARACTERIZATION) ............................................. 159
13
INDEX................................................................................................................ 161
4/00
ix
Tables
Table 2-1 Condensed Specifications _____________________________________________________ 4 Table 2-2 Preliminary Checks __________________________________________________________ 6 Table 2-3 Control Relay Contact Information ______________________________________________ 8 Table 2-4 Alarm Relay Contact Information _______________________________________________ 8 Table 2-5 Mounting Procedure _________________________________________________________ 10 Table 2-6 Permissible Wiring Bundling __________________________________________________ 12 Table 2-7 Universal Output Functionality and Restrictions ___________________________________ 12 Table 4-1 Configuration Prompt Hierarchy _______________________________________________ 24 Table 4-2 Configuration Procedure _____________________________________________________ 25 Table 4-3 TIMER Group (Numeric Code 100) Function Prompts______________________________ 26 Table 4-4 TUNING Group (Numeric Code 200) Function Prompts ____________________________ 27 Table 4-5 SPRAMP Group (Numeric Code 300) Function Prompts ____________________________ 29 Table 4-6 ATUNE Group (Numeric Code 400) Function Prompts _____________________________ 31 Table 4-7 ALGOR Group (Numeric Code 500) Function Prompts _____________________________ 32 Table 4-8 INPUT1 Group (Numeric Code 600) Function Prompts _____________________________ 33 Table 4-9 INPUT2 Group (Numeric Code 700) Function Prompts _____________________________ 35 Table 4-10 CONTRL Group (Numeric Code 800) Function Prompts ___________________________ 36 Table 4-11 Options Group (Numeric Code 900) Function Prompts ____________________________ 38 Table 4-12 Communications Group (Numeric Code 1000) ___________________________________ 39 Table 4-13 ALARMS Group (Numeric Code 1100) Function Prompts__________________________ 41 Table 5-1 Procedure to Enter a Security Code _____________________________________________ 47 Table 5-2 Annunciators ______________________________________________________________ 49 Table 5-3 Lower Display Key Parameter Prompts __________________________________________ 50 Table 5-4 Error Messages _____________________________________________________________ 51 Table 6-1 Single Display Parameters ____________________________________________________ 55 Table 6-2 Procedure for Starting Up the Controller _________________________________________ 56 Table 6-3 Control Mode Definitions ____________________________________________________ 57 Table 6-4 Changing Control Modes (Dual Display Only) ____________________________________ 58 Table 6-5 Procedure for Changing the Local Setpoints ______________________________________ 58 Table 6-6 Procedure for Switching Between Setpoints ______________________________________ 59 Table 6-7 Procedure for Starting TUNE ________________________________________________ 61 Table 6-8 Procedure for Using TUNE at Start-up for Duplex Control __________________________ 62 Table 6-9 Procedure for Accessing Accutune Error Codes ___________________________________ 63 Table 6-10 Accutune Error Codes ______________________________________________________ 63 Table 6-11 Set Up Procedure __________________________________________________________ 65 Table 6-12 Procedure for Switching PID SETS from the Keyboard ____________________________ 65 Table 6-13 Procedure for Displaying Alarm Setpoints ______________________________________ 66 Table 6-14 Procedure for Displaying 3Pstep Motor Position__________________________________ 67 Table 6-15 Procedure for Setting a Failsafe Value__________________________________________ 68 Table 6-16 Procedure for Setting a Failsafe Mode__________________________________________ 69 Table 7-1 Running A Setpoint Ramp ____________________________________________________ 73 Table 7-2 Program Contents ___________________________________________________________ 75 Table 7-3 Run/Monitor Functions ______________________________________________________ 80 Table 8-1 Voltage and Resistance Equivalents for Input 1 Range Values ________________________ 84 Table 8-2 Equipment Needed __________________________________________________________ 86 Table 8-3 Set Up Wiring Procedure for Thermocouple Inputs Using an Ice Bath _________________ 87 Table 8-4 Set Up Wiring Procedure for Thermocouple Inputs using Thermocouple Source _________ 87
4/00
Table 8-5 Set Up Wiring Procedure for RTD Inputs ________________________________________ 88 Table 8-6 Set Up Wiring Procedure for Radiamatic, Milliampere, Millivolts, or Volts Inputs (Except 0-10 Volts) ______________________________________________________________ 88 Table 8-7 Set Up Wiring Procedure for 0 to 10 Volts _______________________________________ 89 Table 8-8 Input 1 Calibration Procedure (Numeric Code 10000) ______________________________ 90 Table 8-9 Input 2 Calibration Procedure (Numeric Code 20000) ______________________________ 93 Table 8-10 Restore Factory Calibration __________________________________________________ 94 Table 9-1 Set Up Wiring Procedure for Current Proportional Output ___________________________ 96 Table 9-2 Current Proportional Output Calibration Procedure (Numeric Code 30000) _____________ 97 Table 9-3 Set Up Wiring Procedure for Auxiliary Output ____________________________________ 98 Table 9-4 Auxiliary Output Calibration Procedure (Numeric Code 50000) ______________________ 99 Table 9-5 3 Position Step Output Calibration Procedure (Numeric Code 40000) _________________ 100 Table 10-1 Procedure for Identifying the Software Version _________________________________ 103 Table 10-2 Procedure for Displaying the Status Test (Numeric Code 1200) Results ______________ 104 Table 10-3 Background Tests _________________________________________________________ 105 Table 10-4 Controller Failure Symptoms ________________________________________________ 107 Table 10-5 Troubleshooting Power Failure Symptoms _____________________________________ 109 Table 10-6 Troubleshooting Current Proportional Output Failure_____________________________ 109 Table 10-7 Troubleshooting Time Proportional Output Failure ______________________________ 110 Table 10-8 Troubleshooting Current/Time or Time/Current Proportional Output Failure __________ 111 Table 10-9 Troubleshooting Alarm Relay Output Failure ___________________________________ 112 Table 10-10 Troubleshooting a Keyboard Failure _________________________________________ 113 Table 11-1 Parts Identification ________________________________________________________ 115 Table 11-2 Parts Not Shown__________________________________________________________ 116 Table 12-1 Function Parameter Look-up Table ___________________________________________ 118
4/00
xi
Figures
Figure 1-1 UDC 2300 Operator Interface__________________________________________________ 1 Figure 2-1 Model Number Interpretation __________________________________________________ 5 Figure 2-2 Jumper Placements __________________________________________________________ 7 Figure 2-3 Mounting Dimensions (not to scale) _____________________________________________ 9 Figure 2-4 Mounting Method __________________________________________________________ 10 Figure 2-5 Composite Wiring Diagram __________________________________________________ 13 Figure 2-6 Mains Power Supply ________________________________________________________ 13 Figure 2-7 Input 1 Connections ________________________________________________________ 14 Figure 2-8 Input 2 Connections ________________________________________________________ 14 Figure 2-9 Electromechanical Relay Output_______________________________________________ 14 Figure 2-10 Solid State Relay Output____________________________________________________ 15 Figure 2-11 Open Collector Relay Output ________________________________________________ 15 Figure 2-12 Current Output ___________________________________________________________ 16 Figure 2-13 External Solid State Relay Option (Internal Open Collector Output) _________________ 16 Figure 2-14 Three Position Step Control Connections_______________________________________ 17 Figure 2-15 Alarm and Duplex Output Connections ________________________________________ 17 Figure 2-16 External Interface Option Connections_________________________________________ 18 Figure 2-17 Transmitter Power for 4-20 mA 2 wire Transmitter Using Open Collector Alarm 2 Output (Model DC230B-XT-XX-XX-XXXXXXX-XX-X) ______________________________ 19 Figure 2-18 Transmitter Power for 4-20 mA 2 Wire Transmitter Using Auxiliary Output (Model DC230B-XX-2X-XX-XXXXXXX-XX-X)______________________________________ 19 Figure 3-1 Operator Interface and Key Functions __________________________________________ 22 Figure 5-1 Operator Interface __________________________________________________________ 46 Figure 7-1 Ramp/Soak Profile Example __________________________________________________ 78 Figure 7-2 Program Record Sheet_______________________________________________________ 79 Figure 8-1 Input 1 and Input 2 Wiring Terminals___________________________________________ 85 Figure 8-2 Wiring Connections for Thermocouple Inputs Using an Ice Bath _____________________ 87 Figure 8-3 Wiring Connections for Thermocouple Inputs Using Thermocouple Source ____________ 87 Figure 8-4 Wiring Connections for RTD (Resistance Thermometer Device) _____________________ 88 Figure 8-5 Wiring Connections for Radiamatic, Milliampere, Millivolts, or Volts (Except 0 to 10 Volts) _________________________________________________________________________ 89 Figure 8-6 Wiring Connections for 0 to 10 Volts___________________________________________ 89 Figure 8-7 Wiring Connections for 4 to 20 mA Input Input 2________________________________ 91 Figure 8-8 Wiring Connections for 1 to 5 Volt Input Input 2 ________________________________ 92 Figure 9-1 Wiring Connections for Calibrating Current Proportional Output _____________________ 96 Figure 9-2 Wiring Connections for Calibrating Auxiliary Output ______________________________ 98 Figure 11-1 UDC 2300 Exploded View _________________________________________________ 115
xii
4/00
Introduction
1 Introduction
1.1 Overview
The UDC 2300 is a microprocessor-based stand-alone controller. It combines reliability and operating simplicity in a cost-effective 1/4-DIN size controller. The UDC 2300 monitors and controls temperatures and other variables in applications such as environmental chambers, plastic processing machines, furnaces and ovens, and packaging machinery. Its features include: Universal AC Power Supply, Input/Output Isolation, Isolated Auxiliary Current Output / Digital Input Modbus and ASCII Communications Timer Accutune II Tuning with Fuzzy Logic Overshoot Suppression. 2nd Input (Remote Setpoint) Setpoint Ramp/Rate/Program Three Position Step Control Duplex (Heat/Cool) The UDC 2300 is also downward compatible with existing UDC 2000 applications and installations except for RTD and 0-10 Volt inputs. See wiring diagrams in Section 2 - Installation.
ALM 1 2 OUT 1 2
2300
DISPLAY MAN-AUTO RESET
SP 2300
FUNCTION
F C M A R L
PV
SET UP
AUTO TUNE
RUN HOLD
Introduction
4/00
Installation
2 Installation
2.1 Overview
Introduction Installation of the UDC 2300 consists of mounting and wiring the controller according to the instructions given in this section. Read the pre-installation information, check the model number interpretation (Subsection 2.2), and become familiar with your model selections, then proceed with installation. Whats in this section? The following topics are covered in this section. TOPIC 2.1 Overview 2.2 Model Number Interpretation 2.3 Preliminary Checks 2.4 Control and Alarm Relay Contact Information 2.5 Mounting 2.6 Wiring 2.7 Wiring Diagrams Composite Wiring Diagram AC Line Voltage Input 1 Connections Input 2 Connections Relay Output Electromechanical Solid State Open Collector Current Output Connections External Solid State Relay Output Option Three Position Step Control Connections Alarm and Duplex Output Connections See Page 3 5 6 8 9 11 12 13 13 14 14 14 15 15 16 16 17 17
4/00
Installation
Pre-installation Information If the controller has not been removed from its shipping carton, inspect the carton for damage then remove the controller. Inspect the unit for any obvious shipping damage and report any damage due to transit to the carrier. Make sure a bag containing mounting hardware is included in the carton with the controller. Check that the model number shown on the inside of the case agrees with what you have ordered.
Condensed Specifications Honeywell recommends that you review and adhere to the operating limits listed in Table 2-1 when you install your controller. Table 2-1 Condensed Specifications
Operating Limits Ambient Temperature: 32 F to 131 F (0 C to 55 C) Relative Humidity: 5 % to 90 % RH up to 104 F (40 C) Vibration: Frequency: 0 to 200 Hz Acceleration: 0.6g Mechanical Shock: Acceleration: 5g Duration: 30 ms Power: 90 Vac to 264 Vac, 50/60 Hz (CSA models rated to 250 Vac maximum) Power Consumption: 12 VA maximum Accuracy 0.25 % of span typical 1 digit for display 15-bit resolution typical Shielded twisted-pair cables are required for all analog I/O, process variable, RTD, thermocouple, dc millivolt, low level signal, 4-20 mA, digital I/O, and computer interface circuits. Refer to 51-52-05-01, How to Apply Digital Instrumentation in Severe Electrical Noise Environments, for additional information.
4/00
Installation
D C 2 3 0
B = Basic Controller Model L = Limit Controller Model I = Digital Indicator Model Output #1 0 _ = None C _ = Current E _ = Relay, E-M A _ = Relay, SS 1 amp S _ = Relay, SS 10 amp T _ = Open Collector Output Output #2 or Alarm #2 and Alarm #1 _ 0 = No additional outputs or alarms _ E = Relay, E-M and Alarm #1 _ A = Relay, SS 1 amp and Alarm #1 _ S = Relay, SS 10 amp and Alarm #1 _ T = Open Collector Output and Alarm #1 Options 0______ 1______ _0_____ _A_____ __0____ __T____ ___0___ ___F___ ____0__ ____B__ ____T__ _____0_ ______0
0
Manuals 0 _ = English F _ = French (Europe) G _ = German (Europe) T _ = Italian (Europe) S _ = Spanish (Europe) Certificate _ 0 = None _ C = Certificate of Conformance (F3391)
External Interface 0 _ = None 1 _ = RS422/485 ASCII / Modbus 2 _ = Auxiliary Output or Digital Input Software Options _ 0 = Single Display (includes Accutune II on DC230B) _ A = Dual Display, MA, + Accutune II _ B = Setpoint Programming (SPP), Dual Display, MA, Accutune II
= 90 to 264 Vac Power = 24 Vac/dc Power (requires Alarms plus IN 2) = UL and CE = UL, CE, CSA and (FM pending) = None = Customer ID Tag = None = Rear Terminal Cover = Gray Elastomer Bezel = Blue Elastomer Bezel = Tan Elastomer Bezel = Future = Future
PV Input 1 _ = T/C, RTD, Radiamatic, mV, 0-5V, 0-20mA, 4-20mA 2_ = T/C, RTD, Radiamatic, mV, Volts, milliamps, 0-10 Volts Optional Input 2 _ 0 = None _ 1 = 0-5V, 1-5V, 0-20mA, 4-20mA
4/00
Installation
Note: Solid State and Open Collector must have jumper set to N.O. (Normally Open). 3 Position Step and Time Duplex must have Output 2 jumper (W202) set to N.O.
4/00
Installation
Jumper Placements
Input #2 Jumper 2 1 Position 2 Volt 2 1 Jumper Position 1 mA Note: Jumpers enlarged for clarity S201 2 1
S201
S101
W101 NO NC
NO NO NC
Position 2: mV, Volt, RTD Output #1 W101 NO Position 4: NC NC NO NO (Default) mA No jumper: 0 -10 volts
NC
4/00
Installation
Off
N.O. N.C.
On
N.O. N.C.
4/00
Installation
2.5 Mounting
Physical Considerations The controller can be mounted on either a vertical or tilted panel using the mounting kit supplied. Adequate access space must be available at the back of the panel for installation and servicing activities. Overall dimensions and panel cutout requirements for mounting the controller are shown in Figure 2-3. The controllers mounting enclosure must be grounded according to CSA standard C22.2 No. 0.4 or Factory Mutual Class No. 3820 paragraph 6.1.5. The front panel is moisture rated NEMA 3/IP65 (IEC) when properly installed with panel gasket.
Overall Dimensions
96 3.780 +0.8 +0.008 92 =0.0 90 -0.0 +0.03 3.622 +0.031 3.5906 -0.0
92 3.622
10 .394
Max (2)
2.62 .103
90.7 3.57
4/00
Installation
Mounting Method Before mounting the controller, refer to the nameplate on the outside of the case and make a note of the model number. It will help later when selecting the proper wiring configuration.
Panel
20752
Figure 2-4 Mounting Method Mounting Procedure Table 2-5 Mounting Procedure
Step 1 2 3 4 Action Mark and cut out the controller hole in the panel according to the dimension information in Figure 2-3. Remove the screw cover and loosen the screw on the front of the controller. Pull the chassis out of the case. Orient the case properly and slide it through the panel hole from the front. Remove the mounting kit from the shipping container and install the kit as follows: Install the screws into the threaded holes of the clips. Insert the prongs of the clips into the two holes in the top and bottom of the case. Tighten both screws to secure the case against the panel. Carefully slide the chassis assembly into the case, press to close, and tighten the screw. Replace the screw cover.
10
4/00
Installation
2.6 Wiring
Electrical Considerations The controller is considered rack and panel mounted equipment per EN61010-1, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use, Part 1: General Requirements. Conformity with 72/23/EEC, the Low Voltage Directive requires the user to provide adequate protection against a shock hazard. The user shall install this controller in an enclosure that limits OPERATOR access to the rear terminals. Mains Power Supply This equipment is suitable for connection to 90 to 264 Vac, 50/60 Hz, power supply mains. It is the users responsibility to provide a switch and non-time delay (North America), quick-acting, high breaking capacity, Type F (Europe), 1/2A, 250V fuse(s), or circuit-breaker, as part of the installation. The switch or circuit-breaker shall be located in close proximity to the controller, within easy reach of the OPERATOR. The switch or circuit-breaker shall be marked as the disconnecting device for the controller. Controller Grounding PROTECTIVE BONDING (grounding) of this controller and the enclosure in which it is installed shall be in accordance with National and Local electrical codes. To minimize electrical noise and transients that may adversely affect the system, supplementary bonding of the controller enclosure to a local ground, using a No. 12 (4 mm2) copper conductor, is recommended. Control/Alarm Circuit Wiring The insulation of wires connected to the Control/Alarm terminals shall be rated for the highest voltage involved. Extra Low Voltage (ELV) wiring (input, current output, and low voltage Control/Alarm circuits) shall be separated from HAZARDOUS LIVE (>30 Vac, 42.4 Vpeak, or 60 Vdc) wiring per Permissible Wiring Bundling, Table 2-6. Electrical Noise Precautions Electrical noise is composed of unabated electrical signals which produce undesirable effects in measurements and control circuits. Digital equipment is especially sensitive to the effects of electrical noise. Your controller has built-in circuits to reduce the effect of electrical noise from various sources. If there is a need to further reduce these effects: Separate External WiringSeparate connecting wires into bundles (See Permissible Wiring Bumdling - Table 2-6) and route the individual bundles through separate conduit metal trays. Use Suppression DevicesFor additional noise protection, you may want to add suppression devices at the external source. Appropriate suppression devices are commercially available.
ATTENTION
For additional noise information, refer to document number 51-52-05-01, How to Apply Digital Instrumentation in Severe Electrical Noise Environments.
4/00
11
Installation
12
4/00
Installation
Wiring the Controller Using the information contained in the model number, select the appropriate wiring diagrams from the composite wiring diagram below. Refer to the individual diagrams listed to wire the controller according to your requirements.
Input Terminal See Figure 2-7 Control Output Terminals See Note 1 Mains Power Supply Terminals See Figure 2-6
8 7 6 5 4 L2 / N L1
9 10 11 12 13 14 15 16
Alarm and Duplex Output Connections See Figure 2-15 External Interface Options Terminals See Figure 2-16 Input #2 Terminals See Figure 2-8
NOTE1: Time Proportional Electromechanical Relay Output See Figure 2-9 Time Proportional Solid State Relay Output See Figure 2-10 Time Proportional Open Collector Output See Figure 2-11 Current Output See Figure 2-12 External Solid State Relay Output See Figure 2-13 Three Position Step Control Output See Figure 2-14
24855
L2 / N L1
24856
1 PROTECTIVE BONDING (grounding) of this controller and the enclosure in which it is installed, shall be in accordance with National and Local electrical codes. To minimize electrical noise and transients that may adversely affect the system, supplementary bonding of the controller enclosure to a local ground, using a No. 12 (4 mm2) copper conductor, is recommended. Before powering the controller, see Preliminary Checks in this section of the Product manual for switch and jumper settings. 2 Provide a switch and non-time delay (North America), quick-acting, high breaking capacity, type F (Europe), 1/2 A, 250 V fuse(s), or circuit-breaker as part of the installation.
4/00
13
Installation
RTD
1 8+
mV, Volts (except 0-10V), Milliamperes, orRadiamatic mV, Volt, or 7Milliampere Source 6R 8+ 76R
1 2
Volt Source
8+ 7 _ 6R
The voltage divider for 0 to 10 Volts is supplied with the controller when the input is specified. You must install it when you wire the controller before start-up. 1
24857
15 16
+ _ 0 to 20 mA,
4 to 20 mA, 0 to 5 Volts 1 to 5 Volts
See Preliminary Checks in this section of the Product Manual for jumper selections.
24858
1 Load Supply Power Control Relay #1 Load 5 amp Fast Blo OUT1 5 4 OUT2/ALM2 9 10
24859
1 Control relays 1 and 2 are configured N.O. as shipped. Alarm relays 1 and 2 are configured N.C. as shipped. N.O. or N.C. configurations are selectable by jumpers on the Main printed wiring boards. See Preliminary Checks in this section of the Product Manual for details. Each SPST relay is rated at 5A, 120 Vac and 30 Vdc, 2.5 A 240 Vac. User-provided fuses should be sized accordingly. For solid state relay outputs, see Figure 2-13. See Figure 2-15 for Alarm and Duplex Output Connections. See Table 2-3 and Table 2-4 for Control and Alarm Relay Contact information.
14
4/00
Installation
OUT1 5 4
OUT2/ALM2 9 10
24860
1 If the load current is less than the minimum rated value of 20 mA, there may be a residual voltage across both ends of the load even if the relay is turned off. Use a dummy resistor as shown to counteract this. The total current through the resistor and the load current must exceed 20 mA. 2 Solid State relay is rated at 1 Amp at 25C, linearly derated to 0.5 Amp at 55C. Customer should size fuse accordingly. See Figure 2-15 for Alarm and Duplex Output Connections. See Table 2-3 and Table 2-4 for Control and Alarm Relay Contact information.
OUT1
OUT2/ALM2
OUT1 OUT2/ALM2
5 4+
9 10+
5 4+
9 10+
24861R
0-24 Vdc
CAUTION
Open collector outputs are internally powered at 24 Vdc. Connecting an external supply will damage the controller. External relays should be fused between power and relay load.
See Figure 2-15 for Alarm and Duplex Output Connections. See Tables 2-3 and 2-4 for Control and Alarm Relay Contact information.
4/00
15
Installation
5 4
CAUTION
Installing a current output instrument into a case wired for relay outputs will damage the instrument.
2 3
Connect shield to ground at one end only. Set output jumper per Figure 2-2.
See Figure 2-15 for Alarm and Duplex Output Connections. See Table 2-3 and Table 2-4 for Control and Alarm Relay Contact information.
10 amp Fast Blo 10 Amp Solid State Relay Assembly White Black L1/H L2/N
1
LOAD
AC
Green
This Solid State relay is rated at 15 Amps at 25C, linearly derated to 10 Amps at 55C. Customer should size fuse accordingly
Figure 2-13 External Solid State Relay Option (Internal Open Collector Output)
16
4/00
Installation
1 Control Relay #2
5+ 4-
Control Relay #1
24864
Load 5 amp Fast Blo Supply Power 1 Alarm Load Relay #1 Load 5 amp fast Blo Supply Power
24867
1 Control relays 1 and 2 are configured N.O. as shipped. Alarm relays 1 and 2 are configured N.C. as shipped. N.O. or N.C. configurations are selectable by jumpers on main printed wiring boards. See Preliminary Checks in this sections of the Product Manual for details. Each SPST relay is rated at 5 A, 120 Vac and 24 Vdc, 2.5 A, 240 Vac. 2 Alarm #2 not available for Time Proportional Duplex or Three Position Step Control.
4/00
17
Installation
1 Auxiliary Output
Digital Inputs 1
13 14
+ _
13 14
+ _
Communications
(B) D
13 14
D+
120 OHMS
Connect shield wires together with supplied crimp part number 30755381-001
Do not run these lines in the same conduit as AC power.
18
4/00
Installation
2 Wire Transmitter
_
INPUT 1 8+ 79 10+
OUTPUT 2
+
Configure: A2S1TYPE = NONE A2S2TYPE = NONE
Figure 2-17 Transmitter Power for 4-20 mA 2 wire Transmitter Using Open Collector Alarm 2 Output (Model DC230B-XT-XX-XX-XXXXXXX-XX-X)
2 Wire Transmitter
_
INPUT 1 8+ 7AUXOUT 13 + 14 -
+
Configure: AUXOUT = OUT Auxiliary Output Calibration ZEROVAL = 4095 SPANVAL = 4095
Figure 2-18 Transmitter Power for 4-20 mA 2 Wire Transmitter Using Auxiliary Output (Model DC230B-XX-2X-XX-XXXXXXX-XX-X)
4/00
19
Installation
20
4/00
Initial Start-up
3 Initial Start-up
3.1 Overview
This section gives you the information necessary to start up your controller prior to configuration. Review the Operator Interface portion to make sure you are familiar with the indicator definitions and key functions.
4/00
21
Initial Start-up
ALM 1 2 OUT 1 2
2300
DISPLAY MAN-AUTO RESET
SP 2300
FUNCTION
F C M A R L
PV
F - Fahrenheit being used C - Centigrade being used M or A - Manual/Auto display R - Remote or Local SP2 setpoint active L - Local setpoint active Lower Display - Six alphanumeric characters Normal operation display is blank unless configured For default prompt of PV or Setpoint Configuration mode - displays functions and parameters
SET UP
Keys
AUTO TUNE
RUN HOLD
24868
FUNCTION
Selects functions within each configuration group. Selects 2nd Setpoint or Remote Setpoint. Returns Controller to normal display from Set Up mode. Toggles various operating parameters for display. Selects Manual or Auto mode. Resets the latching Limit Controller relay. In Set Up mode, used to restore original value or selection. Scrolls through the configuration Setup groups.
AUTO TUNE
Initiates Limit Cycle Tuning (Accutune). Increases setpoint or output value. Increases the configuration values or changes functions in Configuration mode groups. Decreases setpoint or output value. Decreases the configuration values or changes functions in Configuration mode groups.
DISPLAY
MAN-AUTO RESET
SET UP
RUN HOLD
22
4/00
Configuration
4 Configuration
4.1 Overview
Introduction Configuration is a dedicated operation where you use straightforward keystroke sequences to select and establish (configure) pertinent control data best suited for your application. To assist you in the configuration process, there are prompts that appear in the upper and lower displays. These prompts let you know what group of configuration data (Set Up prompts) you are working with and also, the specific parameters (Function prompts) associated with each group. Figure 3-1 shows you an overview of the prompt hierarchy as they appear in the controller. As you will see, the configuration data is divided into 11 main Set Up groups plus prompts for calibration and prompts that show the status of the continuous background tests that are being performed. Whats in this section? The following topics are covered in this section. TOPIC 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 4.13 4.14 4.15 Overview Configuration Prompt Hierarchy Configuration Procedure Timer Set Up Group Tuning Set Up Group SP Ramp Set Up Group Accutune Set Up Group Algorithm Set Up Group Input 1 Set Up Group Input 2 Set Up Group Control Set Up Group Options Set Up Group Communications Set Up Group Alarms Set Up Group Configuration Record Sheet See Page 23 24 25 26 27 29 31 32 33 35 36 38 39 41 43
4/00
23
Configuration
TIMER TUNING
CYC2T2 or CT2 X3
SECUR
LOCK
AUTOMA
A TUNE
RN HLD
SP SL
SPRAMP
TI MIN RPUNIT SGxSP* TUNE OUTALG UNITS BRNOUT XMITR2 SW VAL ACTION MINRPM 0 PCT ComADD SHD_SP A1S2VA A1S1EV ALARM1 FAILSF
FINLSP RECYCL SGx TI* AT ERR 4-20RG IN1TYP EMISS IN2 HI LSPS OUT Hi
SPRATE SOKDEV
EUHRUP PG END
EUHRDN STATE
SPPROG ToBEGN
STRSEG PVSTRT
RLY TYP XMITR1 FREQ IN2 LO RSP SRC OUT Lo IN1 HI DISPLY RATIO2 SP TRK D BAND IN1 LO LNGUAG BIAS 2 PWR UP HYST FILTR2 PWROUT FAILSF SP Hi FSMODE RATIO1 BIAS 1
INPUT2 CONTRL
DI COM PARITY CSP_BI A1S1TY A2S1HL BAUD LOOPBK A1S2TY A2S1EV A2S1TY A2S2HL A2S2TY A2S2EV WS_FLT TXDLY
STATUS
VERSON
24
4/00
Configuration
1 2
SET UP SET UP
Upper Display = SET Lower Display = TIMER (This is the first Set Up Group title) Sequentially displays the other Set Up group titles shown in the prompt hierarchy in Table 4-1 Configuration Prompt Hierarchy. You can also use the [L] [M] keys to scan the Set Up groups in both directions. Stop at the Set Up group title that describes the group of parameters you want to configure. Then proceed to the next step. Upper Display = the current value or selection for the first function prompt of the selected Set Up group. Lower Display = the first Function prompt within that Set Up group. Sequentially displays the other function prompts of the Set Up group you have selected. Stop at the function prompt that you want to change, then proceed to the next step.
FUNCTION
[L] [M]
Increments or decrements the value or selection that appears for the selected function prompt. If you change the value or selection of a parameter while in Set Up mode then decide not to enter it, press [MAN-AUTO/RESET] oncethe original value or selection is recalled. Enters value or selection made into memory after another key is pressed. Exits configuration mode and returns controller to the same state it was in immediately preceding entry into the Set Up mode. It stores any changes you have made. If you do not press any keys for 30 seconds, the controller times out and reverts to the mode and display used prior to entry into Set Up mode.
5 6
FUNCTION DISPLAY
4/00
25
Configuration
TIMER
DIS
PERIOD
102
0:01
145
START
103
KEY
155
L DISP
104
TREM
140
RESET
105
KEY
156
INCRMT
106
MIN
136
26
4/00
Configuration
Function Prompts Table 4-4 TUNING Group (Numeric Code 200) Function Prompts
Prompt English Numeric Code 201 Proportional Band or Gain Rate in Minutes Description Selection or Range of Setting Numeric Code English Factory Setting Reference Guide Page 143
PB or GAIN
PB = 0.1 to 1000 % Gain = 0.01 to 1000 0.00 to 10.00 minutes 0.08 or less = OFF 0.02 to 50.00 0.02 to 50.00
1.0
RATE T
202
0.00
148
I MIN or I RPM
203
Reset in minutes/repeat Reset in repeats/minute Manual Reset Proportional Band 2 or Gain 2 Rate 2 in Minutes Reset in minutes/repeat Reset in repeats/minute
1.0 1.0
136
204 205
-100 to 100 % Output PB = 0.1 to 1000 % Gain = 0.01 to 1000 0.00 to 10.00 minutes 0.08 or less = OFF 0.02 to 50.00 0.02 to 50.00
0.0 1.0
142 144
206
0.00
148
I2 MIN or I2 RPM
207
1.0 1.0
136
4/00
27
Configuration
Table 4-4 TUNING Group (Numeric Code 200) Function Prompts, continued
Prompt English Numeric Code 208 Cycle Time (Heat) Description Selection or Range of Setting Numeric Code English Factory Setting Reference Guide Page 129
CYC T1 or CT1X3
1 to 120 Cycle times are in either second or 1/3-second increments depending upon the configuration of RLY TYP in the Algorithm Set Up group.
20
CYC2T2 or CT2 X3
209
1 to 120
Cycle times are in either second or 1/3-second increments depending upon the configuration of RLY TYP in the Algorithm Set Up group. 0 to 4095 0 1 2 3 4 0 1 0 1 0 1 0 1 NONE CAL CONF VIEW ALL DIS ENAB DIS ENAB DIS ENAB DIS ENAB
20
130
SECUR LOCK
210 211
0 CAL
151 141
AUTOMA
212
Auto/Manual Key Lockout Autotune Key Lockout Run/Hold Key Lockout Setpoint Select Function Lockout
ENAB
121
A TUNE
213
ENAB
120
RN HLD
214
ENAB
150
SP SEL
215
ENAB
155
28
4/00
Configuration
Factory Setting
DIS
Single Setpoint Ramp Time Setpoint Ramp Final Setpoint Setpoint Rate
3 1000 DIS
Rate Up Rate Down Setpoint Ramp/Soak Programming Start Segment Number End Segment Number
0 0 DIS
STRSEG ENDSEG
308 309
-----
156 133
2 4 6 8 10 12
4/00
29
Configuration
Table 4-5 SPRAMP Group (Numeric Code 300) Function Prompts, continued
Prompt English RPUNIT Numeric Code 310 Engineering units for Ramp Segments Number of Program Recycles Guaranteed Soak Deviation Value Program Termination State Program State at Program End Reset Program to the Beginning Program starts at PV value Segment Ramp or Rate Time x = 1 through 11 0 1 0 1 0 1 0 1 Description Selection or Range of Setting Numeric Code 0 1 2 English TIME (hours:minutes) EU-M (Rate EU/Minute) EU-H (Rate EU/Hour) 0 to 99 recycles Factory Setting Reference Guide Page 150
TIME
RECYCL
311
---
149
SOKDEV
312
0 to 99 0 = No Soak LAST (Hold at last SP) FSAF (Manual mode/failsafe) DIS HOLD DIS KEY (Keyboard) DIS ENAB 0-99hours:0-59minutes Engineering Units/minute or Engineering Units /hour
---
152
PG END
313
---
145
STATE ToBEGN PVSTRT SGx RP SG1 SG3 SG5 SG7 SG9 SG11 SGx SP SG2 SG4 SG6 SG8 SG10 SG12 SGx TI SG2 SG4 SG6 SG8 SG10 SG12
155 156
151
317 320 323 326 329 332 318 321 324 327 330 333 319 322 325 328 331 334
---
151
---
152
30
4/00
Configuration
FUZZY
DIS
TUNE
402
TUNE
157
AT ERR
403
---
121
4/00
31
Configuration
CTRALG
ONOF PIDA PIDB PDMR TPSC (3 position step) RLY (Time simplex Relay 1) RLY2 (Time simplex Relay 2) CUR (Current simplex) TPSC (3 Position step) RLYD (Time duplex) CURD (Current duplex) CURT (Current/time duplex) TCUR (Time/current duplex) 100 (Full) 50 (Split) MECH (one sec. increments) S S (1/3 sec increments)
PIDA
OUTALG
502
Output Algorithm
depends on model
142
4-20RG
503
100
119
RLY TYP
504
MECH
149
32
4/00
Configuration
8888
UNITS
602
157
XMITR1
604
Transmitter Characterization
LIN
158
4/00
33
Configuration
Table 4-8 INPUT1 Group (Numeric Code 600) Function Prompts, continued
Prompt English Numeric Code 605 Input 1 High Range Value Input 1 Low Range Value Ratio on Input 1 Bias on Input 1 Filter for Input 1 Description Selection or Range of Setting Numeric Code English 999 to 9999 floating in engineering units 999 to 9999 floating in engineering units -20.0 to 20.0 -999 to 9999 0 to 120 seconds 0 = No Filter 0 1 2 3 NONE UP (Upscale) DOWN (Downscale) NOFS (No Failsafe) 0.01 to 1.00 (RADH & RADI only) 0 1 0 1 2 0 1 2 3 4 5 60 50 SP (Setpoint) PRY ( PV with Label) PRN (PV without Label) ENGL FREN GERM SPAN ITAL NUMB (Numeric) Factory Setting Reference Guide Page 136
IN1 HI
2400
IN1 LO
606
137
BRNOUT
610
UP
126
EMISS
611
Emissivity
1.0
133
FREQ
612
Power Line Frequency Defalut Display (Single Display models only) Language Selection
60
135
DISPLY
613
PRN
LNGUAG
614
ENGL
140
34
4/00
Configuration
IN2TYP
DIS 0-20 (mA) 4-20 (mA) 0-5 (Volts) 1-5 (Volts) 0-2 (Volts) English B EH EL JH JL KH KL NNMH NNML N90H N90L NIC R Numeric 13 14 15 16 17 18 19 20 21 22 23 24 25 English 999 to 9999 floating in engineering units 999 to 9999 floating in engineering units -20.0 to 20.0 -999 to 9999 0 to 120 seconds 0 = No Filter English S TH TL WH WL 100H 100L 200 500 RADH RADI LIN SrT
1-5V
LIN
159
2400
139
IN2 LO
704
139
4/00
35
Configuration
ONE
Automatic Switchover Value Local Setpoint Source Remote Setpoint Source Setpoint Tracking
ALSP
148
PWROUT
807
TPSC (Three Position Step Control) Output Start-up Mode Setpoint High Limit Setpoint Low Limit Control Output Direction
LAST
147
SP Hi SP Lo ACTION
2400 0 REV
36
4/00
Configuration
Table 4-10 CONTRL Group (Numeric Code 800) Function Prompts, continued
Prompt English Numeric Code 811 High Output Limit Description Selection or Range of Setting Numeric Code English Factory Setting Reference Guide Page 143
OUT Hi
100
OUT Lo
812
143
D BAND
813
Deadband
2.0
130
HYST
814
0.0 to 100.0 % of PV
0.5
135
FAILSF
815 816
0 to 100 % For 3 Position Step 0 (Closed position) 100 (Open position) No L (Mode does not clear once unit goes to FS Output) LACH (Unit goes to manual and FS output) GAIN PB MIN RPM
0.0
134
FSMODE
817
Failsafe Mode
NO_L
135
GAIN
145
MINRPM
819
MIN
142
4/00
37
Configuration
902 903
DIG IN
904
Auxiliary Output Low Scaling Factor Auxiliary Output High Scaling Factor Digital Input
0 100
119 119
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 0 1 2 3 4 5
None MAN LSP SP2 DIR HOLD PID2 RUN Begn NO I MNFS LOCK TIMR TUNE INIT RSP MNLT TRAK DIS + PD2 +DIR +SP2 +SP1 +RUN
NONE To Manual To Local SP 1 To Local SP 2 Direct Control Hold SPP/SP Ramp PID Set 2 Start a stopped SPP/SP Ramp SPP Reset Inhibit Integral Manual, Failsafe Output Keyboard Disable Start Timer Start Tune Init SP to PV Remote SP Latching Manual Output tracks Input 2 Disable PID Set 2 Direct Set Point 2 Set Point 1 Start SPP
131
DI COM
905
DIS
131
38
4/00
Configuration
ComADD SDENAB
1002 1003
0 ENAB
TX_DLY WS_FLT
1007 1008
1 FP_B
0 1 2 3
4/00
39
Configuration
LSP
40
4/00
Configuration
90
NONE
124
4/00
41
Configuration
Table 4-13 ALARMS Group (Numeric Code 1100) Function Prompts, continued
Prompt English AxSxHL A1S1 A1S2 A2S1 A2S2 AxSxEV A1S1 A1S2 A2S1 A2S2 ALHYST Numeric Code 1109 1110 1111 1112 Alarmx Setpoint State X = 1 or 2 Description Selection or Range of Setting Numeric Code 0 1 LOW HIGH English Low Alarm High Alarm Factory Setting Reference Guide Page 123
HIGH
0 1
BEGN
123
Alarm Hysteresis
0.0 to 100.0 % of span or full output as appropriate 0 1 0 1 2 3 NO L LACH DIS BK1 only BK2 only BK12 Alarms Disable Blocking Block Alarm 1 Block Alarm 2 Blocks both
0.0
121
ALARM1
1114
NO L
120
BLOCK
1115
DIS
126
42
4/00
Configuration
TUNING
ALGOR
SPRAMP
INPUT1
DECIMAL UNITS IN1TYP XMITR1 IN1 HI IN1 LO RATIO1 BIAS 1 RILTR1 BRNOUT EMIS FREQ DISPLY LNGUAG
_______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______
4/00
43
Configuration
Function Prompt ComSTA ComADD SDENAB SHDTIM PARITY BAUD TX_DLY WS_FLT SDMODE SHDSP UNITS CSRATO CSP_BI LOOPBACK A1S1VA A1S2VA A2S1VA A2S2VA A1S1TY A1S1TY A2S1TY A2S2TY A1S1HL A1S1EV A1S2HL A1S2EV A2S1HL A2S1EV A2S2HL A2S2EV ALHYST ALARM1 BLOCK
Value or Selection _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______
Factory Setting Disable 0 Enable 0 Odd 9600 1 FP_B Last LSP PCT 1.0 0 Disable 90 90 90 90 NONE NONE NONE NONE HIGH BEGN HIGH BEGN HIGH BEGN HIGH BEGN 0.0 NOL DIS
CONTRL
PIDSET SW VAL LSPS RSPSRC SP TRK PWR UP PWROUT SP Hi SP Lo ACTION OUT Hi OUT Lo D BAND HYST FAILSF FSMODE PBorGN MINRPM
_______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______
ONE 0.00 ONE NONE NONE MAN LAST 2400 0 REV 100 0 2.0 0.5 0.0 NOL GAIN MIN
ALARMS
OPTIONS
44
4/00
Monitoring
4/00
45
Monitoring
ALM 1 2 OUT 1 2
2300
DISPLAY MAN-AUTO RESET
SP 2300
FUNCTION
F C M A R L
PV
F - Fahrenheit being used C - Centigrade being used Mor A -Manual/Auto display R - Remote or Local SP2 setpoint active L - Local setpoint active Lower Display - Six alphanumeric characters Normal operation - display is blank unless configured for default prompt of PV or Setpoint) Configuration mode - displays functions and parameters
SET UP
AUTO TUNE
RUN HOLD
24868
46
4/00
Monitoring
Enter Set Up Mode Select any Set Up Group Security Code Entry
FUNCTION
[L] [M]
To enter a four digit number in the upper display (0001 to 4095) This will be your security code.
See Subsection 4.5 - Tuning Parameters Set Up Group prompts to select one of the above. Security Code (see Subsection 5.3)
4/00
47
Monitoring
Individual key lockout There are four keys that can be disabled to prevent unauthorized changes to the parameters associated with these keys. First set the Lock prompt to NONE. These keys are: AUTOTUNE Key - you can disable the Autotune key at configuration Set Up, group prompt Tuning, function prompt A TUNE RUN/HOLD Key - you can disable the Run/Hold key for Set Point Programming at configuration Set Up group prompt Tuning, function prompt RN HLD. AUTO/MAN Key - you can disable the Auto/Manual key at configuration Set Up, group prompt Tuning, function prompt AUTOMA FUNCTION Key - you can disable the Set Point Select function key at configuration Set Up group prompt Tuning, function prompt SP SEL. See Subsection 4.5 - Tuning Parameters Set Up Group prompts to enable or disable these keys. Key error When a key is pressed and the prompt Key Error appears in the lower display, it will be for one of the following reasons: Parameter not available or locked out Not in setup mode, press SET UP key first Individual key locked out.
48
4/00
Monitoring
ALM 1 2
A visual indication of each alarm Blinking 1 indicates alarm latched and needs to be acknowledged before extinguishing when the alarm condition ends
OUT 1 2 A or M
A visual indication of the control relays A visual indication of the mode of the controller AAutomatic Mode MManual Mode
F or C
L or R
A visual indication of setpoint being used L Local Setpoint is active R RSP or LSP 2 is active The upper display is used to show other annunciator functions TUNEAccutuning in progress RUNSP Program in progress HOLDSP Program on hold CSPControlling to the Computer Setpoint LOOPBKLoopback Test running
4/00
49
Monitoring
Viewing the operating parameters Press the DISPLAY key to scroll through the operating parameters listed in Table 5-3. The lower display will show only those parameters and their values that apply to your specific model. Table 5-3 Lower Display Key Parameter Prompts
Lower Display Description
OT
OUTPUTOutput value is percent; for Three Position Step control, this is an estimated motor position when no slidewire exists. LOCAL SETPOINT #1Also current setpoint when using SP Ramp. LOCAL SETPOINT #2 REMOTE SETPOINT INPUT 2 DEVIATIONMaximum negative display is 999.9. TUNING PARAMETER SELECTED SETwhere X is either 1 or 2. TIME REMAININGTime that remains on timer in Hours.Minutes ELAPSED TIMETime that has elapsed on timer in Hours.Minutes.
SP 2L RS 2ND DE PIDSX
RPXXXM AX Sn BI To BGn
SETPOINT RAMP TIMETime remaining in the setpoint ramp in minutes. AUXILIARY OUTPUT SP RATE SETPOINTCurrent setpoint for setpoint rate applications BIASDisplays the manual reset value for algorithm PD+MR. TO BEGINResets Setpoint Program back to beginning of the program.
50
4/00
Monitoring
Diagnostic Error Messages The UDC 2300 performs background tests to verify data and memory integrity. If there is a malfunction, an error message will be displayed. In the case of more than one simultaneous malfunction, the messages will be displayed sequentially on the lower display. If any of these error messages in Table 5-4 occur, refer to Section 10 Troubleshooting for information to correct the failure. Table 5-4 Error Messages
Prompt EE FAIL IN1FL IN2FL CFGERR Description Unable to write to nonvolatile memory. Two consecutive failures of input 1 integration. Two consecutive failures of input 2 integration. Configuration ErrorsLow limit greater than high limit for PV, SP, Reset, or Output. Input 1 Out-of-Range Out-of-range criteria: Linear range: 10 % out-of-range Characterized range: 1 % out-of-range Input 2 Out-of-RangeSame as Input 1. PV Out-of-Range PV = (PV source x PV source ratio) + PV source bias Failsafe conditions for failsafe are: EEROM Test Failed Scratch Pad RAM Test Failed Configuration Test Failed Field or Factory Cal Test Failed Check the Status group. RV LIM Remote Variable Out-of-Range RV = (RV source x RV source ratio) + RV source bias Segment ErrorSP Program starting segment number is less than ending segment number. The lockout feature has been enabled to prevent unauthorized changes of certain functions or parameters.
IN1RNG
IN2RNG PV LIM
FAILSF
SEG ERR
LOCK
4/00
51
Monitoring
52
4/00
Operation
6 Operation
6.1 Overview
Introduction This section gives you all the information necessary to operate your controller. Review the Operator Interface and Key Functions shown in Figure 3-1. Make sure you are familiar with the indicator definitions listed in Table 5-2. Whats in this section? The following topics are covered in this section. TOPIC 6.1 Overview 6.2 Single Display Functionality 6.3 Start Up Procedure for Operation 6.4 Control Modes 0 Setpoints 6.6 Timer 6.7 Accutune 6.8 Fuzzy Overshoot Suppression 6.9 Using Two Sets Of Tuning Constants 6.10 Alarm Setpoints 6.11 Three Position Step Control Algorithm 6.12 Setting A Failsafe Output Value For Restart After A Power Loss 6.13 Setting Failsafe Mode See Page 53 54 54 57 58 59 61 64 64 66 67 68 69
4/00
53
Operation
Exceptions There are three exceptions to the above rules. The displays for PID SET, Timer and Setpoint Ramp will appear the same as on a dual display model and, when displaying Timer or Ramp values, the default display switchover feature is disabled. Auto-only Mode The single display model is Auto only mode. The Auto/Manual key has no effect on controller mode. As a result of this, the failsafe mode is always non-latching. While a failsafe condition exists, the controller output will assume the failsafe value. When the failsafe condition goes away, normal automatic operation continues.
54
4/00
Operation
4/00
55
Operation
MAN/AUTO RESET
Until M indicator is ON. The controller is in manual mode. N/A for Single Display model.
[L] [M]
To adjust the output value and ensure that the final control element is functioning correctly. Upper Display = Pv Value Lower Display = OT and the output value in %
SET UP
Make sure the controller has been configured properly and all the values and selections have been recorder on the Configuration Record Sheet. Refer to Tuning Set Up group to ensure that the selections for PBor GAIN, RATE T, and I MIN, or I RPM have been entered. Use Accutune to tune the controller; see the procedure in this section.
Upper Display = Pv Value Lower Display = SP and the Local Setpoint Value to adjust the local setpoint to the value at which you want the process variable maintained. The local setpoint cannot be changed if the Setpoint Ramp function is running.
MAN/AUTO RESET
Until A indicator is ON. The controller is in Automatic mode. The controller will automatically adjust the output to maintain the process variable at setpoint. N/A for Single Display model.
56
4/00
Operation
4/00
57
Operation
6.5 Setpoints
Introduction You can configure the following setpoints for the UDC 2300 controller. A Single Local Setpoint 2 Local Setpoints a Local Setpoint and a Remote Setpoint Refer to Subsection 4.11 Control Set Up Group for configuration details. Changing the Setpoints Table 6-5 Procedure for Changing the Local Setpoints
Step 1 Operation Select the Setpoint Press DISPLAY Until you see: Upper Display = PV Lower Display = SP or 2L (Value) [L] [M] To change the Local Setpoint to the value at which you want the process maintained. The display blinks if you attempt to enter setpoint values beyond the high and low limits.. To store immediately or will store after 30 seconds. Result
Return to PV Display
DISPLAY
58
4/00
Operation
Switching between setpoints You can switch Local and Remote setpoints or between two Local setpoints when configured.
ATTENTION
you attempt to change the setpoint while a setpoint ramp is enabled, or if you attempt to change the setpoint with the setpoint select function key disabled.
6.6 Timer
Introduction The Timer provides a configurable Time-out period of from 0 to 99 hours:59 minutes or 0 to 99 minutes:99 seconds. Timer Start is selectable as either the RUN/HOLD key or Alarm 2. The Timer display can be either Time Remaining or Elapsed Time. Configuration check Make sure: TIMER is enabled A TIMEOUT period has been selected (in hours and minutes or minutes and seconds) A TIMER FUNCTION START has been selected (KEY or AL2) A TIMER display has been selected (Time remaining or Elapsed time) A timer increment selected Timer reset selected Refer to Subsection 4.4 - Timer Set Up Group for details.
4/00 UDC 2300 Controller Product Manual 59
Operation
Viewing Times The times are viewed on the lower display as follows: TIME REMAINING will show as a decreasing Hrs:Min value (HH:MM) or Min:Sec value (MM:SS) plus a counterclockwise rotating clock face. ELAPSED TIME will show as an increasing Hrs:Min value(HH:MM) or Min:Sec value (MM:SS) plus a clockwise rotating clock face.
Operation When the Timer is enabled (RUN/HOLD key or ALARM 2), it has exclusive control of Alarm 1 relay. At TIME-OUT: Alarm 1 is active The clock character has stopped moving The Time display shows either 00:00 or the time-out period depending on the configuration selection The Timer is ready to be reset At RESET: Alarm 1 relay is inactive The time display shows the time-out period The time-out period can be changed at this time using the L or M keys. The Timer is ready to be activated
60
4/00
Operation
6.7 Accutune II
Introduction AccutuneII (TUNE) may be used for self-regulating and single integrating processes. This autotuning method is initiated on-demand, typically at initial start-up. There are no other requirements necessary, such as prior knowledge to the process dynamics or initial or post tune process line-out to setpoint or manual output. Also, the setpoint value is not required to change in order to initiate the tuning process, but the controller must be in the Automatic mode to start tuning. Configuration check Make sure: TUNE has been enabled see to Subsection 4.7 - Accutune Set Up Group for details. Key Enabled see Subsection 4.5 Tuning Set Up Group for details. Tuning indicators TUNE will flash in the upper display until tuning is completed. Operation TUNE (Accutune II) algortihm provides foolproof, trouble-free on-demand tuning in the UDC 2300 controller. No knowledge of the process is required at start-up. The operator simply initiates the tuning while in the automatic mode. The UDC controller immediately starts controlling to the setpoint while it identifies the process, calculates the tuning constants and enters them into the Tuning group, and begins PID control with the correct tuning parameters. This works with any process, including integrating type processes, and allows retuning at a fixed setpoint. The tuning sequence will cycle the controllers output two full cycles between 0 % and 100 % (or low and high output limits) while allowing only a very small Process Variable change above and below the SP during each cycle. TUNE flashes in the upper display until tuning is completed. After TUNE has been enabled, you can start Accutune as shown in Table 6-7. Table 6-7 Procedure for Starting TUNE
Step 1 Operation Switch to Automatic Mode Initiate Accutune Press MAN/AUTO RESET AUTO TUNE Result Until you A indicator is lit.
4/00
61
Operation
Tune for Duplex (Heat/Cool) TUNE can be done for applications using Duplex (Heat/Cool) control. During tuning, Accutune II assumes SP 1 will cause a Heating demand, and then then the calculated tuning parameters will be automatically entered as PID SET 1. Likewise, it assumes tuning at Local SP 2 will cause a Cooling demand, and the cooling parameters will be entered as PID SET 2. Configuration Check for Duplex Make sure: TUNE has been enabled see to Subsection 4.7 - Accutune Set Up Group for details. Key Enabled see Subsection 4.5 Tuning Set Up Group for details.
Using TUNE at start-up for Duplex (Heat/Cool) Table 6-8 Procedure for Using TUNE at Start-up for Duplex Control
Step 1 Heat Zone: a. Adjust the Local SP1 to a value within the Heat Zone. b. Insure that the UDC is in Automatic mode. c. Press the AUTOTUNE key to initiate Heat zone tuning. The output will cycle between 50 % and 100 % (or high output limit). TUNE flashes in the upper display until tuning is completed and final Heat parameters are entered for PID Set 1 in the Tuning group. 2 Cool Zone: a. Adjust the Local SP2 to a value within the Cool Zone. b. Insure that the UDC is in Automatic mode. c. Press the AUTOTUNE key to initiate Cool tuning. The output will cycle between 0 % and 50 % (or low output limit). TUNE FLASHES IN THE UPPER DISPLAY UNTIL TUNING IS COMPLETED AND FINAL COOL PARAMETERS ARE ENTERED FOR PID SET 2 IN THE TUNING GROUP. Action
62
4/00
Operation
Error Codes Table 6-9 Procedure for Accessing Accutune Error Codes
Step 1 Operation Select Accutune Set-up Group Go to Error Code Prompt Press SET UP Upper Display = SET Lower Display = ATUNE FUNCTION Upper Display = (an error code) Lower Display = ATERR Table 6-10 lists all the error codes, definitions, and fixes. Result
IDFL
ABRT
Aborting Accutune To abort Accutune and return to the last previous operation (SP or output level), press MAN-AUTO/RESET key to abort the Accutune process. Completing Accutune When Accutune is complete, the calculated tuning parameters are stored in their proper memory location in the controller, and the controller will control at the local setpoint using the newly calculated tuning constants.
4/00
63
Operation
or
64
4/00
Operation
FUNCTION
Until you see: Upper Display = (available selections) Lower Display = PID SETS To select the type of function. Available selections are:
ONE1 set of constants 2 KBD2 sets, keyboard selectable 2 PR2 sets, auto switch at PV value 2 SP2 sets, auto switch at SP value
[L] [M]
Refer to TUNING Set up group, subsection 4.5 and set the following tuning parameters: PB or GAIN* RATE T* I MIN or I RPM* CYCT1 or CTIX3* PB2 or GAIN2** RATE 2T** I2MIN or I2RPM** CYC2T2 or CT2X3** *PIDSET1 will be used when PV or SP, whichever is selected, is greater than the switchover value. **PIDSET2 will be used when PV or SP, whichever is selected, is less than the switchover value.
FUNCTION
Until you see: Upper Display = (the switchover value) Lower Display = SW VAL
[L] [M]
Switch between two sets via keyboard (without automatic switch-over) Table 6-12 Procedure for Switching PID SETS from the Keyboard
Step 1 Operation Select Control Set-up Group Press DISPLAY Result Until you see: Upper Display = (the PV value) Lower Display = PIDS X 2 [L] [M] (X= 1 or 2)
To change PID SET 1 to PID SET2 or Vice Versa. You can use Accutune on each set.
4/00
65
Operation
3 4
66
4/00
Operation
4/00
67
Operation
6.12 Setting a Failsafe Output Value for Restart After a Power Loss
Introduction If the power to the controller fails and power is reapplied, the controller goes through the power up tests, then goes to a user configured FAILSAFE OUTPUT VALUE. Set a Failsafe Value Table 6-15 Procedure for Setting a Failsafe Value
Step 1 Operation Select Control Set-up Group Press SET UP Until you see: Upper Display = SET Lower Display = CONTRL 2 Select Failsafe Function Prompt FUNCTION You will see: Upper Display = (range) within the range of the Output 0 to 100 for all output types except 3 Position Step 3 Position Step 0 = motor goes to closed position 100 = motor goes to open position Lower Display = FAILSF To select a failsafe output value in the upper display At power up, the output will go to the value set. Result
3 4
68
4/00
Operation
3 4
4/00
69
Operation
70
4/00
This section explains the operation of each selection and configuration reference where necessary. ATTENTION
For any option to function, the other options must be disabled (see Subsection 4.6 Configuration).
PV Hot Start This is a standard feature. At power-up, the setpoint is set to the current PV value and the Rate or Ramp or Program then starts from this value. RUN/HOLD key You can start or stop the Ramp or Program using the RUN/HOLD key. Whats in this section? The following topics are covered in this section. TOPIC 7.2 Setpoint Rate 7.3 Setpoint Ramp 7.4 Setpoint Ramp/Soak Programming See Page 72 72 74
4/00
71
ATTENTION: A value of 0 will imply an immediate change in setpoint, that is, NO RATE applies. See Subsection 4.6 Configuration group SPRAMP for details.) Operation When a change to local setpoint is made, this controller will ramp from the original setpoint to the target setpoint at the rate specified. The current setpoint value can be viewed at Sn on the lower display. Power outages If power is lost before the target setpoint is reached, upon power recovery, the controller powers up with Sn = Current PV value and it automatically Restarts from Sn = current PV value up to the original target setpoint.
72
4/00
Operation Running a Setpoint Ramp includes starting, holding, viewing the ramp, ending the ramp and disabling it. See Table 7-1. Table 7-1 Running A Setpoint Ramp
Step 1 Operation Select Automatic Mode Press MAN/AUTO Result A indicator is on. Upper Display = Hold and PV value Lower Display = SP and Present value Until start SP value is in lower display Upper Display = Hold and PV value Lower Display = SP and start SP value 3 Start the Ramp RUN/HOLD You will see Upper Display = Run and a changing PV value Lower Display = SP and a changing SP value increasing or decreasing toward a final SP value This holds the ramp at the current setpoint value. Press again to continue. Until you see Upper Display = RUN or HOLD and the PV value Lower Display = RP xx HH.MM (time remaining) When the final setpoint is reached, RUN changes to HOLD in the upper display and the controller operates at the new final setpoint. See Section 4 Configuration group SPRAMP for details.
DISPLAY
Hold/Run the Ramp View the remaining ramp time End the Ramp
RUN/HOLD
DISPLAY
Disable SPRAMP
Power Outage If power is lost during a ramp, upon power-up the controller will be in HOLD and the setpoint value will be the setpoint value prior to the beginning of the setpoint ramp. The ramp is placed in hold at the beginning. Configure the mode at Set Up Group CONTROL, function prompt PWRUP. See Subsection 4.11 CONTRL GROUP FUNCTION Prompts.
4/00
73
74
4/00
ATTENTION Entering 0 will imply an immediate step change in setpoint to the next soak.
Ramp unit The ramp unit selection determines the engineering units for the ramp segments. The selections are: TIME = Hours:Minutes (XX:XX) Range: 0-99 hr.:0-59 min EU-H = Degrees/Hour OR EU-M = Degrees/Minute (Range 0-999) Soak segments A soak segment is a combination of soak setpoint (value) and a soak duration (time). Soaks are even number segments. Segment 2 will be the initial soak value and soak time. The soak setpoint range value must be within the setpoint high and low range limits in engineering units. Soak time is the duration of the soak and is determined in: TIME - Hours:Minutes Start segment number Range = 0-99 hr.:59 min.
The start segment number designates the number of the first segment. Range = 1 to 11
End segment number The end segment number designates the number of the last segment, it must be a soak segment (even number). Range = 2 to 12 Recycle number The recycle number allows the program to recycle a specified number of times from beginning to end. Range = 0 to 99
4/00
75
Definition All soak segments can have a deviation value of from 0 to 99 (specified by SOK DEV) which guarantees the value for that segment. Guaranteed soak deviation values >0 guarantee that the soak segments process variable is within the deviation for the configured soak time. Whenever the deviation is exceeded, soak timing is frozen. There are no guaranteed soaks whenever the deviation value is configured to 0, (that is, soak segments start timing soak duration as soon as the soak setpoint is first reached, regardless of where the process variable remains relative to the soak segment). The soak deviation value is the number in engineering units, above or below the setpoint, outside of which the timer halts. The range is 0 to 99. The decimal location corresponds to input 1 decimal selection.
PV Start
This function determines whether LSP1 or PV is used as the setpoint when the program is initially changed from HOLD to RUN. The selections are: DISABL = When the program is initially changed from HOLD to RUN the present LSP1 value is captured as the default setpoint. If the program is terminated or the power cycled before the program has completed, the LSP1 is used as the control setpoint. The beginning segment uses this value as the initial ramp setpoint. ENABL = When the program is initially changed from HOLD to RUN the present PV value is captured and used as the beginning setpoint value for the ramp segment. If the program is terminated before completion, the setpoint value will revert back to the PV value captured at the initial HOLD to RUN transition. If the power is cycled before program completion, upon power-up the setpoint is set to the PV value at power-up and when the program is restarted that setpoint value is used initially.
Program state
The program state selection determines the program state after completion. The selections are: DIS = program is disabled (so program value changed to DIS) HOLD = program on hold
The program termination state function determines the status of the controller upon completion of the program. The selections are: LAST = controls to last setpoint FSAF = manual mode and failsafe output.
When enabled, this selection allows you to reset the program to the beginning from the keyboard.
76
4/00
Ramp/soak profile example Before you perform the actual configuration, we recommend that you draw a Ramp/Soak profile in the space provided on the Program Record Sheet (Figure 7-2) and fill in the associated information. An example of a Ramp-Soak Profile is shown in Figure 7-1. Start setpoint is at 200 degrees F.
4/00
77
Setpoint 500
SEG 8 SEG 9
400 F F 300
SEG 6
SG 12
10
11
12
13
14 15
16
17
20765
78
4/00
Program record sheet Draw your ramp/soak profile on the record sheet shown in Figure 7-2 and fill in the associated information in the blocks provided. This will give you a permanent record of your program and will assist you when entering the Setpoint data.
20766
4/00
79
Run/Monitor the program Prior to running the program, make sure all the SP PROG function prompts under the Set Up group SP RAMP have been configured with the required data. HOLD appears periodically in the upper display indicating that the program is in the HOLD state. SP Programmer parameter cannot be changed during RUN state (must be in HOLD state). Run/Monitor functions Table 7-3 lists all the functions required to run and monitor the program. Table 7-3 Run/Monitor Functions
Function Set the Local Setpoint Press DISPLAY Result Upper Display = PV value Lower Display = SP To set the Local Setpoint value to where you want the program to start out. Initiates the setpoint program. RUN appears in the upper display indicating that the program is running. Hold State RUN/HOLD Holds the setpoint program. HOLD appears in the upper display indicating that the program is in the HOLD state. The setpoint holds at the current setpoint. External Hold If Remote Switching (Digital Input Option) is present on your controller, contact closure places the controller in the HOLD state, if the setpoint program is running. The HOLD in the upper display will be displayed periodically in lower case.
ATTENTION
ATTENTION The keyboard takes priority over the external switch for the RUN/HOLD function.
Contact reopening runs program. Viewing the present ramp or soak segment number and time DISPLAY until you see Upper Display = PV value Lower Display = XXHH.MM Time remaining in the SEGMENT in hours and minutes. XX = 1 to 12 continued
80
4/00
Result Upper Display = PV value Lower Display = REC_XX Number of cycles remaining in the setpoint program. X = 0 to 99 When the final segment is completed, the RUN in the upper display either changes to HOLD (if configured for HOLD state), or disappears (if configured for disable of setpoint programming). The controller either operates at the last setpoint in the program or goes into manual mode/failsafe output.
End Program
Disable Program
Power outage If power is lost during a program, upon power-up the controller will be in hold and the setpoint value will be the setpoint value prior to the beginning of the setpoint program. The program is placed in hold at the beginning. The mode will be as configured under PWR UP in the CONTROL group.
ATTENTION
Digital input (remote) operation Program can be placed in RUN or HOLD state through a remote dry contact connected to optional digital input terminals, as follows: RUNcontact closure places Program in RUN state, OR HOLDcontact closure places Program in HOLD state Opening contact reverts to original state.
4/00
81
82
4/00
Input Calibration
8 Input Calibration
8.1 Overview
Introduction This section describes the field calibration procedures for Input 1 and Input 2. Every UDC 2300 controller contains all input actuation ranges which are fully factory-calibrated and ready for configuration to range by the user. However, these procedures can be implemented if the factory calibration of the desired range is not within specification.
CAUTION
The field calibration will be lost if a change in input type configuration is implemented at a later time. The original factory calibration data remains available for later use after a field calibration is done. See subsection 8.8 if you want to restore factory calibration values.
Whats in this section? The following topics are covered in this section. TOPIC 8.1 Overview 8.2 Minimum and Maximum Range Values 8.3 Preliminary Information 8.4 Input #1 Set Up Wiring 8.5 Input #1 Calibration Procedure 0 Input #2 Set Up Wiring See Page 83 84 85 87 89 91 92 93
WARNINGSHOCK HAZARD
INPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN ONE SWITCH MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE CALIBRATION.
4/00
83
Input Calibration
84
4/00
Input Calibration
Sensor Type F T T (low) W5W26 W5W26 (low) Honeywell Radiamatic Type RH Type RI RTD (IEC Alpha=0.00385) 100 ohms 100 ohms (low) 200 ohms 500 ohms Linear Milliamps (impedance 249 ) Millivolts -300 -300 -300 -300 to to to to
0 to 3400 0 to 3200
18 to1871 18 to1760
0.00 mV 0.00 mV
57.12 mV 60.08 mV
4.00 mA 0.00 mA 0.00 mV 0.00 mV 0.00 mV 1.00 Volts 0.00 Volts 0.00 Volts 0.00 Volts
20.00 mA 20.00 mA 10.00 mV 50.00 mV 100.00 mV 5.00 Volts 2.00 Volts 5.00 Volts 10.00 Volts
Volts
24869
4/00
85
Input Calibration
Check the Jumper for Input 1 Before you calibrate Input #1, check the internal jumper for Input 1 to make sure it is set for the correct input type. The jumper is located at position S101 on the printed wiring board. Figure 2-2 shows the location of the jumper and position selections. Check the Jumper for Input 2 Before you calibrate Input #2, check the internal jumper for Input 2 to make sure it is set for the correct input type. The jumper is located at position S201 on the printed wiring board. Figure 2-2 shows the location of the jumper and position selections. Equipment Needed Table 8-2 lists the equipment you will need to calibrate the specific types of inputs that are listed in the table. You will need a screwdriver to connect these devices to your controller. Table 8-2 Equipment Needed
Type of Input Equipment Needed
A calibrating device with 0.02 % accuracy for use as a signal source such as a millivolt source. Thermocouple extension wire that corresponds with the type of thermocouple that will be used with the controller input. Two insulated copper leads for connecting the thermocouple extension wire from the ice baths to the mV source. Two containers of crushed ice. A calibrating device with 0.02 % accuracy for use as a signal source such as a millivolt source. Thermocouple extension wire that corresponds with the type of thermocouple that will be used with controller input. A decade box, with 0.02 % accuracy, capable of providing stepped resistance values over a minimum range of 0 to 1400 ohms with a resolution of 0.1 ohm. Three insulated copper leads of equal length for connecting the decade box to the controller. A calibrating device with 0.02 % accuracy for use as a signal source. Two insulated copper leads for connecting the calibrator to the controller. Place current source at zero before switching ON. Do not switch current sources OFF/ON while connected to the UDC 2300 input.
ATTENTION: For radiamatic inputs only, set emissivity value to 1.0. See Subsection 4.9 Configuration Set Up prompt INPUT1, function prompt EMISS.
86
4/00
Input Calibration
Millivolt Source
+ _ Ice Bath
+ _
8 7
24872
Copper Leads
Figure 8-2 Wiring Connections for Thermocouple Inputs Using an Ice Bath Thermocouple Inputs Using a Thermocouple Source Refer to Figure 8-3 and wire the controller according to the procedure given in Table 8-4. Make sure the jumper at S101 is in the #1 position. See Figure 2-2 Jumper Placements. Table 8-4 Set Up Wiring Procedure for Thermocouple Inputs using Thermocouple Source
Step 1 Action Connect the thermocouple extension wires to the terminals for Input #1 as shown in Figure 8-3.
Thermocouple + _ Source
8+ 7_
24873
Figure 8-3 Wiring Connections for Thermocouple Inputs Using Thermocouple Source
4/00
87
Input Calibration
RTD Inputs Refer to Figure 8-4 and wire the controller according to the procedure given in Table 8-5. Make sure the jumper at S101 is in the #2 position. See Figure 2-2 Jumper Placements Table 8-5 Set Up Wiring Procedure for RTD Inputs
Step 1 Action Connect the copper leads from the calibrator to the Input #1 terminals as shown in Figure 8-4. Place current source at zero before switching on. Do not switch current sources ON/OFF while connected to the UDC 2300 input.
2 3
8+ 7_ 6R
24875
Radiamatic, Millivolts, Milliamperes, or Volts Refer to Figure 8-5 and wire the controller according to the procedure given in Table 8-6. Make sure the jumper at S101 is in the #2 position for, mV, Volts, or the #4 position for mA. See Figure 2-2 Jumper Placements. Table 8-6 Set Up Wiring Procedure for Radiamatic, Milliampere, Millivolts, or Volts Inputs (Except 0-10 Volts)
Step 1 Action Connect the copper leads from the calibrator to the Input #1 terminals as shown in Figure 8-5. Place current source at zero before switching on. Do not switch current sources ON/OFF while connected to the UDC 2300 input.
2 3
ATTENTION
For radiamatic inputs only, set emissivity value to 1.0. See Subsection 4.9 Configuration Set Up prompt INPUT1, function prompt EMISS. Continued next page
88
4/00
Input Calibration
8+ 7_
24876
Figure 8-5 Wiring Connections for Radiamatic, Milliampere, Millivolts, or Volts (Except 0 to 10 Volts)
0 to 10 Volts Refer to Figure 8-6 and wire the controller according to the procedure given in Table 8-7. Make sure the jumper at S101 is in parked position. See Figure 2-2 Jumper Placements. Table 8-7 Set Up Wiring Procedure for 0 to 10 Volts
Step 1 Action Connect the copper leads from the calibrator to the Input #1 terminals as shown in Figure 8-6. Place current source at zero before switching on. Do not switch current sources ON/OFF while connected to the UDC 2300 input.
2 3
+ Volt Source _
1 2 3
8+ 7 _
6R
24877
CAUTION
For linear inputs, avoid step changes in inputs. Vary smoothly from initial value to final 100 % value.
4/00
89
Input Calibration
Procedure The calibration procedure for Input #1 is listed in Table 8-8. The numeric codes are also listed. Table 8-8 Input 1 Calibration Procedure (Numeric Code 10000)
Step Operation Press SET UP until you see FUNCTION Result
Upper Display = CAL ( - - - - ) Lower Display = INPUT1 (10000) You will see: Upper Display = DIS ( 0 ) Lower Display = CALIN1 (10001)
The calibration sequence is enabled and you will see: Upper Display = BEGN ( 1 ) Lower Display = CALIN1 (10001) At the completion of the sequence, the selection automatically reverts to disable.
Calibrate 0 %
FUNCTION
You will see: Upper Display = APLY ( 2 ) Lower Display = IN1ZRO (10002) Adjust your calibration device to an output signal equal to the 0 % range value for your particular input sensor. See Table 8-1 for Voltage, Degrees, or Resistance equivalents for 0 % range values. Wait 15 seconds, then go to the next step.
3 Calibrate 100 %
FUNCTION
You will see: Upper Display = APLY ( 2 ) Lower Display = IN1SPN (10003) Adjust your calibration device to an output signal equal to the 100 % range value for your particular input sensor. See Table 8-1 for Voltage, Degrees, or Resistance equivalents for 100 % range values. Wait 15 seconds, and If you are calibrating a Thermocouple input you are calibrating other than a Thermocouple input Then go to step 4 go to step 5
90
4/00
Input Calibration
Step
Operation
Press
Result
FUNCTION
The calculations for zero and span are now stored and you will see: Upper Display = The cold junction temperature at the rear terminals Lower Display = CJTEMP (10004) The value in the upper display is in tenths of a degree. It is the current reading of the temperature as measured at the thermocouple terminals and recognized by the controller. You can change this value, if it is in error, using the [L] [M] keys. NOTE: The accuracy of the controller is directly affected by the accuracy of this value. Change this value only if the zero and span calibration procedures did not bring the controller within the specified accuracy requirements.
The controller stores the calibration constants and exits the calibration mode.
15+ 16 _
4/00
91
Input Calibration
0 to 2 Volts, 0 to 5 Volts, or 1 to 5 Volt Inputs Use the copper leads and connect the calibrator to the rear terminals of Input #2 (see Figure 8-8). Make sure the jumper of S201 is set for Volts (position 2). See Figure 2-2 Jumper Placements.
92
4/00
Input Calibration
Procedure The calibration procedure for Input #2 is listed in Table 8-9. The numeric codes are also listed. Table 8-9 Input 2 Calibration Procedure (Numeric Code 20000)
Step Operation Press SET UP until you see FUNCTION Result
Upper Display = CAL ( - - - - ) Lower Display = INPUT2 (20000) You will see: Upper Display = DIS ( 0 ) Lower Display = CALIN2 (20001)
You will see: Upper Display = BEGN ( 1 ) Lower Display = CALIN2 (20001)
Calibrate 0 %
FUNCTION
You will see: Upper Display = APLY ( 2 ) Lower Display = IN2ZRO (20002) Adjust your calibration device to an output signal equal to the 0 % range value for your particular input sensor. Wait 15 seconds, then go to the next step.
Calibrate 100 %
FUNCTION
You will see: Upper Display = APLY ( 2 ) Lower Display = IN2SPN (20003) Adjust your calibration device to an output signal equal to the 100 % range value for your particular input sensor. Wait 15 seconds, then go to the next step.
FUNCTION DISPLAY
The controller stores the calibration constants. To store the calibration constants and exit the calibration mode.
Input Calibration
ATTENTION: A restored factory calibration overwrites any previous field calibration done for the input and may change the High and Low Range Limits. Be sure to protect any field calibration from accidental overwrites by configuring the appropriate LOCKOUT selection after calibration. See the Section 4 - Configuration for specific instructions to set the lockout. Table 8-10 Restore Factory Calibration
Step Operation Press SET UP Result
until you see: Upper Display = SET UP Lower Display = TUNING Until you see: Upper Display = one of the following: NONE all parameters are read/write CAL all parameters are read/write except Calibration CONF configuration parameters are Read Only; no writes permitted VIEW Tuning and Setpoint Ramp parameters are read/write. No other parameters can be viewed. ALL Tuning and Setpoint Ramp parameters are available for read only. No other parameters can be viewed. Lower Display = LOCK
FUNCTION
Until NONE is in the upper display until you see: Upper Display = SET UP Lower Display = INPUT 1 or 2 until you see: Upper Display = the current selection Lower Display = INxTYP to change the current selection to another selection
until the lower display rolls through the rest of the functions and returns to:
FUNCTION
Upper Display = the new selection Lower Display = INxTYP [L] [M]
until you change the input selection in the upper display back to the proper selection. You will see:
Upper Display = Original Input Selection that matches your type of sensor. Lower Display = INxTYP 4 Return to Normal Operation DISPLAY
to return to Normal operating mode. The factory calibration will be restored. If the problem is not corrected, contact the Honeywell Technical Assistance Center. 1-800-423-9883 USA and Canada
94
4/00
Troubleshooting/Service
9 Output Calibration
9.1 Overview
Introduction This section describes the field calibration procedures for the following types of outputs: Current Proportional Output Auxiliary Output Motor Travel Time Setting for Three Position Step
Whats in this section? The following topics are covered in this section. TOPIC 9.1 Overview 0 Current Proportional Output Calibration See Page 95 96 98 100
9.3 Auxiliary Output Calibration 9.4 Three Position Step Control Output Calibration
WARNINGSHOCK HAZARD
OUTPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN ONE SWITCH MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE CALIBRATION.
4/00
95
Troubleshooting/Service
Milliammeter
+ _
5+ _ 4
24880
96
4/00
Troubleshooting/Service
Procedure The procedure for calibrating the Current Proportional Output is listed in Table 9-2. The numeric codes are also listed. Make sure LOCK in the Tuning Set Up group is set to NONE. (See Subsection 4.5 Tuning Set Up Group.) Table 9-2 Current Proportional Output Calibration Procedure (Numeric Code 30000)
Step Operation Press SET UP Result
Upper Display = CAL ( - - - - ) Lower Display = CURENT (30000) You will see: Upper Display = A Value Lower Display = ZROVAL (30001)
[L] [M]
Until the desired 0 % output is read on the milliammeter, use the values shown below depending on the action of your controller. 0 mA 4 mA For 0 to 20 mA Direct Action For 4 to 20 mA Direct Action
Calibrate 100 %
FUNCTION
This stores the 0 % value and you will see: Upper Display = A Value Lower Display = SPNVAL (30002)
[L] [M]
Until the desired 100 % output is read on the milliammeter, use the values shown below depending on the action of your controller. 20 mA For 0 to 20 mA Direct Action 20 mA For 4 to 20 mA Direct Action 4 mA 0 mA For 4 to 20 mA Reverse Action For 0 to 20 mA Reverse Action
FUNCTION DISPLAY
The controller stores the span value. To exit the calibration mode.
4/00
97
Troubleshooting/Service
Milliammeter
13 14
+ _
24881
98
4/00
Troubleshooting/Service
Procedure The procedure for calibrating the auxiliary output is listed in Table 9-4. The numeric codes are also listed. Make sure LOCK in the Tuning Set Up group is set to NONE (see Subsection 4.5). Table 9-4 Auxiliary Output Calibration Procedure (Numeric Code 50000)
Step Operation Press SET UP Result
Upper Display = CAL ( - - - - ) Lower Display = AUXOUT (50000) You will see: Upper Display = A Value Lower Display = ZROVAL (50001)
[L] [M]
until the desired 0 % output is read on the milliammeter, use the values shown below depending on the action of your controller. To store the 0 % value you will see: Upper Display = A Value Lower Display = SPNVAL (50002)
Calibrate 100 %
FUNCTION
[L] [M]
FUNCTION DISPLAY
The controller stores the span value. To exit the calibration mode.
4/00
99
Troubleshooting/Service
ATTENTION
Action Until you see Upper Display = CAL ( - - - - ) Lower Display = TPSC (40000)
Set Motor Traverse Time NOTE: This is the time it takes the motor to travel from 0 % to 100 %.
FUNCTION
Until you see Upper Display = a value Lower Display = MTR TI (40001)
[L] [M]
until the proper motor stroke time is reached (see the motor specs or measure the time) Range of setting = 5 to 1800 Seconds
The controller will store the 100 % value. To exit the calibration mode.
100
4/00
Troubleshooting/Service
10 Troubleshooting/Service
10.1 Overview
Introduction Instrument performance can be adversely affected by installation and application problems as well as by hardware problems. We recommend that you investigate the problems in the following order: installation related problems application related problems hardware and software related problems and use the information presented in this section to solve them. Whats in this section? The following topics are covered in this section. TOPIC 10.1 10.2 Overview Troubleshooting Aids Overall Error Messages Controller Failure Symptoms Customer Support Determining the Software Version Number Power-up Tests Status Tests Background Tests Controller Failure Symptoms Troubleshooting Procedures Power Failure Current Proportional Output Failure Time Proportional Output Failure Time/Current - Current/Time Proportional Output Failure Alarm Relay Output Failure Keyboard Failure See Page 101 102
4/00
101
Troubleshooting/Service
Installation related problems Read the Installation section in this manual to make sure the UDC 2300 has been properly installed. The installation section provides information on protection against electrical noise, connecting external equipment to the controller, and shielding and routing external wiring. System noise induced into the controller will result in diagnostic error messages recurring. If the diagnostic error messages can be cleared, it indicates a soft failure and is probably noise related. If system noise is suspected, completely isolate the controller from all field wiring. Use calibration sources to simulate PV and check all controller functions; i.e. Gain, Rate, Reset, Output, Alarms, etc. Application related problems Review the application of the controller; then, if necessary, direct your questions to the local sales office. Hardware and software related problems Use the troubleshooting error message prompts and controller failure symptoms to identify typical failures which may occur in the controller. Follow the troubleshooting procedures to correct them.
ATTENTION
102
4/00
Troubleshooting/Service
Customer support If you cannot solve the problem using the troubleshooting procedures listed in this section, you can get technical assistance by dialing 1-800-423-9883 USA and Canada. An engineer will discuss your problem with you. Please have your complete model number, serial number, and Software version available. The model and serial numbers can be found on the chassis nameplate. The software version can be viewed under Setup Group Status. See Table 10-1. If it is determined that a hardware problem exists, a replacement controller or part will be shipped with instructions for returning the defective unit. Do not return your controller without authorization from Honeywells Technical Assistance Center or until the replacement has been received. For a list of frequently asked questions and their answers, dial Honeywells Faxback 24 hour Service: 1-888-423-9883 USA Or check out Honeywells web site at http://www.honeywell.com/sensing. Determining the software version Table 10-1 lists the procedure for identifying the software version number. Table 10-1 Procedure for Identifying the Software Version
Step Operation Press Result
SET UP
FUNCTION You will see: Upper Display = Software version number A1xx Basic Controller and Indicator A2xx Limit Controller Lower Display = VERSON (1201) Please give this number to the Customer Support person. It will indicate which version of UDC 2300 you have and help them determine a solution to your problem.
4/00
103
Troubleshooting/Service
FUNCTION You will see: Upper Display = NO ( 0 ) or YES ( 1 ) YES indicates a failure Lower Display = FAILSF ( 1202) FUNCTION Upper Display = PASS ( 0 ) or FAIL ( 1 ) Lower Display = TEST (1203)
104
4/00
Troubleshooting/Service
FAILSF
This error message shows whenever 1. Run through STATUS check to determine the the controller goes into a failsafe mode reason for the failure. of operation. This will happen if: 2. Press the SET UP key until STATUS appears RAM test failed in the lower display. Configuration test failed 3. Press the FUNCTION key to see whether the Calibration test failed tests pass or fail, then run through the Burnout configured for none STATUS codes a second time to see if the and the input failed. error cleared. Input 1 out of range. The process input 1. Make sure the range and actuation are is outside the range limits. configured properly. 2. Check the input source. 3. Restore the factory calibration. (See Subsection 8.8.) 4. Field calibrate. See Section 8 - Input Calibration.
IN1RNG
IN1_FL
Two consecutive failures of input 1 1. Make sure the actuation is configured integration; i.e., cannot make analog to correctly. See Section 4 - Configuration. digital conversion. This will happen if: 2. Make sure the input is correct. Upscale or Downscale burnout 3. Check for gross over-ranging. Check S101 is selected jumper position. See Figure 2-2 Jumper Input not configured correctly Placements. 4. Restore factory calibration. See Subsection 8.8. Input 2 out of range. The remote input is outside the range limits. Same as IN1RNG above.
IN2RNG
4/00
105
Troubleshooting/Service
Two consecutive failures of input 2 Same as IN1FL above. integration. i.e., cannot make analog to digital conversion. PV low limit is > PV high limit SP low limit is > SP high limit Output low limit > Output high limit PV out of range. PV = INP1 x RATIO1+ INP1 BIAS 1. Check the configuration for each item and reconfigure if necessary.
CNFERR
PV LIM
1. Make sure the input signal is correct. 2. Make sure the Ratio and Bias settings are correct. 3. Recheck the calibration. Use Bias of 0.0
RV LIM
The result of the formula shown below is beyond the range of the remote variable. RV = INP2 X RATIO + BIAS
1. Make sure the input signal is correct. 2. Make sure the Ratio2 and Bias2 settings are correct. 3. Recheck the calibration. Use a Ratio2 of 1.0 and a Bias2 of 0.0. 1. Check SP Program configuration, subsection 4.6 Set up Group SPPROG function prompts STRSEG and ENDSEG.
SEGERR
Setpoint Program start segment number is less than ending segment number.
106
4/00
Troubleshooting/Service
Off OK
OK OK OK
OK OK OK
3 4 5
OK
OK
OK
Keyboard Malfunction
Other symptoms If a set of symptoms or prompts other than the one you started with appears while troubleshooting, re-evaluate the symptoms. This may lead to a different troubleshooting procedure. If the symptom still persists, refer to the installation section in this manual to ensure proper installation and proper use of the controller in your system.
4/00
107
Troubleshooting/Service
WARNINGSHOCK HAZARD
TROUBLESHOOTING MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN ONE SWITCH MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE SERVICING.
Equipment needed You will need the following equipment in order to troubleshoot the symptoms listed in the tables that follow: DC Milliammeter mAdc Calibration sources T/C, mV, Volt, etc. Voltmeter
108
4/00
Troubleshooting/Service
Procedure #1 Table 10-5 explains how to troubleshoot power failure symptoms. Table 10-5 Troubleshooting Power Failure Symptoms
Step 1 What to do Check the AC line voltage. How to do it Use a voltmeter to measure the AC voltage across terminals L1 and L2 on the rear terminal panel of the controller. Check the earth ground connection. 2 3 Make sure the chassis plugs into Withdraw the chassis and visually inspect the the rear of the case properly. controller board and the inside of the case. Check the system for Brownouts, heavy load switching, etc., and conformance to installation instructions. Change Main board. Refer to Section 2 - Installation.
Procedure #2 Table 10-6 explains how to troubleshoot Current Proportional Output failure symptoms. Table 10-6 Troubleshooting Current Proportional Output Failure
Step 1 What to do Make sure the controller is configured for Current output. How to do it Make Algorithm Set Up group function prompt OUT ALG = CUR. Refer to Section 4 - Configuration. 2 3 Check the field wiring. Check the output. Output impedance must be less than or equal to 750 ohms. Put the controller into Manual mode and change the output from 0 % to 100 % (4-20 mA). Use a DC milliammeter at the rear terminals to verify the output. Refer to Section 9 - Output Calibration for details. Installation instructions provided with new board.
4 5 6
Recalibrate the Current Proportional output. Change Main board. Change Controller
4/00
109
Troubleshooting/Service
Procedure #3 Table 10-7 explains how to troubleshoot Time Proportional Output failure. Table 10-7 Troubleshooting Time Proportional Output Failure
Step 1 What to do How to do it Make sure the controller is configured Make Output Algorithm Set Up group function for Time Proportional output. prompt OUTALG = RLY or RLYD. Refer to Section 4 - Configuration. 2 Check the field wiring. Make sure the NO or NC contact selection is correct. Refer to Section 2 - Installation for details. 3 4 Check the output (control) relay jumper position. Check the output. Refer to Section 2 Installation for relay jumper placement and relay contact information. Put the controller into Manual mode. Vary the output above and below the present value. Observe OUT indicator on the operator interface. Contact should change state. 1E 0 % open, 100 % closed. Change relay. Installation instructions supplied with the new board.
5 6
110
4/00
Troubleshooting/Service
Procedure #4 Table 10-8 explains how to troubleshoot Current/Time or Time/Current Proportional Output failure. Table 10-8 Troubleshooting Current/Time or Time/Current Proportional Output Failure
Step 1 What to do How to do it Make sure the controller is configured Make Output Algorithm Set Up group function for Time/Current or Current/Time prompt OUT ALG = TCUR or CURT. Proportional output. Refer to Section 4 Configuration. Check the field wiring. Make sure the NO or NC contact wiring selection is correct. Refer to Section 2 - Installation for details. 3 1. Check the output (control) relays jump position. 2. Check the relay output. 1. Refer to Section 2 Installation for relay jumper placement and relay contact information. 2. Put the controller into Manual mode. Vary the output above and below the present value. Observe OT indicator on the operator interface. 4 Check the Current Proportional Output. Put the controller into Manual mode and change the output from 0 % to 100 % (4-20 mA). Use a DC milliammeter at the rear terminals to verify the output. Refer to Section 9 - Output Calibration for details. Installation instructions supplied with new board.
5 6
4/00
111
Troubleshooting/Service
Procedure #5 Table 10-9 explains how to troubleshoot Alarm Relay Output failure. Table 10-9 Troubleshooting Alarm Relay Output Failure
Step 1 What to do Check the alarm configuration data. If it is correct, check the field wiring. Check that the applicable alarm relay actuates properly depending on what you have set at prompt AxSxTYPE. If it does, check the field wiring. How to do it Reconfigure if necessary. Refer to Section 4 - Configuration for details. If the alarm type is set for PV, place the controller in manual mode. Vary the input to raise and lower the PV around the setpoint. Listen for a click from the relay as the PV moves in either direction and note that the proper ALM1 or ALM2 is lit. EXAMPLE: If the alarm is set for MAN, put the controller into manual mode. The alarm light is ON. Put the controller into automatic mode and the alarm light is OFF. 3 Check the contacts. Make sure the NO or NC contact wiring is correct. Refer to Section 2 - Installation for relay jumper placement and relay contact information. 4 Change Main board. Installation instructions supplied with new board.
112
4/00
Troubleshooting/Service
Procedure #6 Table 10-10 explains how to troubleshoot a Keyboard failure. Table 10-10 Troubleshooting a Keyboard Failure
Step 1 What to do Make sure the keyboard is connected properly. Controller Keyboard or specific keys may be LOCKED OUT via the security code. How to do it Withdraw the chassis from the case and visually inspect the connection. Use your four-digit security code number to change the lockout level. Refer to Section 4 Configuration.
ATTENTION Using 1000 as a security code number will override the 4-digit code previously entered.
3 Replace the display/keyboard if any keys are not functioning. Installation instructions supplied with new display/keyboard.
4/00
113
Troubleshooting/Service
114
4/00
Parts List
11 Parts List
11.1 Exploded View
Introduction Figure 11-1 is an exploded view of the UDC 2300 Controller. Each part is labeled with a key number. The part numbers are listed by key number in Table 11-1. Parts not shown are listed in Table 11-2.
5 4 3
2 1 Figure 11-1 UDC 2300 Exploded View Table 11-1 Parts Identification
Key Number 1 2 3 Part Number 30756667-503 51309766-501 51309782-501 51309831-501 4 5 51309796-501 51404896-501 Bezel Assembly (Gray) Display/Keyboard Auxiliary Output/Digital Input PWA RS-422/485 Communications PWA Current Output PWA Case Assembly (includes 30755050-001 Mounting Kit) Description
4/00
115
Parts List
116
4/00
Reader assumptions It is assumed that you are familiar with the operation of the UDC 2300 controller, and that you have read the Configuration section - Section 4. In this section Refer to Table 12-1 for a listing of each function parameter and respective reference subsection.
4/00
117
Section
12.2.1 12.2.2 12.2.3 12.2.4 12.2.5 12.2.6 12.2.7 12.2.8 12.2.9 12.2.10 12.2.11 12.2.12 12.2.13 12.2.14 12.2.15 12.2.16 12.2.17 12.2.18 12.2.19 12.2.20 12.2.21 12.2.22 12.2.23 12.2.24 12.2.25 12.2.26
Prompt
DICOM DIGIN DISPLY EMISS ENDSEG EUHRDN EUHRUP FAILSF FILTR1 FILTR2 FINLSP FREQ FSMODE FUZZY HYST I MIN or I RPM I2 MIN or I2 RPM INCRMT IN1 HI IN1 LO IN1TYP IN2 HI IN2 LO IN2TYP L DISP LNGUAG
Section
12.2.29 12.2.30 12.2.31 12.2.32 12.2.33 12.2.34 12.2.35 12.2.36 12.2.37 12.2.38 12.2.39 12.2.40 12.2.41 12.2.42 12.2.43 12.2.44 12.2.45
Prompt
LSPS MANRST MINRPM OUTALG OUT Hi OUT Lo PARITY PB or GAIN PB 2 or GAIN 2 PBorGN PERIOD PG END PIDSET PVSTRT PWROUT PWR UP RATE T
Section
12.2.57 12.2.58 12.2.59 12.2.60 12.2.61 12.2.62 12.2.63 12.2.64 12.2.65 12.2.66 12.2.67 12.2.68 12.2.69 12.2.70 12.2.71 12.2.72 12.2.73 12.2.74 12.2.75 12.2.76 12.2.77 12.2.78 12.2.79 12.2.80 12.2.81 12.2.82 12.2.83 12.2.84
Prompt
SGx SP SGx TI SDMODE SHD_SP SHDTIM SOKDEV SP Hi SP Lo SPPROG SPRAMP SPRATE SP SEL SP TRK START STATE STRSEG SW VAL TI MIN TIMER ToBEGN TUNE TX DLY UNITS UNITS XMITR1 XMITR2
Section
12.2.85 12.2.86 12.2.87 12.2.88 12.2.89 12.2.90 12.2.91 12.2.92 12.2.93 12.2.94 12.2.95 12.2.96 12.2.97 12.2.98 12.2.99 12.2.100 12.2.101 12.2.102 12.2.103 12.2.104 12.2.105 12.2.106 12.2.107 12.2.108 12.2.109 12.2.110
12.2.46 12.2.47 12.2.48 12.2.49 12.2.50 12.2.51 12.2.52 12.2.53 12.2.54 12.2.55 12.2.56
RATE2T RATIO1 RATIO2 RECYCL RLY TY RESET RN HLD RPUNIT RSPSRC SECUR SGx RP
12.2.27 12.2.28
LOCK
LOOPBACK
118
4/00
12.2.1
This prompt is part of the Options Set Up Group. This selection uses a value in engineering units to represent AUXOUT except output which is in percent (%). Range of setting: within the range of the selected variable to represent 4 mA.
12.2.2
This prompt is part of the Options Set Up Group. This selection uses a value in engineering units to represent AUXOUT except output which is in percent (%). Range of setting: within the range of the selected variable to represent 20 mA.
12.2.3
4-20 RG
This prompt is part of the Algorithm Set up group. Used with Output Algorithm selections CURD, CURT, or TCUR. Selections Definitions
50
CURRENT DUPLEX RANGE (SPLIT)This setting should be used for Relay/Current and Current/Relay Duplex Outputs. It can also be used for Current Duplex when an Auxiliary Output board is present. This enables the normal control current output to provide heat control and the auxiliary current output to provide cool control. To enable this: AUX OUT in the Options Set Up group must be selected for Out. The Auxiliary Current Output is scaled as desired for 0-50 % controller output. Deadband for this configuration only applies to the Current Output. The Auxiliary Output must have the Deadband scaled in.
FOR EXAMPLE: If a 2 % Deadband is desired, then enter 2.0 for the Deadband selection in the Control Algorithm group. This will apply Deadband to the Current Output. In the Options group, set the Auxiliary Output 4mA VAL selection to 49.0 and the 20mA VAL selection to 0.0.
100
CURRENT DUPLEX RANGE (FULL) enables the Current Output to provide both heat and cool functions for control over 0-100 % of the controller output. The PID heat parameters apply when the output is greater than 50 % and the PID cool parameters apply when the output is less than 50 %. The second current output is not required for this type of duplex operation.
4/00
119
12.2.4
A TUNE
This prompt is part of the Tuning Set up group. This selection allows you to disable the AUTOTUNE key. LOCK must be set to None. Selections DIS ENAB Definitions Disable the AUTOTUNE key Enables the AUTOTUNE key
12.2.5
ACTION
This prompt is part of the Control Set up group. This selection allows you to select the direction you want the controller output to go when the process variable increases. Selections DIR REV Definitions DIRECT ACTING CONTROLThe controller's output increases as the process variable increases. REVERSE ACTING CONTROLThe controller's output decreases as the process variable increases.
12.2.6
ALARM1
This prompt is part of the Alarms Set up group. Each alarm output can be configured to be Latching or Non-latching. ATTENTION
When configured for latching, the alarm will stay on, after the alarm condition ends, until the RUN/HOLD key is pressed.
Definitions
120
4/00
12.2.7
ALHYST
(ALARM HYSTERESIS)
This prompt is part of the Alarms Set up group. A single adjustable hysteresis is provided on alarms such that when the alarm is OFF it activates at exactly the alarm setpoint; when the alarm is ON, it will not deactivate until the variable is 0.0 % to 100 % away from the alarm setpoint. Configure the hysteresis of the alarms based on INPUT signals as a % of input range span. Configure the hysteresis of the alarm based on OUTPUT signals as a % of the full scale output range. Range of Setting: 0.0 to 100.0 % of span or full output as appropriate
12.2.8
AT ERR
This prompt is part of the ATUNE Set up group. ACCUTUNE ERROR STATUSWhen an error is detected in the Accutune process, an error prompt will appear. Selections RUN NONE IDFL ABRT Definitions RUNNINGAn Accutune process is still active checking process gain, even though TUNE is not displayed. It does not affect keyboard operation. NONENo errors occurred during last Accutune procedure. IDENTIFICATION PROCESS FAILEDAn illegal value for Gain, Rate, or Reset was calculated. CURRENT ACCUTUNE PROCESS ABORTEDCaused by one of the following conditions: changing to manual mode digital input detected in heat region of output but a cool output is calculated, or vice versa.
(AUTO/MANUAL KEY LOCKOUT)
12.2.9
AUTOMA
This prompt is part of the Tuning Set up group. This selection allows you to disable/enable the AUTO/MANUAL key. LOCK must be set to None for the prompt to the displayed. Selections DIS ENAB Definitions Disable the AUTO/MANUAL key Enables the AUTO/MANUAL key
4/00
121
12.2.10
This prompt is part of the Options Set Up Group. This selection provides an MA output representing one of several control parameters. The display for auxiliary output viewing will be in engineering units for all but output. Output will displayed in percent. Selections DIS IN 1 Definitions No Auxiliary Output This represents the configured range of Input 1 For example: Type J Thermocouple (0 F to 1600 F) 0 F display = 0 % output 1600 F display = 100 % output IN 2 PROC DEV This represents the configured range of Input 2 Process Variable Deviation (Process Variable minus Setpoint) Represents 100 % to + 100 % of the selected PV span in engineering units. For Example: Type T Thermocouple PV range = -300 F to +700 F PV span = 1000 F Deviation Range = 1000 F to +1000 F If PV = 500 F and SP = 650 F then Deviation Display = 150 F Auxiliary Output = 42.5 % When Deviation is selected, only one operating parameter will be entered. This value represents the deviation level that will produce 20 mA (100 %) output Zero deviation will produce a center scale (12 mA or 50 %) output. A negative deviation equal in magnitude to the auxiliary output high value will produce a low end (4 mA or 0 %) output. OUTPUT SP LSP1 OUTPUT represents the displayed controller output in percent (%). Cannot be used with 3 Position Step Control. SETPOINT represents the value of the setpoint in units of PV. Local Setpoint One Auxiliary output represents local setpoint one regarless of active setpoint.
122
4/00
12.2.11
AxSxEV
This prompt is part of the Alarms Set up group. Select whether you want the alarm type chosen in prompt AxSxTY to alarm the beginning or end of a segment in setpoint Ramp/Soak programming. ATTENTION
Select if Setpoint Programming is enabled and if the Alarm Type is configured for Event On/Off. Alarms configured for events will not operate on Setpoint Program segments of zero length.
12.2.12
AxSxHL
This prompt is part of the Alarms Set up group. Select whether you want the alarm type chosen in prompt AxSxTY to alarm High or Low . ATTENTION
Select if Setpoint Programming is disabled or if the Alarm Type is not configured for Event On/Off.
Definitions
4/00
123
12.2.13
AxSxTY
This prompt is part of the Alarms Set up group. Select what you want Setpoint x of Alarm x to represent. It can represent the Process Variable, Deviation, Input 1, Input 2, Output, Remote Setpoint, PV rate of Change, Loop Break, or Failsafe, and if you have a model with communications, you can configure the controller to alarm on SHED. If you have setpoint programming, you can alarm when a segment goes ON or OFF. Selections NONE IN 1 IN 2 PV DE OUT SHED EVON EVOF MAN RSP FSAF PVRT DI DE II BRAK Definitions Disables the alarms. Input 1 Input 2 Process Variable Deviation Output (note 1) Shed from Communications Event ON (Setpoint Programmer) Event OFF (Setpoint Programmer) Alarm on Manual mode (note 2) Remote Setpoint Failsafe PV Rate of Change Alarm on Digital Input Deviation Alarm based on deviation from 2nd Local Setpoint or Remote SP regardless of which SP is active. Loop Break (note 3)
NOTE 1 When the controller is configured for Three Position Step Control, alarms set for Output will not function. NOTE 2 Not available if Timer is enabled because Alarm 1 is dedicated to Timer output. NOTE 3 When enabled, the control output is checked for minimum and maximum limits. When this occurs, a timer begins and, if the output has not caused the PV to be corrected by a pre-determined amount and time, the alarm activates. For loop break alarms, the timer value may be changed only for controllers configured for On-Off control.
124
4/00
12.2.14
AxSxVA
This prompt is part of the Alarms Set up group. This is the value at which you want the alarm type chosen in Prompt AxSxTY to actuate. The value depends on what the alarm setpoint has been configured to represent. For SP Programming, the value is the segment number for which the event applies. For PV Rate of Change, the value is the amount of PV rate of change in one minute in engineering units. This prompt does not appear for Alarm on Manual type alarm (i.e., AxSxTY is set to MAN). Range of Setting: within the range of the selected parameter or of the PV Span for Deviation configurations.
12.2.15
BAUD
(BAUD RATE)
12.2.16
BIAS 1
(INPUT 1 BIAS)
This prompt is part of the Input 1 Set up group. Bias is used to compensate the input for drift of an input value due to deterioration of a sensor, or some other cause. Select the bias value you want on Input 1. Range of Setting: 999 to 9999
12.2.17
BIAS 2
(INPUT 2 BIAS)
This prompt is part of the Input2 Set up group. Bias is used to compensate the input for drift of an input value due to deterioration of a sensor, or some other cause. Select the bias value you want on Input 2. Range of Setting: 999 to 9999
4/00
125
12.2.18
BLOCK
(ALARM BLOCKING)
This prompt is part of the Alarms Set up group. Prevent nuisance alarms when the controller is first powered up. The alarm is suppressed until the parameter gets to the non-alarm limit or band. Alarm blocking affects both alarm setpoints. ATTENTION
When enabled on power up or initial enabling via configuration, the alarm will not activate unless it has not been in alarm for one cycle (167 ms).
Definitions Disable Blocking Blocks Alarm 1 only Blocks Alarm 2 only Blocks Alarm 1 and Alarm 2
(BURNOUT PROTECTION - SENSOR BREAK)
12.2.19
BRNOUT
This prompt is part of the Input 1 Set up group. BURNOUT PROTECTION (SENSOR BREAK) provides most input types with upscale or downscale protection if the input fails. 1-5V, 0-10V, or 4-20 mA inputs require no burnout or NONE selection. Selections NONE Definitions NO BURNOUTPre-configured Failsafe output applied if failed input is detected (does not apply for an input out of range). Error message IN 1 FAIL is flashed on the lower display intermittently every 10 seconds. UPSCALE BURNOUT will make the PV signal increase to full scale, +10 %, when a sensor fails, and flash IN 1 FAIL on the lower display intermittently every 10 seconds. The controller remains in Automatic control mode and adjusts the controller output signal in response to the full scale PV signal developed by the Burnout circuitry. DOWNSCALE BURNOUT will make the PV signal decrease to the lower range value, -10 %, when a sensor fails, and flash INPUT 1 FAIL on the lower display intermittently every 10 seconds. The controller remains in Automatic control mode and adjusts the controller output signal in response to the zero percent PV signal developed by the Burnout circuitry. NOFS NO FAILSAFE This selection does not provide input failure detection and should only be used when an absolute accuracy is the most important criteria. (For this selection, no burnout signal went to the sensor.)
UP
DOWN
126
4/00
12.2.20
ComADD
(STATION ADDRESS)
This prompt is part of the Communications Set up group. This is a number that is assigned to a controller that is to be used with the communications option. This number will be its address. Range of Setting: 1 to 99
12.2.21
ComSTA
(COMMUNICATIONS STATE)
This prompt is part of the Communications Set up group. This prompt lets you select the type of communications protocol. Selections DIS R422 MODB Disable RS-422/485 ASCII - Allows RS422/485 ASCII communication prompts. MODBUS - Allows Modbus RTU communication prompts Definitions
12.2.22
CSP BI
This prompt is part of the Communications Set up group. Computer setpoint bias Range of Setting: -999 to 9999 in Engineering Units
12.2.23
CTRALG
(CONTROL ALGORITHM)
This prompt is part of the Algorithm Set up group. This prompt lets you select the type of control that is best for your process. Selections ONOF Definitions ON/OFF is the simplest control type. The output can be either ON (100 %) or OFF (0 %). The Process Variable (PV) is compared with the setpoint (SP) to determine the sign of the error (ERROR = PV-SP). The ON/OFF algorithm operates on the sign of the error signal. In Direct Acting Control, when the error signal is positive, the output is 100 %; and when the error signal is negative, the output is 0 %. If the control action is reverse, the opposite is true. An adjustable overlap (Hysteresis Band) is provided between the on and off states. Other prompts affected: HYST DUPLEX ON/OFF is an extension of this algorithm when the output is configured for Duplex. It allows the operation of a second ON/OFF output. There is a deadband between the operating ranges of the two inputs and an
4/00 UDC 2300 Controller Product Manual 127
adjustable overlap (hysteresis) of the on and off states of each output. Both Deadband and Hysteresis are separately adjustable. With no relay action the controller will read 50 %. Other prompts affected: HYST and D BAND PIDA PID A is normally used for three-mode control. This means that the output can be adjusted somewhere between 100 % and 0 %. It applies all three control actionsProportional (P), Integral (I), and Derivative (D)to the error signal. Proportional (Gain)Regulates the controllers output in proportion to the error signal (the difference between Process Variable and Setpoint). Integral (Reset)Regulates the controller's output to the size of the error and the time the error has existed. (The amount of corrective action depends on the value of proportional Gain.) Derivative (Rate)Regulates the controller's output in proportion to the rate of change of the error. (The amount of corrective action depends on the value of proportional Gain.)
NOTE: PID A should not be used for Proportional only action (that is, no integral (reset) action). Instead, use PD+MR with rate set to 0.
PIDB
Unlike the PID A equation, the controller gives only an integral response to a setpoint change, with no effect on the output due to the gain or rate action, and it gives full response to PV changes. Otherwise controller action is as described for the PID A equation. See note on PID A PD WITH MANUAL RESET is used whenever integral action is not wanted for automatic control. The equation is computed with no integral contribution. The MANUAL RESET, which is operator adjustable, is then added to the present output to form the controller output. Switching between manual and automatic mode will not be bumpless. If you select PD with Manual Reset you can also configure the following variations PD (Two Mode) control, P (Single Mode) control. Set Rate (D) to 0. Other prompts affected: MANRST in the TUNING Set Up Group.
PDMR
TPSC
The THREE POSITION STEP algorithm allows the control of a valve (or other actuator), with an electric motor driven by two controller relay outputs; one to move the motor upscale, the other downscale without a feedback slidewire linked to the motor shaft. The deadband and hysteresis are adjustable in the same manner as the relay duplex output algorithm. The Three Position Step Control algorithm provides an output display (OUT) which is an estimated motor position since the motor is not using any feedback. Although this output indication is only an approximation, it is
128
4/00
corrected each time the controller drives the motor to one of its stops (0 % or 100 %). It avoids all the control problems associated with the feedback slidewire (wear, dirt, noise). When operating in this algorithm, the estimated OUT display is shown to the nearest percent (that is, no decimal). Other prompts affected: D BAND
12.2.24
CSRATO
This prompt is part of the Communications Set up group. RATIOComputer setpoint ratio Range of Setting: -20.0 to 20.0
12.2.25
CYC T1 or CT1 X3
This prompt is part of the Tuning Set up group. CYCLE TIME (HEAT) determines the length of one time proportional output relay cycle. Defined as HEAT Cycle time for Heat/Cool applications. CYC TIElectromechanical relays (seconds) CTIX3Solid state relays (1/3 seconds) Cycle times are in either second or 1/3-second increments depending upon the configuration of RLY TY in the Output Algorithm Set Up group. Range of Setting: 1 to 120 ATTENTION
If 1/3 second increments are used, 1 = .33 seconds and 120 = 40 seconds.
4/00
129
12.2.26
CYC2T2 or CT2 X3
This prompt is part of the Tuning Set up group. CYCLE TIME2 (COOL) determines the length of one time proportional output relay cycle. Defined as COOL Cycle time for Heat/Cool applications. CYC2TIElectromechanical relays (seconds) CT2X3Solid state relays (1/3 seconds) Cycle times are in either second or 1/3-second increments depending upon the configuration of RLY TY in the Output Algorithm Set Up group. Range of Setting: 1 to 120 ATTENTION
If 1/3 second increments are used, 1 = .33 seconds and 120 = 40 seconds.
12.2.27
DBAND
(DEADBAND)
This prompt is part of the Control Set up group. DEADBAND is an adjustable gap between the operating ranges of output 1 and output 2 in which neither output operates (positive value) or both outputs operate (negative value). It is the difference between the nominal trip points of relays 1 and 2. Shows when only Time Duplex or Three Position Step is selected. Range of Setting: -5.0 to 25.0 % (Time Duplex) 0.5 to 5.0 % (Three Position Step)
12.2.28
DECMAL
This prompt is part of the Input 1 Set up group. This selection determines where the decimal point appears in the display. Selections 8888 888.8 88.88 None One Place Two Places (range is only 99.99 Definitions
130
4/00
12.2.29
This prompt is part of the Options Set Up Group There are five selections available for combination with any digital input selection. Selections DIS +PD2 +DIR +SP2 +SP1 +RUN Definitions DISABLE-Disables combination function. Any Digital Input Selection PLUS PID2-Contact closure selects PID Set 2. Any Digital Input Selection PLUS DIRECT ACTION Contact closure selects direct controller action. Any Digital Input Selection PLUS SETPOINT 2 Contact closure puts the controller into setpoint 2. Any Digital Input Selection PLUS SETPOINT 1 Contact closure puts the controller into setpoint 1. Any Digital Input Selection PLUS RUN SETPOINT PROGRAM/RAMP Contact closure starts SP Program/Ramp if enabled.
12.2.30
This prompt is part of the Options Set Up Group This selection allows remote selection of various parameters. Selections NONE MAN LSP Definitions NO DIGITAL INPUT SELECTIONS TO MANUAL Contact closure puts the affected loop into manual mode. Contact open returns controller to former mode. TO LOCAL SETPOINT When a remote setpoint is configured, contact closure puts the controller into local setpoint 1. When contact opens, the controller returns to former operation local or remote setpoint unless SETPOINT SELECT key is pressed while digital input is active. If this happens, the controller will stay in the local setpoint mode when contact opens. TO LOCAL SETPOINT TWO - Contact closure puts the controller into local setpoint 2. TO DIRECT ACTION - Contact closure selects direct controller action. TO HOLD Contact closure suspends Setpoint Program or Setpoint Ramp. When contact reopens, the controller starts from the Hold point of the Ramp/Program unless the Ramp/Program was not previously started via the RUN/HOLD key. This selection applies to either loop. PID2 TO PID2 Contact closure selects PID Set 2.
4/00
131
RUN
RUN Contact closure starts a stopped SP Ramp or Program. Upper left characters blinks R. Reopening the contact puts controller in HOLD mode. EXTERNAL SP PROGRAM RESET Contact closure resets SP Program back to the beginning of the first segment in the program and places the program in HOLD mode. Program cycle number is not affected. Reopening switch has not effect. Once the last segment of the setpoint program has timed out, the controller enters the mode of action specified in the configuration data and the program cannot be reset to the beginning of the first segment by digital input closure.
ATTENTION
BEGN
NO_I MANFS
INHIBIT INTEGRAL (RESET) Contact closure disables PID Integral (Reset) action. MANUAL FAILSAFE OUTPUT Controller goes to Manual mode, output goes to the Failsafe value. This will cause a bump in the output when switching from Automatic to Manual. The switch back from Manual to Automatic is bumpless. When the switch is closed, the output can be adjusted from the keyboard after pressing the MANUAL/AUTO key to the put the controller in the Manual mode.
ATTENTION
KEYBOARD LOCKOUT Contact closure disables all keys. Lower display shows LOCKED if a key is pressed. TIMER Contact closure starts timer, if enabled. Reopening the switch has no effect. INITIATE LIMIT CYCLE TUNING Contact closure starts the tuning process. The lower display shows TUNE ON. Opening the contact has no effect. SETPOINT INITIALIZATION Contact closure forces the setpoint to the current PV value. Opening the contact has no effect. TO REMOTE SETPOINT Contact closure selects the Remote setpoint. MANUAL LATCHING Contact closure transition forces the loop to Manual mode. Opening the switch has no effect. If the MANUAL/AUTO key is pressed while the switch is closed, the loop will return to Automatic mode. OUTPUT TRACKING Contact closure allows output to track Input 2. For the Output Tracking, when the switch is open, the output is in accordance with its predefined functionality. When the switch is closed, the output value (in percent) will track the Input 2 percent of range value. When the switch is reopened, the output will start at this last output value and normal PID action will then take over control. The transfer is bumpless. NOTE: Output Tracking does not apply to Three Position Step Control.
TRAK
132
4/00
12.2.31
This prompt is part of the Input 1 Set Up Group on single display models. Pressing the DISPLAY key will cycle through all applicable values. One minute after the last press of the display key, the display will revert to the display configured here. Selections SP PRY PRn Definitions Active Setpoint Process Variable with lower display prompt. Process Variable with no lower display prompt.
12.2.32
EMISS
(EMISSIVITY)
This prompt is part of the Input 1 Set up group. EMISSIVITY is a correction factor applied to the Radiamatic input signal that is the ratio of the actual energy emitted from the target to the energy which would be emitted if the target were a perfect radiator. Available only for Radiamatic inputs. Range of Setting: 0.01 to 1.00
12.2.33
ENDSEG
(END SEGMENT)
This prompt is part of the Setpoint Ramp/Program Set up group. The end segment number designates the number of the last segment, it must be a soak segment (even number). Range of Setting: 2 to 12
12.2.34
EUHRDN
This prompt is part of the Setpoint Rate Set up group. When making a setpoint change, this is the rate at which the controller will change from the original setpoint down to the new one. The ramping (current) setpoint can be viewed as SPn in the lower display. Entering a 0 will imply an immediate change in Setpoint (i.e., no rate applies). Range of Setting: 0 to 9999 in Engineering Units per Hour
(RATE UP VALUE)
12.2.35
EUHRUP
This prompt is part of the Setpoint Rate Set up group. When making a setpoint change, this is the rate at which the controller will change from the original setpoint up to the new one. The ramping (current) setpoint can be viewed as SPn in the lower display. Entering a 0 will imply an immediate change in Setpoint (i.e., no rate applies). Range of Setting: 0 to 9999 in Engineering Units per Hour
4/00
133
12.2.36
FAILSF
This prompt is part of the Control Set up group. The value used here will also be the output level when Input 1 fails for all inputs except T/C, or when NO BURNOUT is configured and input 1 fails for T/C Inputs. Range of Setting: 0 to 100 % For 3 Position Step 100 - Motor position set to 100 % output position (open) 0 - Motor position set to 0 % output position (closed)
12.2.37
FILTR1
(INPUT 1 FILTER)
This prompt is part of the Input 1 Set up group. A software digital filter is provided for input 1 to smooth the input signal. You can configure the first order lag time constant from 1 second to 120 seconds. If you do not want filtering, enter 0. Range of Setting: 1 to 120 0 = No Filter
12.2.38
FILTR2
(INPUT 2 FILTER)
This prompt is part of the Input 2 Set up group. A software digital filter is provided for input 2 to smooth the input signal. You can configure the first order lag time constant from 1 second to 120 seconds. If you do not want filtering, enter 0. Range of Setting: 1 to 120 0 = No Filter
12.2.39
FINLSP
This prompt is part of the Setpoint Ramp/Program Set up group. Enter the value desired for the final setpoint. The controller will operate at the setpoint set here when ramp is ended. ATTENTION
If the ramp is on HOLD, the held setpoint can be changed by the increment or decrement keys. However, the ramp time remaining and original ramp rate is not changed. Therefore, when returning to RUN mode, the setpoint will ramp at the same rate as previous to the local setpoint change and will stop if the final setpoint is reached before the time expires. If the time expires before the final setpoint is reached, it will jump to the final setpoint.
Range of Setting:
134
4/00
12.2.40
FREQ
This prompt is part of the Input 1 Set up group. At what power line frequency are you going to operate? Selections Definitions 60 50 60 Hertz 50 Hertz
12.2.41
This prompt is part of the Control Set Up group. This selection determines what state the controller will revert to if it goes into Failsafe. Selections NO L LACH Definitions Controller stays in last mode (automatic or manual); output goes to Failsafe value. Controller goes to manual mode; output goes to Failsafe value.
12.2.42
FUZZY
This prompt is part of the Accutune Set up group. The UDC will use Fuzzy Logic to inherently suppress or minimize any overshoot that may occur, when PV approaches SP, as a result of the existing tuning parameters. It does NOT change the parameters. Can be enabled or disabled independently of whether Demand Tuning is enabled or disabled. Selections Definitions DIS ENAB Disable the Fuzzy Overshoot Suppression. Enables the Fuzzy Overshoot Suppression.
12.2.43
HYST
This prompt is part of the Control Set up group. HYSTERESIS is an adjustable overlap of the ON/OFF states of each control output. This is the difference between the value of the process variable at which the control outputs energize and the value at which they de-energize. Only applicable for ON-OFF control. Range of Setting: 0.0 to 100.0 % of PV (On/Off Control)
4/00
135
12.2.44
I MIN or I RPM
This prompt is part of the Tuning Set up group. I MIN = RESET TIME IN MINUTES / REPEAT I RPM = RESET TIME IN REPEATS PER MINUTE RESET RATE or INTEGRAL TIME adjusts the controllers output in accordance with both the size of the deviation (SP-PV) and the time it lasts. The amount of the corrective action depends on the value of Gain. The Reset adjustment is measured as how many times proportional action is repeated/minute. Used with control algorithm PID-A. Defined as HEAT Reset on Duplex models for variations of Heat/Cool applications. The selection of minutes per repeat or repeats per minute is made in the Control parameters group under prompt MINRPM. Range of Setting: 0.02 to 50.00
12.2.45
I2 MIN or I2 RPM
This prompt is part of the Tuning Set up group. I2 MIN = RESET IN MINUTES / REPEAT I2 RPM = RESET IN REPEATS PER MINUTE RESET RATE 2 or INTEGRAL TIME 2 adjusts the controllers output in accordance with both the size of the deviation (SP-PV) and the time it lasts. The amount of the corrective action depends on the value of Gain. The Reset adjustment is measured as how many times proportional action is repeated/minute. Used with control algorithm PID-A. Defined as COOL Reset on Duplex models for variations of Heat/Cool applications or for a Second Set of PID constants. The selection of minutes per repeat or repeats per minute is made in the Control parameters group under prompt MINRPM. Range of Setting: 0.02 to 50.00
12.2.46
This prompt is part of the Timer Set Up group. This selection determines how the timers count will increment. Selections MIN SEC Definitions Counts in hours:minutes. Counts in minutes:seconds.
136
4/00
12.2.47
IN1 HI
This prompt is part of the Input 1 Set up group. This selection lets you the Input 1 high range value in engineering units. Linear or Square Root Inputs only. Scale the #1 input signal to the display value you want for 100 %. EXAMPLE: Actuation (Input) = 4 to 20 mA Process Variable = Flow Range of Flow = 0 to 250 Gal/Min High Range display value = 250 Then 20 mA = 250 Gal/Min The control setpoint will be limited by the range of units selected here. Range of Setting: -999 to 9999 (floating) in Engineering Units
12.2.48
IN1 LO
This prompt is part of the Input 1 Set up group. This selection lets you the Input 1 Low range value in engineering units. Linear or Square Root Inputs only. Scale the #1 input signal to the display value you want for 0 %. EXAMPLE: Actuation (Input) = 4 to 20 mA Process Variable = Flow Range of Flow = 0 to 250 Gal/Min Low Range display value = 0 Then 4 mA = 0 Gal/Min The control setpoint will be limited by the range of units selected here. Range of Setting: -999 to 9999 (floating) in Engineering Units
4/00
137
12.2.49
IN1TYP
This prompt is part of the Input 1 Set up group. This selection determines what actuation you are going to use for Input 1. ATTENTION
Changing the input type will result in the loss of Field Calibration values and will restore Factory Calibration values.
Selections B EH EL JH JL KH KL NNMH NNML N90H N90L NIC R S TH TL WH WL 100H 100L 200 500 RADH RADI 0-20 4-20 10m 50m 0-5 1-5 0-10 100m
Definitions BB Thermocouple E HE Thermocouple High E LE Thermocouple Low J HJ Thermocouple High J HJ Thermocouple Low K HK Thermocouple High K HK Thermocouple Low NNMHNi-Ni-Moly Thermocouple High NNMLNi-Ni-Moly Thermocouple Low N90HNiMo-NiCo Thermocouple High N90LNiMo-NiCo Thermocouple Low NICNicrosil-Nisil Thermocouple RR Thermocouple SS Thermocouple T HT Thermocouple High T LT Thermocouple Low W HW5W26 Thermocouple High W LW5W26 Thermocouple Low 100H100 Ohm RTD High 100L100 Ohm RTD Low 200200 Ohm RTD 500500 Ohm RTD RADHRadiamatic RH RADIRadiamatic RI 0-200 to 20 Milliamperes 4-204 to 20 Milliamperes 10m0 to 10 Millivolts 50m0 to 50 Millivolts 0-50 to 5 Volts 1-51 to 5 Volts 0-100 to 10 Volts 100m0 to 100 Millivolts
138
4/00
12.2.50
IN2 HI
This prompt is part of the Input2 Set up group. This selection lets you the Input2 high range value in engineering units. Linear or Square Root Inputs only. Scale the #2 input signal to the display value you want for 100 %. EXAMPLE: Actuation (Input) = 4 to 20 mA Process Variable = Flow Range of Flow = 0 to 250 Gal/Min High Range display value = 250 Then 20 mA = 250 Gal/Min The control setpoint will be limited by the range of units selected here. Range of Setting: -999 to 9999 (floating) in Engineering Units
12.2.51
IN2 LO
This prompt is part of the Input2 Set up group. This selection lets you the Input 2 Low range value in engineering units. Linear or Square Root Inputs only. Scale the #2 input signal to the display value you want for 0 %. EXAMPLE: Actuation (Input) = 4 to 20 mA Process Variable = Flow Range of Flow = 0 to 250 Gal/Min Low Range display value = 0 Then 4 mA = 0 Gal/Min The control setpoint will be limited by the range of units selected here. Range of Setting: -999 to 9999 (floating) in Engineering Units
4/00
139
12.2.52
IN2TYP
This prompt is part of the Input2 Set up group. This selection determines what actuation you are going to use for Input 2. Selections DIS 0-20 4-20 0-5 1-5 0-2 Definitions DISDisable Input 2 0-200 to 20 Milliamperes 4-204 to 20 Milliamperes 0-50 to 5 Volts 1-51 to 5 Volts 0-20 to 2 Volts
12.2.53
L DISP
This prompt is part of the Timer Set up group. This selection allows you to select what is displayed for the timer option. The time is shown on the lower display in hh:mm or mm:ss format along with a rotating clock character. Selections TREM ET Definitions If the clock rotation is counterclockwise, time remaining is indicated. If the clock rotation is clockwise, elapsed time is indicated.
12.2.54
LNGUAG
(LANGUAGE)
This prompt is part of the Input 1 Set up group. Select what the language will be for the displays. Selections ENGL FREN GERM SPAN ITAL NUMB English French German Spanish Italian Numeric Definitions
140
4/00
12.2.55
LOCK
(LOCKOUT)
This prompt is part of the Tuning Set up group. LOCKOUT applies to one of the functional groups: Configuration, Calibration, Tuning, Accutune. DO NOT CONFIGURE UNTIL ALL CONFIGURATION IS COMPLETE. .Selections NONE CAL CONF Definitions No lockout; all groups are read/write All groups are available for read/write except for the Calibration and Keyboard Lockout groups. Timer, Tuning, SP Ramp, and Accutune groups are read/write. All other groups are read only. Calibration and Keyboard Lockout groups are not available. Tuning and Setpoint Ramp parameters are read/write. No other parameters can be viewed. Tuning and Setpoint Ramp parameters are available for read only. No other parameters can be viewed.
VIEW ALL
12.2.56
LOOPBACK
This prompt is part of the Communications Set up group. Selections DIS ENAB Definitions Disables the Loopback test Allows loopback test. The UDC goes into Loopback mode in which it sends and receives its own message. The UDC displays PASS or FAIL status in the upper display and LOOPBACK in the lower display while the test is running. The UDC will go into manual mode. The test will run until the operator disables it here, or until power is turned off and on. The UDC does not have to be connected to the RS-485 link to perform this test. If it is connected, only one UDC 2300 should run the loopback test at a time. The computer should not be transmitting on the link while the loopback test is active.
ATTENTION
12.2.57
LSPS
This prompt is part of the Control Set up group. This selection determines what your local setpoint source will be. Selections ONE TWO Definitions LOCAL SETPOINT 1The setpoint entered from the keyboard. TWO LOCAL SETPOINTSThis selection lets you switch between two local setpoints using the FUNCTION key.
4/00
141
12.2.58
MANRST
(MANUAL RESET)
This prompt is part of the Tuning Set up group. MANUAL RESET is only applicable if you have control algorithm PD WITH MANUAL RESET (PD + MR). Because a proportional controller will not necessarily line out at setpoint, there will be a deviation (offset) from setpoint. This eliminates the offset and lets the PV line out at setpoint. NOTE: This Manual Reset value is also available as a lower display parameter, BI. Range of Setting: -100 to +100 (in % of output)
12.2.59
MINRPM
(RESET UNITS)
This prompt is part of the Control Set up group. Selects units of minutes or repeat per minutes for the I term of the PID algorithm. 20 Repeats per Minute = 0.05 Minutes per Repeat. Selections RPM MIN Definitions REPEATS PER MINUTE The number of times per minute that proportional action is repeated by reset. MINUTES PER REPEAT The time between each repeat of the proportional action by reset.
12.2.60
OUTALG
(OUTPUT ALGORITHM)
This prompt is part of the Algorithm Set up group. The OUTPUT ALGORITHM lets you select the type of output you want. Not applicable with Control Algorithm prompt TPSC. Selections are model dependent. For example, current output models cannot be configured for Time Proportioning Simplex Output. Selections RLY Definitions TIME SIMPLEX Type of output using one SPDT relay. Its normally open (NO) or normally closed (NC) contacts are wired at the rear terminals. Other prompts affected: HYST CUR CURRENT SIMPLEX Type of output using one 4 to 20 mA signal that can be fed into a positive or negative grounded load of 0 to 750 ohms. The signal can be recalibrated for any desired range from 4 mA to 20 mA for 0 % to 100 % output. TIME DUPLEX Type of output using two SPST relays. Its normally open (NO) or normally closed (NC) contacts are wired at the rear terminals. Other prompts affected: D BAND and HYST
142 UDC 2300 Controller Product Manual 4/00
RLYD
CURD
CURRENT DUPLEX is similar to current simplex but uses a second current output. The second output is usually scaled so that zero and span correspond with 0 % and 50 % output (cool zone). When the output is 0 % to 50 %, the controller uses tuning parameter set #2, when the output is 50 % to 100 % it uses set #1. Other prompts affected: 4-20RG CURRENT/TIME DUPLEX is a variation of duplex with current active for 0 % to 50 % output (tuning set 2) and time is active 50 % to 100 % output (tuning set 1). Relay controls heat, current controls cool. Other prompts affected: 4-20RG TIME CURRENT DUPLEX is similar to CUR TI except that current is active for 50 % to 100 % and time is active for 0 % to 50 %. Relay controls cool, current controls heat. Other prompts affected: 4-20RG
CURT
TCUR
12.2.61
OUT Hi
This prompt is part of the Control Set up group. This is the highest value of output beyond which you do not want the controller automatic output to exceed. Use 0 % to 100 % for time proportional output type. Range of Setting: -5.0 to 105 % of Output (Current) 0.0 to 100.0 % of Output (Relay)
12.2.62
OUT Lo
This prompt is part of the Control Set up group. This is the highest value of output below which you do not want the controller automatic output to exceed. Use 0 % to 100 % for time proportional output type. Range of Setting: -5.0 to 105 % of Output (Current) 0.0 to 100.0 % of Output (Relay)
(PARITY)
12.2.63
PARITY
This prompt is part of the Communications Set up group. PARITY pertains to the use of a self-checking code employing binary digits in which the total number of ONE's (or ZERO's) in each permissible code expression is either ODD or EVEN.
4/00
143
12.2.64
PB or GAIN
This prompt is part of the Tuning Set up group. PROPORTIONAL BAND is the percent of the range of the measured variable for which a proportional controller will produce a 100 % change in its output. GAIN is the ratio of output change (%) over the measured variable change (%) that caused it. 100 % G = PB % where PB is the proportional band (in %) If the PB is 20 %, then the Gain is 5. Likewise, a 3 % change in the error signal (SP-PV) will result in a 15 % change in the controllers output due to proportional action. If the gain is 2, then the PB is 50 %. Defined as HEAT Gain on Duplex models for variations of Heat/Cool applications. The selection of Prop. Band or Gain is made in the Control parameter group under prompt PB or GN. Range of Setting: PB = 0.1 to 1000 % GAIN = 0.01 to 1000
12.2.65
PB 2 or GAIN 2
This prompt is part of the Tuning Set up group. PROPORTIONAL BAND 2 is the percent of the range of the measured variable for which a proportional controller will produce a 100 % change in its output. GAIN 2 is the ratio of output change (%) over the measured variable change (%) that caused it. 100 % G = PB % where PB is the proportional band (in %) If the PB is 20 %, then the Gain is 5. Likewise, a 3 % change in the error signal (SP-PV) will result in a 15 % change in the controllers output due to proportional action. If the gain is 2, then the PB is 50 %. Defined as COOL Gain on Duplex models for variations of Heat/Cool applications or for a Second Set of PID constants. The selection of Prop. Band or Gain is made in the Control parameter group under prompt PB or GN. Range of Setting: PB 2 = 0.1 to 1000 % GAIN 2 = 0.01 to 1000
144
4/00
12.2.66
PBorGN
This prompt is part of the Control Set up group. Select one of the following for the Proportional (P) term of the PID algorithm: Selections PB Definitions PROPORTIONAL BAND Selects units of percent proportional band for the P term of the PID algorithm. Where: PB % = 100 % GAIN GAIN selects the unitless term of gain for the P term of the PID algorithm. Where: GAIN = 100 % PB %
GAIN
12.2.67
PERIOD
(TIMEOUT PERIOD)
This prompt is part of the Timer Set up group. This selection allows you to configure a Time-out period Range of Setting: 0.00 to 99:59 (Hours:Minutes)
12.2.68
PG END
This prompt is part of the Setpoint Ramp/Program Set up group. The program termination state function determines the status of the controller upon completion of the program. Selections LAST FSAF Definitions Hold at last Setpoint in program Manual Mode/Failsafe Output
4/00
145
12.2.69
PIDSET
This prompt is part of the Control Set up group. This selection lets you choose one or two sets of tuning constants (gain, rate, and reset). Selections ONE Definitions ONE SET ONLYOnly one set of tuning parameters is available. Configure the values for: Gain (proportional band), Rate, Reset Time, and Cycle Time (if time proportional is used). TWO SETS KEYBOARD SELECTABLETwo sets of tuning parameters can be configured and can be selected at the operator interface or by using the Digital Inputs. Press DISPLAY key until you see PID SET1 or PID SET2 to switch between sets. Configure the values for: Gain, Rate, Reset, Cycle Time Gain #2, Rate #2, Reset #2, Cycle #2 Time 2 PV TWO SETS PV AUTOMATIC SWITCHOVERWhen the process variable is GREATER than the value set at prompt SW VAL (Switchover Value), the controller will use Gain, Rate, Reset, and Cycle Time. The active PID SET can be read in the lower display. When the process variable is LESS than the value set at prompt SW VAL, the controller will use Gain #2, Rate #2, Reset #2, and Cycle #2 Time. The active PID SET can be read in the lower display. Other prompts affected: SW VAL 2 SP TWO SETS SP AUTOMATIC SWITCHOVERWhen the setpoint is GREATER than the value set at prompt SW VAL (Switchover Value), the controller will use Gain, Rate, Reset, and Cycle. When the setpoint is LESS than the value set at prompt SW VAL, the controller will use Gain #2, Rate #2, Reset #2, and Cycle #2. Other prompts affected: SW VAL
2KBD
146
4/00
12.2.70
This prompt is part of the Setpoint Ramp/Program Set up group. This function determines whether LSP1 or PV is used as the setpoint when the program is initially changed from HOLD to RUN. Selections DIS Definitions DISABLEWhen the program is initially changed from HOLD to RUN the present LSP1 value is captured as the default setpoint. If the program is terminated or the power cycled before the program has completed, the LSP1 is used as the control setpoint. The beginning segment uses this value as the initial ramp setpoint. ENABLE When the program is initially changed from HOLD to RUN the present PV value is captured and used as the beginning setpoint value for the ramp segment. If the program is terminated before completion, the setpoint value will revert back to the PV value captured at the initial HOLD to RUN transition. If the power is cycled before program completion, upon power-up the setpoint is set to the PV value at power-up and when the program is restarted that setpoint value is used initially.
ENAB
12.2.71
PWROUT
This prompt is part of the Control Set up group. This selection determines what position the motor will be in when powered up (the last one prior to shutdown or in the failsafe position). Selections LAST Definitions LAST OUTPUTAt power-up in automatic mode, the motor position will be the last one prior to power down. When the unit goes into FAILSAFE, it will stay in automatic mode; motor will not be driven to the configured failsafe position. FAILSAFE OUTPUTAt power-up in manual mode, the motor will be driven to either the 0 % or 100 % output position, whichever is selected at prompt FAILSF. For Burnout/None, when the unit goes into FAILSAFE, it will go to manual mode; motor will be driven to the configured failsafe position.
FSAF
4/00
147
12.2.72
PWR UP
This prompt is part of the Control Set up group. This selection determines which mode and setpoint the controller will use when the controller restarts after a power loss. Selections MAN ALSP Definitions MANUAL, LSP, FAILSAFE OUTPUTAt power-up, the controller will use manual mode with the local setpoint displayed. AUTOMATIC MODE, LAST LSPAt power-up, the controller will use automatic mode with the last local setpoint used before power down displayed. AUTOMATIC MODE, LAST RSPAt power-up, the controller will use automatic mode with the last remote setpoint used before power down displayed. LAST MODE/LAST SETPOINT used before power down LAST MODE/LAST LOCAL SETPOINT on power down.
ARSP
AMSP AMLS
12.2.73
RATE T
(RATE TIME)
This prompt is part of the Tuning Set up group. RATE Time affects the controller's output whenever the deviation is changing; and affects it more when the deviation is changing faster. Defined as HEAT Rate on Duplex models for variations of Heat/Cool applications. Range of Setting: 0.08 to 10.00 minutes
0.08 or less = OFF
12.2.74
RATE2T
(RATE2 TIME)
This prompt is part of the Tuning Set up group. RATE 2 Time affects the controllers output whenever the deviation is changing; and affects it more when the deviation is changing faster. Defined as COOL Rate on Duplex models for variations of Heat/Cool applications or for a Second Set of PID constants. Range of Setting: 0.08 to 10.00 minutes
0.08 or less = OFF
148
4/00
12.2.75
RATIO1
(INPUT 1 RATIO)
This prompt is part of the Input 1 Set up group. Select the Ratio value you want on Input 1. Range of Setting: 20.0 to 20.0
12.2.76
RATIO2
(INPUT 2 RATIO)
This prompt is part of the Input 2 Set up group. Select the Ratio value you want on Input 2. Range of Setting: 20.0 to 20.0
12.2.77
RECYCL
(RECYCLES)
This prompt is part of the Setpoint Ramp/Program Set up group. The recycle number allows the program to recycle a specified number of times from beginning to end. Range of Setting: 0 to 99
12.2.78
RLY TY
This prompt is part of the Algorithm Set up group. RELAY CYCLE TIME INCREMENT selection is used only for Time Simplex and Duplex output configurations. This configuration sets the increment size of the relay cycle times in the Tuning Set Up group. The Lockout selection must be set to NONE in order to view this selection. Selections MECH SS Definitions ELECTROMECHANICAL RELAYCycle time in one-second increments. SOLID STATE RELAYCycle time in 1/3-second increments. This is useful for solid state relay applications that require shorter cycle times. DO NOT use this setting unless cycle times of less than 1 second are required.
4/00
149
12.2.79
This prompt is part of the Timer Set Up group. This selection determines how the timer will be reset. Selections KEY AL1 Alarm 1 Definitions Run/Hold key.
12.2.80
RN HLD
This prompt is part of the Tuning Set up group. This selection allows you to disable/enable the Setpoint Ramp/Program RUN/HOLD key. LOCK must be set to None. Selections DIS ENAB Definitions Disable the RUN/HOLD key Enables the RUN/HOLD key
12.2.81
RPUNIT
This prompt is part of the Setpoint Ramp/Program Set up group. This selection determines the engineering units for ramp segments. Selections TIME EU-M EU-H Definitions Hours:Minutes Rate - Engineering units per minute Rate - Engineering units per hour
12.2.82
RSPSRC
This prompt is part of the Control Set up group. This selection determines what your Remote setpoint source will be when toggled by the FUNCTION key or Digital Input. Selections NONE INP2 Definitions NONENo remote setpoint. INPUT 2Remote Setpoint is Input 2.
150
4/00
12.2.83
SECUR
(SECURITY CODE)
This prompt is part of the Tuning Set up group. SECURITY CODEThe level of keyboard lockout may be changed in the Set Up mode. Knowledge of a Security code may be required to change from one level to another. Select this number here, copy it, and keep it in a secure location. Entering 0 disables the security code feature. NOTE: The Security Code is for keyboard entry only and is not available via communications. Can only be changed if LOCK selection is NONE. .Range of Setting: 0 to 4095 (Default = 1000)
12.2.84
SGx RP
This prompt is part of the Setpoint Ramp/Program Set up group. A ramp segment is the time it takes to change the setpoint to the next setpoint value in the program. Ramps are odd number segments. Segment #1 will be the initial ramp time. ATTENTION
The selection of time or rate is made at prompt RP UNIT.
Range of Setting: TIME - Hours:Minutes Range = 0-99 hrs:59 min or EU-M - Degrees/Minute Range = 0 to 999 EU-H - Degrees/Hour Range = 0 to 999
12.2.85
SGx SP
This prompt is part of the Setpoint Ramp/Program Set up group. A soak segment is a combination of soak setpoint (value) and a soak duration (see SGx TI). This is Segment x Soak Setpoint Value .Range of Setting: within the setpoint limits
4/00
151
12.2.86
SGx TI
This prompt is part of the Setpoint Ramp/Program Set up group. A soak segment is a combination of soak setpoint (see SGx SP) and a soak duration. This is the Soak Setpoint Duration (Time) of Segment x. .Range of Setting: 0-99 hrs:59 min
(SHED MODE)
12.2.87
SDMODE
This prompt is part of the Communications Set up group. SHED CONTROLLER MODE AND OUTPUT LEVELDetermines the mode of local control you want when the controller is shed from the communications link. Selections LAST Man_ FSAF AUTO Definitions SAME MODE AND OUTPUTThe controller will return to the same mode (manual or automatic) at the same output level that it had before shed. MANUAL MODE, SAME OUTPUTThe controller will return to manual mode at the same output level that it had before shed. MANUAL MODE, FAILSAFE OUTPUTThe controller will return to manual mode at the output value selected at Control prompt FAILSAFE. AUTOMATIC MODE, LAST SPThe controller will return to the automatic mode and the last setpoint used before shed.
(SHED SETPOINT RECALL)
12.2.88
SHD_SP
This prompt is part of the Communications Set up group. The setpoint to be used after Shed is recalled. Selections LSP CSP Definitions Controller will use last local or remote setpoint used. When in slave mode, the controller will store the last host computer setpoint and use it at the Local setpoint. When in monitor mode, the controller will shed to the last UDC Local or Remote setpoint used, and the LSP is unchanged.
12.2.89
SHDTIM
(SHED TIME)
This prompt is part of the Communications Set up group. The number that represents how many sample periods there will be before the controller sheds from communications. Each period equals 1/3 seconds; 0 equals No shed. Range of Setting: 0 to 255 Sample Periods
152
4/00
12.2.90
SOKDEV
This prompt is part of the Setpoint Ramp/Program Set up group. Each soak segment can have a deviation value of from 0 to 99 which guarantees the value for that segment. Guaranteed soak segment values >0 guarantee that the segments process variable is within the deviation for the configured soak time. Whenever the deviation is exceeded, soak timing is frozen. There are no guaranteed soaks whenever the deviation value is configured to 0 (that is, soak segments start timing soak duration as soon as the soak setpoint is first reached, regardless of where the process variable remains relative to the soak segment). The value is the number in engineering units, above or below the setpoint, outside of which the timer halts. Range of Setting: selection. 0 to 99. The decimal location corresponds to input 1 decimal
12.2.91
SP Hi
This prompt is part of the Control Set up group. This selection prevents the local and remote setpoints from going above the value selected here. The setting must be equal to or less than the upper range of input 1 and input 2. Input 2, when configured for remote setpoint, will be restricted to this upper limit. Range of Setting: 0 to 100 % of span input in engineering units with decimal place
12.2.92
SP Lo
This prompt is part of the Control Set up group. This selection prevents the local and remote setpoints from going below the value selected here. The setting must be equal to or greater than the lower range of input 1 and input 2. Input 2, when configured for remote setpoint, will be restricted to this lower limit. Range of Setting: 0 to 100 % of span input in engineering units with decimal place
4/00
153
12.2.93
SPPROG
This prompt is part of the Setpoint Ramp/Program Set up group. This selection allows you to disable/enable the Setpoint Ramp/Soak Program function. SPRAMP and SPRATE must be disabled. Selections DIS ENAB Definitions Disables the Ramp/Soak Program Function. Allows SPRAMP or SPRATE option to be selected. Enables the setpoint Ramp/Soak Program Function.
12.2.94
SPRAMP
This prompt is part of the Setpoint Ramp/Program Set up group. This selection allows you to disable/enable the Setpoint Ramp function. Make sure you configure a ramp time (TI MIN) and a final setpoint value (FINLSP). SPPROG and SPRATE must be disabled. Selections DIS ENAB Definitions Disables the Setpoint Select Function. Allows SPPROG or SPRATE option to be selected. Enables the Setpoint Select Function.
(SETPOINT RATE)
12.2.95
SPRATE
This prompt is part of the Setpoint Ramp/Program Set up group. This selection allows you to configure a specific rate of change for any local setpoint change. SPRAMP and SPPROG must be disabled Selections DIS ENAB Definitions Disables the Setpoint Rate option. Enables the Setpoint Rate option. SP Rate parameters (EUHRUP, EUHRDN) appear when Rate is enabled.
154
4/00
12.2.96
SP SEL
This prompt is part of the Tuning Set up group. This selection allows you to disable/enable the Setpoint Select function. LOCK must be set to NONE. Selections DIS ENAB Definitions Disables the Setpoint Select Function. Enables the Setpoint Select Function.
(SETPOINT TRACKING)
12.2.97
SP TRK
This prompt is part of the Control Set up group. The local setpoint can be configured to track either PV or RSP as listed below. ATTENTION
For selections other than NONE, LSP is stored in nonvolatile memory only when there is a mode change; i.e., when switching from RSP to LSP or from Manual to Automatic. If power is lost, then the current LSP value is also lost.
Definitions NO TRACKINGIf local setpoint tracking is not configured, the LSP will not be altered when transfer from RSP to LSP is made. PROCESS VARIABLELocal setpoint tracks the PV when in manual. REMOTE SETPOINTLocal setpoint tracks remote setpoint when in automatic. When the controller transfers out of remote setpoint, the last value of the remote setpoint (RSP) is inserted into the local setpoint.
12.2.98
START
This prompt is part of the Timer Set up group. This selection allows you to select whether the Timer starts with the keyboard RUN/HOLD key or Alarm 2. Selections KEY AL2 Definitions Starts with RUN/HOLD key. Starts on Alarm 2.
12.2.99
STATE
This prompt is part of the Setpoint Ramp/Program Set up group. The program state selection determines the program state after completion. Selections DIS HOLD Definitions Program disabled at program end. Program held at program end.
4/00
155
12.2.100
STRSEG
(START SEGMENT)
This prompt is part of the Setpoint Ramp/Program Set up group. The start segment number designates the number of the first segment. Range of Setting: 1 to 11
12.2.101
SW VAL
This prompt is part of the Control Set up group. This is the value of Process Variable or Setpoint at which the controller will switch from Tuning Constant Set #2 to Set #1. Only appears when PIDSET selection is configured for either 2 PV or 2 SP. Range of Setting: Value in engineering units within PV or SP range limits
12.2.102
TI MIN
This prompt is part of the Setpoint Ramp/Program Set up group. Enter the number of minutes desired to reach the final setpoint of a single setpoint ramp. A ramp time of 0 implies an immediate change of setpoint to the final setpoint. Range of Setting: 0 to 255 minutes
12.2.103
TIMER
(TIMER OPTION)
This prompt is part of the Timer Set up group. This selection enables or disables a configured Time-out period. Selections ENAB DIS Definitions Enables the Timer option. Disables the Timer option.
12.2.104
ToBEGN
This prompt is part of the Setpoint Ramp/Program Set up group. This selection enables or disables programming reset. Selections DIS KEY Definitions Disables programming reset. Allows programming reset from the keyboard.
156
4/00
12.2.105
TUNE
This prompt is part of the Accutune Set up group. If TUNE is selected, and tuning is initiated through the operator interface or digital input (if configured), the algorithm calculates new tuning parameters and enters them into the tuning group. This tuning requires no process knowledge and does not require line out for initialization. Selections DIS ENAB Definitions Disable Accutune. Enables Accutune.
12.2.106
TX DLY
(RESPONSE DELAY)
This prompt is part of the Communications Set up group. TX DELAYConfigurable response-delay timer allows you to force the UDC to delay its response for a time period of from 1 to 500 milliseconds compatible with the host system hardware/software. Range of Setting: 1 to 500 milliseconds
12.2.107
UNITS
This prompt is part of the Communications Set up group. This selection determines how the controller values are expressed during communications. Selections PCT ENG Definitions Percent Engineering units
12.2.108
UNITS
(TEMPERATURE UNITS)
This prompt is part of the Input 1 Set up group. This selection will be indicated on the annunciatorwhat display of temperature you want. Selections F C NONE Definitions Degrees Fahrenheit Degrees Centigrade None
4/00
157
12.2.109
XMITR1
(TRANSMITTER CHARACTERIZATION)
This prompt is part of the Input 1 Set up group. This selection lets you instruct the controller to characterize a linear input to represent a non-linear one. ATTENTION
Prompt only appears when a linear actuation is selected at prompt IN1TYP. FOR EXAMPLE: If input 1 is a 4 to 20 mA signal, but the signal represents a type K thermocouple, select K H and the controller will characterize the 4 to 20 mA signal so that it is treated as a type K thermocouple input (high range).
Selections B EH EL JH JL KH KL NNMH NNML N90H N90L NIC R S TH TL WH WL 100H 100L 200 500 RADH RADI LIN SrT
Definitions BB Thermocouple E HE Thermocouple High E LE Thermocouple Low J HJ Thermocouple High J LJ Thermocouple Low K HK Thermocouple High K LK Thermocouple Low NNMHNi-Ni-Moly Thermocouple High NNMLNi-Ni-Moly Thermocouple Low N90HNiMo-NiCo Thermocouple High N90LNiMo-NiCo Thermocouple Low NICNicrosil-Nisil Thermocouple RR Thermocouple SS Thermocouple T HT Thermocouple High T LT Thermocouple Low W HW5W26 Thermocouple High W LW5W26 Thermocouple Low 100H100 Ohm RTD High 100L100 Ohm RTD Low 200200 Ohm RTD 500500 Ohm RTD RADHRadiamatic RH RADIRadiamatic RI LINLinear SrTSquare Root
158
4/00
12.2.110
XMITR2
(TRANSMITTER CHARACTERIZATION)
This prompt is part of the Input 2 Set up group. This selection lets you instruct the controller to characterize a linear input to represent a non-linear one. ATTENTION
Prompt only appears when a linear actuation is selected at prompt IN2TYP. FOR EXAMPLE: If input 2 is a 4 to 20 mA signal, but the signal represents a type K thermocouple, select K H and the controller will characterize the 4 to 20 mA signal so that it is treated as a type K thermocouple input (high range).
Selections B EH EL JH JL KH KL NNMH NNML N90H N90L NIC R S TH TL WH WL 100H 100L 200 500 RADH RADI LIN SrT
Definitions BB Thermocouple E HE Thermocouple High E LE Thermocouple Low J HJ Thermocouple High J LJ Thermocouple Low K HK Thermocouple High K LK Thermocouple Low NNMHNi-Ni-Moly Thermocouple High NNMLNi-Ni-Moly Thermocouple Low N90HNiMo-NiCo Thermocouple High N90LNiMo-NiCo Thermocouple Low NICNicrosil-Nisil Thermocouple RR Thermocouple SS Thermocouple T HT Thermocouple High T LT Thermocouple Low W HW5W26 Thermocouple High W LW5W26 Thermocouple Low 100H100 Ohm RTD High 100L100 Ohm RTD Low 200200 Ohm RTD 500500 Ohm RTD RADHRadiamatic RH RADIRadiamatic RI LINLinear SrTSquare Root
4/00
159
160
4/00
Index
13 Index
A
Aborting Accutune, 63 Accuracy, 4 ACCUTUNE - DEMAND TUNING, 157 Accutune Error Codes, 31, 63 ACCUTUNE ERROR CODES, 121 Accutune II, 61 Accutune Set Up Group, 31 Alarm and Duplex Output Connections, 17, 19 Alarm Blocking, 42 ALARM BLOCKING, 126 Alarm Hysteresis, 42 ALARM HYSTERESIS, 121 Alarm Relay Action., 6 Alarm Relay Output failure, 112 Alarm Relays, 8 Alarm Setpoints, 66 Alarm Setpoints Display, 66 Alarms Set Up Group, 41 Alarmx Segment Event x, 42 Alarmx Setpoint x State, 42 ALARMx SETPOINTx EVENT, 123 ALARMx SETPOINTx STATE, 123 Alarmx Setpointx Type, 41 ALARMx SETPOINTx TYPE, 124 Alarmx Setpointx Value, 41 ALARMx SETPOINTx VALUE, 125 Algorithm Set Up Group, 32 Ambient Temperature, 4 Annunciators, 49 Application related problems, 102 ATUNE Group, 31 Auto/Manual key, 48 Auto/Manual Key Lockout, 28 AUTO/MANUAL KEY LOCKOUT, 121 Automatic Switchover Value, 36 AUTOMATIC SWITCHOVER VALUE, 156 AUTOMATIC with LOCAL SETPOINT, 57 AUTOMATIC with REMOTE SETPOINT, 57 Auto-only Mode, 54 Autotune is complete, 63 Autotune key, 48 Autotune Key Lockout, 28 AUTOTUNE KEY LOCKOUT, 120 Auxiliary Output, 38 AUXILIARY OUTPUT, 122 Auxiliary Output Calibration, 98 Auxiliary Output Calibration Procedure, 99 AUXILIARY OUTPUT HIGH SCALING FACTOR, 119 AUXILIARY OUTPUT LOW SCALING FACTOR, 119
B
Bckground tests, 105 Baud Rate, 39 BAUD RATE, 125 Bias on Input 1, 34 Bias on Input 2, 35 Burnout Protection, 34 BURNOUT PROTECTION, 126
C
Calibration Mode, 94 Calibration Steps, 84 CE Conformity, 4 CE Conformity (Europe), 2 Changing Control Modes, 58 Changing the Local Setpoints, 58 COMMUNICATION OVERRIDE UNITS, 157 Communications Override Units, 40 Communications State, 39 COMMUNICATIONS STATE, 127 Composite Wiring Diagram, 13 Computer Setpoint Bias, 40 COMPUTER SETPOINT BIAS, 127 Computer Setpoint Ratio, 40 COMPUTER SETPOINT RATIO, 129 Configuration, 23 Configuration Procedure, 25 Configuration Prompt Hierarchy, 24 Control Algorithm, 32 CONTROL ALGORITHM, 127 Control and Alarm Relay Contact Information, 8 Control Modes, 57 Control Output Direction, 36 CONTROL OUTPUT DIRECTION, 120 Control Relay 1, 6 Control Relay 2, 6 Control Relays, 8 Control Set Up Group, 36 Control/Alarm Circuit Wiring, 11 Controller Failure Symptoms, 107 Controller Grounding, 11 Current Duplex Range, 32 CURRENT DUPLEX RANGE, 119 Current Output, 6, 16 Current Proportional Output Calibration, 96 Current Proportional Output Failure, 109
4/00
161
Index
Current/Time or Time/Current Proportional Output failure, 111 Customer support, 103 CYCLE TIME - HEAT, 129 Cycle Time (Cool), 28 Cycle Time (Heat), 28 CYCLE TIME2 - COOL, 130
D
Deadband, 37 DEADBAND, 130 DECIMAL POINT LOCATION, 130 Decimal Point Selection, 33 Demand Tuning, 31 Digital Input, 38 DIGITAL INPUT, 131 Digital input (remote) operation, 81 Digital Input Combinations, 38 DIGITAL INPUT COMBINATIONS, 131 Dimensions, 9 DISPLAY FOR TIMER OPTION, 140 DOWNSCALE BURNOUT, 126 Duplex Control, 62
Failsafe Output Value for Restart After a Power Loss, 68 features, 1 Field Wiring, 85 Filter for Input 1, 34 Filter for Input 2, 35 Function Parameter Reference Guide, 117 Function Prompts, 24 Fuzzy Overshoot Suppression, 31, 64 FUZZY OVERSHOOT SUPPRESSION, 135
G
Guaranteed soak, 76 GUARANTEED SOAK DEVIATION, 153 Guaranteed Soak Deviation Value, 30
H
High Output Limit, 37 HIGH OUTPUT LIMIT, 143 High Scaling Factor, 38 Hysteresis, 37 HYSTERESIS - OUTPUT RELAY ONLY, 135
E
ELAPSED TIME, 60 Electrical Considerations, 11 Electrical Noise Precautions, 11 Electromechanical Relay Output, 14 Emissivity, 34 EMISSIVITY, 133 END SEGMENT, 133 End segment number, 75 End Segment Number, 29 Engineering units for Ramp Segments, 30 ENGINEERING UNITS FOR RAMP SEGMENTS, 150 equipment you will need to calibrate, 86 Error Codes, 63 Error Messages, 51 Estimated Motor Position, 67 External Interface Option Connections, 18 External Solid State Relay Option, 16 External Wiring, 11
I
Initial Start-up, 21 Input 1 Actuation Type, 33 INPUT 1 ACTUATION TYPE, 138 Input 1 and Input 2 Wiring Terminals, 85 INPUT 1 BIAS, 125 Input 1 Calibration Procedure, 89 Input 1 Connections, 14 INPUT 1 FILTER, 134 Input 1 High Range Value, 34 INPUT 1 HIGH RANGE VALUE, 137 Input 1 Low Range Value, 34 INPUT 1 LOW RANGE VALUE, 137 INPUT 1 RATIO, 149 Input 1 Set Up Group, 33 Input 1 Set Up Wiring, 87 Input 2 (RSP) Jumper Placement, 6 INPUT 2 ACTUATION TYPE, 140 INPUT 2 BIAS, 125 Input 2 Calibration Procedure, 92 Input 2 Connections, 14 INPUT 2 FILTER, 134 Input 2 High Range Value, 35 INPUT 2 HIGH RANGE VALUE, 139 Input 2 Low Range Value, 35 INPUT 2 LOW RANGE VALUE, 139 INPUT 2 RATIO, 149 Input 2 Set Up Group, 35 Input 2 Set Up Wiring, 91 Input 2 Type, 35
F
Factory calibration, 93 Failsafe Function Prompt, 68, 69 Failsafe Manual Mode, 21, 104 Failsafe Mode, 37, 69 FAILSAFE MODE, 135 Failsafe Output Value, 37 FAILSAFE OUTPUT VALUE, 68, 134
162
4/00
Index
Input Calibration, 83 Input I Jumper Placement, 6 Installation, 3 Installation related problems, 102 Internal Open Collector Output, 16
N
Non-Latching, 69 Number of Program Recycles, 30 Number of Tuning Parameter Sets, 36 NUMBER OF TUNING PARAMETER SETS, 146
J
Jumper for Input 1, 86 Jumper for Input 2, 86 Jumper Placement, 7
O
Open Collector Relay Output, 15 Operating Limits, 4 operating parameters, 50 Operation, 53 Operator Interface, 1, 22, 46 Output Algorithm, 32 OUTPUT ALGORITHM, 142 Output Calibration, 95
K
Key error, 48 Key Error Message, 22 Key Functions, 22 key lockout, 48 Keyboard failure, 113
P, Q
Parity, 39 PARITY, 143 Parts Identification, 115 Parts List, 115 Permissible Wiring Bundling, 12 Physical Considerations, 9 Position proportional or 3 position step test failures, 104 Power, 4 Power Consumption, 4 power failure symptoms, 109 Power Line Frequency, 34 POWER LINE FREQUENCY, 135 Power outage, 81 Power Outage, 73 Power Up Controller Mode Recall, 36 POWER UP CONTROLLER MODE RECALL, 148 Powering Up, 21 Power-up Tests, 104 Pre-installation Information, 4 Preliminary Checks, 6 Program Contents, 74 Program record sheet, 79 Program state, 76 Program State at Program End, 30 PROGRAM STATE AT PROGRAM END, 155 Program termination state, 76 Program Termination State, 30 PROGRAM TERMINATION STATE), 145 Proportional Band 2 or Gain 2, 27 PROPORTIONAL BAND 2 or GAIN 2, 144 Proportional Band or Gain, 27 PROPORTIONAL BAND or GAIN, 144 Proportional Band Units, 37 PROPORTIONAL BAND UNITS, 145 PV Hot Start, 71
L
LANGUAGE, 140 Language Selection, 34 Latching, 69 Latching Alarm for Output, 42 LATCHING ALARM FOR OUTPUT, 120 Local Loopback Test, 40 LOCAL LOOPBACK TEST, 141 Local Setpoint Source, 36 LOCAL SETPOINT SOURCE, 141 Lockout, 28 LOCKOUT, 141 lockout feature, 47 Lockout levels, 47 Low Output Limit, 37 LOW OUTPUT LIMIT, 143 Low Scaling Factor, 38 Lower Display Key Parameter Prompts, 50
M
Mains Power Supply, 11, 13 MANUAL, 57 Manual Reset, 27 MANUAL RESET, 142 Mechanical Shock, 4 Minimum and Maximum Range Values, 84 Model Number Interpretation, 5 Monitoring t, 45 Motor Position Display, 67 Motor Time, 100 Mounting, 9 Mounting Method, 10 Mounting Procedure, 10
4/00
163
Index
R
Ramp time or rate segments, 75 Ramp unit, 75 Ramp/soak profile example, 77 Rate 2 in Minutes, 27 Rate Down, 29 RATE DOWN VALUE, 133 Rate in Minutes, 27 RATE TIME, 148 Rate Up, 29 RATE UP VALUE, 133 RATE2 TIME, 148 Ratio on Input 1, 34 Ratio on Input 2, 35 Recycle number, 75 RECYCLES, 149 Relative Humidity, 4 Relay Cycle Time Increment, 32 RELAY CYCLE TIME INCREMENT, 149 Remote Setpoint Source, 36 REMOTE SETPOINT SOURCE, 150 RESET - INTEGRAL TIME, 136 Reset in minutes/repeat, 27 Reset in repeats/minute, 27 Reset Program to Beginning, 76 Reset Program to the Beginning, 30 RESET PROGRAMMING TO BEGINNING, 156 Reset Units, 37 RESET UNITS, 142 RESET2 - INTEGRAL TIME, 136 Response Delay, 39 RESPONSE DELAY, 157 Restore Factory Calibration, 93 RTD Inputs, 88 Run/Hold key, 48 RUN/HOLD key, 71 Run/Hold Key Lockout, 28 RUN/HOLD KEY LOCKOUT, 150 Run/Monitor the program, 80
S
Security Code, 28, 46 SECURITY CODE, 151 SEGMENT DURATION, 152 SEGMENT RAMP, 151 Segment Ramp or Rate Time, 30 SEGMENT SETPOINT, 151 Segment Soak Duration, 30 Segment Soak Setpoint Value, 30 Set Point Select function key, 48 Set Up Group, 24 Set Up groups, 23 Set Up Wiring Procedure for Auxiliary Output, 98 Setpoint High Limit, 36
SETPOINT HIGH LIMIT, 153 Setpoint Low Limit, 36 SETPOINT LOW LIMIT, 153 Setpoint Ramp, 29, 72 Setpoint Ramp Final Setpoint, 29 SETPOINT RAMP/SOAK PROGRAM, 154 Setpoint Ramp/Soak Programming, 29, 74 Setpoint Rate, 29, 72 SETPOINT RATE, 154 Setpoint Rate/Ramp/Program Operation, 71 Setpoint Select Function Lockout, 28 SETPOINT SELECT FUNCTION LOCKOUT, 155 Setpoint Tracking, 36 SETPOINT TRACKING, 155 Setpoints, 58 SHED MODE, 152 Shed Output Mode, 40 Shed Setpoint Recall, 40 SHED SETPOINT RECALL, 152 Shed Time, 39 SHED TIME, 152 Shock hazard warning, 108 SINGLE DISPLAY DEFAULT, 133 Single Display Functionality, 54 Single Display Parameters, 55 SINGLE SETPOINT RAMP, 154 SINGLE SETPOINT RAMP FINAL SETPOINT, 134 Single Setpoint Ramp Time, 29 SINGLE SETPOINT RAMP TIME, 156 Soak segments, 75 software version number, 103 Solid State Relay Output, 15 SP RAMP, 29 SP Ramp Set Up Group, 29 Specifications, 4 SPPROG, 29 SPRATE, 29 Start Segment, 29 START SEGMENT, 156 Start segment number, 75 Start Segment Number, 29 start up, 21 Start Up Procedure for Operation, 56 Station Address, 39 STATION ADDRESS, 127 Status Tests, 104 Suppression Devices, 11 Switch between two sets via keyboard, 65 Switching between setpoints, 59
T
Temperature Units, 33 TEMPERATURE UNITS, 157
164
4/00
Index
Test Failures, 21, 104 Thermocouple Inputs Using a Thermocouple Source, 87 Thermocouple Inputs Using an Ice Bath, 87 Three position step control, 100 Three Position Step Control, 36 Three Position Step Control algorithm, 67 Three Position Step Control Connections, 17 THREE POSITION STEP CONTROL OUTPUT START-UP MODE, 147 TIME COUNT INCREMENT, 136 Time Proportional Output failure, 110 TIME REMAINING, 60 TIME-OUT, 60 Time-out Period, 26 TIMEOUT PERIOD, 145 Timer, 59 Timer Count Increment, 26 Timer Display, 26 Timer Function Start, 26 TIMER OPTION, 156 Timer Reset Control, 26 TIMER RESET CONTROL, 150 Timer Set Up Group, 26 TIMER START SELECTION, 155 Transmitter Characterization, 33 TRANSMITTER CHARACTERIZATION, 158, 159 Transmitter Characterization for, 35 Troubleshooting Aids, 102 troubleshooting procedures, 108 Troubleshooting/Service, 101 TUNE, 31, 61 Tune for Duplex (Heat/Cool), 62 Tuning, 27
U
Universal Output Functionality and Restrictions, 12 UPSCALE BURNOUT, 126
V
Vibration, 4 Voltage and Resistance Equivalents for 0% and 100% Range Values, 84
W, X, Y, Z
WARNINGSHOCK HAZARD, 108 Wiring, 11 Wiring Bundling, 12 Wiring Connections for 1 to 5 Volt Input Input 2, 92 Wiring Connections for 4 to 20 mA Input Input 2, 91 Wiring Connections for Calibrating Auxiliary Output, 98 Wiring Connections for Calibrating Current Proportional Output, 96 Wiring Connections for Radiamatic, Milliampere, Millivolts, or Volts (Except 0 to 10 Volts), 89 Wiring Connections for RTD (Resistance Thermometer Device), 88 Wiring Diagrams, 12 Wiring the Controller, 13 worksheet, 74
4/00
165
Index
166
4/00
Sensing and Control Honeywell Inc. 11 West Spring Street Freeport, IL 61032
51-52-25-73C 400 Printed in USA
www.honeywell.com/sensing