Power Meters PDF
Power Meters PDF
Power Monitoring
Power Monitoring Systems Overview Intelligent Metering and Control Devices Power Meters PAC3100 PAC3200 PAC4200 9340 / 9360 9510 / 9610 9510 RTU Advanced Data Recorder Enclosed Meters Branch Circuit Monitoring / Embedded Metering Low Voltage Current Transformers Energy Management Software Powermanager Software WinPM.net Software Application Engineering Application Engineering Services
9-2 9-3 9-4 9-5 9-6 9-7 9-8 9-9 9-10 9-11 9-12 9-13 9-14 9-15 9-16 9-17 9-18
Powermanager Software WinPM.net Software
Siemens recognizes that high performance facilities make for high performance business. Energy is the lifeline of your business, and better efficiency and sustainability can have a large positive impact on your bottom line. Energy Management and Control Systems from Siemens are complete enterprise solutions that help you manage the energy costs and availability of your business. With our advanced meters and controls, you can be sure to use only the energy you need, when you need it. Siemens Power Distribution Solutions contribute toward achieving LEED certification and provides the needed energy metering data for federal/local government energy reductions programs.
Quality Reliability & Analysis Cost Allocation & Billing n Utilities Usage Aggregation n Load Preservation n Equipment Monitoring n Facility Monitoring & Automation n Sequence of Event Recording n Preventative Maintenance n Electrical Asset Management
n Utilities
Additional Products/Services Available: n Branch Circuit Monitoring n Sub-Billing and Cost Allocation n Application Engineering n Services Agreements n Network/Communication Components n Integration with Existing n SCADA/BAS Systems n Incorporation of Third Party Devices
9
POWER MONITORING
Power Meters
For Technical Assistance Contact: 1-800-333-7421 Online Support: www.siemens.com/ automation/ support-request For The Latest Information Go To: www.usa.siemens.com/pds
1. Power Meters Siemens power monitors combine the best of new technologies and proven practices. Monitor critical loads, power quality, and demand via the web directly from the meters. 2. Power Monitoring Software WinPM.Net and Powermanager web-enabled software facilitates easy, enterprise-wide connection to power monitoring equipment, circuit breakers, and other devices from Siemens and third parties. Access information via the web with unlimited no-cost clients using built-in WebReachTM via your web browser. 3. Communications Networks Utilize existing Ethernet or RS-485 communications networks to extract the information you need and get it where it needs to go. 4. Components Current Transformers (CTs), Voltage/Potential Transformers (PTs), Power Supplies, Ethernet Switches, Protocol Converters. Siemens can provide everything required for your system. 5. Intelligent I/O Our S7 I/O enables plug-n-play communications with Modbus devices and expands digital and analog input and output functionality of Siemens Systems. 6. Billing and Load Allocation Software Powermanager is the simplified solution for cost allocation, billing & load/demand analysis using your web browser.
7. Engineering Services PDS Application Engineers can help from design through commissioning of even the most demanding power quality and monitoring systems. 8. Motor Control Centers Monitor mains and feeders for critical or power-intensive loads. Communicate with WL and VL breakers, SIMOCODE, I/O and devices from other manufacturers. Use Siemens power meters to web-enable new as well as existing MCCs. 9. Low & Medium Voltage Switchgear Web-enable switchgear by having Siemens power monitoring as well as breaker status and upload the information to a corporate Intranet or to the Internet. Use MeterMailTM directly from meters for alarm conditions or simple reporting. 10. Facility Management Systems Tie into building automation systems to provide the required power and energy information. Many communications options are available ranging from legacy protocols to XML directly from the power monitors. 11. Distributed Control Systems, Automation, and SCADA/Human Machine Interface Siemens power monitors and/or software can talk to all major vendors systems.
POWER MONITORING
9-2
PAC3200
n n n n n
PAC4200
n n n n n n
9340
n n n n n n n
9360
n n n n n n n n
9510 ADR
9510
n n n n n n n n
9610/9610H
n n n n n n n n n 17 s @ 60 Hz, (20 s @ 50 Hz) 127th/256th 512/1024 n n n n n n 800 n
63rd 128 n
63rd 256
n n n n 3 n n
n n n n 800 n
800
0.1
n n n
0.1
n n
0.001
n n 1 2 (1) 1 (1)
0.001
n n 1 2 (1) 1 (1) n n n n n (2) n n n (4) (4) 8/8 7 cycle n n n n 0.2S n n n n n n n n
0.001
n n 1 2 (1) 1 (1) n n n n n (2) n n n (4) (4) 8/8 7
n n 3
2 2
9
POWER MONITORING
Revenue metering
ANSI C12.16 accuracy compliant ANSI C12.20 EN50160 IEC 60687 0.2S compliant IEC 60687 accuracy class 0.5S compliant ANSI class 10 (5A nominal, 10A max) ANSI class 2, IEC 1/10 (1A nominal, 10A max) ANSI class 20, IEC 5/20 (5A nominal, 20A max) MV-90 on serial; Ethernet ports Time-of-use Transformer/line loss compensation 1S 0.5S n n 0.2S n n n n
Some features are optional. Refer to datasheets for allowable port configurations. Products meet or exceed the accuracy requirements of the standards listed; due to form factors, not all ANSI/IEC compliance tests may apply. Some products certified by third-party laboratory.
9-3
Precision
n n
Energy Management
n n n n n n
Reliability
Economical Measurement Commercial Industrial Residential n Degree of Protection Front IP65 Rear IP20 n 480V Connected Voltage n Simple Retrofit Installation n Integration with Existing Systems
n
ANSI C12.16 Class1s Energy Measurement Voltage +/- 1% Current +/- 1% Power Factor +/- 1% Sampling Rate 64/per cycle Revenue Accurate Sub Billing Cost Allocation Cost Effective
Energy Consumption Demand Control Automation Integration Solution for LEED credit Monitors Critical Equipment Sub Metering
MODBUS RTU
96 mm 3.78 in.
96 mm 3.78 in.
Full Graphic LCD Display to indicate: Display title or designation of the displayed measurements Phase Measured value Unit Labeling of function keys
POWER MONITORING
Order information
Product SENTRON PAC3100 compression terminals AC/DC SENTRON Adapter Plate for 4700/4720 meter cutout SENTRON PAC32/4200 Meter DIN Rail adapter Meter display will not be seen Catalog Number
Languages included as standard in the meter are English, German, French, Spanish, Italian, Portuguese, Turkish, Russian and Chinese.
9-4
Precision
n n
Energy Management
Energy Consumption Automation Integration n Solution for LEED credit n Monitors Critical Equipment n Modbus TCP/RTU n Industrial Systems PROFIBUS PROFINET
n n
Reliability
Economical Measurement Commercial Industrial Residential n Degree of Protection Front IP65 Rear IP20 n 600V Connected Voltage n Simple Retrofit Installation n Integration with Existing Systems
n
ANSI C12.20 Class 0.5s Energy Measurement Voltage +/- .3% Current +/- .3% Power Factor +/- .5% Sampling Rate 64/per cycle Total Harmonic Distortion (THD) Revenue Accurate Sub Billing Cost Allocation Cost Effective
Modbus TCP integrated into the meter as standard SENTRON PAC, PROFIBUS DP, MODBUS RTU and PROFINET expansion modules for remote data transmission
96 mm 3.78 in.
96 mm 3.78 in. Terminal blocks for voltage and current measuring, control power and digital input and output (available with compression terminals)
Full Graphic LCD Display to indicate: Display title or designation of the displayed measurements Phase Measured value Unit Labeling of function keys
Example of operating menu: The texts can be displayed in several languages, which can be selected directly on the device. The large graphic LCD display facilitates reading even from a distance. For optimum visability even in poor light conditions the PAC3200 comes with a gradually adjustable background illumination.
9
POWER MONITORING
Order information
Product SENTRON PAC3200 compression terminals not suitable for use with ring tongue terminals, AC/DC SENTRON PAC3200 compression terminals not suitable for use with ring tongue terminals, DC only SENTRON PAC PROFIBUS DP expansion module SENTRON PAC MODBUS RTU expansion module SENTRON PAC PROFINET expansion module Connector block suitable for use with ring tongue terminals SENTRON Adapter Plate for 4700/4720 meter cutout SITOP Power Supply AC 99-264VAC, 24 VDC, 0.5A SENTRON PAC3200/4200 Meter DIN Rail adapter Meter display will not be seen Catalog Number 7KM2112-0BA00-3AA0 7KM2111-1BA00-3AA0 7KM9300-0AB00-0AA0 7KM9300-0AM00-0AA0 7KM9300-0AE00-0AA0 Consult Siemens Sales 93-47ADAPTER 6EP1331-2BA10 7KM9900-0YA00-0AA0
Languages included as standard in the meter are English, German, French, Spanish, Italian, Portuguese, Turkish, Russian and Chinese. Omit dashes from part numbers when ordering except on 93-47ADAPTER.
9-5
Precision
n n
Energy Management
Serves two masters via the TCP connection n Energy Consumption n Min/Max and Event Logs Storage Capacity 40 days at 15 min intervals Event Logging 4000 events n Demand Control n Automation Integration n Modbus Gateway n Modbus TCP/RTU n Industrial Systems PROFIBUS PROFINET
n
MODBUS TCP integrated into the meter as standard
Reliability
n n
n n
ANSI C12.20 Class .2s Energy Measurement Voltage +/- .2% Current +/- .2% Power Factor +/- .5% Sampling Rate 170/per cycle Individual Harmonics up to 31st Power Quality Revenue Accurate Sub Billing Cost Allocation Cost Effective
n n n n n
Monitors Critical Equipment Economical Measurement Commercial Industrial Degree of Protection Front IP65 Rear IP20 600V Connected Voltage Customizable Displays Simple Retrofit Installation Integration with Existing Systems Solution for LEED credit
SENTRON PAC, PROFIBUS DP, MODBUS RTU and PROFINET expansion modules for remote data transmission.
Terminal blocks for voltage and current measuring, control power and digital input and output Digital input and output module provides 4 additional digital inputs and 2 digital outputs
96 mm 3.78 in.
POWER MONITORING
96 mm 3.78 in.
77 mm 3.03 in.
Order information
Product SENTRON PAC4200 compression terminals not suitable for use with ring tongue terminals, AC/DC SENTRON PAC PROFIBUS DP expansion module SENTRON PAC MODBUS RTU expansion module SENTRON PAC PROFINET expansion module SENTRON PAC I/O module 4DI + 2DO Connector block suitable for use with ring tongue terminals SENTRON Adapter Plate for 4700/4720 meter cutout SENTRON PAC32/4200 Meter DIN Rail adapter Meter display will not be seen SITOP Power Supply AC 99-264VAC, 24 VDC, 0.5A Catalog Number 7KM4212-0BA00-3AA0 7KM9300-0AB00-0AA0 7KM9300-0AM00-0AA0 7KM9300-0AE00-0AA0 7KM9300-0AB00-0AA0 Consult Siemens Sales 93-47ADAPTER 7KM9900-0YA00-0AA0 6EP1331-2BA10
99mm, 3.90 in., with expansion module Omit dashes from part numbers when ordering except on 93-47ADAPTER.
9-6
Precision
ANSI C12.20 Class 0.5s Energy Measurement Voltage +/- .1% Current +/- .1% Power Factor +/- .5% Sampling Rate 128/per cycle 9340 Individual Harmonics up to 31st 9360 Individual Harmonics up to 63rd 9360 Sags / Swells Detection Programmable Math / Logic Function n Revenue Accurate Sub Billing Cost Allocation
n
Energy Management
Energy Consumption 9360 Waveform Capture n Customizable Webpages n Min/Max and Event Logs 9340 Storage Capacity 80kb 9360 Storage Capacity 800kb n Demand Control n Automation Integration n Solution for LEED credit n Monitors Critical Equipment n Modbus Gateway n Modbus TCP/RTU n Industrial Systems
n n
Reliability
n Economical Measurement Commercial Industrial n Degree of Protection Front IP52 Rear IP30 n 600V Connected Voltage n Customizable Displays n Email Alarms through Ethernet n Field Addable Modules n Simple Retrofit Installation n Integration with Existing Systems
Order information
Meter with integrated display ACCES S 9340 meter with display, THD, alarming, 80 kb logging ACCESS 9360 meter with display, THD, alarming, 800 kb logging, configurable waveform sag, swell detection Meter with remote display ACCESS 9340 meter with remote display, basic instrumentation, THD, alarming, 80 kb logging ACCESS 9360 meter with display, THD, alarming, 800 kb logging, configurable waveform sag, swell detection Meter without display ACCESS 9340 meter without display, THD, alarming, 80 kb logging ACCESS 9360 meter without display, THD, alarming, 800 kb logging, configurable waveform sag, swell detection Remote display, adapter and accessories ACCESS 9340 display adapter kit ACCESS 9360 display adapter kit ACCESS 9340 and 9360 display adapter ACCESS 9340/60 gasket analog meter round ACCESS 9340/60 I/O module, 2 relay output, 6 digital input ACCESS 9340/60 I/O module, 2 relay output, 2 digital input, 2 analog input, 2 analog output ACCESS 9340/60 ethernet communication card ACCESS 9340/60 RJ11 extender kit Catalog Number 9340DC 9360DC Catalog Number 9340RC 9360RC Catalog Number 9340TC 9360TC Catalog Number 9340-DISPKIT 9360-DISPKIT 9340-60-DISPADA 9340-60-GASKET 9340-60-I/O26 9340-60-I/O2222 9340-60-ETHER 9340-60-RJ11EXT
9
POWER MONITORING
9-7
Precision
n n
Energy Management
n n n n n n
Reliability
n
ANSI C12.20 Class .2s Energy Measurement Voltage +/- .01% Current +/- .01% Power Factor +/- .5% 9510 Sampling Rate 256/per cycle 9610 Sampling Rate 512/per cycle 9610 XH Sampling Rate 1024/per cycle 9510 Individual Harmonics up to 127th 9610 Individual Harmonics up to 256th Sags / Swells Detection Programmable Math / Logic Function Revenue Accurate Sub Billing Cost Allocation
n n n n n n
Energy Consumption Waveform Capture Transient Capture 17 s @ 60 Hz Disturbance Direction Detection (DDD) Customizable Webpages Min/Max and Event Logs Storage Capacity up to 3.3 years at 15 min intervals Event Logging up to 20,000 Waveform Captures up to 390 Demand Control Automation Integration Monitors Critical Equipment Modbus Master / Gateway Supports Multiple Protocols Supports Multiple Master via Ethernet
n n n n
n n n n
Economical Measurement Commercial Industrial 600V Connected Voltage Transformer Line Loss Compensation Email Alarms Customizable Displays Event / Alarm Log Trending Phasor Diagrams Password Protected Hardware Lockable Supports Copper or Fiber Ethernet Integration with Existing Systems
POWER MONITORING
Front view
Side view
Back View
9-8
Description
Meter base unit and display options Meter with integrated display and 5MB logging memory Meter with integrated display and 10MB logging memory Meter without display (Tran version) and 5MB logging memory Meter without display (Tran version) and 10MB logging memory Sampling rate Standard sampling (256 for 9510) ( 512 for 9610) per cycle maximum 1024 Samples per cycle (9610 only) Power Supply 85-240 Vac / 110-300 Vdc 20-60 Vdc Input Voltage 120 to 347 L-N / 208 to 600 L-L V AC Input Current 1A Nominal (10 Amp full scale) 5A Nominal (20 Amp full scale) Frequency 50 Hz 60 Hz Communication Cards RS232/RS485 (Selectable) RS485 Infrared (Note 1) Modem (Notes 1 & 2) 10/100 Base-T 10/100 Base-FX A C G H J K 1 2 C H D E T U
1 5 5 6
Auxiliary I/O Cards None (base meter includes 8 digital in and 7 digital out) 8 Binary Inputs; 4 Analog Inputs 0 to 20 mA and 4 Analog Outputs 0 to 20 mA 8 Binary Inputs; 4 Analog Inputs 0 to 1 mA and 4 Analog Outputs -1 to 1 mA Tropicalization Option None Yes Specials None Password protected and hardware lockable (lock enabled/disabled via jumper on comm card) EN50160 Compliance Monitoring (available on 9610 only) EN50160 Compliance Monitoring with password protected and hardware lockable (lock enabled/disabled via jumper on comm) (available on 9610 only) Note 1 The infrared and modem connections cannot be operated simultaneously. The connection type is configurable. Note 2 The listed modems are not suitable for European applications. Contact Siemens for special versions.
Z F G
Z T
9
POWER MONITORING
A B C D
9-9
The 9510-RTU unit can serve many uses through out a facility. This lowcost central display - data recorder can provide HTML web pages and customizable displays to allow easy access to the data and provide E-mail alarming for critical information. This multi-functional unit supports communications to any Modbus RTU device and digital / analog I/O, allowing the 9510-RTU to provide solutions for many different applications.
Description
E
D E T U
Meter base unit and display options Option #1 Meter with integrated display and 5MB logging memory Option #2 Meter with integrated display and 10MB logging memory Option #3 Meter without display, with a 5MB logging memory (TRAN version) Option #4 Meter without display with a 10MB logging memory (TRAN version) Communications ION / Modbus RTU - Factory configured for ION Power Supply 85-240 Vac / Vdc 20-60 Vdc No Display Option Remote transducer option Communication Cards RS232/RS485 (Selectable) RS485 Infrared (Note 1) Modem (Notes 1 & 2) 10/100 Base-T 10/100 Base-FX
C 1 2 R T U
A C G H J K Z F G Z T A
POWER MONITORING
Auxiliary I/O Cards None (base meter includes 8 digital in and 7 digital out) 8 binary inputs; 4 Analog Inputs 0 to 20 mA and 4 Analog Outputs 0 to 20 mA 8 binary inputs; 4 Analog Inputs 0 to 1 mA and 4 Analog Outputs -1 to 1 mA Tropicalization Option None Yes Specials Standard (password protected, no locking or sealing) Note 1 The infrared and modem connections cannot be operated simultaneously. The connection type is configurable. Note 2 The listed modems are not suitable for European applications. Contact Siemens for special versions.
9-10
Features:
n n n n n
Rugged design and small footprint for easy installation Bright, easy-to-read LCD display Multiple configurations Packaged by voltage and current ratings to accommodate any installation Utilizes 5A secondary current input for improved accuracy and increased compatibility
Benefits:
n n n n n
Property Management Firms Government Applications Universities Corporate Campus Facilities Malls Food Courts Building Retrofits
Replace multiple utility meters with one enclosure, saves wall space Consolidate utility bills for sub-billing and energy management, bill tenants on actual usage Improve energy efficiency Aggregate energy purchases for reduced rates Improve productivity when coupled with Siemens software solutions or third party billing software
Catalog Logic:
E N C L X X X X X X X X X X
Meter 31 PAC3100 Series Meter 32 PAC3200 Series Meter 42 PAC4200 Series Meter Voltage 240 240V 480 480V Type 01 NEMA 1 Enclosure 12 NEMA 12 Enclosure Module TC Standard RT Modbus RTU PD PROFIBUS PN PROFINET Options X Standard Meter Enclosure Without Meter Catalog Number ENX24001-121208 ENX24012-121208 ENX48001-121208 ENX48012-121208 Description 12W 12W 12W 12W x x x x 12H 12H 12H 12H x x x x 8D 8D 8D 8D NEMA NEMA NEMA NEMA 1 Enclosure 240V 12 Enclosure 240V 1 Enclosure 480V 12 Enclosure 480V
9
POWER MONITORING
PAC3100 standard is Modbus RTU. PAC3200 and PAC4200 Standard is Modbus TCP. Modules not available on PAC3100.
9-11
Designer and contractor benefits include: n Much smaller footprint versus the traditional socket meter combo units n Factory pre-wired less installation time n Drastically less installation wiring n No CT installation required in the field n All equipment fits into the standard Siemens panel design n Additional utilities like water, air and gas can be easily integrated into the system for a comprehensive monitoring system n Hardwire and wireless communication options n All components factory calibrated to meet revenue metering requirements n Additional meters can be added in the field n UL and CSA-us listed
Branch Circuit Monitoring applications include: n Mixed Tenant & Retail n Industrial Manufacturing n Higher Ed n Strip Malls n Critical Power n Goverment n LEEDS buildings n Airports
POWER MONITORING
Please Contact Your Siemens Sales Engineer for additional information regarding Branch Circuit Monitoring / Embedded Metering 9-12
Siemens Industry, Inc. SPEEDFAX 2011 Product Catalog
Amps 100A 200A 300A 400A 600A 800A 1000A 1200A 1600A 2000A 3000A
Catalog Number PDS-CTSC-011 PDS-CTSC-021 PDS-CTSC-031 PDC-CTSC-042 PDS-CTSC-062 PDS-CTSC-083 PDS-CTSC-013 PDS-CTSC-123 PDS-CTSC-163 PDS-CTSC-200 PDS-CTSC-03R
200A 300A A = 3.75 (95mm) B = 1.51 (38mm) C = 1.25 (32mm) D = 1.13 (29mm) E = 4.20 (107mm) F = 4.75 (121mm)
400A 800A A = 4.90 (124mm) B = 2.89 (73mm) C = 2.45 (62mm) D = 1.13 (29mm) E = 5.57 (141mm) F = 5.91 (150mm)
1000A 1200A A = 4.90 (124mm) B = 5.50 (140mm) C = 2.45 (62mm) D = 1.13 (29mm) E = 8.13 (207mm) F = 5.92 (150mm)
Split-core Round Window Split-core round rubber insulated flexible CTs with 12 heavy duty leads (18 AWG) and 5A secondary output for use on low voltage applications of 600V. Accuracy is 4% for 200/400A, 3% for 400A, and 2% for 600A and above.
Amps 200A 300A 400A 600A 800A 1200A 2000A 3000A 4000A
Window (A) 4.00 4.00 4.00 4.00 4.00 4.00 6.00 6.00 6.00
Catalog Number PDS-CTHC-024 PDS-CTHC-034 PDC-CTHC-044 PDS-CTHC-064 PDS-CTHC-084 PDS-CTSC-123 PDS-CTHC-206 PDS-CTHC-306 PDS-CTHC-406
POWER MONITORING
9-13
Solid core Round metering grade, 600V Catalog Number SMU-CT-011 SMU-CT-021 SMU-CT-025 SMU-CT-031 SMU-CT-041 SMU-CT-061 SMU-CT-081 SMU-CT-123 SMU-CT-02R Primary 100A 200A 250A 300A 400A 600A 800A 1000A 2000A Size 1.75 x 2.47, 1 Window 1.75 x 2.47, 1 Window 1.75 x 2.47, 1 Window 1.75 x 2.47, 1 Window 1.1 x 3.56, 1.56 Window 1.1 x 3.56, 1.56 Window 1.1 x 3.56, 1.56 Window 1.1 x 3.56, 1.56 Window 1.15 x 5.73, 3.25 Window
Shorting Block All low voltage current transformers should be installed with a shorting block to allow for easy removal of the metering unit and to provide a safe method for disconnecting the CT signal. One shorting block is required per meter. Various size shorting blocks are available; 4, 6, and 8 pole configurations are available with four slotted shorting screws and cover. Wire size is 18-10 AWG.
Catalog Number IKU4SC IKU6SC IKU8SC IKU12SC Mounting Ckts. 4 6 8 12 L 3.25 4.50 5.75 8.25 D min. 2.88 4.12 5.38 7.88 D max. 3.00 4.25 5.50 8.00
POWER MONITORING
Typical electrical meter CT and shorting block installation This example shows a common three phase, three wire installation where three CTs and one shorting block are used.
9-14
Cost allocation and Sub-billing Reports Cost allocation and sub-billing functionality in the Powermanager software allows the user to track energy related costs by building, floor, tenant, feeder or location. Match virtually any fixed rate billing structure and use comprehensive multi-year scheduling and time-of-use features to manage the energy costs. Load Studies and Asset Management Trend power usage data to take full advantage of your electrical distribution system capacity and avoid over-design. Create usage profiles that will allow you to distribute loads and avoid demand peak which helps to identify energy leaks such as equipment running during down time. Equipment Monitoring and Control Powermanager allows you to meter all your utilities including gas, steam, air and water and set up general condition alarming and pre-event alarms for impending or imminent conditions. Interface with other energy management and SCADA systems through multiple communication channels and protocols like OPC. Reports Standard reports provide models of daily electricity usage so you can distribute loads and avoid demand peaks. This enables you to allocate energy consumption and/or costs to individual areas and identify expensive processes that need attention. The historic trending report compiles data from load circuits over a users predefined period. This enables the user to fully utilize the power distribution system and run at near rated tolerances. Ordering information
Powermanager Software and Device License Trial License 10 devices, feature packages Expert and Web, 30 days Lean License 10 devices Lean Plus License 10 devices, feature packages Expert and Web Standard Plus License 50 devices, feature packages Expert and Web Advanced Plus License 100 devices, feature packages Expert and Web Maximum Plus License 200 devices, feature packages Expert and Web Powermanager Add Ons and Upgrades Lean Plus to Standard Plus Upgrade License Standard Plus to Advanced Plus Advanced Plus to Maximum Plus Windows Client <= 5 Expansion up to 5 total clients Windows Client <=10 Expansion from 5 to 10 clients, requires <=5 Contact Siemens for upgrade information
Benefits n Visibility and control of power flows n Exact knowledge of the consumption profile n Increase of energy efficiency n Optimization of power supply contracts n Compliance with contractual terms or regulations n Allocation of costs to individual cost centers n Optimization of plant maintenance n Identification of critical systems conditions The Powermanager software: Is available in a stand-alone or LAN/WAN based configuration that can also exchange information with other supervisory systems like building automation software n Can utilize any Ethernet or serial based connections n Is expandable from the basic monitoring application to a fully customized enterprise management system n Is fully scalable with regard to the connected devices and to the softwares function to meet current and future needs
n n
Ensures the seamless integration of power monitoring devices from the Siemens SENTRON PAC series meters and SENTRON WL/VL circuit breakers as well as other Modbus communicating devices Is designed to collect, archive, monitor, display and evaluate any kind of energy related device data Provides web based reporting and detailed graphics construction utilities as standard
Catalog Number 3ZS27110CC200YA7 3ZS27110CC200YA0 3ZS27118CC200YA0 3ZS27128CC200YA0 3ZS27138CC200YA0 3ZS27148CC200YA0 Catalog Number 3ZS27120CC200YD0 3ZS27130CC200YD0 3ZS27140CC200YD0 3ZS27103CC200YH0 3ZS27104CC200YH0
POWER MONITORING
9-15
Cost allocation and sub-billing Track energy-related costs by building, feeder, or tool. Match virtually any billing structure and use comprehensive multi-year scheduling and time-of-use activity profiles. Load studies and asset management Trend power usage data to take full advantage of your electrical distribution system capacity and avoid over-design. Create usage profiles so you can distribute loads and avoid demand peak. Demand and power factor control Eliminate penalties through automated power factor correction, load shedding, or peak shaving.
9
POWER MONITORING
Equipment monitoring and control Meter all your utilities including gas, steam, air and water. Set up alarms for pending problems, prealarm on impending or imminent conditions. Interface with other energy management and SCADA systems through multiple communication channels and protocols. Preventative maintenance Base your maintenance schedule on actual operating history.
9-16
Commercial Construction: New / Retrofit Tenant / Sub Billing Critical Power: Data Centers Hospitals JCAHO Government: Local, State & Federal Government EPACT projects Universities Airports Industrial Applications: Petro - Chem., Cement, Food & Beverage, Waste water, Automotive
n n n n n n n n n n
LAN WAN based solutions using our WinPM.Net web-based software Custom power metering logic Custom billing, energy usage or load profile reports Integration of other utilities like gas, water, steam, air and more Custom interactive one-line, elevation or floor plan graphics Third party hardware and software Integration Extensive alarm configuration and implementation Custom data logging and data retrieval. Siemens or others plant factory witness testing On-site and remote hands-on system training Overall PMC project management
n n
Communication network topology approval drawings Project management plan for the PMC system Interface to Siemens APOGEE building management system Power monitoring workstations and server configuration Final as-built operation and maintenance manuals Integrate with Siemens medium voltage, low voltage Switchgear & motor control centers Integration with Siemens Industrial Automation components & Software WinCC / PCS 7 System communication troubleshooting Site Acceptance Test procedure (SAT), Method of Procedures (MOP), Factory Acceptance Test Procedure (FAT) On-site startup & commissioning
Reliable Power Quality Whether you are designing a fault tolerant mission critical infrastructure or you want to intelligently balance workloads to optimize energy usage and control costs, you need a reliable and industry proven monitoring solution. You will gain a visible look into the actual power consumption to understand the average and peak power utilization, monitor and manage UPSs and power distribution units, or even a complete IT support infrastructure, including generators, environmental systems and detection devices, as well as other components from multiple vendors. A Siemens designed solution using WinPM.Net or Powermanager, coupled with high quality Siemens meters will result in a powerful tool, helping to analyze, identify and correct power issues before they become critical. Instant notification by email or alarm when power quality issues such as sag/swell or voltage disturbance occur.
Flexible Easily integrate with any vendors equipment using standard communication protocols to combine critical alerts and realtime data. Monitor and manage critical power devices from a single uninterruptible power system (UPS), an enterprise-wide network of many UPSs and power distribution devices, or a complete IT support infrastructure, including generators, environmental systems and detection devices, and other components from multiple vendors. Informative Siemens Power Distribution and Solutions provide an energy monitoring solution that can provide you with the reports and the data you need for your operation. Complete power analysis from the incoming utility power to individual branch circuits.
Siemens Industry, Inc. SPEEDFAX 2011 Product Catalog
9
POWER MONITORING
9-17
Technical experts Single source supplier Available 24/7, 365 days a year Reduced total cost of ownership (TCO) Avoid unscheduled downtime with preventive maintenance
POWER MONITORING
9-18