Honeywell L5100 Garage Door Zone Programming Guide
Honeywell L5100 Garage Door Zone Programming Guide
Honeywell L5100 Garage Door Zone Programming Guide
How to Programming Garage Door zones for Alarm or Monitor on the L5100
The L5100 (Rev 6+) provides 3 zones (46, 47, and 48) specifically for the Supervision of garage doors Intrusion Detection and Status Monitoring. The first step in this process is to program in the transmitters used to detect the status of the Garage Door, ie: 5816, 5822T, etc.
3. Learn in the transmitter serial number by pressing Serial Number. Fault and restore the Garage Door Transmitter once and wait for a single beep, fault and restore again and wait for a double beep. The serial and loop number should appear on the display. Fault and restore the transmitter a 3rd time, you should hear three beeps, confirmation the wireless zone. The screen will go back to the Zone Screen.
-1-
Updated: 5/13/13
Step-By-Step
4. Press Device type
6. Press Response Type a. Choose Garage for an Alarm protection point or Garage Monitor if you only want to monitor the garage door status. b. Set choice for Alarm Report, Chime, and Transmitter Supervision as desired (Garage Monitor does not report). c. Finally, press the save button to complete zone programming.
Garage Zone Type = Uses entry delay #2 time when armed in AWAY or STAY modes. Can be armed with the door faulted and will automatically be included in the protection zones when shut. Selectable for Chime and can be bypassed. Report CID code E134. Garage Monitor Zone Type = For monitoring of the garage door open/close status, will not initiate an alarm, report to C.S., or Log. Zone will chime if selected, and the panel can be armed with the zone faulted, and can be bypassed. -2Updated: 5/13/13
Step-By-Step
Compass programming instructions
1. Access the Zone Configuration page located under the Zones tab, scroll down to zones 46, 47, or 48.
2. Click the Device Type drop down and select 3- Garage Door.
-3-
Updated: 5/13/13
Step-By-Step
3. Click the Response Type drop down and select: 50-Garage if programming the zone for Garage door Alarm protection 53-Garage Monitor if programming the zone for Garage door monitoring only
4. Set choice for Alarm Report, Chime, and Input Type as desired. (Garage Monitor does not report)
-4-
Updated: 5/13/13
Step-By-Step
5. Enter the correct loop number utilized on the transmitter
6. Final step is to enter the correct serial number for the transmitter and download to the panel
-5-
Updated: 5/13/13