24ABC6 Baset16 Air Conditioner with Puronr Refrigerant
Wiring Diagram
*CHS BLK or RED RED or BLK L1 11 23 EQUIP GND YEL (NOTE #14) YEL/ BLU *LPS YEL/PNK YEL/PNK *LLS BLK YEL/ BLU BLK BLK *DTS BLK BLU/PNK BLK *CTD *HPS BLU/PNK T1 BRN/YEL C R EXTERNAL POWER SUPPLY 24 V (NOTE #3) Y G R INDOOR THERMOSTAT R C LOGIC T3 *LLS IFR T2 BRN/YEL VIO *LPS (NOTE #14) CONT *DTS *HPS LOGIC T1 * CTD T3 T2 *CH BLK (NOTE #9) CONT L2 COMP BLU BLK C S H R C 23 YEL YEL F OFM BRN BLK BLK
CONNECTION DIAGRAM
BLK CAP YEL *SC (NOTE #8) BLU BLU YEL +t *ST BRN 1 2 5 *SR
SCHEMATIC DIAGRAM (LADDER FORM)
L1 CONT 11 21 5 EQUIP GND *CHS 2 1 *SR *CH OFM C F CAP *SC H CONT 23 23 COMP R C S *ST +t L2
21
208/230 1 POWER SUPPLY
Y R G INDOOR THERMOSTAT (NOTE #6)
EXTERNAL POWER SUPPLY 24 V
INDOOR BLOWER MOTOR
For use with units using R-410A refrigerant COOLING ONLY REQUIRED LIQUID LINE TEMPERATURE CHARGING PROCEDURE Liquid Pressure Required Subcooling
at Service Valve (psig)
251 259 266 274 283 291 299 308 317 326 335 345 354 364 374 384 395 406 416 427 439 450 462 474
CONDENSING UNIT CHARGING INSTRUCTIONS
LEGEND
FACTORY POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING FIELD POWER WIRING COMPONENT CONNECTION FIELD SPLICE JUNCTION CONTACTOR CAPACITOR (DUAL RUN) CRANKCASE HEATER CRANKCASE HEATER SWITCH COMPRESSOR COMPRESSOR TIME DELAY DISCHARGE TEMP SWITCH HIGH PRESSURE SWITCH INDOOR FAN RELAY LIQ LINE SOLENOID VALVE LOW PRESSURE SWITCH OUTDOOR FAN MOTOR START CAPICATOR START RELAY START THERMISTOR
Temperature (F)
8
76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116
6
78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124
10 12 14 16
68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114
1. Only use sub cooling charging method when OD ambient is greater than 70F and less than 100F, indoor temp is greater than 70F and less than 80F, and line set is less than 80 ft. 2. Operate unit a minimum of 15 minutes before checking the charge. 3. Measure liquid service valve pressure by attaching an accurate gauge to the service port. 4. Measure the liquid line temperature by attaching an accurate thermistor type or electronic thermometer to the liquid line near the outdoor coil. 5. Refer to unit rating plate for required subcooling temperature. 6. Find the point where the required subcooling temperature intersects the measured liquid service valve pressure. 7. To obtain the required subcooling temperature at specific liquid line pressure, add refrigerant if liquid line temperature is higher than indicated. When adding refrigerant, charge in liquid form using a flow restricting device into suction service port. Recover refrigerant if temperature is lower. Allow a tolerance of +/- 3F.
CONT CAP *CH *CHS COMP *CTD *DTS *HPS IFR *LLS *LPS OFM *SC *SR *ST
* MAY BE FACTORY INSTALLED
NOTES:
1. 2. 3. 4. 5. 6. 7. Symbols are electrical representation only. Compressor and fan motor furnished with inherent thermal protection. To be wired in accordance with National Electric N.E.C. and local codes. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS. Use copper conductors only. Use conductors suitable for at least 75C (167F). Connection for typical cooling only thermostat. For other arrangements see installation instructions. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN/YEL lead. 8. When start relay and start capacitor are installed, start thermistor is not used. 9. CH not used on all units. 10. If any of the original wire, as supplied must be replaced, use the same or equivalent wire. 11. Check all electrical connections inside control box for tightness. 12. Do not attempt to operate unit until service valves have been opened. 13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize between high and low side before starting. 14. Wire not present if HPS, LPS or CTD are used.
CAUTION
1. Compressor damage may occur if system is over charged. 2. This unit is factory charged with R-410A in accordance with the amount shown on the rating plate. The charge is adequate for most systems using matched coils and tubing not over 15 feet long. Check refrigerant charge for maximum efficiency. See Product Data Literature for required Indoor air Flow Rates and for use of line lengths over 15 feet. 3. Relieve pressure and recover all refrigerant before system repair or final disposal. Use all service ports and open all flow-control devices, including solenoid valves. 4. Never vent refrigerant to atmosphere. Use approved recovery equipment. 330440-101 REV. F
Fig. 1 Wiring Diagram Model sizes 1-1/2 - 5 tons, 208/230-1
Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 01/10
Catalog No: 24ABC6---1W
Replaces: New
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.