Cpu 224xp

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Product data sheet

6ES7214-2AD23-0XB0
SIMATIC S7-200, CPU 224XP COMPACT UNIT, DC POWER SUPPLY 14 DI DC/10 DO DC, 2 AI, 1 AO 12/16 KB CODE/10 KB DATA, 2 PPI/FREEPORT PORTS

Supply voltage
24 V DC permissible range, lower limit (DC) permissible range, upper limit (DC) Yes 20.4 V 28.8 V

Load voltage L+
Rated value (DC) permissible range, lower limit (DC) permissible range, upper limit (DC) 24 V 20.4 V 28.8 V

Input current
Inrush current, max. from supply voltage L+, max. 12 A ; at 28.8 V 900 mA ; 120 to 900 mA, output current for expansion modules (DC 5 V) 660 mA

Encoder supply 24 V encoder supply


24 V Short-circuit protection Output current, max. Yes ; permissible range: 15.4 to 28.8 V Yes ; electronic at 280 mA 280 mA

Memory

6ES7214-2AD23-0XB0 Page 1/ 7

07/12/2013

subject to modifications Copyright Siemens AG 2013

Number of memory modules (optional)

1 ; pluggable memory module, content identical with integral EEPROM; can additionally store recipes, data logs and other files

Data and program memory


Data memory, max. Program memory, max. 10 kbyte 16 kbyte ; 12 KB with active run-time edit

Backup
present Yes ; Program: Entire program maintenance-free on integral EEPROM, programmable via CPU; data: Entire DB 1 loaded from PG/PC maintenance-free on integral EEPROM, current values of DB 1 in RAM, retentive memory bits, timers, counters, etc. maintenancefree via high-performance capacitor; optional battery for long-term buffering

Battery Backup battery


Battery operation Backup time, max. 100 h ; (min. 70 h at 40 C); 200 days (typ.) with optional battery module

CPU processing times


for bit operations, max. 0.22 s

Counters, timers and their retentivity S7 counter


Number 256

of which retentive with battery


adjustable lower limit upper limit Yes ; via high-performance capacitor or battery 1 256

Counting range
lower limit upper limit 0 32767

S7 times
Number 256

of which retentive with battery


adjustable upper limit Yes ; via high-performance capacitor or battery 64

Time range
lower limit upper limit 1 ms 54 min ; 4 timers: 1 ms to 30 s; 16 timers: 10 ms to 5 min; 236 timers: 100 ms to 54 min

Data areas and their retentivity Flag


Number, max. 32 byte

6ES7214-2AD23-0XB0 Page 2/ 7

07/12/2013

subject to modifications Copyright Siemens AG 2013

Retentivity available of which retentive with battery of which retentive without battery

Yes ; M 0.0 to M 31.7 0 to 255, via high-performance capacitor or battery, adjustable 0 to 112 in EEPROM, adjustable

Hardware configuration
Expansion devices, max. 7 ; Only expansion modules of the S7-22x series can be used. Due to the limited output current, the use of expansion modules may be limited. SIMATIC PG/PC, standard PC

Connectable programming devices/PCs

Expansion modules
Analog inputs/outputs, max. 38 ; 2 onboard inputs and 1 output, also max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 outputs (EM) 168 ; max. 94 inputs and 74 outputs (CPU + EM) 62 ; AS-Interface A/B slaves (CP 243-2)

Digital inputs/outputs, max. AS-Interface inputs/outputs max.

Digital inputs
Number/binary inputs m/p-reading 14 Yes ; optionally, per group

Input voltage
Rated value, DC for signal "0" for signal "1" 24 V 0 to 5 V; 0 to 1 V (I 0.3 to I 0.5) min. 15 V; min. 4 V (I 0.3 to I 0.5)

Input current
for signal "1", typ. 2.5 mA ; 8 mA for I0.3 to I0.5

Input delay (for rated value of input voltage) for standard inputs
Parameterizable at "0" to "1", min. at "0" to "1", max. Yes ; all 0.2 ms 12.8 ms

for interrupt inputs


Parameterizable Yes ; I 0.0 to I 0.3

for counter/technological functions


Parameterizable Yes ; (E0.0 to E1.5) up to 200 kHz

Cable length
Cable length, shielded, max. Cable length unshielded, max. 500 m ; Standard input: 500 m, high-speed counters: 50 m 300 m ; not for high-speed signals

Digital outputs
Number/binary outputs Functionality/short-circuit strength Limitation of inductive shutdown voltage to 10 ; Transistor No ; to be provided externally 1W

Switching capacity of the outputs

6ES7214-2AD23-0XB0 Page 3/ 7

07/12/2013

subject to modifications Copyright Siemens AG 2013

with resistive load, max. on lamp load, max.

0.75 A 5W

Output voltage
for signal "1", min. L+ (-0.4 V (5 V / 20.4 V for A 0.0 to A 0.4; 20.4 V A 0.5 to A1.1))

Output current
for signal "1" rated value for signal "0" residual current, max. 750 mA 10 A

Output delay with resistive load


"0" to "1", max. 15 s ; of the standard outputs, max. (Q0.2 to Q1.1) 15 s; of the pulse outputs, max. (Q0.0 to Q0.1) 0.5 s 130 s ; of the standard outputs, max. (Q0.2 to Q1.1) 130 s; of the pulse outputs, max. (Q0.0 to Q0.1) 1.5 s

"1" to "0", max.

Parallel switching of 2 outputs


for increased power Yes

Switching frequency
of the pulse outputs, with resistive load, max. 100 kHz ; Q0.0 to Q0.1

Aggregate current of outputs (per group) all mounting positions


up to 40 C, max. 3.75 A

horizontal installation
up to 55 C, max. 3.75 A

Relay outputs
Max. number of relay outputs, integrated 0

Cable length
Cable length, shielded, max. Cable length unshielded, max. 500 m 150 m

Analog inputs
Number of analog potentiometers 2 ; Analog potentiometer; resolution 8 bit

Encoder Connectable encoders


2-wire sensor Permissible quiescent current (2-wire sensor), max. Yes 1 mA

1st interface
Type of interface Physics Integrated RS 485 interface RS 485

Functionality
MPI Yes ; As MPI slave for data exchange with MPI masters (S7-300/S7400 CPUs, OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communication is possible in the MPI network with restrictions; transmission rates: 19.2/187.5 kbit/s

6ES7214-2AD23-0XB0 Page 4/ 7

07/12/2013

subject to modifications Copyright Siemens AG 2013

PPI

Yes ; with PPI protocol for program functions, HMI functions (TD 200, OP), S7-200-internal CPU/CPU communication ; transmission rates 9.6/19.2/187.5 kbit/s Yes ; As freely programmable interface with interrupt facility for serial data exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbit/s; the PC/PPI cable can also be used as RS232/RS485 converter

Serial data exchange

MPI
Transmission rate, max. Transmission rate, min. 187.5 kbit/s 19.2 kbit/s

2nd interface
Type of interface Physics Integrated RS 485 interface RS 485

Functionality
MPI Yes ; As MPI slave for data exchange with MPI masters (S7-300/S7400 CPUs, OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communication is possible in the MPI network with restrictions; transmission rates: 19.2/187.5 kbit/s Yes ; with PPI protocol for program functions, HMI functions (TD 200, OP), S7-200-internal CPU/CPU communication ; transmission rates 9.6/19.2/187.5 kbit/s Yes ; As freely programmable interface with interrupt facility for serial data exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbit/s; the PC/PPI cable can also be used as RS232/RS485 converter

PPI

serial data exchange

MPI
Transmission rate, max. Transmission rates, min. 187.5 kbit/s 19.2 kbit/s

Integrated Functions
Number of counters 6 ; High-speed counters (2 to 200 kHz and 4 to 30 kHz), 32 bits (incl. sign), can be used as up/down counters or for connecting incremental encoders with 2 pulse trains offset by 90 (max. 1 to 100 kHz and 3 to 20 kHz (A/B counters)); parameterizable enable and reset input; interrupt facilities (incl. call of subroutine with any content) when the setpoint is reached; reversal in counting direction, etc. 200 kHz 4 ; 4 rising edges and/or 4 falling edges 2 ; High-speed outputs, 20 kHz, with interrupt option; pulse-width and frequency modulation option 20 kHz

Counter frequency (counter) max. Number of alarm inputs Number of pulse outputs

Limit frequency (pulse)

Galvanic isolation Galvanic isolation digital inputs


between the channels between the channels, in groups of Yes 6 and 8

Galvanic isolation digital outputs

6ES7214-2AD23-0XB0 Page 5/ 7

07/12/2013

subject to modifications Copyright Siemens AG 2013

between the channels between the channels, in groups of

Yes ; Optocoupler 5

Permissible potential difference


between different circuits 500 V DC between 24 V DC and 5 V DC

Degree and class of protection


IP20 Yes

Ambient conditions
Environmental conditions For further environmental conditions, see "Automation System S7200, System Manual"

Operating temperature
horizontal installation, min. horizontal installation, max. vertical installation, min. vertical installation, max. 0 C 55 C 0 C 45 C

Air pressure
permissible range, min. permissible range, max. 860 hPa 1080 hPa

Relative humidity
Operation, min. Operation, max. 5% 95 % ; RH class 2 in accordance with IEC 1131-2

Configuration programming
Command set Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, transmissions instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions, integer maths, floating-point math instructions, numerical functions free cycle (OB 1), interrupt-controller, time-controlled (1 to 255 ms) 1 OB, 1 DB, 1 SDB subroutines with/without parameter transfer 64

Program processing Program organization Number of subroutines, max.

Programming language
LAD FBD STL Yes Yes Yes

Know-how protection
User program protection/password protection Yes ; 3-stage password protection

Connection method
Plug-in I/O terminals Yes

Dimensions

6ES7214-2AD23-0XB0 Page 6/ 7

07/12/2013

subject to modifications Copyright Siemens AG 2013

Width Height Depth

140 mm 80 mm 62 mm

Weight
Weight, approx. Status 390 g Jul 10, 2013

6ES7214-2AD23-0XB0 Page 7/ 7

07/12/2013

subject to modifications Copyright Siemens AG 2013

You might also like