Merlin Gerin Multi 9 CT Modular Contactors Technical PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

CT modular contactors Multi 9 Merlin Gerin

Modular contactors are not only used in the residential sector but in the tertiary sector or in industrial utilities for the control of single or three-phase loads up to 100 A. They act as an interface between the order giver (e.g. power utility signal, load-shedding device, pushbutton, thermostat, programmable time switch, centralised technical management,) and the power circuit for final circuits: lighting, utility motors: ventilation, heat pumps, watering system,, hot water, heating, ovens, climatic chambers

Operation
The range includes two types of contactors: s Contactors with no manual operating mechanism: - with closing poles, pole closing is controlled by the presence of voltage on the coil and pole opening by the disappearance of this voltage, - with opening poles, the poles are closed with the coil de-energized and open when the coil is fed with power. Mainly used for load-shedding, - with mixed poles (closing and opening). s Contactors with manual operating mechanism: they additionally allow closing or opening of the poles using the selector switch on the front panel during maintenance operations, or are used to override an automatic system. The selector switch has 3 positions: OFF/automatic operation/ manual or permanent operation.

CT: 15962

Adv Adv antag antag es


A complete range of modular contactors: s 16 to 100 A ratings in single, two, three or four-pole. s Closing, opening or mixed poles with or without manual operating mechanism. s Comply with the standards in force in residential and tertiary applications: IEC61095. s Silent (< 20 dB). s With an adaptable indication auxiliary for 25 to 100 A contactors. s With control auxiliaries compatible with the reverser relay range and remote control of the C60 circuit-breaker. s Anti-interference filter. s With accessories: screw cover, clip-on markers, spacers. s Homogenous with the entire Multi 9 offer: - matching design, - same profile, - identical connections.

The rang e
time delay ACTt anti-interference ACTp

(AUS01PL20-A) Auxiliaries product sheet

ACTo+f

CT 16 A

CT 25 A

CT 63 A

CT 40-63-100 A

impulse/latched control ACTc

BatiBUS interface ATB1s

Get more with the worlds Power & Control specialist

IMPLEMENTA IMPLEMENTATION s Designed to be installed in modular switch boxes and switchboards. s Optimised dimensions: in accordance with the rating and number of poles. s Easy symmetrical rail mounting using a twostate latch. s Easy connection using grooved tunnel terminals with flap. s Mixed +/- socket screws which cannot be lost. s Auxiliaries simply clipped on to contactors. SPECIFICATIONS SPECIFICATIONS Electrical specifications s Power circuit: rating at 40C: 16 to 100 A (AC7a category). s Control circuit: s operating voltage: 24 V AC 10% 230/240 V AC: -15% +6%, s coil frequency: 50 Hz. s Electrical endurance: s AC1 and AC7a categories: - 16 A ratings, 100,000 operations - 25 A ratings, 250,000 operations - 40-63-100 A ratings, 200,000 operations. Mechanical specifications s Visualisation of contactor state on front panel (coil fed or manual operation). s Mechanical endurance: 1,000,000 operations. s Connections: s control circuit: - rigid cable: 2 x 1.5 mm2 - supple cable: 2 x 2.5 mm2 , s power circuit: - rigid cable: 6 mm 2 up to 25 A 25 mm 2 for 40 and 63 A 50 mm 2 for 100 A supple cable: 2 x 2.5 mm2 up to 25 A 2 x 10 mm2 for 40 and 63 A 2 x 35 mm2 for 100 A.820. ENVIRONMENT ENVIRONMENT s Tropicalisation: treatment 2 (relative humidity: 95% at 55C ). s Protection class: IP 201 (front panel: IP 4). s Operating temperature: - 5C to +60C. s Storage temperature: - 40C to +70C. s Complies with the strictest regulations and directives in the area of environmental protection.

SCHEMATIC SCHEMATIC DIAGRAMS DIAGRAMS


A1 1 A1 R1 1 A1 1 3 A1 R1 R3

A2

A2

R2

A2

A2

R2

R4

1-pole (1N/O)
A1 1 3 5

2-pole (1N/O+1N/C)
A1 1 3

2-pole (2N/O)
5 7 A1 R1

2-pole (2N/C)
R3 R5 R7

A2

A2

A2

R2

R4

R6

R8

3-pole (3N/O)
A1 R1 1 3 R3

4-pole (4N/O)
A1 I auto O 1

4-pole (4N/C)
3

A2

R2

R4

A2

4-pole (2N/O+2N/C)

2-pole (2N/O) manual op. mech.


A1 1 3 5 7

A1 I auto O

5 I auto O
P

A2 A2 2 4 6

3-pole (3N/O) manual op. mech.

4-pole (4N/O) manual op. mech.

SELECTION TABLE
number power circuit of poles rating (A) 1P 2P 25 16 25 width type of control voltage in mod. contacts (V AC) (9 mm) 250 250 250 2 2 2 2 2 2 4 4 4 6 4 6 6 4 4 4 4 4 6 6 6 6 6 6 6 12 1N/O 1N/O+N/C 2N/O 2N/O 2N/O 2N/C 2N/O 2N/O 2N/O 2N/O 3N/O 3N/O 3N/O 4N/O 4N/O 4N/C 4N/C 2N/O+N/C 4N/O 4N/C 4N/O 4N/O 4N/C 4N/C 2N/O+2N/C 4N/O references circuit voltage (V AC) 230/240 230/240 230/240 230/240 24 230/240 230/240 230/240 24 230/240 230/240 230/240 230/240 230/240 24 230/240 24 230/240 230/240 230/240 230/240 24 230/240 24 230/240 230/240 man. op. with mech. without 15958 15956 15957 15959 16020 15960 15966 15971 16024 15977 15961 15967 15972 15962 16022 15963 16023 15964 15968 15969 15973 16025 15974 16026 15975 15978

15981

40 63 100 25 40 63 25

250 250 250 400 400 400 400

15984 15987

3P

15982

4P

15983

40 63

400 400

15986 15988

100

400

SCHNEIDER ELECTRIC HELP CENTRE Tel: 1300 369 233 Fax: 1300 369 288 Email: [email protected] www.schneider-electric.com.au