Merlin Gerin Multi 9 CT Modular Contactors Technical PDF
Merlin Gerin Multi 9 CT Modular Contactors Technical PDF
Merlin Gerin Multi 9 CT Modular Contactors Technical PDF
Modular contactors are not only used in the residential sector but in the tertiary sector or in industrial utilities for the control of single or three-phase loads up to 100 A. They act as an interface between the order giver (e.g. power utility signal, load-shedding device, pushbutton, thermostat, programmable time switch, centralised technical management,) and the power circuit for final circuits: lighting, utility motors: ventilation, heat pumps, watering system,, hot water, heating, ovens, climatic chambers
Operation
The range includes two types of contactors: s Contactors with no manual operating mechanism: - with closing poles, pole closing is controlled by the presence of voltage on the coil and pole opening by the disappearance of this voltage, - with opening poles, the poles are closed with the coil de-energized and open when the coil is fed with power. Mainly used for load-shedding, - with mixed poles (closing and opening). s Contactors with manual operating mechanism: they additionally allow closing or opening of the poles using the selector switch on the front panel during maintenance operations, or are used to override an automatic system. The selector switch has 3 positions: OFF/automatic operation/ manual or permanent operation.
CT: 15962
The rang e
time delay ACTt anti-interference ACTp
ACTo+f
CT 16 A
CT 25 A
CT 63 A
CT 40-63-100 A
IMPLEMENTA IMPLEMENTATION s Designed to be installed in modular switch boxes and switchboards. s Optimised dimensions: in accordance with the rating and number of poles. s Easy symmetrical rail mounting using a twostate latch. s Easy connection using grooved tunnel terminals with flap. s Mixed +/- socket screws which cannot be lost. s Auxiliaries simply clipped on to contactors. SPECIFICATIONS SPECIFICATIONS Electrical specifications s Power circuit: rating at 40C: 16 to 100 A (AC7a category). s Control circuit: s operating voltage: 24 V AC 10% 230/240 V AC: -15% +6%, s coil frequency: 50 Hz. s Electrical endurance: s AC1 and AC7a categories: - 16 A ratings, 100,000 operations - 25 A ratings, 250,000 operations - 40-63-100 A ratings, 200,000 operations. Mechanical specifications s Visualisation of contactor state on front panel (coil fed or manual operation). s Mechanical endurance: 1,000,000 operations. s Connections: s control circuit: - rigid cable: 2 x 1.5 mm2 - supple cable: 2 x 2.5 mm2 , s power circuit: - rigid cable: 6 mm 2 up to 25 A 25 mm 2 for 40 and 63 A 50 mm 2 for 100 A supple cable: 2 x 2.5 mm2 up to 25 A 2 x 10 mm2 for 40 and 63 A 2 x 35 mm2 for 100 A.820. ENVIRONMENT ENVIRONMENT s Tropicalisation: treatment 2 (relative humidity: 95% at 55C ). s Protection class: IP 201 (front panel: IP 4). s Operating temperature: - 5C to +60C. s Storage temperature: - 40C to +70C. s Complies with the strictest regulations and directives in the area of environmental protection.
A2
A2
R2
A2
A2
R2
R4
1-pole (1N/O)
A1 1 3 5
2-pole (1N/O+1N/C)
A1 1 3
2-pole (2N/O)
5 7 A1 R1
2-pole (2N/C)
R3 R5 R7
A2
A2
A2
R2
R4
R6
R8
3-pole (3N/O)
A1 R1 1 3 R3
4-pole (4N/O)
A1 I auto O 1
4-pole (4N/C)
3
A2
R2
R4
A2
4-pole (2N/O+2N/C)
A1 I auto O
5 I auto O
P
A2 A2 2 4 6
SELECTION TABLE
number power circuit of poles rating (A) 1P 2P 25 16 25 width type of control voltage in mod. contacts (V AC) (9 mm) 250 250 250 2 2 2 2 2 2 4 4 4 6 4 6 6 4 4 4 4 4 6 6 6 6 6 6 6 12 1N/O 1N/O+N/C 2N/O 2N/O 2N/O 2N/C 2N/O 2N/O 2N/O 2N/O 3N/O 3N/O 3N/O 4N/O 4N/O 4N/C 4N/C 2N/O+N/C 4N/O 4N/C 4N/O 4N/O 4N/C 4N/C 2N/O+2N/C 4N/O references circuit voltage (V AC) 230/240 230/240 230/240 230/240 24 230/240 230/240 230/240 24 230/240 230/240 230/240 230/240 230/240 24 230/240 24 230/240 230/240 230/240 230/240 24 230/240 24 230/240 230/240 man. op. with mech. without 15958 15956 15957 15959 16020 15960 15966 15971 16024 15977 15961 15967 15972 15962 16022 15963 16023 15964 15968 15969 15973 16025 15974 16026 15975 15978
15981
40 63 100 25 40 63 25
15984 15987
3P
15982
4P
15983
40 63
400 400
15986 15988
100
400
SCHNEIDER ELECTRIC HELP CENTRE Tel: 1300 369 233 Fax: 1300 369 288 Email: [email protected] www.schneider-electric.com.au
AUS01PL19-A