Double Reg Valves PDF
Double Reg Valves PDF
Double Reg Valves PDF
Distribution of flow :
The main reason for these problems is that incorrect flows are available in the various circuits. If this is the case, the problem may be solved by installing a double regulating and commissioning valves or flow regulators in the corresponding pipes. The course of pressure in a circuit makes clear why this occurs. 27
Energy Saving :
Wrong flow rates in the various circuits lead to an increased energy consumption. On the one hand, a higher pump capacity must be provided to guarantee a sufficient supply of each appliance and on the other hand appliances being installed at a favourable hydronic position are then over supplied. This will result in an increased room temperature or, in chilled water air conditioning systems, in too low a room temperature. If the average temperature in a building exceeds the nominal value by 1 degree C, the energy consumption is increased by 6 10 % . In chilled water air conditioning systems , temperatures being 1 degree C too low will result in an increase in energy consumption of about 15%.
28
ECON Bronze Double Regulating Valve, Variable Orifice; PN 25, Fig: 2601V
Specification:
Bronze Double Regulating and Commissioning Valve, Y pattern, Threaded ends to BS 21(BSPP), PN 25 rated, Variable Orifice with linear scale and circular scale (fine adjustment). Maintenance free valve. Low flow resistance due to unique design. Complies to BS 7350 accuracy requirements. Tight closure of valve is assured by use of PTFE disc insert. Hand wheel embraces a vernier scale for accurate setting. Valves have unique design which enables the disc to be locked in the set position. Valve can be sealed in the set position with the sealing wire and lead seal. Two points (inlet/outlet) are available on the body of the DRV (Fig: 2601V). These points are for fixing the measuring nipples or test plugs for the measurement of flow / delta P (balancing).
Fig: 2601V
Material Specification:
No. 1 2 3 4 5 6 7 Component Body Stem Disc Bonnet Seat Ring O-Ring Cap / Knob Material Bronze DZR Brass DZR Brass DZR Brass PTFE EPDM ABS DIN G-CuSn5ZnPb BS 1400LG2 2874 CZ132 2874 CZ132 2874 CZ132 -
Flowrate :
Dimensions (millimeters) mm L 90 102 110 121 142 161 mm H 90 90 90 116 116 116 m3/hr. Kv (Open) 2.6 4.3 6.6 14.5 22.5 33.1
**
DRV with Test Nipple or Test Plug
29
NEW
Section 4 : Double Regulating Valves
ECON Cast Iron Double Regulating Valve, Variable Orifice; PN 16, Fig: 2920W
Specification:
Double Regulating and Commissioning Valves. Conforms to BS 5152 (EN13789). Y pattern,Flanged to BS 4504 / DIN PN 16 (EN1092). Variable Orifice with linear scale and circular scale (fine adjustment). Maintenance free valve Low flow resistance due to unique design. Complies to BS 7350 requirements Tight closure of valve is assured by use of soft seating. Hand wheel embraces a vernier scale for accurate setting. Valves have unique design which enables the disc to be locked in the set position with a screwdriver. Valve is supplied with a screw driver secured to the hand wheel. Two points (inlet/outlet) are available on the body of the valve for fixing the measuring nipples / test plugs for measurement of flow / delta P(balancing).
Fig: 2920W
Material Specification:
No. 1 2 3 4 Component Body Disc Disc Nut Stem O-Ring Bonnet Gasket Hand Wheel Gland Nut Position indicator Adjusting Bolt Bolt Material Cast Iron C I + EDPM Coated Brass Stainless Steel EPDM Cast Iorn Graphite GGG40 + Epoxy Coating Carbon Steel ASTM B 16 Plastic ASTM B 16 Carbon DIN 1691GG25 1691GG25 CuZn39Pb2 X10GR13 CuSn 5ZnPb 1691GGLS BS 1452GR260 1452GR260 2874-CZ121 410S21 1400LG2 1452GR260 -
5 6 7 8 9 10 11 12 13
Note:
2920W is supplied with a screw driver tied to the handwheel.
ECON Cast Iron Double Regulating Valve, Variable Orifice; PN 16, Fig: 2920W
Specification:
Double Regulating and Commissioning Valves. Conforms to BS 5152 (EN13789). Y pattern,Flanged to BS 4504 / DIN PN 16 (EN1092). Variable Orifice with linear scale and circular scale (fine adjustment). Maintenance free valve Low flow resistance due to unique design. Complies to BS 7350 requirements Tight closure of valve is assured by use of soft seating. Hand wheel embraces a vernier scale for accurate setting. Valves have unique design which enables the disc to be locked in the set position with a screwdriver. Valve is supplied with a screw driver secured to the hand wheel. Two points (inlet/outlet) are available on the body of the valve for fixing the measuring nipples / test plugs for measurement of flow / delta P(balancing).
Fig: 2920W
Material Specification:
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 Component Body Disc Disc Nut Stem O-Ring Bonnet Gasket Hand Wheel Gland Nut Position indicator Adjusting Bolt Bolt Material Cast Iron SS + EDPM Ring Brass Stainless Steel EPDM Cast Iorn Graphite GGG40 + Epoxy Coating Carbon Steel ASTM B 16 Plastic ASTM B 16 Carbon CuZn39Pb2 X10GR13 CuSn 5ZnPb 1691GGLS 2874-CZ121 410S21 1400LG2 1452GR260 DIN 1691GG25 BS 1452GR260
Note:
2920W is supplied with a screw driver tied to the handwheel.
PFM 2000
Portable meter for measuring flow and pressure difference across Double Regulating valves.
Description: The PFM 2000 is a precision instrument for measuring pressure and flow (PFM = Pressure Flow Meter). It is designed for use in monitoring and documenting water flow in heating and cooling installations, (the PFM 2000 measures across the balancing valves in such installations). The instrument is built around a sensor with two interacting ceramic membranes which detect pressure differences across the balancing valve. This is a new system and operates by balancing, at a basic physical level, the plus and minus sides of the measuring membranes. The pressure differential range is factory calibrated to cover pressures from 0 to 1.5 bar (150 kPa). The storage case containing the PFM 2000 and all accessories is as below.
The PFM 2000 (new) package comprises: Part: Quantity: Digital Meter (electronic) 1 Sensor unit 1 Cable between meter and sensor unit 1 Hoses and connectors 2 Battery charger 1 Storage case with carrying strap 1 Operating Manual 1 Calibration protocol (Certificate) 1 Connecting probes 2 Allen key - 3mm 1 Allen key - 5mm 1
32
33
34
35
NEW
Section 4 : Double Regulating Valves
0 0
1 9.0
2 14.5
3 22.7
4 33.1
5 44.7
6 59.9
7 67.3
8 74.5
0 0
1 16.7
2 25.6
3 38.2
4 55.6
5 74.0
6 89.0
7 106.6
8 118.4
NEW
Section 4 : Double Regulating Valves
0 0
1 25.0
2 48.7
3 71.4
4 104.0
5 138.6
6 163.2
7 187.1
8 203.0
115.5 141.2 159.9 178.5 195.0 213.6 237.5 257.8 281.0 296.2
112.5 137.5 169.8 197.7 233.5 270.3 303.1 338.7 377.5 399.2 415.9
205.3 254.9 312.5 375.7 420.5 476.7 537.1 592.9 655.4 711.5 759.3
131.5 177.4 224.1 275.4 349.3 425.7 505.9 590.5 671.4 755.2 836.6 901.0 966.9 1030.6 1058.8
Presetting :
1. The preset valve of the valve is adjusted with the handwheel. a. The display of the basic setting is shown in the lower windows by the sliding indicator. Each turn of the handwheel is represented by a number inside the window. b. The display of the fine setting is shown in the handwheel windows scale and each number indicates 1/10th of a turn of the handwheel. 2. Carefully remove the cover plug in the centre of the handwheel by using a small screwdriver in the slot and gently prising it off. 3. With the valve at the required preset value,using a 3 mm allen key, turn the inner screw clockwise until it seats. The inner screw is located in the hole through the nut. The 3 mm allen key is supplied along with every valve. 4. Refit the cover plug.
For presetting and fine adjustment of the flow volume (balancing), Econosto offers the PFM 2000 - Pressure and Flow Measuring Instrument.
The Econosto PFM-2000 - Pressure and Flow Measuring Instrument is an advanced programmable microprocessor with memory store (please refer page 32 of this catalogue for more details).
40
Maintenance
Every part of the valve is designed in such a way that the whole valve is maintenance free.The materials are carefully matched with the parts to make the friction as small as possible. However, due to safety reasons, every valve should be inspected regularly. Before valve removal from the plant or before service the suitable part of the pipeline should be closed.
Installation
Take off the plastic covers from the flanges. Blow inside valve by compressed air. The pipeline should be placed in such a way that valve body does not carry bending moments nor tension forces. The linear scale and the plastic set should be protected against painting. The valves could be installed in every position in inlet and outlet pipelines with the hand wheel in down direction. Attention should be paid to flow direction indicated by the arrow on the valve body. Before starting pipelinework (especially after repairs) whole pipeline should be rinsed out by fully opeing the valves in order to remove all solid residues which could be dangerous for sealing surfaces. Turning the hand wheel clockwise (according to direction indicated on the hand wheel) can close the valve. The valve is opened by anti-clockwise roation of the hand wheel. It is prohibited to use additional lever for turning the hand wheel. For pressure and fine adjustment of the flow volume (balancing), Econosto offers the PFM- 2000 / 2050 pressure and flow measurement instrument. The econosto PFM 2000 / 2050 pressure and flow measuring instrument advance programmable microprocessor.