Roofpak Units With Energy Recovery Wheels: Packaged Heating and Cooling Units
Roofpak Units With Energy Recovery Wheels: Packaged Heating and Cooling Units
Roofpak Units With Energy Recovery Wheels: Packaged Heating and Cooling Units
220
MEA
368-93-N
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
McQuay Energy Recovery Systems . . . . . . . . . . . . . . . . . . . . 3 Factory-Installed and Tested Package . . . . . . . . . . . . . . . . . . 3
Fan Performance DataSupply Fans . . . . . . . . . . . . 35 Fan Performance DataAirfoil Return Fans . . . . . 40 Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Section Options and Locations . . . . . . . . . . . . . . . . . . . . . . . 41 Electrical Knockout Locations . . . . . . . . . . . . . . . . . . . . . . . . 46 Drain and Air Connection Locations . . . . . . . . . . . . . . . . . . . 47 Piping Entrance Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Application Considerations . . . . . . . . . . . . . . . . . . . . . . 10
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unit Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Split Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Curb Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Acoustical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Variable Air Volume Application . . . . . . . . . . . . . . . . . . . . . . Fan Operating Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fan Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Altitude Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 10 10 10 11 12 12 13 13 13 13
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Supply Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Unit Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Selection Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
McQuay and MicroTech are registered trademarks of McQuay International. DesignFlow, Hi-F, Protocol Selectability, RoofPak, SelectTools, SpeedTrol, SuperMod, UltraSeal, and VaneTrol are trademarks of McQuay International. Microsoft is a registered trademark of Microsoft Corporation. Windows is a trademark of Microsoft Corporation. Copyright 2006 McQuay International. All rights reserved throughout the world.
Introduction
Introduction
McQuay Energy Recovery Systems
Our energy recovery device transfers both heat and moisture energy between the exhaust and ventilation air. In doing so, it conditions the incoming ventilation air. This total energy device offers a cost-effective and efficient method for containing energy costs while meeting the ventilation requirements of ASHRAE Standard 62.1-1999. ARI certified enthalpy wheel, exhaust fan with VFD, prefilters, and, for economizer applications, optional bypass dampers and controls (see Figure 1). This helps to eliminate field coordination and leakage problems associated with field installation. The outdoor and exhaust air flows are arranged in counterflow for better efficiency, and to reduce field cleaning requirements. Exhaust contaminants cannot enter the ventilation air because the exhaust air static pressure is always less than the ventilation air static pressure. Frost protection and purge options are also available.
Cassette Design
Heavy duty galvanized steel construction with removable side panels No-maintenance bearings standard on small cassettes Flanged outboard bearings used on larger cassettes Full contact brush seals minimize leakage AC drive motor with Power Twist link belt Optional variable speed drive motor available Adjustable purge section, provided as standard, reduces cross-contamination
Figure 2: Energy wheel construction
2" pre-filters are provided in both the outdoor and return air, to minimize the need for cleaning the wheel.
ARI and UL conformance
The McQuay energy recovery wheel is ARI certified for performance and UL recognized for safety. Integrated cooling, heating and recovery control Mechanical heating and cooling are supplied as necessary to supplement the wheel and maintain space conditions. Free cooling Units with economizers include bypass dampers that are opened when free cooling is available. The wheel is simultaneously turned off. Proper exhaust Exhaust fan speed is controlled for proper exhaust, using a factory installed Variable Frequency Drive (VFD) and space building pressure sensor.
A return/exhaust air fan is provided in a typical exhaust fan configuration. This allows the exhaust to be at a lower pressure than the OA intake and minimizes cross-contamination. However, this fan has characteristics of both a return air fan (RAF) and an exhaust air fan (EAF). EAF characteristic - It only exhausts air and must be sized to handle return duct APD at maximum exhaust cfm. RAF characteristic - It always operates whenever the SAF operates and the SAF does not need to be sized for the return duct APD. RAF characteristic - The fan will do an excellent job of preventing positive building pressure because it draws a large negative at the return of the unit. The EAF/RAF must be controlled by building pressure. This control is included with the MicroTech II controls option.
Exhaust Air
NOTE: Maintain the pressure gradient to prevent cross contamination from the Exhaust to Outside Supply Air
Handling Moisture
Low space humidity is a common problem in the winter and can cause both discomfort and health problems for tenants. It also leads to increased static electricity, which can be damaging to computer equipment. However, mechanical humidification requires 1,100 btu per pound of humidity. Our energy recovery system provides the added benefit of significantly raising the humidity level of outdoor air in the winter. Not only can this have a dramatic impact on the first cost and operating cost of an HVAC system, it can also dramatically improve indoor air quality and comfort for building occupants.
OUTSIDE AIR
EXHAUST AIR
Summer Performance
Enthalpy wheels provide twice as much summer energy recovery as sensible devices because summer ventilation air involves as much latent load as sensible load. In fact, our wheel normally cools outdoor air down to 67F wet bulb.
$5,359.00
$4,579.00
$8,048.00
$5,381.00
$4,625.00
$4,363.00
$5,041.00
Table 2: Typical payback (in years) for McQuay energy recovery wheel*
Minneapolis With Winter Humidification Without Winter Humidification 1.2 - 2.6 Phoenix 2.6 - 7.4 Miami 0.7 - 2.7 Dallas 1.8 - 5.2 N.Y.C. 2.0 - 6.1 Atlanta 2.6 - 7.1 Chicago 1.5 - 4.1
1.9 - 4.9
2.6 - 7.4
0.7 - 2.7
1.9 - 5.4
2.6 - 7.1
2.9 - 7.3
2.1 - 6.0
* Above charts based on gas fired unit, 4,000 hours, $0.10 per KWHR and $0.50 per Therm)
outside air and all return air is exhausted (see Figure 5).
2 Economizer unit (up to 30,000 total cfm and 16,000 cfm of
outdoor air): SAF supplies minimum or economizer outside (mixed) air and some return air is exhausted (see Figure 6).
Figure 5: Energy recovery make-up air arrangement (both side return and bottom return offered)
during economizer operation or excessive positive building pressure will occur. For VAV units, note that RA cfm during economizer operation normally is less that design return cfm. An energy analysis must be careful not to overwhelm the EAF with return duct ESP except during economizer cooling.
Set 2: OA wheel and OA bypass path to the SAF Set 3: EA wheel and bypass path to the EAF
APD. Therefor, the air balancer must adjust the RA dampers to not open fully so that sufficient OA is achieved.
2 The RA path includes return duct ESP. Normally, the SAF
100% Outdoor Air Units There are no parallel flow paths in a 100% OA unit. Instead, there is one counter-flow path (OA and EA paths throughout the wheel). The EAF must be sized for design return duct cfm and ESP.
handles both of these paths. Therefore, the EAF need not handle the return duct ESP. However: The RA path is not open during economizer operation, so the EAF must handle return duct ESP
Figure 7: Parallel Air Paths
Humidity Ration
Application Considerations
Application Considerations
The following section contains basic application and installation guidelines that must be considered as part of the detailed analysis of any specific project. Recommended Clearances on page 52 for recommended clearances. Consult your McQuay sales representative if available clearances do not meet minimum recommendations. Where code considerations, such as the NEC, require extended clearances, they take precedence. In applications utilizing a future cooling unit (RFS), take care in choosing a location of the unit so it will provide proper roof support and service and ventilation clearance necessary for the later addition of a mechanical cooling section (RCS).
General
Units are intended for use in normal heating, ventilating and air conditioning applications. Consult your local McQuay sales representative for applications involving operation at high ambient temperatures, high altitudes, non-cataloged voltages and for applications requiring modified or special control sequences. Consult your local McQuay sales representative for job specific unit selections that fall outside of the range of the catalog tables, such as 100% outside air applications. For proper operation, units should be rigged in accordance with instructions stated in the unit installation manual (IM). Fire dampers, if required, must be installed in the ductwork according to local or state codes. No space is allowed for these dampers in the unit. Follow factory check, test and start procedures explicitly to achieve satisfactory start-up and operation (see IM 738). Most rooftop applications take advantage of the significant energy savings provided with economizer operation. When an economizer system is used, mechanical refrigeration is typically not required below an ambient temperature of 50F. Standard RoofPak refrigeration systems are designed to operate in ambient temperatures down to 45F. For applications where an economizer system cannot be used, McQuays SpeedTrol head pressure control system is available on size 045C to 075C units to permit operation down to 0F. However, if the condenser coils are not properly shielded from the wind, the minimum ambient conditions stated above must be raised.
Split Units
Units may sometimes have to be split into multiple pieces to accommodate shipping limitations or jobsite lifting limitations. Units exceeding 52 feet in length may need to be split for shipping purposes. Units exceeding the rating of an available crane or helicopter may also need to be split for rigging purposes. Unit can be split at the condensing section or split between the supply fan and heat section. Contact your local McQuay sales representative for more details.
Curb Installation
The roof curb is field assembled and must be installed level (within 1/16 in. per foot side to side). A sub-base has to be constructed by the contractor in applications involving pitched roofs. Gaskets are furnished and must be installed between the unit and curb. For proper installation, follow NRCA guidelines. Typical curb installation is illustrated in Roof Curbs on page 49. In applications requiring post and rail installation, an I-beam securely mounted on multiple posts should support the unit on each side. Applications in geographic areas that are subjected to seismic or hurricane conditions must meet code requirements for fastening the unit to the curb and the curb to the building structure. For acoustical considerations, the condensing section is provided with a support rail versus a full perimeter roof curb. When curbs are installed on a built-up roof with metal decking, an inverted 6 in. channel should be provided on both sides of the unit. Acoustical material should be installed over the decking, inside the roof curb. Only the supply and return air ducts should penetrate the acoustical material and decking. Apply appropriate acoustical and vibration design practices during the early stages of design to provide noise compatibility with the intended use of the space. Consult your McQuay sales representative for unit sound power data.
Unit Location
The structural engineer must verify that the roof has adequate strength and ability to minimize deflection. Take extreme caution when using a wooden roof structure. Locate the unit fresh air intakes away from building flue stacks or exhaust ventilators to reduce possible reintroduction of contaminated air to the system. Unit condenser coils should be located to avoid contact with any heated exhaust air. Allow sufficient space around the unit for maintenance/service clearance as well as to allow for full outside air intake, removal of exhaust air and for full condenser airflow. Refer to
10
Application Considerations
Acoustical Considerations
Good acoustical design is a critical part of any installation and should start at the earliest stages in the design process. Each of the four common sound paths for rooftop equipment must be addressed. These are: Radiated sound through the bottom of the unit bottom (air handling section and condensing section) and into the space Structure-borne vibration from the unit to the building Airborne sound through the supply air duct Airborne sound through the return air duct Locating rooftop equipment away from sound sensitive areas is critical and the most cost effective means of avoiding sound problems. If possible, rooftop equipment should always be located over less sensitive areas such as corridors, toilet facilities or auxiliary spaces and away from office areas, conference rooms and classrooms. Some basic guidelines for good acoustical performance are: Always provide proper structural support under all areas of the unit. Always locate the units center of gravity close to a main support to minimize roof deflection. Maintaining a roof deflection under 1/3 in. minimizes vibration-induced noise. Use a concrete deck or pad when a unit has to be located over an occupied space where good acoustics are essential. Only the supply and return air ducts should penetrate the acoustical material and decking within the curb perimeter, and the openings must be sealed once the duct is installed. Dont overlook the return air path. Never leave a clear line of sight into a return or exhaust fan; always include some duct work (acoustically lined tee) at the return inlet.
Figure 9: Optimal fan selection line
Place an acoustical material in the area directly beneath the condensing section. Select acoustic material that does not encourage microbial growth. Minimize system static pressure losses to reduce fan sound generation. Select the appropriate fan for the application. Fans should be selected as close as possible to their peak static efficiency. To assist you, peak static efficiency is identified by the first system curve to the right of the shaded Do not select region, as illustrated in Figure 9. Design duct systems to minimize turbulence. Account for low frequency duct breakout in system design. Route the first 20 ft. of rectangular duct over non-sensitive areas and avoid large duct aspect ratios. Consider round or oval duct to reduce breakout. When an added measure of airborne fan sound control is required, sound attenuators can be supplied, factory installed in a unit discharge air section, to treat the supply fan. On the return side, additional attenuation can often be achieved by routing the return duct within the curb area beneath the unit. There are many sound sources in rooftop systems. Fans, compressors, condenser fans, duct take-offs, etc. all generate sound. For guidelines on reducing sound generation in the duct system, refer to the 2003 ASHRAE Applications Handbook, Chapter 47. Contact your local McQuay sales representative for equipment supply, return and radiated sound power data specific to your application.
Do not select.
Do not select.
11
Application Considerations
Ductwork
A well-designed duct system is required to allow the rooftop equipment to provide rated performance and to minimize system resistance and sound generation. Duct connections to and from units should allow straight, smooth airflow transitions. Avoid any abrupt change in duct size and sharp turns in the fan discharge. Avoid turns opposed to wheel rotation since they generate air turbulence and result in unwanted sound. If 90 turns are necessary, use turning vanes. Refer to the 2003 ASHRAE Applications Handbook, Chapter 47 for specific guidelines relevant to rooftop equipment. Return Duct The return path is the most often overlooked. A section of return duct is required to avoid a line of sight to the return air opening and to provide attenuation of return air sound. Install an insulated tee with a maximum duct velocity of 1000 to 1200 feet per minute. Extend the duct 15 feet to provide adequate attenuation. Supply Duct Insulate supply air ductwork for at least the first 20 feet from the unit. Consider the use of round or oval ductwork, as it significantly reduces low frequency breakout noise near the equipment. If rectangular duct is used, keep the aspect ratio of the duct as low as possible. The large flat surfaces associated with high aspect ratios increase low frequency breakout to the space and can generate noise, such as oil canning. The maximum recommended supply duct velocity is 1800 to 2000 feet per minute. Duct High Limit All McQuay RoofPak systems with VAV control include an adjustable duct high limit switch as a standard feature. This is of particular importance when fast acting, normally closed boxes are used. The switch is field adjustable and must be set to meet the specific rating of the system ductwork. Vibration Isolation Make duct attachments to the unit with a flexible connection. Smoke and Fire Protection McQuay optionally offers factory-installed outdoor air, return air, and exhaust air dampers as well as smoke detectors in the supply and return air opening, complete with wiring and control. These components often are used in the buildings smoke, fume, and fire protection systems. However, due to the wide variation in building design and ambient operating conditions into which our units are applied, we do not represent or warrant that our products are fit and sufficient for
smoke, fume, and fire control purposes. The owner and a fully qualified building designer are responsible for meeting all local and NFPA building code requirements with respect to smoke, fume, and fire control. McQuay offers the flexibility to offer these various components and control sequences, as directed by the customer, to help meet code requirements.
Filters
General Routinely replace filters to minimize filter loading. As filters get dirty, the filter pressure drop increases, causing a decrease in airflow. Depending on fan type, forward curved or airfoil, this airflow change can be significant. The effect of filter loading is the most critical when using 65% and 95% efficient filters. When making a fan selection, include a pressure drop component in the system total static pressure for filters since they get dirty. Generally, select a value midway between clean and dirty filter ratings. If a minimum airflow is critical, the fan selection should be made using the higher, dirty filter pressure drop value. Following these recommendations should limit airflow fluctuation as the filters load. Final Filters The application of final filters (filters downstream of the fan) places special requirements on unit selection. When final filters are employed, cooling coils must be located in the drawthrough position so that the filters will not be in a saturated air stream. Also, final filters applications for a unit with gas heat requires the filters to be rated for 500F. Instruct maintenance personnel to use properly rated replacement filters. Wheel Cleaning McQuay energy recovery wheels generally only require periodic and easy cleaning as long as outdoor and return air is relatively clean. The counter-flow arrangement causes the wheel to be selfcleaning as long as it rotates. McQuay provides pre-filters on both the outdoor and return air. Vacuums or soft brushes should be used to periodically clean the wheel so that dirt does not accumulate and promote microbial growth. Be careful not to force dirt into the interior of the wheel. If periodic cleaning is forgotten and dirt or mildew persists, then water and mild detergents can be used. However, care must be taken to control the water and keep it out of the floor and other exterior cabinet insulation.
12
Application Considerations
Fan Isolation
All McQuay RoofPak systems feature internally isolated fans. All supply and return air fans are statically and dynamically balanced in the factory and mounted on rubber-in-shear (RIS) or 2 in. deflection spring isolators. Flexible isolation is provided as standard between the fan outlet and the discharge bulkhead to prevent hard contact and vibration transmission. Spring isolated fan assemblies also are available with seismic restraints. The choice of 2 in. deflection spring isolation or RIS isolation depends on an analysis of the roof structure and whether or not an isolation curb is being provided. When using an isolation curb, consult with the curb manufacturer before selecting spring isolation in the rooftop unit. Doubling or stacking spring isolation can generate a resonant vibration.
Altitude Adjustments
Fan curve performance is based on 70F air temperature and sea level elevation. Selections at any other conditions require the following adjustment for air densities listed in Table 3. Higher elevations generally require more rpm to provide a given static pressure but less bhp due to the decrease in air density.
1 Assume 10,000 cfm is required at 3.5" TSP. The elevation
is 5000 ft. and 70F average air temperature is selected. A 20" DWDI airfoil fan is selected.
2 The density adjustment factor for 5000 ft. and 70F is 0.83. 3 TSP must be adjusted as follows; 3.5" / 0.83 = 4.22" 4 Locate 10,000 cfm and 4.22 on the fan curve. rpm = 2270
bhp
13
Application Considerations
The actual derate varies with each individual unit and design conditions. Your local McQuay representative can provide exact performance data. Wheel Performance Wheel performance must be adjusted for altitude as shown in Unit Selection on page 15. Furnace Performance Gas heat performance data is based on standard 70F air temperature and zero feet altitude (sea level). For altitudes of 2000 feet and higher, the gas burner must be derated 4% for ever 1000 feet of altitude. Example: A 1000 MBh furnace at an altitude of 5000 feet is derated (0.04 3 = 0.12). At 1000 MBh input (1000 0.12 MBh), the actual input is (1000 120 = 880 MBh) at 5000 feet. Above 6000 feet, consult factory
Condenser Performance Altitudes greater than sea level require a derate in condenser and cooling performance that can be estimated as follows: 0 to 6000 feet Cooling capacity decrease factor (all sizes) = 0.5% per 1000 feet Compressor kW increase factor = 0.6% per 1000 feet
Figure 11: RPS/RFS 015C to 030C 20 in. airfoil supply fan
14
Unit Selection
Unit Selection
Achieving the optimal performance of a rooftop system requires both accurate system design and proper equipment selection. Factors that control the unit selection include applicable codes, ventilation and air filtration requirements, heating and cooling loads, acceptable temperature differentials, and installation limitations. McQuay RoofPak units offer a wide selection of component options providing the capability to meet diverse application requirements. The McQuay SelectTools software selection program allows your local McQuay sales representative to provide you with fast, accurate and complete selection of McQuay RoofPak units. You also can select your unit through reference to physical, performance, dimensional, and unit weight data included in this catalog. Due to the variety of cooling coil options available, only a sample of cooling capacity data is presented in the catalog. To properly select unit equipment:
1 Select unit size and cooling coil 2 Select heating coils and equipment 3 Select fans and motors
Selecting Unit Size to Satisfy Summer Design Unit size is based on coil face area and cooling capacity requirements. Supply air capacity and maximum face velocity constraints should serve as a guide for selecting coil dimensions and cabinet size. Many model sizes are available with a standard and a high airflow coil selection. This flexibility prevents the need to increase cabinet size to accommodate high airflow per ton applications. Based on the given data, the appropriate coil face area may be determined as follows: Minimum face area = supply air volume/maximum face velocity = 20,000 cfm/550 fpm = 36.4 square feet Referring to Physical Data on page 18, the 39.5 square foot, small face area coil of the RPS 045C to 75C units satisfies the required face velocity.
Wheel Cooling Capacity Figure 12: Total and sensible effectiveness charts
Total Effectiveness
0.950
Below are examples that illustrate the equations and catalog references used in the unit selection process.
Selection Example
Wheel SCFM
Constant volume system with DX cooling and natural gas heat. System design: Supply air volume 20,000 cfm Return air volume 20,000 cfm Minimum outside air volume 7000 cfm Maximum face velocity 550 fpm Supply fan external SP 2.00 in. w.g. Return fan external SP 1.00 in. w.g. Altitude Sea level Economizer with return air fan Energy recovery wheel 30% throw-away filters 460V/60Hz/3Ph Fully modulating heat Summer design: (RAT) Return air temperature 75F/62F (OAT) Outdoor air temperature 95F/75F (WLAT) Wheel leaving air temperature 80F/65.5F DX coil capacity 700MBh Winter design: Return air temperature 72F dB Outdoor air temperature 33F dB Wheel leaving air temperature 61F dB Gas heat MBh output 380 MBh Maximum motor HP: Supply fan 20 hp Return/exhaust fan 15 hp
Sensible Effectiveness
1.000 0.900 0.800 0.700 0.600 0.500 0.400 0.300 0.200 0.100 0.000
50 00 60 00 70 00 80 00 90 00 10 ,0 00 11 ,0 0 12 0 ,0 00 13 ,0 00 14 ,0 00 30 00 40 00
Wheel SCFM
purge, and no frost conditions. The 7812 wheel should normally be used if wheel cfm > 8000 cfm.
15
Unit Selection
Refer to below. The 7806 wheel is normally used at 7000 cfm. Wheel sensible and total effectiveness = 80%. Therefore, WLAT, both dry bulb and wet bulb, can be calculated by equation 1. Equation 1: WLAT - RAT + 80% x (OAT - RAT) when adjusted for SCFM. Adjusting for SCFM is done with air density (see table) 95F air density = 96% x 75F air density as shown in Equation 2 below. Equation 2: WLAT - RAT = 80% x 96% x (OAT - RAT). Solving Equation 2 indicates WLAT = 79.6 / 65.0F. This is acceptable (80 / 65.5 is specified). Total energy recovery wheel cooling capacity is approximately 247 MBh based on enthalpy charts.
DX Cooling Coil Capacity
selected. Also, use this table when specifying baffle position based on minimum airflow design. Refer to Altitude Adjustments on page 13.
Note: In VAV applications, consider range of airflow
modulation when selecting furnace model and baffle position. Wheel Heating Capacity Refer to (Figure) for the 7806 wheel. Wheel sensible effectiveness = 80%. Therefore, WLAT dry bulb can be calculated by using Equation 3. Equation 3: WLAT - OAT = 80% x (RAT - OAT) when adjusted for SCFM. Adjusting for SCFM is done with air density (see table). 33F air density = 91.5% x 72F air density. Therefore, Equation 3 must be modified and Equation 4 is used instead. Equation 4: WLAT - OAT = 80% x 91.5% x (RAT - OAT). Solving Equation 4 indicates WLAT = 61.5F. This is acceptable (61F is specified). Energy recovery wheel heating capacity is calculated by Equation 5. Equation 5: SMBh = 1.085 x (cfm / 1000) x (WLAT - OAT) = 618 MBh. Furnace Capacity Furnace output capacity is specified to be 380 MBh and the 400 MBh furnace is the most likely selection. Minimum airflow (12,000 cfm with baffle C) is less than design cfm for this constant volume unit. Therefore, the 400 MBh furnace is the proper selection. Total unit heating capacity = 618 + 400 = 1018 MBh. Selecting Fans and Motors Fan and motor selections are based on total static pressure drop and design airflow. Total static pressure includes internal air pressure drops of unit components and external air pressure drops in supply and return ducts. Refer to Component Pressure Drops on page 32 for internal pressure drops of unit components. Fan curves provided in Fan Performance DataSupply Fans on page 35 and Fan Performance DataAirfoil Return Fans on page 40 should be used when selecting unit fans and motors. To optimize fan performance, select the fan size having design airflow and static pressure intersecting as close to the first system curve after the shaded Do Not Select region as possible. Refer to Application Considerations on page 10. When selecting motor size, select the motor just below the horsepower curve. An oversized motor (large horsepower to load ratio) can greatly increase electric consumption due to the reduction in motor performance.
DX coil entering air temperature (EAT) must first be calculated and is equal to mixed air temperature (MAT) on a draw-through cooling coil. MAT, both dry bulb and wet bulb, is found through using psychometric chart mixing calculations (Equation 3). Equation 3: MAT - RAT = (OA cfm / total cfm) x (WLAT RAT). Solving Equation 3 indicates DX coil EAT and MAT = 76.6 / 63.0F. DX coil capacity is specified to be 700 MBh and the RPS 60 is the most likely selection. RPS 60 DX capacity for a small face area coil is 707 MBh per the table (compressor KW = 63.7) and is acceptable (700 MBh is specified). Total unit cooling capacity = 247 + 707 = 956 MBh. R-407C versus R-22 The cooling tables (Tables 720 on pages 2026) document the R-22 cooling capacity and compressor kW. The R-407C performance correction factors vary slightly with unit size and operating conditions but can be estimated as shown in the table below. Use the McQuay SelectTools computer selection program to get the exact R-407C performance.
Table 4: R-407C versus R-22
Compressor capacity 1.001.01 Compressor kW 1.071.10
For all heat exchangers, there exist a maximum temperature rise. This limitation is determined by the heat exchanger surface area to airflow ratio. Refer to Table 24 on page 29 for verification of the temperature rise capability of the furnace
16
The return/exhaust fan ISP varies depending on whether or not the optional economizer and bypass damper will be utilized. RAF / EAF TSP = return duct ESP + internal pressure drop (ISP).
1 100% OA unit (no economizer or bypass) - ISP = wheel +
For a constant volume system a forward curve or airfoil type fan can be selected. Reference Application Considerations on page 10 for discussion on acoustical consideration. Considering its favorable brake horsepower, an airfoil type fan will be selected. Entering the standard 30 in. airfoil fan curve (see Figure 21 on page 38) at 20,000 cfm and 3.86 in. w.g., the required fan motor size is 20 hp operating at 1266 rpm. Fan brake horsepower is 17.7 horsepower. Supply Power Wiring for Units Without Electric Heat Sizing supply power wire for a unit is based on the circuit with the largest amperage draw. All electrical equipment is wired to a central panel for single or optional multipower connections. Refer to Electrical Data on page 54 for FLA and RLA ratings of equipment. Determination of Minimum Circuit Ampacity (MCA) is as follows:
Fans and Cooling:
path ISP values should be used. The bypass path will be larger unless design OA / EA > 70% of the total design cfm.
a Wheel path: ISP = wheel + wheel prefilter + hood
prefilter + hood pressure drop and is based on maximum exhaust cfm during economizer operation. Therefore, for our example: Fan cfm = design exhaust cfm RAF / EAF TSP = 1.00 ESP + 1.71 ISP RAF / EAF cfm = 20,000 cfm 14.2 bhp and a 15 hp motor are required
Supply Fan and Motor
MCA = 1.25 RLA or FLA of largest motor + 1.00 FLA of other loads Example Compressors 1 - 4 15 hp ea Condenser fan motors, (6) 1 hp Supply fan motor, 20 hp Return fan motor, 15 hp Therefore, MCA = (1.25 25) + 1.00 [(4)23.7 + (6)2 + 20.3] = 160 amps FLA/RLA 23.7 amps ea 2 amps ea 25 amps 20.3 amps
Supply fan TSP = supply duct ESP + ISP (see tables). The return duct static pressure drop is not added to the supply fan pressure drop. Therefore, the total static pressure for the supply fan in the example is as follows: Internal pressure drops: Hood, wheel prefilter, wheel and damper 30% angular filters Gas furnace Evaporative coil (small 5-row, 12 fpi) Total internal pressure drop External pressure drops: Supply duct Total external pressure drop 0.71 in. w.g. 0.14 in. w.g. 0.20 in. w.g. 0.81 in. w.g. 1.86 in. w.g.
Select power supply wire based on 160 amperes. Calculating Unit Length Referring to unit Dimensional Data on page 41 for a drawthrough RPS 060C: Total unit length = energy recovery + angular filter + DX coil section + fan section + heat section + discharge plenum + condensing unit = 192 in. + 24 in. + 24 in. + 72 in. + 48 in. + 48 in. + 83 in. = 491 inches.
Note: When selecting unit curb length, do not include the
cooling coil diffuser pressure drop. In VAV applications with gas heat, consult your McQuay sales representative for design pressure drop determinations.
17
Physical Data
Physical Data
Table 5: Physical data, RPS/RFS 015C to 040C and RDS 800 to 802
Unit size RDS 802 RPS/RFS RPS/RFS RPS/RFS RPS/RFS 025C 030C 036C 040C Nominal airflow (cfm) 10000 12000 14000 16000 Type Scroll Compressor Quantity hp 14.5, 110 16,7, 110 16.7, 115 26.7, 113 26.7, 115 26.7, 210 410 Std. capacity control 100-65-35-0 100-60-40-0 100-69-31-0 100-75-50-25-0 100-75-50-25-0 100-70-50-20-0 100-75-50-25-0 Rows/FPI 2/16 2/16 2/16 3/16 3/16 2/16 2/16 Condenser coil (aluminum fins) Face area (sq. ft.) 36.8 36.8 36.8 36.8 36.8 76.2 76.2 No. dia. (In.) 226 226 226 326 326 426 426 Condenser fans Std. airflow (cfm) 14552 14552 14552 16047 16047 29376 29376 Cond. fan motors No. Hp 21.0 21.0 21.0 31.0 31.0 41.0 41.0 Type Forward curved LP Forward Curved LP/MP No. dia. (in.) 2 156 2 156 2 156 2 156 2 156 1 24 1 24 Supply fans No. dia. (in.) 2 1515 2 1515 2 1515 2 1515 2 1515 Type DWDI airfoil No. dia. (in.) 1 20 1 20 1 20 1 20 1 20 1 24 1 24 Type SWSI airfoil RAF/EAF No. dia. (in.) 1 24 1 24 1 24 1 24 1 24 1 24 1 24 Rows 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 Evaporator coils FPI 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 F.A., small (sq. ft.) 18.5 18.5 18.5 27.0 27.0 27.0 27.0 Type rows 5WH1 5WH1 5WH1 5WH1 5WH1 5WH1 5WH1 Type rows 5WS2 5WS2 5WS2 5WS2 5WS2 5WS2 5WS2 Hot water coils FPI 9 9 9 9 9 9 9 Face area (sq. ft.) 20.3 20.3 20.3 20.3 20.3 20.3 20.3 Type rows 5JA1 5JA1 5JA1 5JA1 5JA1 5JA1 5JA1 Steam coils FPI 6, 12 6, 12 6, 12 6, 12 6, 12 6, 12 6, 12 Face area (sq. ft.) 20.3 20.3 20.3 20.3 20.3 20.3 20.3 Input (MBh) 250, 312, 400, 500, 625, 800, 812, 988, 1000, 1250 Gas furnace Nom. output (MBh) 200, 250, 320, 400, 500, 640, 650, 790, 800, 1000 Electric heat Nom. output (kW) 20, 40, 60, 80, 100, 120, 140, 160, 180, 200, 220, 240 Type 30% pleated Panel filters Area (sq. ft.) 50.0 50.0 50.0 50.0 50.0 50.0 50.0 Type Prefilter, standard flow Pre-filters (for cartridge filters) Area (sq. ft.) 24.0 24.0 24.0 24.0 24.0 24.0 24.0 Type 65% or 95%, standard flow Cartridge filters Area (sq. ft.) 24.0 24.0 24.0 24.0 24.0 24.0 24.0 Type 30% pleated EA or OA prefilters Area (sq. ft.) 60.0 60.0 60.0 60.0 60.0 60.0 60.0 Quantity 1 (2 available without economizer bypass) Diameter (in.) 60.0 60.0 60.0 60.0 60.0 60.0 60.0 Wheel 4.0 Depth (in.) 4.0 4.0 4.0 4.0 4.0 4.0 Drive motor (hp) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 Data RPS/RFS 015C 6000 RPS/RFS 018C 7000 RDS 800 RPS/RFS 020C 8000
18
Physical Data
RAF/EAF fans
Evaporator coils
Cartridge filters
EA or OA pre-filters Wheel
2/16 2/16 78.0 78.0 41.0 61.0 Forward curve, LP/MP 1 27 127 127 127 DWDI airfoil, with or without variable inlet vanes 127,30 127,30 130, 33 130, 33 SWSI airfoil, with or without variable inlet vanes 140 140 140 140 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 39.5 39.5 39.5 39.5 47.1 47.1 47.1 5WH1 5WH1 5WH1 5WH1 5WS2 5WS2 5WS2 5WS2 9 9 9 9 29.7 29.7 29.7 29.7 5JA1, 2 5JA1, 2 5JA1, 2 5JA1, 2 6, 12 6, 12 6, 12 6, 12 29.7 29.7 29.7 29.7 250, 312, 400, 500, 625, 800, 812, 988, 1000, 1250 200, 250, 320, 400, 500, 640, 650, 790, 800, 1000 40, 60, 80, 100, 120, 160, 200, 240 30% pleated 73.9 73.9 73.9 73.9 Prefilter, standard flow 40.0 40.0 40.0 40.0 Prefilter, medium flow 48.0 48.0 48.0 48.0 65% or 95%, standard flow 40.0 40.0 40.0 40.0 65% or 95%, medium flow 48.0 48.0 48.0 48.0 30% pleated 73.9 73.9 73.9 73.9 78.0 78.0 78.0 78.0 6 or 12 6 or 12 6 or 12 6 or 12 1 1 1 1
610 613 100-83-67-50-33- 100-83-67-50-3317-0 17-0 2/16 2/16 117.0 117.0 61.0 81.0 127 130, 33 140 3, 4, 5 8, 10, 12 39.5 47.1 5WH1 5WS2 9 29.7 5JA1, 2 6, 12 29.7
19
80
85
80
85
80
85
a. Compressor kW
Table 8: RPS 018C R22 low airflow coil, 575 voltsmultiply TH and SH by approximately .97 and kW by approximately .94
Unit data Entering air DB 75 6000 cfm 5 row 12 fpi WB 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 TH 226 242 259 227 242 259 231 242 259 232 248 264 233 248 264 242 249 265 236 252 269 240 252 269 252 255 269 85 SH 166 138 110 199 171 143 228 204 176 180 147 114 218 186 153 242 225 191 193 156 119 234 200 163 252 244 207 kWa 14.8 15.2 15.5 14.9 15.2 15.5 14.9 15.2 15.5 15 15.3 15.7 15 15.3 15.7 15.2 15.3 15.7 15.1 15.4 15.8 15.1 15.4 15.8 15.4 15.4 15.8 Ambient air temperature (F) 95 TH SH kWa 217 162 16.4 233 134 16.7 249 106 17.1 218 196 16.4 233 168 16.7 249 139 17.1 224 222 16.5 233 201 16.8 249 172 17.1 223 176 16.5 238 143 16.9 254 111 17.2 225 215 16.6 238 182 16.9 254 149 17.2 234 234 16.8 240 221 16.9 254 188 17.2 227 189 16.6 242 152 17 258 115 17.3 232 228 16.7 243 196 17 258 159 17.3 244 244aa 17 246 239 17 259 203 17.3 TH 208 223 239 209 223 239 216 224 239 213 228 243 216 228 243 226 230 244 217 232 223 232 235 236 105 SH 158 130 102 192 164 135 216 197 169 172 140 107 210 178 145 226 217 184 185 148 221 193 235 232 kWa 18.2 18.6 18.9 18.2 18.6 18.9 18.4 18.6 18.9 18.3 18.7 19 18.4 18.7 19 18.6 18.7 19 18.4 18.8 18.5 18.8 18.8 18.9
80
85
80
85
80
85
a. Compressor kW
20
Cooling Capacity Data Table 9: RPS 020C R22 low airflow coil, 575 voltsmultiply TH and SH by approximately .97 and kW by approximately .95
Unit data Entering air DB 75 6000 cfm 5 row 12 fpi WB 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 TH 268 287 308 268 287 308 269 287 307 283 302 323 284 303 323 291 303 323 292 311 296 312 311 314 85 SH 185 157 128 218 190 161 252 223 194 213 176 138 257 220 182 291 264 226 239 193 290 248 311 301 kWa 19.6 20 20.4 19.6 20 20.4 19.6 20 20.4 19.9 20.3 20.7 19.9 20.3 20.7 20.1 20.3 20.7 20.1 20.5 20.2 20.5 20.5 20.5 Ambient air temperature (F) 95 TH SH kWa 257 180 21.9 276 152 22.3 296 124 22.7 258 213 21.9 276 185 22.3 296 157 22.7 259 247 21.9 276 219 22.3 296 190 22.7 271 208 22.2 290 171 22.6 310 133 23 272 252 22.2 290 215 22.6 310 177 23 281 281 22.4 291 259 22.6 310 221 23 280 234 22.4 298 188 22.8 284 283 22.5 299 243 22.8 301 301 22.8 302 295 22.9 TH 246 264 283 247 264 283 248 265 283 259 277 260 277 271 278 267 285 273 285 289 290 105 SH 175 147 119 208 180 152 242 214 185 203 166 247 210 271 254 229 183 273 238 289 287 kWa 24.5 24.9 25.3 24.5 24.9 25.3 24.5 24.9 25.3 24.8 25.2 24.8 25.2 25.1 25.2 24.9 25.4 25.1 25.4 25.5 25.5
80
85
80
85
80
85
a. Compressor kW
Table 10: RPS 025C R22 low airflow coil, 575 voltsmultiply TH and SH by approximately .96 and kW by approximately .93
Unit data Entering air DB 75 8000 cfm 5 row 12 fpi WB 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 TH 330 354 379 331 354 379 333 354 379 344 367 392 345 367 393 356 369 393 352 376 357 377 377 380 85 SH 234 197 159 279 241 203 323 285 247 262 215 168 318 271 224 356 326 279 289 233 353 299 377 365 kWa 23.3 23.8 24.3 23.3 23.8 24.3 23.3 23.8 24.3 23.6 24.1 24.6 23.6 24.1 24.6 23.8 24.1 24.6 23.8 24.3 23.8 24.3 24.3 24.3 Ambient air temperature (F) 95 TH SH kWa 318 229 26 340 191 26.5 364 153 27 318 273 26 340 235 26.5 364 197 27 321 317 26 340 280 26.5 364 242 27 330 256 26.2 352 210 26.8 377 163 27.3 332 312 26.3 353 265 26.8 377 218 27.3 345 345 26.6 354 320 26.8 377 273 27.3 338 283 26.4 360 227 27 344 343 26.6 361 294 27 364 364 27 365 358 27.1 TH 303 325 348 304 325 348 308 326 348 315 336 317 337 332 338 323 344 330 345 350 350 105 SH 222 185 147 267 229 191 308 274 236 250 203 305 259 332 314 276 221 330 287 350 349 kWa 29 29.6 30.2 29.1 29.6 30.2 29.2 29.6 30.2 29.3 29.9 29.4 29.9 29.8 29.9 29.5 30.1 29.7 30.1 30.2 30.2
80
85
80
85
80
85
a. Compressor kW
21
Table 11: RPS 030C R22 low airflow coil, 575 voltsmultiply TH and SH by approximately .96 and kW by approximately .94
Unit data Entering air DB 75 10000 cfm 5 row 12 fpi WB 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 TH 366 391 418 367 391 418 374 392 418 376 401 379 402 397 404 384 409 392 410 414 415 85 SH 272 225 178 327 280 233 374 336 288 299 243 364 309 397 375 325 261 391 337 414 409 kWa 26.1 26.7 27.2 26.1 26.6 27.2 26.3 26.7 27.2 26.3 26.9 26.4 26.9 26.8 26.9 26.5 27 26.7 27.1 27.2 27.2 Ambient air temperature (F) 95 TH SH kWa 351 266 29.1 375 219 29.7 401 171 30.3 352 321 29.2 375 274 29.7 401 227 30.3 362 362 29.4 376 329 29.7 401 282 30.3 360 292 29.4 384 236 29.9 364 357 29.4 385 303 29.9 383 383 29.9 388 368 30 367 318 29.5 391 254 30.1 377 377 29.8 392 331 30.1 399 399 30.3 399 398 30.3 TH 335 358 336 358 349 359 344 366 349 367 368 370 350 373 362 374 105 SH 259 212 314 267 349 322 285 230 347 296 368 360 311 247 362 324 kWa 32.6 33.2 32.6 33.2 33 33.2 32.8 33.4 32.9 33.4 33.5 33.5 33 33.6 33.3 33.6
80
85
80
85
80
85
a. Compressor kW
Table 12: RPS 036C R22 low airflow coil, 575 voltsmultiply TH and SH by approximately .96 and kW by approximately .95
Unit data Entering air DB 75 12000 cfm 5 row 12 fpi WB 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 TH 437 468 502 439 469 502 450 470 502 448 480 453 480 470 484 457 488 466 489 488 496 85 SH 325 270 213 392 336 280 443 402 346 352 288 426 365 470 440 378 305 451 393 488 470 kWa 28.9 29.4 30 29 29.4 30 29.1 29.5 30 29.1 29.6 29.2 29.6 29.4 29.7 29.2 29.7 29.4 29.8 29.8 29.9 Ambient air temperature (F) 95 TH SH kWa 420 318 32.3 450 262 32.8 423 384 32.3 451 329 32.8 482 272 33.4 434 432 32.5 452 395 32.8 431 345 32.5 461 281 33 437 415 32.5 461 357 33 455 455 32.9 465 432 33 439 370 32.6 468 298 33.1 448 439 32.8 470 385 33.1 TH 403 431 405 431 418 433 412 440 419 441 439 446 420 447 431 449 105 SH 310 255 376 321 418 387 337 273 403 350 439 421 362 290 427 377 kWa 36.1 36.6 36.1 36.6 36.3 36.6 36.3 36.8 36.4 36.8 36.7 36.9 36.4 36.9 36.6 36.9
80
85
80
85
80
85
a. Compressor kW
22
80
85
80
85
80
85
a. Compressor kW
80
85
80
85
80
85
a. Compressor kW
23
80
85
80
85
80
85
a. Compressor kW
80
85
80
85
80
85
a. Compressor kW
24
80
85
80
85
80
85
a. Compressor kW b. Maximum airflow is 23,700 cfm
80
85
80
85
80
85
a. Compressor kW
25
80
85
80
85
80
85
a. Compressor kW
80
85
80
85
80
85
a. Compressor kW
26
80
85
80
85
80
85
a. Compressor kW b. Maximum airflow is 25,675 cfm
WB 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71
TH 905 97 1040 907 970 1039 912 972 1038 933 999 1070 936 999 1069 952 1000 1069 954 1021 1091 959 1021 1091 994 1025 1091
85 SH 640 538 435 760 658 555 878 779 674 693 574 454 833 715 594 952 855 735 744 609 472 901 770 632 994 928 794
kWa 69.5 70.7 72.0 69.5 70.7 72.0 69.6 70.7 72.0 70.0 71.2 72.5 70.0 71.2 72.5 70.3 71.2 72.5 70.4 71.6 72.9 70.5 71.6 72.9 71.1 71.7 72.9
Ambient air temperature (F) 95 TH SH kWa 870 624 77.5 933 523 78.8 1000 420 80.1 872 744 77.5 933 642 78.7 999 539 80.1 878 861 77.6 933 762 78.7 999 659 80.1 896 677 78.0 959 558 79.3 1026 438 80.7 899 817 78.0 959 699 79.3 1026 579 80.6 921 921 78.5 961 838 79.3 1026 720 80.6 915 728 78.4 979 593 79.7 1047 456 81.1 920 883 78.5 979 753 79.7 1046 617 81.0 962 962 79.3 984 911 79.8 1047 778 81.0
TH 831 892 955 833 891 954 842 892 954 855 915 980 859 916 979 887 917 979 873 934 998 880 934 998 925 939 998
105 SH 607 506 403 727 625 523 840 745 643 659 541 421 798 682 562 887 821 703 710 575 439 863 736 600 925 891 761
kWa 86.6 88.0 89.4 86.6 87.9 89.4 86.8 87.9 89.4 87.1 88.5 90.0 87.2 88.5 89.9 87.8 88.5 89.9 87.6 88.9 90.4 87.7 88.9 90.4 88.7 89.0 90.3
27
1500
Model 1000 Model 800 Model 790 Model 650 Model 640 Model 500 Model 400 Model 320 Model 250
MBH Output
700
600
500 400
300
200 1 1.5 2 3 4 5 6 7 8 9 10 15 20 30 40
Model 200
p20
Table 23: RPS 015C to 135C gas furnace air temperature rise (F)
Unit size 015C 020C 025C 030C 036C 040C 045C 050C 060C 070C 075C 080C 090C 105C 115C 125C 135C Nominal airflow (cfm) 7000 8000 10000 12000 14000 16000 16000 20000 24000 28000 30000 32000 36000 40000 46000 48000 50000 Furnace Size (MBh Output)a 200 26.3 23.0 18.4 15.4 13.2 11.5 11.5 9.2 7.7 6.6 6.1 250 32.9 28.8 23.0 19.2 16.5 14.4 14.4 11.5 9.6 8.2 7.7 320 42.1 36.9 29.5 24.6 21.1 18.4 18.4 14.7 12.3 10.5 9.8 400 52.7 46.1 36.9 30.7 26.3 23.0 23.0 18.4 15.4 13.2 12.3 500 65.8 57.6 46.1 38.4 32.9 28.8 28.8 23.0 19.2 16.5 15.4 14.4 12.8 11.5 10.0 9.6 9.2 640 59.0 49.2 42.1 36.9 36.9 29.5 24.6 21.1 19.7 18.4 16.4 14.7 12.8 12.3 11.8 650 85.6 74.9 59.9 49.9 42.8 37.4 37.4 30.0 25.0 21.4 20.0 18.7 16.6 15.0 13.0 12.5 12.0 790 60.7 52.0 45.5 45.5 36.4 30.3 26.0 24.3 22.8 20.2 18.2 15.8 15.2 14.6 800 92.2 73.7 61.4 52.7 46.1 46.1 36.9 30.7 26.3 24.6 23.0 20.5 18.4 16.0 15.4 14.7 1000 57.6 57.6 46.1 38.4 32.9 30.7 28.8 25.6 23.0 20.0 19.2 18.4
28
Table 24: Gas Furnace design maximum air temperature rise (F) and minimum airflow
Baffle position Maximum temperature rise (F) Minimum airflow (cfm) Column Number for Pressure Drop (See Table 37: Furnace pressure drop (in. W.C.), RPS 015C to 135C on page 34) Furnace size (MBh) 200 250 320 400 500 640 650 790 800 1000 80 61 100 61 100 61 100 61 100 61 2300 3800 2950 6000 4600 9600 5970 12000 7340 15000 1 1 1 1 2 2 3 3 3 3 62 42 78 35 63 42 73 52 76 50 3000 5500 3800 10500 7400 14000 8200 14000 9800 18500 4 4 4 4 5 5 4 4 4 4 46 15 59 31 55 37 65 46 71 40 4000 15000 5000 12000 8400 16000 9200 16000 10400 23000 9 9 9 9 10 10 10 10 10 10
Notes: Temperature rise and airflow limit applicable to all burner types. VAV application, consider the minimum turndown airflow when selecting baffle position.
29
Electric Heat
208 Volts
Table 26: RPS 015C to 040C or 800 to 802208V electric heat air temperature rise (F)
Electric heater model number Airflow (cfm) 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 16000 20 51 7.8 6.7 5.9 5.2 4.7 4.3 3.9 3.6 3.4 3.1 2.9 40 102 15.7 13.4 11.8 10.4 9.4 8.5 7.8 7.2 6.7 6.3 5.9 60 154 23.7 20.3 17.7 15.8 14.2 12.9 11.8 10.9 10.1 9.5 8.9 80 204 31.3 26.9 23.5 20.9 18.8 17.1 15.7 14.5 13.4 12.5 11.8 100 255 39.2 33.6 29.4 26.1 23.5 21.4 19.6 18.1 16.8 15.7 14.7 120 306 47.0 40.3 35.3 31.3 28.2 25.6 23.5 21.7 20.1 18.8 17.6 Electric heater capacity (MBh) 14000 15000 16000 17000 18000 19000 20000 21000 22000 23000 24000 25000 26000 27000 28000 29000 30000
Table 27: RPS 045C to 075C (or RAH 047C)208V electric heat air temperature rise (F)
Electric heater model number Airflow (cfm) 40 60 80 100 120 160
Electric heater capacity (MBh) 102 6.7 6.3 5.9 5.5 5.2 4.9 4.7 4.5 4.3 4.1 3.9 3.8 3.6 3.5 3.4 3.2 3.1 154 10.1 9.5 8.9 8.3 7.9 7.5 7.1 6.8 6.5 6.2 5.9 5.7 5.5 5.3 5.1 4.9 4.7 204 13.4 12.5 11.8 11.1 10.4 9.9 9.4 9.0 8.5 8.2 7.8 7.5 7.2 7.0 6.7 6.5 6.3 255 16.8 15.7 14.7 13.8 13.1 12.4 11.8 11.2 10.7 10.2 9.8 9.4 9.0 8.7 8.4 8.1 7.8 306 20.1 18.8 17.6 16.6 15.7 14.8 14.1 13.4 12.8 12.3 11.8 11.3 10.8 10.4 10.1 9.7 9.4 408 26.9 25.1 23.5 22.1 20.9 19.8 18.8 17.9 17.1 16.3 15.7 15.0 14.5 13.9 13.4 13.0 12.5
The maximum temperature rise allowed for electric heat is 60F with leaving air temperature not to exceed 140F. The minimum airflow required for unit sizes 015C to 040C with electric heat is 6,000 cfm.
The maximum temperature rise allowed for electric heat is 60F with leaving air temperature not to exceed 140F. The minimum airflow required for unit sizes 045C to 075C with electric heat is 14,000 cfm.
6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 16000
The maximum temperature rise allowed for electric heat is 60F with leaving air temperature not to exceed 140F. The minimum airflow required for units 015C to 040C with electric heat is 6,000 cfm. 180, 200, 220, and 240 electric heaters available at 460 or 575 Volts only.
30
Table 29: RPS 045C to 075C (or RAH 047C)230V, 460V, 575V electric heat air temperature rise (F)
Electric heater model number Airflow (cfm) 40 60 80 100 120 160 180 200 240
Electric heater capacity (MBh) 125 188 12.4 11.6 10.8 10.2 9.6 9.1 8.7 8.3 7.9 7.5 7.2 6.9 6.7 6.4 6.2 6.0 5.8 249 16.4 15.3 14.3 13.5 12.7 12.1 11.5 10.9 10.4 10.0 9.6 9.2 8.8 8.5 8.2 7.9 7.6 312 20.5 19.2 18.0 16.9 16.0 15.1 14.4 13.7 13.1 12.5 12.0 11.5 11.1 10.7 10.3 9.9 9.6 374 24.6 23.0 21.5 20.3 19.2 18.1 17.2 16.4 15.7 15.0 14.4 13.8 13.3 12.8 12.3 11.9 11.5 499 32.9 30.7 28.7 27.1 25.6 24.2 23.0 21.9 20.9 20.0 19.2 18.4 17.7 17.0 16.4 15.9 15.3 564 37.1 34.7 32.5 30.6 28.9 27.4 26.0 24.8 23.6 22.6 21.7 20.8 20.0 19.3 18.6 17.9 17.3 624 41.1 38.3 35.9 33.8 32.0 30.3 28.8 27.4 26.1 25.0 24.0 23.0 22.1 21.3 20.5 19.8 19.2 748 49.2 46.0 43.1 40.6 38.3 36.3 34.5 32.8 31.3 30.0 28.7 27.6 26.5 25.5 24.6 23.8 23.0
14000 15000 16000 17000 18000 19000 20000 21000 22000 23000 24000 25000 26000 27000 28000 29000 30000
8.2 7.7 7.2 6.8 6.4 6.1 5.8 5.5 5.2 5.0 4.8 4.6 4.4 4.3 4.1 4.0 3.8
31
Based on maximum exhaust cfm during economizer operation. If design OA cfm through the wheel is > 70% of design cfm, then check APD with your local representative.
Economizer - Based on maximum exhaust cfm during economizer operation. If design OA cfm through the wheel is > 70% of design cfm, then check APD with your local representative. No Economizer - Based on design OA cfm through the wheel.
32
Table 34: RPS/RFS 015C to 040C or RDS 800 to 802 (in. w.g.)
Filter Unit airflow Angular rack Flat rack (cfm) 30% pleated Pre-filters 65% cartr. 95% cartr. 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000 18,000 .02 .03 .04 .05 .07 .08 .09 .10 .12 .13 .14 .16 .18 .19 .21 .06 .08 .10 .13 .16 .19 .22 .25 .28 .32 .35 .39 .43 .47 .50 .08 .12 .16 .20 .25 .31 .36 .43 .49 .56 .63 .71 .79 .87 .95 .12 .17 .23 .29 .35 .42 .49 .56 .64 .72 .81 .89 .98 1.07 1.17 018C 020C 5-row 8 fpi .16 .22 .30 .37 .45 .54 .63 .72 .81 5-row 10 fpi .19 .27 .35 .44 .54 .64 .74 .84 .95 5-row 12 fpi .23 .33 .42 .53 .64 .75 .87 .99 5-row 8 fpi .17 .21 .26 .31 .36 .41 .46 .54 .60 .67 .73 .80 Evaporator coilsa 025C 040C 5-row 10 fpi .20 .25 .31 .36 .42 .49 .55 .64 .71 .79 .86 .94 5-row 12 fpi .24 .30 .37 .43 .50 .58 .65 .75 .84 .92 1.01
Table 35: RPS/RFS 015C to 040C or RDS 800 to 802 (in. w.g.)
Coils Unit airflow (cfm) 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000 18,000 Hot water Low cap. High cap. .03 .05 .04 .08 .06 .11 .08 .14 .09 .18 .12 .22 .14 .27 .17 .31 .20 .36 .22 .41 .26 .46 .29 .53 .32 .60 .36 .66 .40 .74 Steam Low cap. .02 .03 .04 .05 .06 .07 .08 .09 .10 .11 .12 .13 .15 .16 .17 High cap. .04 .06 .07 .09 .11 .13 .14 .16 .18 .20 .23 .25 .27 .30 .32
33
Filter options
Plenum Options
Cooling optionsa b c
Heating optionsb
a. Pressure drop of cooling coils not shown can be found in the McQuay Selection Program output. b. DX coil pressure drops are based on wet coils. c. A cooling diffuser is provided on units with blow-through cooling only.
Table 37: Furnace pressure drop (in. W.C.), RPS 015C to 135C
Airflow (cfm) 4000 6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 26000 28000 30000 Column number, see Table 25 on page 29 1 0.06 0.13 0.24 0.37 0.53 0.72 0.94 1.19 2 0.05 0.1 0.17 0.27 0.39 0.54 0.7 0.89 1.09 3 0.14 0.22 0.32 0.44 0.57 0.72 0.89 1.08 4 0.08 0.12 0.17 0.24 0.31 0.39 0.48 0.58 0.69 0.81 0.94 1.08 5 0.07 0.11 0.16 0.21 0.28 0.35 0.43 0.52 0.62 0.73 0.85 0.97 6 0.09 0.13 0.18 0.24 0.3 0.37 0.44 0.53 0.62 0.72 0.83 7 0.08 0.12 0.16 0.2 0.26 0.32 0.39 0.46 0.54 0.63 0.72 8 0.09 0.12 0.15 0.19 0.24 0.29 0.34 0.4 0.47 0.54 9 0.08 0.1 0.13 0.17 0.21 0.25 0.3 0.35 0.41 0.47 10 0.1 0.12 0.16 0.2 0.24 0.28 0.33 0.38 0.44
Table 38: Gravity relief damper air pressure drop, 0 to 100% economizer
Exhaust cfm Size 015C-040C Size 045C-075C 5000 10000 .25 15000 .54 .36 20000 .61 25000 1.00 30000 35000 40000
Note: If all exhaust must occur through the economizer gravity relief damper, and no return or exhaust fan is provided, then the building may be pressurized by the sum of the return duct pressure drop plus the gravity relief pressure.
34
Figure 15: 015C to 030C or RDS 800 (2) 15 in. 15 in. forward curved supply fan
35
Fan Performance DataSupply Fans Figure 16: 015C to 030C or RDS 800 20 in. airfoil supply fan
Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in).
Figure 17: 036C to 040C or RDS 802 24 in. forward curve supply fan
Class II
Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in).
36
Fan Performance DataSupply Fans Figure 18: 036C to 040C or RDS 802 24 in. airfoil supply fan
Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in).
Figure 19: RPS/RFS 045C to 050C or RAH 047C 27 in. forward curved supply fan
Class II
Note: Maximum allowable static pressure at fan bulkhead is 5.0 in. (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in).
37
Fan Performance DataSupply Fans Figure 20: RPS/RFS 045C to 050C or RAH 047C 27 in. airfoil supply fan
Note: Maximum allowable static pressure at fan bulkhead is 5.0 in. (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in).
Figure 21: RPS/RFS 045C to 075C or RAH 047C 30 in. airfoil supply fan
Note: Maximum allowable static pressure at fan bulkhead is 5.0 in. (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in).
38
Fan Performance DataSupply Fans Figure 22: RPS/RFS 060C to 075C or RAH 047C 33 in. airfoil supply fan
Note: Maximum allowable static pressure at fan bulkhead is 5.0 in. (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in).
39
140
Static Pressure - in. w.g.
0 7.5 5
10
100 800
120 0
1.5
Airflow - cfm
Figure 24: RPS/RFS/RDT 045C to 075C or RAH 047C 40 in. airfoil return fan
40
Dimensional Data
Dimensional Data
Section Options and Locations
Figures 2527 show section options, curb lengths, and relative positions. Curb lengths (in inches) are shown below each icon.
Figure 25: RPS/RFS 015C to 030C, draw-through coil section (RDS 800 varies slightly)
Energy Recovery
108
Economizer
120
100% OA, High Capacity
132
41
Dimensional Data Figure 26: RPS/RFS/RCS 036C and 040C, blow-through coil section (n/a final filters, (RDS 802 varies slightly)
Energy Recovery
108
Economizer
120
100% OA, High Capacity
132
42
Dimensional Data Figure 27: RPS/RFS/RCS 036C and 040C, draw-through coil section (RDS 802 varies slightly)
Energy Recovery
108
Economizer
120
100% OA, High Capacity
132
43
Dimensional Data Figure 28: RPS/RFS/RCS 045C to 075C, blow-through coil section (n/a final filters)
Position A Outdoor/ Energy Recovery
Bottom Return
Angular
Blank
Steam/Hot Water
Blank
192 24 Side Return Low Airflow Cartridge (40 sq. Ft) 48 72 VFD Section 060C-075C 30 Dia 48 Electric 48 Sound Attenuator 24 050C-075C (39.5 sq. ft.) 48 72 83 (Does not affect curb length) 070C-075C 24 216 Side Return High Airflow 48 240 Blender & Angular or 40 sq ft Cartridge 96 Cartridge (48 sq. Ft.) 48 72 33Dia 48 Gas 48 Sound Attenuator 24 Air-cooled Condenser
48 Blank 72 48
96 Blank
24 or 48
Note: Exhaust fan section dimensions do not include the hood. See page 38.
44
Dimensional Data Figure 29: RPS/RFS/RCS 045C to 075C, draw-through coil section (RAH 047C varies slightly)
Position A Outdoor/ Energy Recovery
Bottom Return
Angular
Blank
Blank
192 24 Side Return Low Airflow Cartridge (40 sq. ft.) 48 VFD Section 24 050C-070C (39.5 sq. ft.) 72 060C-075C 30 Dia 48 Electric 48 48 Cooling Only, Steam or Hot Water Sound Attenuator 48 Gas or Electric Heat (48 sq. ft.) 72 83 (Does not affect curb length) 070C-075C Air-cooled Condenser 48 Gas or Electric Heat 48 Blank 48 72 48 72 Blender & 48 sq ft Cartridge Blank Sound Attenuator* 72 Blank 1 19 (Does not affect curb length)
48 Gas
240
96
72
96 Blank
24 or 48
Note: Exhaust fan section dimensions do not include the hood. See page 38.
Use Figures 25 through 29 to determine the total air handler length and total unit length. The total air handler length, which is needed to determine roof curb knockouts, incudes all unit sections except the air cooled condensing section.
Example: RPS 045C with draw-through coil section (from Figure 29)
Section description Length (in.) Energy Recovery with bottom return = 192 Angular filters = 24 Cooling coil = 24 Supply fan = 72
Gas heat = 48 Final filter, standard flow = 48 Discharge plenum = 48 Air cooled condensing unit = 83 Total air handler length = 456 Total unit length (including condensing unit) = 539 For a custom certified drawing of your specific requirements, consult your local McQuay sales representative.
45
Dimensional Data
6.6
7.6
8.8
Figure 31: Main control panel/discharge plenum, RPS/RFS 045C to 075C or RAH 047C
Reference from leaving air end of section 8.8 7.6
3.0 dia. K.O. (qty = 3) 6.6 11.9 0.9 dia. K.O. (qty = 4) 17.7 18.7 22.3 24.3 12.9 15.3
3 .0 D ia . K .O . (Q ty = 2 ) 0 .9 D ia . K .O .
2 9 .3 3 0 .3 3 2 .7
6 .6
7 .6
8 .8
46
Dimensional Data
47
B 12.0 6.0
C 5.0 4.2
D 2.7 4.0
B A D C Unit size 015C040C or 800-802C 045C 075 C or 47C A 6.0 6.0 B 6.5 9.0 C 1.0 1.0 D 29.0 37.0
B A C D
48
Roof Curbs
Roof Curbs
Figure 37: Roof curb, RPS/RFS 015C to 040C (without blank compartment)
C D A 20.0 6.8 1.5 6.0 RPS Only
RA OPENING
SA OPENING
76.0
97.0
See Figure 43
D 2 Typ 4 Typ
Roof curb must be installed level.
See Figure 42
7.5
See Figure 41
6.0 E 8.0
Figure 38: Roof curb, RPS/RFS 015C to 040C (with blank compartment)
C D A 20.0 6.8 46.8 1.5 6.0 RPS Only
RA OPENING
SA OPENING
76.0
97.0
See Figure 43
D 2 Typ 4 Typ
See Figure 42 See Figure 41
7.5 6.0 E
49
Roof Curbs Figure 39: Roof curb, RPS/RFS 045C to 075C (without blank compartment)
6.8 138.8 1.5 38 28 1.5
5.0
7.5
Figure 40: Roof curb, RPS/RFS 045C to 075C (with blank compartment)
See Figure 43
2.1
3.1
4.3
50
Curb gasketing Unit base Curb gasketing 24 nailer strip Duct support
Counterflashing*
Flashing*
Cant strip* Roofing material*
*Not furnished
Unit base Duct support 16 9.8 Counterflashing* Flashing* Roofing material* 2 4 nailer strip Cant strip* Rigid insulation* Rigid insulation* Cant strip*
14.4
4.6
Galvanized curb
Galvanized curb
51
Recommended Clearances
Recommended Clearances
Service Clearance
Allow recommended service clearances shown in Figure 44. Provide a roof walkway along two sides of the unit for service and access to most controls.
Figure 44: Service clearances
Cooling coil, heat and supply fan service clearance Additional clearance, A is recommended adjacent to the cooling coil, heat, and supply fan sections. See Figures 2527 on pages 4143 to identify these sections.
Table 42: Service clearance
Unit size 015C to 040C or 800 to 802C 045C to 075C or 047C A 30 24 B 60 72 C 60 72
Overhead Clearance
1 Unit(s) surrounded by screens or solid walls must have no
52
Recommended Clearances
Ventilation Clearance
Unit(s) surrounded by a screen or a fence:
1 The bottom of the screen should be a minimum of 1 ft.
restrictions.
b Walls on more than two adjacent sideswall height not
to exceed unit height. Do not locate outside air intakes near exhaust vents or other sources of contaminated air. If the unit is installed where windy conditions are common, install wind screens around the unit, maintaining the clearances specified above. This is particularly important to prevent blowing snow from entering outside air intakes and to maintain adequate head pressure control when mechanical cooling is required at low outdoor air temperatures. SpeedTrol, required for compressor operation below 45F, maintains proper head pressure in calm wind conditions.
53
Electrical Data
Electrical Data
Table 43: Compressor amps, RPS/RFS/RDT 015C to 075C
Model Voltage R-22 Circuit 1 Circuit 2 Comp 1 Comp 3 Comp 5 Comp 2 Comp 4 Comp 6 LRA LRA LRA LRA LRA LRA RLA RLA RLA RLA RLA RLA 14.7 14.7 7.4 5.9 22.4 22.4 10.9 7.4 22.4 22.4 10.9 7.4 22.4 22.4 10.9 7.4 22.4 22.4 10.9 7.4 22.4 22.4 10.9 7.4 33.6 33.6 16.5 13.7 33.6 33.6 16.5 13.7 41.0 41.0 21.8 17.3 48.1 48.1 23.7 21.2 33.6 33.6 16.5 13.7 41.0 41.0 21.8 17.3 124 124 60 49 164 164 100 54 164 164 100 54 164 164 100 54 164 164 100 54 164 164 100 54 278 278 127 100 278 278 127 100 350 350 158 125 425 425 187 148 278 278 127 100 350 350 158 125 22.4 22.4 10.9 7.4 22.4 22.4 10.9 7.4 22.4 22.4 10.9 7.4 33.6 33.6 16.5 13.7 33.6 33.6 16.5 13.7 41.0 41.0 21.8 17.3 48.1 48.1 23.7 21.2 33.6 33.6 16.5 13.7 41.0 41.0 21.8 17.3 164 164 100 54 164 164 100 54 164 164 100 54 278 278 127 100 278 278 127 100 350 350 158 125 425 425 187 148 278 278 127 100 350 350 158 125 33.6 33.6 16.5 13.7 41.0 41.0 21.8 17.3 278 278 127 100 350 350 158 125 30.1 30.1 15.5 12.1 37.2 37.2 17.2 12.4 48.1 48.1 23.7 21.2 41.0 41.0 21.8 17.3 48.1 48.1 23.7 21.2 33.6 33.6 16.5 13.7 33.6 33.6 16.5 13.7 33.6 33.6 16.5 13.7 41.0 41.0 21.8 17.3 48.1 48.1 23.7 21.2 33.6 33.6 16.5 13.7 41.0 41.0 21.8 17.3 225 225 114 80 239 239 125 80 425 425 187 148 350 350 158 125 425 425 187 148 278 278 127 100 278 278 127 100 278 278 127 100 350 350 158 125 425 425 187 148 278 278 127 100 350 350 158 125 33.6 33.6 16.5 13.7 33.6 33.6 16.5 13.7 33.6 33.6 16.5 13.7 41.0 41.0 21.8 17.3 48.1 48.1 23.7 21.2 33.6 33.6 16.5 13.7 41.0 41.0 21.8 17.3 278 278 127 100 278 278 127 100 278 278 127 100 350 350 158 125 425 425 187 148 278 278 127 100 350 350 158 125 33.6 33.6 16.5 13.7 41.0 41.0 21.8 17.3 278 278 127 100 350 350 158 125 R-407C Circuit 1 Circuit 2 Comp 1 Comp 3 Comp 5 Comp 2 Comp 4 Comp 6 LRA LRA LRA LRA LRA 14.7 14.7 7.4 22.4 22.4 10.9 7.4 22.4 22.4 10.9 7.4 22.4 22.4 10.9 7.4 22.4 22.4 10.9 7.4 22.4 22.4 10.9 7.4 36.9 36.9 19.9 16.4 36.9 36.9 19.9 16.4 43.9 43.9 24.4 17.3 49.4 49.4 28.8 23.1 36.9 36.9 19.9 16.4 43.9 43.9 24.4 17.3 124 124 60 164 164 100 54 164 164 100 54 164 164 100 54 164 164 100 54 164 164 100 54 278 278 127 100 278 278 127 100 350 350 158 125 350 350 187 148 278 278 127 100 350 350 158 125 22.4 22.4 10.9 7.4 22.4 22.4 10.9 7.4 22.4 22.4 10.9 7.4 36.9 36.9 19.9 16.4 36.9 36.9 19.9 16.4 43.9 43.9 24.4 17.3 49.4 49.4 28.8 23.1 36.9 36.9 19.9 16.4 43.9 43.9 24.4 17.3 164 164 100 54 164 164 100 54 164 164 100 54 278 278 127 100 278 278 127 100 350 350 158 125 350 350 187 148 278 278 127 100 350 350 158 125 36.9 36.9 19.9 16.4 43.9 43.9 24.8 17.3 278 278 127 100 350 350 158 125 30.1 30.1 15.5 37.2 37.2 17.2 12.4 49.4 49.4 28.8 23.1 43.9 43.9 24.5 17.3 49.4 49.4 28.8 23.1 36.9 36.9 19.9 16.4 36.9 36.9 19.9 16.4 36.9 36.9 19.9 16.4 43.9 43.9 24.4 17.3 49.4 49.4 28.8 23.1 36.9 36.9 19.9 16.4 43.9 43.9 24.4 17.3 225 225 114 239 239 125 80 425 425 187 148 350 350 158 125 425 425 187 148 278 278 127 100 278 278 127 100 278 278 127 100 350 350 158 125 350 350 187 148 278 278 127 100 350 350 158 125 36.9 36.9 19.9 16.4 43.9 43.9 24.8 17.3 278 278 127 100 350 350 158 125 LRA RLA RLA RLA RLA RLA RLA
015C
018C
020C
025C
030C
036C
040C
045C
050C
060C
070C
075C
208/60/3 230/60/3 460/60/3 575/60/3 208/60/3 230/60/3 460/60/3 575/60/3 208/60/3 230/60/3 460/60/3 575/60/3 208/60/3 230/60/3 460/60/3 575/60/3 208/60/3 230/60/3 460/60/3 575/60/3 208/60/3 230/60/3 460/60/3 575/60/3 208/60/3 230/60/3 460/60/3 575/60/3 208/60/3 230/60/3 460/60/3 575/60/3 208/60/3 230/60/3 460/60/3 575/60/3 208/60/3 230/60/3 460/60/3 575/60/3 208/60/3 230/60/3 460/60/3 575/60/3 208/60/3 230/60/3 460/60/3 575/60/3
36.9 36.9 19.9 16.4 36.9 36.9 19.9 16.4 36.9 36.9 19.9 16.4 43.9 43.9 24.4 17.3 49.4 49.4 28.8 23.1 36.9 36.9 19.9 16.4 43.9 43.9 24.4 17.3
278 278 127 100 278 278 127 100 278 278 127 100 350 350 158 125 350 350 187 148 278 278 127 100 350 350 158 125
Note: 1. Data given is for individual compressors and condenser fan motors. 2. Locked Rotor Amps for part winding start are for the first winding for 1 second. 3. 115-volt receptacle or marine light options require separate power.
54
Electrical Data
SpeedTrol fan
FLA LRA
4 2 1.7
* Units ordered with SpeedTrol low ambient control have two SpeedTrol fan motors (one per circuit) in lieu of two of the standard condenser fan motors.
1.5
7.5
10
15
20
25
30
40
50
ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC
a. For 380/50/3 applications, 460/60/3 motors are used. Derate nameplate by 0.85 to obtain actual horsepower.
55
Electrical Data
240/60/3 Stages 2 2 3 3 3 3
b
480/60/3
a
600/60/3
a
Steps 2 2 4 4 6 6
Stages 2 2 3 3 3 3
Steps 2 2 2 2 4 4 4 4 6 6 6 6
Stages 2 2 2 2 3 3 3 3 3 3 3 3
Stepsa Stagesb 2 2 2 2 4 4 4 4 6 6 6 6 2 2 2 2 3 3 3 3 3 3 3 3
119.4 287.2
119.4 143.6 139.1 167.3 159.2 191.5 179.1 215.4 199.0 239.4 218.7 263.0 238.8 287.2
119.4 114.9 139.1 133.8 159.2 153.2 179.1 172.3 199.0 191.5 218.7 210.4 238.8 229.8
a. Number of fused circuits b. Number of controlled heat stages from MicroTech II solid-state control system; additional fused circuits controlled by time delay relays. See Table 5 on page 18 for electric heat availability by unit size.
*Not available on RPS/RFS 808C135C on 208/240 volt applications. See Table 5 on page 18 and Table 6 on page 19 for electric heat availability by unit size.
56
Electrical Data
Nameplate 208V: Min. 187V, Max. 229V Nameplate 230V: Min. 207V, Max. 253V Nameplate 460V: Min. 414V, Max. 506V Nameplate 575V: Min. 518V, Max. 633V
b 50 Hertz
connections, each must be considered alone in selecting power wiring components. The MCA is calculated based on the following formulas:
1 Units with cooling and all heating except electric heat
the cooling mode and the heating mode and the greater of the two values is used.
a Heating Mode
Electric heat less than or equal to 50 kW MCA = 1.25 (heater FLA + largest motor FLA) + remaining SAF (or RAF/EAF FLA). Electric heat greater than or equal to 50 kW MCA = 1.25 (largest motor FLA) + heater FLA + remaining SAF (or RAF/EAF FLA).
Note: The compressor and condenser are not included in
this calculation.
b Cooling Mode
MCA = 1.25 largest FLA or RLA load + sum of all the other loads
Note: Control circuit ampacity does not need to be
considered in the calculation for wire sizing ampacity. If the unit is provided with one or more fan section lights, they are powered from the separate 15 amp (minimum), 120V supply required by the NEC for the unit convenience outlet.
3 Size wires in accordance with Table 310-16 or 310-19 of
57
Unit Weights
Unit Weights
Table 50: RPS/RFS 015C to 040C and RDS 800C to 802C (lbs)
Unit size Components 015C and 018C Unit configurationd RPS basic unita, standard cond. fan RPS basic unit , quiet cond. fan. RDS and RFS basic unita Economizer Filter optionsdraw-through section 30% pleated 65% cartridge with prefilter 95% cartridge with prefilter With cooling only, steam, or hot water heat With gas or electric heat Supply air fan assembly (2) 15" 6" diameter forward curved (2) 15" 15" diameter forward curved 20" diameter airfoil 24" diameter forward curvedLP 24" diameter forward curvedMP 24" diameter airfoil Evaporator coils 3-row, 8 fpi 3-row, 10 fpi 3-row, 12 Fpi 4-row, 8 Fpi 4-row, 10 Fpi 4-row, 12 Fpi 5-row, 8 Fpi 5-row, 10 Fpi 5-row, 12 Fpi 140 150 160 184 198 211 219 235 252 140 150 160 184 198 211 219 235 252 224 238 253 273 292 311 324 348 372 224 238 253 273 292 311 324 348 372 224 238 253 273 292 311 324 348 372 233 247 261 281 300 320 332 356 380 345 375 556 345 375 556 345 375 556 345 375 556 539 569 574 539 569 574 9 146 154 625 794 9 146 154 625 794 9 146 154 625 794 9 146 154 625 794 9 146 154 625 794 9 146 154 625 794
a
RDS 800C 020C 6774 8054 6205 370 025C 8030 8450 6213 370 030C 8051 8471 6213 370 036C 9353 9913 7041 370
Filter optionsblow-through section (final filters, 95% cartridge)including liners in the filter and discharge section
a. Basic unit consists of energy recovery section, angular filter section with 2" throwaway filters, supply fan section without fan or motor, cooling section without coil, discharge plenum, and condensing unit (RPS only). d. Add 880 lbs for units with (2) energy recovery wheels.
58
Unit Weights Table 50: RPS/RFS 015C to 040C and RDS 800C to 802C (lbs)
Unit size Components 015C and 018C Hot water heatb Low capacity High capacity Steam heatb Low capacity High Capacity Electric heatb 20 kW 40 kW 60 kW 80 kW 100 kW 120 kW 140 kW 160 kW 180 kW 200 kW Gas furnaceb 200, 250, 320, 400 MBh 500, 640 MBh 650, 790 MBh 800, 1000 MBh Blank or heating section 40", unlined 52", unlined Accessory items Variable frequency driveSAFb Variable frequency drive RAFb Insulation and linersc Weight per foot of unit length 24 24 24 24 24 24
a. Basic unit consists of energy recovery section, angular filter section with 2" throwaway filters, supply fan section without fan or motor, cooling section without coil, discharge plenum, and condensing unit (RPS only). b. Does not include weight of blank or heating section. c. Nominal 2", 1.5 lbs. density solid liners, excluding condensing unit section and blank compartment. Weights shown are sufficient for both reciprocating and scroll compressor units. d. Add 880 lbs for units with (2) energy recovery wheels.
RDS 800C 020C 580 630 575 605 656 664 668 696 769 777 811 819 841 849 964 1041 1155 1237 405 512 150 100 025C 580 630 575 605 656 664 668 696 769 777 811 819 841 849 964 1041 1155 1237 405 512 150 100 030C 580 630 575 605 656 664 668 696 769 777 811 819 841 849 964 1041 1155 1237 405 512 150 100 036C 580 630 575 605 656 664 668 696 769 777 811 819 841 849 964 1041 1155 1237 405 512 150 100
RDS 802C 040C 580 630 575 605 656 664 668 696 769 777 811 819 841 849 964 1041 1155 1237 405 512 150 100
580 630 575 605 656 664 668 696 769 777 811 819 841 849 964 1041 1155 1237 405 512 150 100
59
RAH 047C 050C 12,590 13,153 9749 8775 9335 4 57 538 67 550
a
Motor hp
Supply, Exhaust and Retrun Fan Motor Weight (lbs) Open dripproof 39 48 48 71 82 124 144 185 214 266 310 404 452 620 680 Totally enclosed 40 49 49 72 85 140 170 235 300 330 390 510 570 850 910
1 1.5 2 3 5 7.5
RDT basic unit, standard cond. fan RDT basic unit, quiet cond. fanb
Filter optionsdraw-thru section 30% pleated 65% cartridgestd. flow Med. flow High flow 95% cartridgestd. flow Med. flow High flow
10 15 20 25 30 40 50 60
Filter optionsblow-thru section (final filters) including liners in filter and discharge plenum 95% cartridgestd. flow Med. flow High flow Supply air fan assembly 27 diameter forward curvedLP 27 diameter forward curvedMP 27 diameter airfoil 30 diameter airfoil 33 diameter airfoil Condenser coil options Copper fins Coil guards 267 435 15 435 15 649 23 649 23 919 942 868 965 919 942 868 965 965 1452 965 1452 965 1452 1083 1509 1083 1509 1083 1509 1083 1509 1083 1509
75
a. Basic unit consists of energy recovery section, angular filter section with 2" throwaway filters, supply fan section without fan or motor, cooling section without coil, discharge plenum, and condensing unit (RPS only). For RPS 015C to 030C and RPS 018C to 030C, cooling section is incorporated in the supply fan section. b. Basic unit consists of energy recovery section, angular filter section with 2" throwaway filters, supply fan section without fan or motor, cooling section without coil, and condensing unit (RPS only). For RPS 015C to 030C and RPS 018C to 030C, cooling section is incorporated in the supply fan section. c. Add 200 lbs for the 12 wheel option.
60
Fan Motor Weights Table 51: RPS/RFS/RDT 045C to 075C or RAH 047C (lbs) (continued)
Unit size Components 045C 3-row, 8 Fpi 3-row, 10 Fpi 3-row, 12 Fpi 4-row, 8 Fpi 4-row, 10 Fpi 4-row, 12 Fpi 5-row, 8 Fpi 5-row, 10 Fpi 5-row, 12 Fpi 3-row, 8 Fpi 3-row, 10 Fpi 3-row, 12 Fpi 4-row, 8 Fpi 4-row, 10 Fpi 4-row, 12 Fpi 5-row, 8 Fpi 5-row, 10 Fpi 5-row, 12 Fpi 3-row, 8 Fpi 3-row, 10 Fpi 3-row, 12 Fpi 4-row, 8 Fpi 4-row, 10 Fpi 4-row, 12 Fpi 5-row, 8 Fpi 5-row, 10 Fpi 5-row, 12 Fpi 3-row, 8 Fpi 3-row, 10 Fpi 3-row, 12 Fpi 4-row, 8 Fpi 4-row, 10 Fpi 4-row, 12 Fpi 5-row, 8 Fpi 5-row, 10 Fpi 5-row, 12 Fpi Hot water coild 1-row 2-row Steam coild 1-row, 6 Fpi 331 331 331 331 331
d. Does not include weight of heating section.
RAH 047C 050C 370 395 419 445 478 510 518 559 600 1001 1030 1059 1135 1151 1166 1176 1224 1272 591 671 750 739 845 951 886 1019 1151 1262 1356 1450 1437 1562 1687 1611 1768 1924 373 449 060C 370 395 419 445 478 510 518 559 600 1001 1030 1059 1135 1151 1166 1176 1224 1272 591 671 750 739 845 951 886 1019 1151 1262 1356 1450 1437 1562 1687 1611 1768 1924 373 449 070C 370 395 419 445 478 510 518 559 600 1001 1030 1059 1135 1151 1166 1176 1224 1272 591 671 750 739 845 951 886 1019 1151 1262 1356 1450 1437 1562 1687 1611 1768 1924 373 449 075C 370 395 419 445 478 510 518 559 600 1001 1030 1059 1135 1151 1166 1176 1224 1272 591 671 750 739 845 951 886 1019 1151 1262 1356 1450 1437 1562 1687 1611 1768 1924 373 449
Evaporator coilsaluminum fins, standard airflow face area 370 395 419 445 478 510 518 559 600 591 671 750 739 845 951 886 1019 1151 373 449
61
Fan Motor Weights Table 51: RPS/RFS/RDT 045C to 075C or RAH 047C (lbs) (continued)
Unit size Components 045C 1-row, 12 Fpi 2-row, 6 Fpi Electric heatd 40 kW 60 kW 80 kW 100 kW 120 kW 160 kW 200kW 240 kW Gas furnaced 200, 250 MBh 320, 400 MBh 500, 640 MBh 650, 790 MBh 800, 1000 MBh Accessory items Variable frequency driveSAF Variable frequency driveRAF Sound attenuator Plenum options Burglar barsdischarge Burglar barsreturn Isolation dampersdischarge Isolation dampersreturn Blank or heating section 4-foot, unlined 6-foot, unlined Insulation linerse 2, 1.5 lbs., with solid liners: Weight per foot of unit length 25 25 25 25 25 574 915 574 915 574 915 574 915 574 915 53 73 85 112 53 73 85 112 53 73 85 112 53 73 85 112 53 73 85 112 150 100 150 100 150 100 Consult Factory 150 100 150 100 319 372 428 512 577 319 372 428 512 577 319 372 428 512 577 319 372 428 512 577 319 372 428 512 577 278 286 289 295 301 312 336 348 278 286 289 295 301 312 336 348 278 286 289 295 301 312 336 348 278 286 289 295 301 312 336 348 278 286 289 295 301 312 336 348 354 405 050C 354 405 RAH 047C 060C 354 405 070C 354 405 075C 354 405
a. Basic unit consists of energy recovery section, angular filter section with 2" throwaway filters, supply fan section without fan or motor, cooling section without coil, discharge plenum, and condensing unit (RPS only). For RPS 015C to 030C and RPS 018C to 030C, cooling section is incorporated in the supply fan section. b. Basic unit consists of energy recovery section, angular filter section with 2" throwaway filters, supply fan section without fan or motor, cooling section without coil, and condensing unit (RPS only). For RPS 015C to 030C and RPS 018C to 030C, cooling section is incorporated in the supply fan section. c. Add 200 lbs for the 12 wheel option. d. Does not include weight of heating section. e. Excluding condensing unit section and blank compartment.
62
Example of Additional Weights for RPS 030C Unit Component Basic unit w/economizer Economizer Lbs. 8,051 370 9 556 372 1237 214 185 552 11,546 ft 10 2 4.3 3.3 3.3 23 feet
Additional Weights
1 For return plenum with bottom opening, add 91 lbs. (sizes
30% efficiency filters 20" airfoil supply fan DX coil5-row 12 fpi, Aluminum fins Gas heat1000 MBh SAF motor20 hp RAF motor 15 hp Liners24 lbs/foot x 23 feet Liner calculations Section length
For curb length greater than 144 in., add 30 lbs. For curb length greater than 288 in., add 60 lbs. For curb length greater than 432 in., add 90 lbs. For curb length greater than 576 in., add 120 lbs.
5 For condenser section support rail (RPS/RDT only), add
139 lbs.
63
Heating and Cooling Unit(s) model [RPS] [RFS] [RDT]. Unit performance and electrical characteristics shall be per the job schedule.
B The complete unit shall be [ETL/MEA] [ETL-Canada]
shipment. The factory test shall include final balancing of the supply and exhaust fan assemblies, a refrigeration circuit run test, a unit control system operations checkout, [test and adjustment of the gas furnace], a unit refrigerant leak test and a final unit inspection.
F All units shall have decals and tags to indicate caution areas
listed. The burner and gas train for the unit furnace shall be [UL] [IRI/FIA] [FM] approved.
C All components included herein are designed,
manufactured and independently tested, rated and certified to meet the seismic compliance standards of the International Building Code. Components designated for use in systems that are life safety, toxic, high hazard, combustible or flammable shall meet the on line, anchorage and load path requirements for life safety as defined in IBC sections 1621.1.6, 1621.3.3,1707.7.2. and IBC Commentary, Volume II, section 1621.1.6, IBC notes pertaining to the release of hazardous material. All components used as part of a system other than the above shall meet as a minimum, all load path and anchorage standards for components as outlined in IBC section 1621.3.3 & 1707.7.2. All completed component assemblies shall be clearly labeled for field inspection. Seismic Compliance Labels shall include the manufacturer's identification, designation of certified models, definitive information describing the product's compliance characteristics, and the Independent Certifying Agency's name and report identification. In addition to all seismic requirements for IBC Certification listed elsewhere in the project specification, manufacturer's submittals shall include:
1 Certificate of Compliance from the Independent
and aid unit service. Unit nameplates shall be fixed to the main control panel door. Electrical wiring diagrams shall be attached to the control panels. Installation, operating and maintenance bulletins and start-up forms shall be supplied with each unit.
G Performance: All scheduled capacities and face areas are
minimum accepted values. All scheduled amps, kW, and hp are maximum accepted values that allow scheduled capacity to be met.
H Warranty: The manufacturer shall provide 12-month parts
only warranty. [The manufacturer will provided extended 48-month, parts only, warranty on the compressor.] Defective parts will be repaired or replaced during the warranty period at no charge. The warranty period shall commence at startup or six months after shipment, whichever occurs first.
Certifying Agency clearly indicating that components supplied on this project are included in the component manufacturer's Certificate of Compliance.
2 Clear installation instructions including all accessory
application and include a weatherproof cabinet. Units shall be of a modular design with factory installed access sections available to provide maximum design flexibility. Each unit shall be [completely factory assembled and shipped in one piece] [split at the condensing section] and/ or [split (size 36-75C) between the supply fan section and the heat section]. RPS and RDT packaged units shall be shipped fully charged with Refrigerant [22] [407C]. RFR/ RCS split systems and all units split between the evaporator and the condensing section are shipped with a nitrogen holding charge only.
64
doors and floor areas shall be provided with 22 gauge solid galvanized steel inner liners to protect insulation during service and maintenance. Insulation shall be a minimum of 1" thick, 3/4-lb. density neoprene coated glass fiber. Unit cabinet shall be designed to operate at total static pressures up to 5.5 inches w.g. Insulation on ceiling and end panels shall be secured with adhesive and mechanical fasteners. [Heavy gauge solid galvanized steel liners shall be provided throughout, allowing no exposed insulation within the air stream. All cabinet insulation, except floor panels, shall be a nominal 2" thick, 1-lb. density, R6.5, glass fiber.] [A combination of solid and perforated galvanized steel liners shall be provided throughout. Perforated liners to be used in the supply and return air plenums to provide improved sound attenuation. All cabinet insulation, except floor panels, shall be a nominal 2" thick, 1-lb. density, R6.5, glass fiber.] All floor panels shall include [double wall construction and include a nominal 2" thick, 1 lb. density, R6.5 glass fiber insulation.] [a minimum 1" thick, 3 lb. density, R4.2 glass fiber glass insulation.]
B Exterior surfaces shall be constructed of pre-painted
galvanized steel for aesthetics and long term durability. Paint finish to include a base primer with a high quality, polyester resin topcoat of a neutral beige color. Finished surface to withstand a minimum 750-hour salt spray test in
McQuay Cat 220
accordance with ASTM B117 standard for salt spray resistance. Service doors shall be provided on both sides of each section in order to provide user access to all unit components. Service doors shall be constructed of heavy gauge galvanized steel with a gauge, galvanized steel interior liner. All service doors shall be mounted on multiple, stainless steel hinges and shall be secured by a latch system that is operated by a single, flush-mounted handle. The latch system shall feature a staggered engagement for ease of operation. Removable panels, or doors secured by multiple, mechanical fasteners are not acceptable.
C The unit base frame shall be constructed of heavy-gauge
A single width, single inlet (SWSI) airfoil centrifugal return air fan shall be provided. The fan shall be Class II construction. The fan wheel shall be Class II construction and fabricated from heavy-gauge aluminum with fan blades continuously welded to the back plate and end rim. The fan shall be mounted using shafts and hubs with mating keyways. Exhaust fans are not acceptable.
F [The supply air fan and return air fan sections shall be
pre-painted galvanized steel. The unit base shall overhang the roof curb for positive water runoff and shall have a formed recess that seats on the roof curb gasket to provide a positive, weather tight seal. Lifting brackets shall be provided on the unit base with lifting holes to accept cable or chain hooks.
balanced at the factory, including a final trim balance, prior to shipment. All fan assemblies shall employ solid steel fan shafts. Heavy-duty pillow block type, self-aligning, grease lubricated ball bearings shall be used. Bearings shall be sized to provide an L-50 life at 200,000 hours. The entire fan assembly shall be isolated from the fan bulkhead and mounted on [rubber-in-shear isolators] [spring isolators] [spring isolators with seismic restraints]. [Fixed] [Adjustable] pitch V-belt drives with matching belts shall be provided. V-belt drives shall be selected at [the manufacturer's standard service factor] [1.5 times fan brake horsepower].
B Fan motors shall be heavy-duty 1800 rpm [open drip-proof
for the supply [and return] air fan. [Two independent drives, one per fan, shall be provided.] Each drive shall be factory installed downstream of the filters in a manner that the drive(s) are directly cooled by the filtered, mixed air stream. Drives shall meet UL Standard 95-5V and the variable frequency drive manufacturer shall have specifically approved them for plenum duty application. The completed unit assembly shall be listed by a recognized safety agency, such as ETL. Drives are to be accessible through a hinged door assembly complete with a single handle latch mechanism. Mounting arrangements that expose drives to high temperature, unfiltered ambient air is not acceptable.
B The unit manufacturer shall install all power and control
wiring. [A manual bypass contactor arrangement shall be provided. The bypass arrangement will allow fan operation at full design cfm, even if the drive has been removed for service]. [Line reactors shall be factory installed for each drive].
C The supply air fan drive output shall be controlled by the
(ODP)] [totally enclosed TEFC] type with grease lubricated ball bearings. [Motors shall be high efficiency and meet applicable EPACT requirements.] [Motors shall be premium efficiency.] Motors shall be mounted on an adjustable base that provides for proper alignment and belt tension adjustment.
C Airfoil supply fans
factory installed main unit control system and drive status and operating speed shall be monitored and displayed at the main unit control panel. [The supply and return/exhaust fan drive outputs shall be independently controlled in order to provide the control needed to maintain building pressure control. Supply and return/exhaust air fan drives that are slaved off of a common control output are not acceptable.]
D All drives shall be factory run tested prior to unit shipment.
Supply fan shall be double width, double inlet (DWDI) airfoil centrifugal fan. All fans shall be mounted using shafts and hubs with mating keyways. Fans shall be Class II type and fabricated from heavy-gauge aluminum. Fan blades shall be continuously welded to the back plate and end rim.
D Forward curved supply fans
ELECTRICAL
A Unit wiring shall comply with NEC requirements and with
Supply fan shall be double width, double inlet forward curved centrifugal fan. All fans shall be mounted using shafts and hubs with mating keyways. The forward curved fan wheel and housing shall be fabricated form galvanized steel and shall be [Class I] [Class II] construction to satisfy the specified application.
McQuay Cat 220
all applicable UL standards. All electrical components shall be UL recognized where applicable. All wiring and electrical components provided with unit shall be number and color-coded and labeled according to the electrical diagram provided for easy identification. The unit shall be provided with a factory wired weatherproof control panel. Unit shall have a [single] [dual] point power terminal block for main power connection. A terminal board shall be provided for low voltage control wiring. Branch short circuit protection, 115-volt control circuit transformer and
65
fuse, system switches, high temperature sensor, and a 115volt receptacle with a separate electrical connection shall also be provided with unit. Each compressor and condenser fan motor shall be furnished with contactors and inherent thermal overload protection. Supply and return fan motors shall have contactors and external overload protection. Knockouts shall be provided in the bottom of the main control panels for field wiring entrance. All 115600 voltage wire shall be protected from damage by raceways or conduit.
B [A factory installed and wired marine service light, with
Sockets shall be medium bi-pin, single click safety, twist lock type and are to constructed of a UVCresistant poly carbonate. Lamp shall be a high output, hot cathode, T8 diameter, medium bi-pin that produces UVGI of 254 nm. Each tube produces the specified output at 500 fpm and air temperatures of 55F135F.
3 A [single] [dual] non-fused disconnect switch[es] shall
switch and receptacle, shall be provided in the supply air and return/exhaust fan section. The separate, main unit service receptacle electrical circuit shall also power the light circuit.]
C [Part winding start shall be provided for the unit
be provided for disconnecting electrical power at the unit. [The second switch will service the condensing section.] Disconnect switches shall be mounted internally to the control panel and operated by an externally-mounted handle. Externally-mounted handle is designed to prohibit opening of the control panel door without the use of a service tool.
wired to the unit compressors. Power factor capacitors shall be selected to provide correction to a minimum of 0.90.]
E [Phase failure and under voltage protection on three-phase
motors shall be provided to prevent damage from single phasing, phase reversal, and low voltage conditions.]
F [Ground fault protection shall be provided to protect
installed in the [supply air opening] [supply and return air openings]. Smoke detectors to be ionization type, which responds to invisible products of combustion without requiring the sensing of heat, flame or visible smoke. Upon sensing smoke, the unit shall provide a control output for use by building management system.
2 Unit to have factory-mounted UV lights located on the
blow-through configuration, downstream of the supply air fan. A factory-tested diffuser shall be used in order to provide air distribution across the cooling coil. A blowthrough coil is specified to minimize the impact of fan motor heat.] [The cooling coil section shall be installed in a draw through configuration, upstream of the supply air fan.] The coil section shall be complete with factory piped cooling coil and sloped drain pan. Hinged access doors on both sides of the section shall provide convenient access to the cooling coil and drain pan for inspection and cleaning. Submittals must demonstrate that scheduled unit leaving air temperature (LAT) is met, that fan and motor heat temperature rise (TR) have been considered, and scheduled entering air temperature (EAT) equals mixed air temperature (MAT). Draw-through coolingScheduled EAT equals cooling coil EAT and scheduled unit LAT equals cooling coil LAT plus TR. Blow-through coolingCooling coil EAT equals scheduled EAT plus TR and scheduled unit LAT equals cooling coil LAT. Direct expansion (DX) cooling coils shall be fabricated of seamless 1/2" diameter high efficiency copper tubing that is mechanically expanded into high efficiency [aluminum] [copper] plate fins. Coils shall be a multi-row, staggered tube design with a minimum of [3] [4] [5] rows and a maximum of [8] [10] [12] fins per inch. All units shall have two independent refrigerant circuits and shall use an interlaced coil circuiting that keeps the full coil face active at all load conditions. All coils shall be factory leak tested with high pressure air under water.
leaving air side of the cooling coil. Unit to have view port to allow for visual indication of operation through UV resistant glass. Unit to have door interlocks on each door accessing UV light. Interlock to kill power to UV light when door is opened. Lamp and fixture to consist of a housing, power source, lamp sockets, and lamp. All components are to be constructed to withstand typical HVAC environments and are UL/C-UL listed. Housings are to be constructed of type 304 stainless steel and are to be equipped with both male and female power plugs with one type at each end to facilitate simple fixture-tofixture plug-in for AC power. Power source shall be an electric, rapid-type with overload protections and is to be designed to maximize radiance and reliability at UL/C-UL listed temperatures of 55F135F. Power source will include RF and EMI suppression.
66
sloped drain pan shall be provided with the cooling coil. The drain pan shall extend beyond the leaving side of the coil and underneath the cooling coil connections. The drain pan shall have a minimum slope of 1/8" per foot to provide positive draining. The drain pan shall be connected to a threaded drain connection extending through the unit base. Units with stacked cooling coils shall be provided with a secondary drain pan piped to the primary drain pan. Hot Water Heating Option
C A [1] [2] row hot water heating coil shall be factory
[A factory installed, non-averaging type freezestat shall be factory installed to provide some protection against coil freeze-up.] Coils shall be factory leak tested with high pressure air under water. Gas Heating Option
E A natural gas fired furnace shall be installed in the unit heat
installed in the unit heat section. Coils shall be fabricated of seamless 5/8" diameter copper tubing that is mechanically expanded into high efficiency HI-F rippled and corrugated aluminum plate fins. All coil vents and drains shall be factory installed. The hot water heat section shall be installed downstream of the supply air fan. A factory-tested diffuser shall be used in order to provide air distribution across the coil. Hinged access doors shall provide convenient access to the coil and valve for inspection and cleaning. [A factory installed three-way modulating control valve and spring return valve actuator shall provide control of the hot water coil. The valve actuator shall be controlled by the factory installed main unit control system] [[Ethylene glycol] [propylene glycol] shall be added to the hot water circuit to protect against coil freeze-up.] [A factory installed, non-averaging type freezestat shall be factory installed to provide some protection against coil freeze-up.] Coils shall be factory leak tested with high pressure air under water. Steam Heating Option
D A [1 row, 6 fin per inch] [1 row, 12 fin per inch] [2 row, 6
section. The heat exchanger shall include a type 321 stainless steel cylindrical primary combustion chamber, a type 321 stainless steel header, type 321 stainless steel] secondary tubes and type 321stainless steel turbulators. Carbon and aluminized steel heat exchanger surfaces are not acceptable. The heat exchanger shall have a condensate drain. Clean out of the primary heat exchanger and secondary tubes shall be accomplished without removing casing panels or passing soot through the supply air passages. The furnace section shall be positioned downstream of the supply air fan. [The furnace will be supplied with a modulating forced draft burner. The burner shall be controlled for low fire start. The burner shall be capable of continuous modulation between 33% and100% of rated capacity and shall operate efficiently at all firing rates.] [The furnace shall be supplied with a McQuay SuperMod forced draft burner capable of continuous modulation between 5% and 100% of rated capacity, without steps. The burner shall operate efficiently at all firing rates. The burner shall have proven open damper low-high-low pre-purge cycle, and proven low fire start. The combustion air control damper shall be in the closed position during the off cycle to reduce losses.] The burner shall be specifically designed to burn natural gas and shall include a microprocessor based flame safeguard control, combustion air proving switch, prepurge timer and spark ignition. The gas train shall include redundant gas valves, [maximum 0.5psi pressure regulator] [23psi high pressure regulator] [510psi high pressure regulator], shutoff cock, pilot gas valve, pilot pressure regulator, and pilot cock. The burner shall be rated for operation and full modulation capability at inlet gas pressures down to [7.0. W.C. (models 200650)] [8.0 in. W.C. (models 790, 800] [9.0 in. W.C. (model 100)]. The gas burner shall be controlled by the factory installed main unit control system. The burner shall be fired, tested and adjusted at the factory. Final adjustments shall be made in the field at initial startup by a qualified service technician to verify that installation and operation of the burner is according to specifications.
fin per inch] fin per inch team heating coil shall be factory installed in the unit heat section. Coils shall be fabricated of seamless 5/8" diameter copper tubing that is mechanically expanded into high efficiency HI-F rippled and corrugated aluminum plate fins. Steam coils shall be of the jet distributing type. The steam heat section shall be installed downstream (RFS/RPS) of the supply air fan. A factorytested diffuser shall be used in order to provide air distribution across the coil. Hinged access doors shall provide convenient access to the coil and valve for inspection and cleaning. [A factory installed two-way modulating control valve and spring return valve actuator shall provide control of the steam coil. The valve actuator shall be controlled by the factory installed main unit control system]
67
unit heat section. Heating coils shall be constructed of a low watt density, high nickel-chromium alloy resistance wire, mechanically stacked and heli-arc welded to corrosion resistant terminals. A corrosion resistant heavy gauge rack shall support the elements. Safety controls shall include automatic reset high limit control for each heater element with manual reset backup line break protection in each heater element branch circuit (Note: Manual reset not provided when ETL-Canada label is provided). Heating element branch circuits shall be individually fused to maximum of 48 Amps per NEC requirements. The electric heat section shall be positioned downstream of the supply air fan. The electric heat elements shall be controlled by the factory installed main unit control system.
1, AmericanAirFilter cartridge filters shall be provided. 2" panel, 30% efficient pre-filters shall be included. Cartridge filters shall consist of filter media permanently attached to a metal frame and shall slide into a gasketed, extruded aluminum rack contained within the unit. The filter rack shall have secondary gasketed, hinged end panels to insure proper sealing. Filters shall be accessible from both sides of the filter section.]
G [Filters shall be provided with INTERSEPT
antimicrobial treatment.]
FILTERS
Draw-through Filters
A Unit shall be provided with a draw-through filter section.
The filter section shall be supplied complete with the filter rack as an integral part of the unit. The draw-through filter section shall be provided with [panel] [cartridge] filters.
B 2" thick AmericanAirFilter 30% efficient pleated panel
Damper blades shall be fully gasketed and side sealed and arranged horizontally in the hood. Damper leakage shall be less than 0.2% at 1.5 inches static pressure differential. Leakage rate to be tested in accordance with AMCA Standard 500. Damper blades shall be operated from multiple sets of linkages mounted on the leaving face of the dampers. [Control of the dampers shall be from a factory installed, two-position actuator.]
B Unit shall be provided with [a modulating outdoor air
filters shall be provided. Filters shall be frame mounted and shall slide into galvanized steel racks contained within the unit. Filters shall be installed in an angular arrangement to maximize filter area and minimize filter face velocity. Filters shall be accessible from both sides of the filter section.
C [12" deep [60-65%] [90-95%] efficient, UL Std. 900, Class
1, AmericanAirFilter cartridge filters shall be provided. 2" panel, 30% efficient pre-filters shall be included. Cartridge filters shall consist of filter media permanently attached to a metal frame and shall slide into a gasketed, extruded aluminum rack contained within the unit. The filter rack shall have secondary gasketed, hinged end panels to insure proper sealing. Filters shall be accessible from both sides of the filter section.]
D [[30% efficient pleated] [60-65% efficient cartridge] [90
economizer section with] an ARI Certified energy recovery wheel. [The economizer section shall include outdoor, return and return exhaust air control and bypass dampers and damper actuators shall be included that automatically bypass outdoor air around the wheel during economizer operation.] Outdoor air shall enter at the back of the section through a factory installed hood capable of handling 100% outdoor air. The outdoor air hood shall be factory installed and constructed from galvanized steel finished with the same prepainted finish as the main unit. The hood shall include a bird screen to prevent infiltration of foreign materials and a rain lip to drain water away from the entering air stream. Return air shall enter through the bottom of the unit. The entire section shall be double wall construction.
C The enthalpy wheel shall be constructed of corrugated
95% efficient cartridge] filters shall be provided with INTERSEPT antimicrobial treatment.] Final Filters Option
E Final FiltersUnit shall be provided with a final filter
section downstream of the supply fan. Unit to have 40" of unit length between the fan discharge and the final filters to allow for proper air distribution. The final filter section shall be supplied complete with the filter rack as an integral part of the unit. The final filter section shall be provided with cartridge filters.
synthetic fibrous media, with a desiccant intimately bound and uniformly and permanently dispersed throughout the matrix structure of the media. Rotors with desiccants coated, bonded, or synthesized onto the media are not acceptable due to delamination or erosion of the desiccant material. Media shall be synthetic to provide corrosion resistance and resistance against attack from laboratory chemicals present in pharmaceutical, hospital, etc. environments as well as attack from external outdoor air conditions. Coated aluminum is not acceptable. Face flatness of the wheel shall be maximized (+/- 0.032 in) in order to minimize wear on inner seal surfaces and to minimize cross leakage. Rotor shall be constructed of alternating layers of flat and corrugated media. Wheel
68
layers should be uniform in construction forming uniform aperture sizes for airflow. Wheel construction shall be fluted or formed honeycomb geometry so as to eliminate internal wheel bypass. Wheel layers that can be separated or spread apart by airflow are unacceptable due to the possibility of channeling, internal bypass or leakage, and performance degradation. The media shall be in accordance with NFPA or UL guidelines. The desiccant material shall be a molecular sieve, and specifically a 4A or smaller molecular sieve to minimize cross contamination. The wheel frames shall consist of evenly spaced steel spokes, galvanized steel outer band and rigid center hub. The wheel construction should allow for post fabrication wheel alignment. The wheel seals shall be brush seals, neoprene bulb seals or equivalent. Seals should be easily adjustable. Cassettes shall be fabricated of heavy duty reinforced galvanized steel. Cassettes shall have a built in adjustable purge section minimizing cross contamination of supply air. Bearings shall be inboard, zero maintenance, permanently sealed roller bearings, or alternatively, external flanged bearings. Drive systems shall consist of fractional horsepower A.C. drive motors with multilink drive belts. The wheel capacity, air pressure drop, and efficiency shall be tested in accordance with NFPA or UL guidelines and shall be UL recognized or equivalent. The wheel capacity, air pressure drop and effectiveness shall be ARI certified by ARI and its testing agencies. Alternative independent performance testing must be pre-approved to be accepted. [Wheel shall be provided with variable speed control for frost protection].
D The wheel recovers energy from the factory-supplied
both sides of the section and shall have the same construction features as the rest of the unit. Blank Compartment
B An insulated, blank compartment shall be provided. The
section shall be located after the discharge plenum and will be out of the air stream. The section shall be complete with insulation, double wall construction [and a service light].
manufacturer as an integral part of the unit to attenuate fan noise at the source. Variable range of splitter thickness and air passages provided to optimize acoustic performance and energy conservation. The attenuators shall have perforated double-wall construction and be located downstream of the supply fan. Hinged access doors shall be provided on both sides of the section and shall have the same construction as the rest of the unit. [Sound attenuator shall have Tedlar coating for moisture protection]. Combustion rating for the silencer acoustic fill shall not be greater than the following UL fire hazard classification: Flame Spread.15 Fuel Contributed.0 Smoke Developed0 Tested in accordance with UL Test Procedure 723.
B The attenuator rating shall be determined using the duct-to-
return/exhaust section and includes an SWSI airfoil fan and motor in accordance with construction already specified. Gravity relief dampers and fold out exhaust hood shall be provided. All necessary exhaust fan motor starters, branch short circuit protection, and wiring and controls shall be provided. Two inch, 30% pleated filters shall be provided in both air inlets to protect the wheel from dust and dirt in both the outdoor and return/exhaust air paths. Dampers to be McQuay UltraSeal low leak type, and shall be provided on outdoor or return dampers. Damper blades shall be fully gasketed and side sealed and arranged horizontally in the hood. Damper leakage shall be less than 0.2% at 1.5 inches static pressure differential. Leakage rate to be tested in accordance with AMCA Standard 500. Damper blades shall be operated from multiple sets of linkages mounted on the leaving face of the dampers.
reverberant room test method which provides for airflow in both directions through the attenuator in accordance with latest version of ASTM specification E-477. Insertion Loss Ratings (ILR) shall be:
Octave band at center frequency (Hz) 63 ILR (no Tedlar) ILR (Tedlar coating) 7 6 125 9 10 250 22 20 500 1000 2000 4000 8000 28 16 29 14 29 18 18 13 12 12
insertion loss, self-generated sound power levels, and aerodynamic performance for reverse and forward flow test conditions to the design professional in writing as least 10 days prior to the bid.
located [upstream] [downstream] [upstream and downstream] of the supply air fan, as shown on the unit drawing. Access sections shall have hinged access doors on
plenum section shall be lined with a perforated acoustic liner to enhance sound attenuation.] The plenum section shall have a [bottom] [side] [front (RFR only)] discharge opening.
B A combination burglar bar/safety grate shall be provided in
the [bottom return air opening] [bottom supply air opening] [bottom return and supply air openings]. Burglar bar/safety
69
grate shall be made of 3/4" diameter ground and polished steel shaft welded to a galvanized steel frame.
C Isolation dampers shall be provided in the [bottom return
air opening] [bottom supply air opening] [bottom return and supply air openings]. [A two-position actuator shall be provided to close the dampers when the fans are not running.]
Each refrigerant circuit shall include a subcooling circuit to provide 15 degrees of liquid subcooling. Each circuit shall be dehydrated and factory charged with Refrigerant [22] [407C] and oil.
F Refrigeration capacity control shall be accomplished by
staging of the unit's multiple compressors. To maintain desired temperature control, the unit shall have a minimum of [three] [four] [six] steps of capacity control.
G All compressor capacity control staging shall be controlled
bottom to provide access and to allow airflow through the coils. Condenser coils shall be multi-row and fabricated from 3/8" high efficiency rifled copper tubing mechanically bonded to high efficiency aluminum fins. Each condenser coil shall be factory leak tested with high-pressure air under water. [Condenser coil guards shall provide protection from incidental contact to coil fins. Coil guards to be constructed of cross wire welded steel with PVC coating.]
B Condenser fans shall be direct drive, propeller type
by the factory installed main unit control system. Hot Gas Bypass
I Hot gas bypass control shall be factory installed on one
[both] refrigerant circuits. Hot gas bypass control shall include a modulating hot gas bypass control valve, solenoid valve, all associated piping and be automatically operated by the units microprocessor control.
designed for low tip speed and vertical air discharge. [Condenser fan rpm shall be 1140 rpm maximum.] [Condenser fans shall have airfoil blades, discharge shrouds for quiet operation, and shall run at 850 maximum rpm.] Fan blades shall be constructed of steel and riveted to a steel center hub. Condenser fan motors shall be heavyduty, inherently protected, three-phase, non-reversing type with permanently lubricated ball bearing and integral rain shield.
C Each circuit shall have fan cycling of at least one condenser
ROOF CURB
A A prefabricated 12-gauge galvanized steel, mounting curb,
fan to maintain positive head pressure. An ambient thermostat shall prevent the refrigeration system from operating below 45F. [SpeedTrol condenser fan speed control shall be added to the last fan off on each refrigeration circuit to provide cooling operation to ambient temperatures down to 0F. Fan speed control shall be field adjustable (size 36-75C only).]
D Each unit shall have multiple, heavy-duty Copeland scroll
designed and manufactured by the unit manufacturer, shall be provided for field assembly on the roof decking prior to unit shipment. The roof curb shall be a full perimeter type with complete perimeter support of the air handling section and rail support of the condensing section. Supply and return opening duct frames shall be provided as part of the curb structure allowing duct connections to be made directly to the curb prior to unit arrival. The curb shall be a minimum of 16" high and include a nominal 2" x 4" wood nailing strip. Gasket shall be provided for field mounting between the unit base and roof curb.
CONTROLS
A Each unit shall be equipped with a complete MicroTech II
compressors. Each compressor shall be complete with gauge ports, crankcase heater, sight-glass, anti-slug protection, motor overload protection and a time delay to prevent short cycling and simultaneous starting of compressors following a power failure. Compressors shall be isolated with resilient rubber isolators to decrease noise transmission.
E Each unit shall have two independent refrigeration circuits.
Each circuit shall be complete with a liquid line solenoid valve, low pressure control, filter-drier, liquid moisture indicator/sight-glass, thermal expansion valve, liquid line shutoff valve with charging port, discharge line shutoff valve, a manual reset high pressure safety switch, high pressure relief device and pump down switch. The thermal expansion valve shall be capable of modulation from 100% to 25% of its rated capacity. Sight-glasses shall be accessible for viewing without disrupting unit operation.
microprocessor based control system. The unit control system shall include all required temperature and pressure sensors, input/output boards, main microprocessor and operator interface. The unit control system shall perform all unit control functions including scheduling,], unit diagnostics and safeties. Control sequences shall include [constant air volume, zone temperature control (CAV-ZTC)] [constant air volume, discharge temperature control (CAV-DTC)] [variable air volume, cooling only discharge temperature control (VAV-DTC)] [variable air volume, cooling/modulating heating discharge temperature control (VAV-DTC)] [duct static pressure control], [supply/ return air fan tracking control] and [building static pressure control. All boards shall be individually replaceable for ease of service. All microprocessors, boards, and sensors shall be factory mounted, wired and tested.
B The microprocessor shall be a stand-alone DDC controller
70
remote PC or master control panel. The microprocessor shall maintain existing set points and operate stand alone if the unit loses either direct connect or network communications. The microprocessor memory shall be protected from voltage fluctuations as well as any extended power failures. All factory and user set schedules and control points shall be maintained in nonvolatile memory. No settings shall be lost, even during extended power shutdowns.
C The main microprocessor shall support an RS-232 direct
provided. A unit-mounted switch brings either the unitmounted or remote-mounted UI into control. The control contractor is responsible for wiring between the unit and the remote UI. The maximum wiring distance to the remote UI is 1200 feet. Optical isolation shall protect the main unit controller from remote UI wiring problems. The remote UI shall be provided with the same keypad/display and have identical functionality to the unit-mounted UI.]
K The display shall provide the following information as
connection to a product service tool or a modem. A [BACnet ethernet] [BACnet MSTP] [LonTalk] communications port shall be provided for direct communication into the BAS network.
D All digital inputs and outputs shall be protected against
damage from transients or wrong voltages. Each digital input and digital output shall be equipped with an LED for ease of service. All field wiring shall be terminated at a separate, clearly marked terminal strip.
E The microprocessor memory shall be protected from all
voltage fluctuations as well as any extended power failures. The microprocessor shall support an RS-232 direct connect from an IBM PC or 100% true compatible using MicroTech software. The microprocessor shall maintain existing set points and operate stand alone if the rooftop loses either direct connect or network communications.
F The microprocessor shall have a built-in time schedule. The
schedule shall be programmable from the unit keypad interface. The schedule shall be maintained in nonvolatile memory to insure that it is not lost during a power failure. There shall be one start/stop per day and a separate holiday schedule. The controller shall accept up to sixteen holidays each with up to a 5-day duration. Each unit shall also have the ability to accept a time schedule via BAS network communications.
G If the unit is to be programmed with a night setback or
setup function, an optional space sensor shall be provided. Space sensors shall be available to support field selectable features. Sensor options shall include:
1 Zone sensor with tenant override switch. 2 #1 above plus a heating and cooling set point
4 lines. The character font shall be a 5 8 dot matrix. The display shall be a supertwist liquid crystal display (LCD) with black characters on yellow background providing high visibility. The display form shall be in plain English coded formats. Lookup tables are not acceptable
I The keypad shall be equipped with 8 individual touch-
based on one of the following: Return air temperature, outdoor air temperature, space temperature, airflow, or external (1-5 VDC) signal
9 Reset schedule temperature 10 High supply, low supply, and high return air
sensitive membrane key switches. All control settings shall be password protected from changes by unauthorized personnel.
71
Engineering Guide Specification 15 Return fan tracking (VaneTrol) settings that include 1 Minimum outdoor airflow reset based on DesignFlow
direct OA volume measurement, percent of cfm capacity, and fixed outdoor damper position
2 Economizer changeover based on enthalpy, dry bulb or
(1-5 VFD) percent of cfm capacity, and fixed outdoor damper position
17 Minimum outdoor airflow reset based on DesignFlow
network signal
3 Current time and date 4 Occupied/unoccupied time schedules with allowances
direct OA volume measurement, percent of cfm capacity, and fixed outdoor damper position
18 Economizer changeover based on enthalpy, dry bulb or
network signal
19 Current time and date 20 Occupied/unoccupied time schedules with allowances
(all time delays), timers fast (all time delays 20 seconds), and normal
O Open Communications ProtocolThe unit control system
(all time delays), timers fast (all time delays 20 seconds), and normal
M Open Communications Protocol-The unit control system
shall have the ability to communicate to an independent Building Management System (BMS) through a direct [BACnet ethernet] [BACnet MSTP] [LonTalk] communication connection. The independent BMS system shall have access to [quantity from specification] "read only' variables and [quantity from specification] "read and write" variables. Communications shall not require field mounting of any additional sensors or devices at the unit. [The communications protocol shall be LONMARK 3.3 certified under the [Discharge Air] [Space Comfort] functional profiles.]
1 The BMS system shall be capable of interacting with the
shall have the ability to communicate to an independent Building Management System (BMS) through a direct [BACnet ethernet] [BACnet MSTP] [LonTalk] communication connection. The independent BMS system shall have access to [quantity from specification] read only variables and [quantity from specification] read & and write variables. Communications shall not require field mounting of any additional sensors or devices at the unit. [The communications protocol shall be LONMARK 3.3 certified under the [Discharge Air] [Space Comfort] functional profiles.] The BMS system shall be capable of interacting with the individual rooftop controllers in the following ways:
1 Monitor controller inputs, outputs, set points,
CAV-DTC units)
7 Set the representative zone temperature (CAV-ZTC
units)
P It will be the responsibility of the Systems Integrating
Contractor to integrate the rooftop data into the BMS control logic and interface stations.
CAV-DTC units)
8 Set the representative zone temperature (CAV-ZTC
EXECUTION
Installation Install in accordance with manufacturers instructions.
units)
N It will be the responsibility of the Systems Integrating
Contractor to integrate the rooftop data into the BMS control logic and interface stations.
72
McQuay Training and Development Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority. For training information on all McQuay HVAC products, please visit us at www.mcquay.com and click on training, or call 540-248-9646 and ask for the Training Department.
Warranty All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local McQuay Representative, go to www.mcquay.com.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
11/06