ELECTRICAL APPARATUS - PROGRAMMABLE LOGIC CONTROLLER: Provide one (1) complete Programmable Logic Controller (P.L.C.

) control system as described herein. The system shall employ industry standard Programmable Logic Controllers as described herein. The system shall be completely factory integrated and tested. The telemetry system shall be as manufactured by Engineered Fluid, Inc., Allen Bradley Series. SCOPE: The system shall consist of the following sites: 1. Booster Pump Station. BASIS FOR DESIGN This equipment specification and related documents represent a design based on the Allen-Bradley Programmable Logic Controllers. Communications, interface, input/output and other peripheral devices have been proven to be 100% compatible with Allen-Bradley equipment. No other equipment is acceptable unless the "Prebid Submittal" requirements of this specification are strictly adhered to and the Engineer provides written notification of alternate system approval in writing prior to the bid date. COMPLETE SYSTEM RESPONSIBILITY The System Supplier shall be the System Integrator and will have complete responsibility for the Station P.L.C. Control System and Related Control Functions. Specifically, this shall include identifying all electrical, mechanical and plumbing schematics and wiring inter-connect diagrams, providing instrument installation details, preparing input/output listings, writing software, performing software and hardware integration, installation in the station at the factory, debugging, calibrating and tuning the various components and subsystems and providing training and warranty services. elsewhere in this contract ) UL LISTING REQUIREMENT The system integrator shall produce panels that fully comply with Underwriters Laboratory Standard for Industrial Control Panels # 508.

All panels shall be UL 508 listed. The UL 508 "sticker" shall be clearly displayed in the appropriate location within the panel. The UL 508 listing shall be in the name of the equipment manufacturer. Third party substitutions of UL 508 listed equipment shall be strictly prohibited. SYSTEM INTEGRATOR FACILITY & STAFF: The system integrator shall have on staff no less than Four (4) full time Control System Engineers who are dedicated to the development of P.L.C. programs, SCADA software, Instrumentation configuration and control logic development. The system integrator shall have no less than Three (3) electrical engineers on staff dedicated to the development of panel wiring diagrams, panel layouts and general electrical design. The system Integrator shall have a field service department with no less than 5 fully equipped, trained and competent field service technicians able to work on any and all devices provided with this system. The system integrator shall have been in the business of providing telemetry, control and SCADA systems to the water production and water distribution market for no less than 10 years. The System Integrator shall submit a list of all personnel with title, job function, years with the company, years in this field and educational achievements with the submittal. Companies that do not meet the above requirements will not be approved. FACTORY ACCEPTANCE TEST The system manufacturer shall completely demonstrate to the Owner and, if the Owner desires, the Owner's engineer the operation of the equipment and logic built for this project. This demonstration shall be performed at the system manufacturer's facility at which the system was engineered, assembled and programmed. The Factory Acceptance Test shall consist of the following: 1. Use of panels and instrumentation for this project. Off- the-shelf or stock item substitutions are not allowed. System communications will use the radio or phone modem installed in the panels. Hardwired communications around the system's communication equipment will not be allowed.

2.

3.

System logic shall be tested in a methodical step by step manner. The system's Operation Description in this specification will serve as the basis for the system logic demonstration.

The system manufacturer shall provide for transportation, lodging and meals for the Owner and the Owner's chosen attendee. The Factory Acceptance Test shall be at least one 8-hour day in length. GENERAL EQUIPMENT SPECIFICATIONS A. Enclosures: Enclosures shall be corrosion resistant NEMA 4 for outdoor locations; NEMA Type 1 for indoor locations. Enclosure shall be fabricated from a minimum of 14 gauge cold rolled steel with a baked enamel finish in the manufacturer's standard color. Units shall include a single gasket front door. Hinges, locking hasp and door clamping hardware shall be included. B. Incoming Power Requirements & UPS: Controls shall operate from a source of 120 volts, 1 phase, 60 Hz. Each panel shall come equipped with an uninterruptable power supply (UPS). The UPS shall condition the power as well as provide 500 VA of power during outages. A 15 amp control power circuit breaker shall be employed as both a method of equipment protection and as a means of power disconnection. The circuit breaker shall be a single pole, thermal, magnetic type with a 10,000 Amp interrupt rating. The circuit breaker shall be UL listed. C. Freeze Protection: A freeze protective heater and thermostat shall also be provided at those outdoor locations containing water. D. Power Supplies: All DC power supplies required for operation shall be provided. Units shall provide sufficient voltage regulation and ripple control to assure powered components can operate within their required tolerances. E. Transient Voltage Surge Suppression (TVSS) - Data

Communications and Signal Wiring: The system manufacturer shall provide transient voltage and surge suppression for all PLC data communication devices whenever the communications cable is located outside the building in which the panel resides. This also applies to all outdoor panels with communications cables exiting the PLC panel enclosure. The TVSS unit shall be UL 497B listed. The TVSS unit shall have a maximum DC operating voltage of 9.6 VDC, a clamping voltage of 81V, and an 8 x 20 US surge current rating of 1000 amps. The unit shall be approved for use by AllenBradley Company on the Allen-Bradley Data Highway communications products. Transient voltage and surge suppression shall also be provided for 10-32 VDC instrumentation signal systems. The TVSS units shall be employed when the signal cable extends beyond the boundaries of the building in which the PLC panel is located. The TVSS unit shall be UL 497B listed. The TVSS unit shall have a maximum operating voltage of 32 VDC, a clamping voltage of 100V, and an 8 x 20 US surge current capability of 1000 amps. TVSS units must be as manufactured by Leviton, Inc., of Little Neck, New York, Model 3803-485/DHP for PLC communications and Model 3420-009/035 for 10-32 VDC signal wiring, without exception. F. Wiring Requirements: All wiring shall be in complete conformance with the National Electrical Code, state, local and NEMA electrical standards. All incoming and outgoing wires shall be connected to numbered terminal blocks and all wiring neatly tied and fastened to chassis as required. G. Remote Diagnostics System: This system shall be equipped with a remote diagnostics modem. This system shall use a standard 2 or 4 wire telephone line capable of DTMF dialing and data rates of 19.2 KBaud. This system shall be integrated with the PLC and shall consist of a data modem, telephone line, transient voltage surge suppressor, and all required configuration changes. This system shall allow engineering and service personnel the ability to monitor station performance, download PLC programs to new PLC processors and modify

existing PLC programs from the manufacturer's place of business. H. NETWORK DATA LINE SURGE SUPPRESSORS: Provide transient surge suppressors for all leased telephone line, and Ethernet connections that are included as a part of this system. Unit shall have a connection capabilities for RJ45, 100 BASE-T, 10 BASET, Token Ring, and RS-422 connections. The unit shall have a nominal clamping voltage of 7.5 volts and a Peak Pulse Current rating of 750 amperes. Unit shall be as manufactured by Tripp Lite, Inc., Model DNET-1. I. TELEPHONE LINE SURGE SUPPRESSORS: Provide the following for all dial-up connected to data modems or automated alarm dialing equipment that are included as a part of this system. Unit shall have a connection capabilities for RJ11 or RJ45. The unit shall have a nominal clamping voltage of 260 volts and a Peak Pulse Current rating of 1020 amperes. Unit(s) shall be as manufactured by Tripp Lite, Inc., Model DTEL2. PROGRAMMABLE LOGIC CONTROLLERS PROGRAMMABLE LOGIC CONTROLLER (PLC) - MODULAR: Provide microprocessor-based Programmable Logic Controllers (PLC) as detailed in this specification and on the applicable plan sheets. The PLC shall be capable of use in a stand-alone configuration and also be capable of being networked into a larger system. It shall be specifically suitable for use in a telemetry system as an intelligent remote telemetry unit. The PLC shall be programmable in standard ladder logic. The PLC shall be of modular design with a common plug-in "rack" in which the CPU and I/O cards are placed. The racks shall be available in 4, 7, 10 & 13 slot sizes. The system shall be capable to add racks in order to add I/O cards. The PLC Central Processing Unit (CPU) shall be programmable in standard ladder logic. The CPU shall have a minimum of 12,000 bytes of RAM memory and also include a non-volatile Electrically Erasable Programmable Read Only Memory (EEPROM) unit that shall store the program and setpoints.

The PLC CPU shall have the capability to have "On-Line" programming modifications made. The PLC shall have integral to it at least two (2) communication ports, one (1) of which shall be capable of RS-232 (DF-1) communications to serial devices such as modems and the other shall be used for connection to local DH-485 network communications or to accessories communicating with DH-485. The communications operations shall include the capability of report by exception polling. There shall be standard cards available that can be placed in the rack in order to provide additional communication ports as required. The PLC and I/O cards shall all be U.L. listed. I/O cards shall be interchangeable in any slot in the rack. The quantity and type of I/O cards required for this project are detailed in this specification and plans. It shall be the responsibility of the telemetry system manufacturer to insure that at least 20% spare of each type of I/O is provided. The following describes the requirements for each type of I/O card: 1. Discrete Input Cards: Discrete input cards shall be available in 4, 8 and 16 channel configurations. The cards shall accept 20-48 VDC, 100-240 VAC signals. The cards shall have easily visible LED indicators showing the status of each input channel. (LED ON = INPUT PRESENT). Cards shall have a removable terminal strip. 2. Relay Output Cards: Relay output cards shall be available in 4, 8 and 16 channel versions. Cards shall be rated for 5-265 VAC and 5-125 VDC voltages. The cards shall have an LED indication for each channel showing the relay is closed. Cards shall have a removable terminal strip. 3. Analog Input Cards: Analog input cards shall be available in channel configurations. The cards shall be input signals between -20 mA and 20 mA. shall employ a 16 bit twos compliment type digital conversion chip. Cards shall have a terminal strip. 4. Analog Output Card: 4 and 8 rated for The cards analog to removable

Analog output cards shall be available in 2 (combination 2 input and 2 output) and 4 output channel configurations. Outputs shall be either 0-10 VDC or 0-21 mA DC. The output digital to analog converter shall have 16 bit resolution. The cards shall source the loop with 24 VDC. The cards shall have a removable terminal strip. THE PLC, INCLUDING ALL CARDS AND ACCESSORIES AS DETAILED IN THIS SPECIFICATION, SHALL BE AS MANUFACTURED BY ALLENBRADLEY CO., OF 1201 SOUTH SECOND STREET, MILWAUKEE, WI 53204, MODEL SLC 5/03, WITH 1746 SERIES I/O.

PROGRAMMABLE LOGIC CONTROLLER - PROGRAMMING SOFTWARE: All PLC equipment supplied on this project shall be programmable in standard ladder logic. The ladder logic development and configuration software shall be the same for all PLC's listed in this specification. Equipment requiring separate program development and configuration software for each product is not acceptable. The software program shall be Windows based and be Microsoft certified for use with Windows NT, Windows 95, Windows 98 and future versions. The software shall be able to develop the ladder logic programs, provide equipment configurations, diagnostics for both equipment and software, upload programs, download programs, and edit programs "on-line" where applicable. THE SOFTWARE SHALL BE AS MANUFACTURED BY ROCKWELL SOFTWARE, A DIVISION OF ROCKWELL AUTOMATION, MODEL RS-LOGIX. ELECTRICAL APPARATUS OPERATOR INTERFACE PANELVIEWTM 600 TOUCH SCREEN

The PLC control system shall include a front panel mounted touch screen display for operator interface. The display shall have a 4.5" x 3.4" screen with 320 x 234 pixel resolution using 16 colors. The screen shall have 128 touch cells. Unit shall have 240K of flash memory. Unit shall have a battery backed real time clock.

THE TOUCH SCREEN OPERATOR INTERFACE SHALL BE AS MANUFACTURED BY ALLEN-BRADLEY CO., MILWAUKEE, WI 53204, MODEL #2711-T6C2L1. All required communication modules, cables and accessories shall be provided for a complete and operational system. PRESSURE TRANSMITTERS Pressure transmitters shall be supplied to measure suction pressure, discharge pressure and tank level. The transmitters shall sense gauge pressure and transmit a 4-20 mA dc signal. The instruments shall measure pressure of a predetermined span. Range is to be fully adjustable throughout using allowable span and range limits. The accuracy shall be "0.20% of span. Each transmitter shall provide an analog output and include a standard LCD with pushbuttons to provide Intelligent transmitter configuration directly from the on-board pushbuttons. The two-line digital indicator shall display the measurement in any selected units. The pushbuttons shall provide calibration of zero and span, setting of linear output, forward or reverse direction, external zero enable or disable, damping, failsafe action and local display including upper and lower range value selection. All process-wetted parts of each instrument shall be Type 316L stainless steel. The transmitter shall be protected by a gasketed, weatherproof NEMA 4X enclosure. The transmitter shall be approved for use in hazardous locations (Nonincendive for Class 1 and Class II, Division 2 locations; intrinsically safe or explosion-proof for Class 1 and Class II, Division 1 locations). The transmitter shall weigh less than 3.3 lbs. and have a 1/2 inch NPT male thread. The instruments shall be IGP10 I/A series intelligent gauge pressure transmitters as manufactured by the Foxboro Company. ELECTRICAL APPARATUS - TELEMETRY CONTROL - DESIGN, ASSEMBLY & TEST The telemetry panel design, assembly, installation and startup, and the integration of component parts will be the

responsibility of the manufacturer of record for this booster pumping equipment. That manufacturer shall maintain at its regular place of business a complete telemetry design, assembly and test facility to assure continuity of control design with equipment application. Telemetry panels designed, assembled or tested at other than the regular production facilities or by other than the regular production employees of the manufacturer of record for this booster pumping equipment will not be approved.