Model Calculation
Model Calculation
Contents
Introduction ............................................................................................................................................................ 2 1. Load Summation.................................................................................................................................................. 3 Example 1: Load Summation ......................................................................................................................................... 3 2. Circuit protective device current rating ................................................................................................................ 6 Example 2.1: CPD rating ................................................................................................................................................ 6 Example 2.2: CPD rating: motor circuit ......................................................................................................................... 6 3. Cable sizing.......................................................................................................................................................... 7 Example 3.1: Cable sizing: Grouped cable subject to simultaneous overload ......................................................... 7 Example 3.2: Cable sizing: Grouped cable not subject to simultaneous overload ................................................... 8 Example 3.3: Cable sizing motor circuit ...................................................................................................................... 9 Example 3.4: Cable sizing: ring final circuit to sockets ................................................................................................ 10 Example 3.5: Cable sizing: cable run through thermal insulation ............................................................................... 10 Example 3.6: Cable sizing: direct in ground ................................................................................................................. 11 4. Voltage Drop ..................................................................................................................................................... 13 Example 4.1: Voltage drop calculation ........................................................................................................................ 13 5. Phase Fault ........................................................................................................................................................ 14 Example 5.1: Maximum phase fault current ............................................................................................................... 15 Example 5.2: Minimum phase fault current ................................................................................................................ 16 Example 5.3: Line conductor adiabatic check ............................................................................................................. 17 6. Earth Fault ......................................................................................................................................................... 19 Example 6.1: earth fault disconnection by CPD .......................................................................................................... 19 Example 6.2: earth fault adiabatic............................................................................................................................... 20
v4 09/11
Page 2 of 21
o o
Loads resolved into resistive and reactive components and diversity applied: Using: r = z cos = PF; and x = r tan(cos-1) Load 1: r = 70 x 0.9 = 63 A; x = 63 x 0.484 = 30.5122926 A Diversity for load = 0.8 x 0.9, therefore: r = 63 x 0.72 = 45.36 A; x = 30.5122926 x 0.72 = 21.96885067 A Load 2: r = 15 x 0.8 = 12 A; x = 12 x 0.75 = 9 A Diversity for load = 1.0 x 0.9, therefore: r = 12 x 0.9 = 10.8 A; x = 9 x 0.9 = 8.1 A Load 3: r = 20 x 1.0 = 20 A; x = 20 x 0 = 0 A Diversity for load = 1.0 x 0.9, therefore: r = 20 x 0.9 = 18 A; x = 0 x 0.9 = 0 A
v4 09/11
Page 3 of 21
Total load current/power factor: using: I = (r2+x2); and PF = r/z Phase L1: (63.362 + 21.968850672) = 67.06056963 A; and PF = 63.36/67.06056963 = 0.944817503 Phase L2: (45.362 + 21.968850672) = 50.4 A; and PF = 45.36/50.4 = 0.90 Phase L3: (56.162 + 30.06885672) = 63.70307483 A; and PF = 56.16/63.70307483 = 0.881590098 Compare to ProDesign Results: Rounded to 1 decimal place, gives the same values as the report: Phase L1: 67.1 A, 0.94 PF; Phase L2: 50.4 A; 0.90 PF; Phase L3: 63.7 A; 0.88 PF Summing Phase Loads to Give Neutral Load Current: To find the neutral current, the three phase load current vectors are summed. From Table 2 above, the phase load current components are: L1: r = 63.36, x = 21.96885067; L2: r = 45.36, x = 21.96885067; L3: r = 56.16, x = 30.0688567. Expressed as complex numbers, the phase load current vectors are: L1= 63.36 + j21.96885067; L2= 45.36 + j21.96885067; L3 = 56.16 +j30.0688567. Before summing the phase currents, the phase load vectors have to be rotated by their phase angle displacements: L1 + 0 rads (or 0); L2 + 2/3 rads (or 120); L3 + 4/3 rads (or 240). To do this the complex numbers representing the vectors are converted to polar form, as follows: Complex form: Z = r +jx; Polar form: Z, where: = tan-1(x/r) In polar form: L2 = Z = 50.4tan-1(21.96885067/45.36)= 50.40.451026811 L3 =Z = 63.70307483tan-1(30.0688567/56.16) = 63.703074830.491575912 Then the phase angle displacements are added: L2 = 50.40.451026811 + 02.094395102 = 50.42.545421913 L3 = 63.703074830.491575912 + 04.188790205 = 63.703074834.680366117
v4 09/11
Page 4 of 21
Find the neutral current magnitude from the resistive and reactive components: Neutral current = (r2 + x2) = (19.614811032 13.403077322) = 23.75675258 A Compare to ProDesign Results: Rounded to 1 decimal place, gives the same value as the report: Neutral current = 23.8 A
v4 09/11
Page 5 of 21
v4 09/11
Page 6 of 21
v4 09/11
Page 7 of 21
v4 09/11
Page 8 of 21
v4 09/11
Page 11 of 21
v4 09/11
Page 12 of 21
The circuit impedance and voltage drop calculation: r Data from table [m/m] Per phase conductor [3] Correction for power factor [cos r + sin x] r corrected for temperature, using Ct = 0.9059*. [Z = r + x] Total Voltage drop (V) [r = (Ir x Z x length)/1000; x = (Ix x Z x length)/1000; Z = (r2 + x2)] * Ct calculated using formula (10)* from Appendix 4, section 6.1: Ct = {230 + tp [Ca2Cg2 (Ib2/It2)](tp 30)} / (230 + tp) tp = max. permitted normal operating temperature. The total voltage drop per phase Vd calculated by ProDesign = 3.5317 V 3.1785 1.5394 3.5317 1.100 0.6351 0.5716 0.5178 x 0.170 0.0982 0.0428 0.0428 0.5606 Z
v4 09/11
Page 13 of 21
Per unit values to a 100 MVA base are used in the Zbus matrix calculations, the impedances shown in the matrix are the per unit values used. The following worked examples for maximum and minimum fault currents, and earth fault current in the next section, use conventional calculation methods to demonstrate the accuracy of the ProDesign calculations, while avoiding the complexities of the construction of the Zbus matrices. Also, each worked example is repeated showing the calculations that are performed by ProDesign using the impedances obtained from the Zbus matrix. In some versions of ProDesign a Zbus matrix viewer is provided. This is displayed by clicking View Impedance Matrices in the Calculation menu.
[Ze = external impedance; Z1 = phase conductor impedance] [Zn = neutral conductor impedance]
r 0.000064 0.004000
x 0.000637 0.019596
x 0.3980
0.0398
4.5132 14.449
v4 09/11
Page 15 of 21
r 0.0041
x 0.0202
0.1250 0.0722 0.0722 0.0722 0.0013 0.0013 0.0274 0.0007 0.0007 0.0311
x 0.3980
0.0398
9.1793 17.156
v4 09/11
Page 16 of 21
v4 09/11
Page 18 of 21
the earth fault loop impedance (Zs) is calculated; Using the earth fault loop impedance, the earth fault current (Ief) is calculated; Using the earth fault current, the earth fault disconnection time is determined from the circuit protective device (CPD) characteristic (or the residual current device (RCD) characteristic where an RCD is used); A check is made to determine whether the disconnection time is within the maximum for the circuit (411.3.2, Table 41.1); Where an RCD is used on a TT system, a check is made to ensure the Touch Voltage does not exceed the limit for the circuit (411.5.3); An adiabatic calculation is performed to ensure that the maximum permitted CPC temperature is not exceeded during an earth fault (543.1.3).
Example 6.1 below describes the calculation for earth fault disconnection by means of the CPD. Example 6.2 below describes the adiabatic calculation. Example 6.3 below describes the calculation for earth fault disconnection by means of an RCD.
r 0.0041
x 0.0202
v4 09/11
Page 19 of 21
52.3221 53.471
v4 09/11
Page 20 of 21
v4 09/11
Page 21 of 21