Inverter Ip5a
Inverter Ip5a
Inverter Ip5a
STARVERT iP5A
5.5~30kW(7.5~40HP) 3Phase 200~230Volts 5.5~450kW(7.5~600HP) 3Phase 380~480Volts
Drive Solution
STARVERT iP5A
LS Starvert iP5A is basically created for centrifugal fan and pump, so iP5A can help construct competitive system in your various applications.
STARVERT
iP5A
Contents
4 8 9 11 15 17 20 21 22 33 35 40 45
Overview Model & Type Standard Specifications Wiring Terminal Configurations (Power Circuit Terminal) Terminal Configurations (Control Circuit Terminal) Programming Keypad Programming Keypad (Parameter Navigation) Parameter Description Trial Run Dimensions DB (Dynamic Braking) Unit External DB Resistor / Peripheral Device
iP5A
PID Control
In the centrifugal fan and pump field, PID control is provided as a standard function in order to maintain a constant process control of pressure, flow and oil level. This function includes Pre-PID, Sleep and Wake up and output inverse sub-functions.
Dual PID
In case of an external PID control needed or cascade PID control, the built-in Dual PID function of iP5A can construct various systems.
PID feedback
600 RPM
iP5A
20
30
40
50
60
70
Load %
iP5A
Intelligent Control
Regardless of outside alteration affecting inverters performance, iP5A generates constant performance with effectual functions and protection methods.
Emitted energy
The mechanical energy stored during blackout can be used for inverters power.
Mechanical energy
Load
Consumed energy
Safety Stop
When unexpected power-failure blocks power supply, inverter stops motor by using inertia energy of load that prevents unexpected second accident (Parameter setting is required).
PWM
Zero vector
Zero vector
Valid vector
Valid vector
Protection
iP5A has optimum optimal protection functions such as safety stop and prior motor operation.
Easy Start
When pushingSTOPkey for 2~3 seconds in case inverter turns on, the inverter turns into Easy Start Modewith FWD, REV, and STOP command. SHIFT/ESCcan return it to previous mode. Control method: V/F Control frequency: Jog
1 4 2 6
7 9
NPN/PNP Input
iP5A has both NPN and PNP input, and you can select one of them easily.
6 3
Others
Removable terminal board External fan available Cooling fan on/off control
iP5A
Motor Rating
5.5kW (7.5HP) 7.5kW (10HP) 11kW (15HP) 15kW (20HP) 18.5kW (25HP) 22kW (30HP) 30kW (40HP) 37kW (50HP) 45kW (60HP) 55kW (75HP) 75kW (100HP) 90kW (125HP) 110kW (150HP) 132kW (200HP) 160kW (250HP) 220kW (300HP) 280kW (350HP) 315kW (400HP) 375kW (500HP) 450kW (600HP)
200~230V Class
SV055iP5A-2NE SV075iP5A-2NE SV110iP5A-2NE SV150iP5A-2NO SV185iP5A-2NO SV220iP5A-2NO SV300iP5A-2NO
380~480V Class
SV055iP5A-4NE SV075iP5A-4NE SV110iP5A-4NE SV150iP5A-4NO SV185iP5A-4NO SV220iP5A-4NO SV300iP5A-4NO SV370iP5A-4O SV450iP5A-4O SV550iP5A-4O SV750iP5A-4O SV900iP5A-4O SV1100iP5A-4OL SV1320iP5A-4OL SV1600iP5A-4OL SV2200iP5A-4OL SV2800iP5A-4OL SV3150iP5A-4O SV3750iP5A-4O SV4500iP5A-4O
SV
055
Motor Rating 055 900 5.5 kW 90 kW
iP5A
Series Name iP5A
--
2
Input Voltage 2 4 200-230V 380-480V
NE
N: No Keypad O: UL Open Type E: UL Enclosed Type 1 L: Built-in DC Choke
SV055iP5A-2NE
INPUT 200-230 V 3 Phase 25A 50/60HZ OUTPUT 0-Input V 3 Phase 24A 0.01-120HZ 9.1KVA, Enclosed Type 1
Model Number Input Rating Output Rating Protection Degree Bar Cord Serial Number
Standard Specifications
200~230V Class (5.5~30kW / 7.5~40HP)
Model Number (SV iP5A-2)
Capacity [kVA]
Note1)
055
9.1 7.5 5.5 24 5.5 3.7 17
075
12.2 10 7.5 32 7.5 5.5 23
110
17.5 15 11 46
150
185
220
300
43.8 40 30 115 30 22 84
Fan or pump load Output ratings General load Frequency Voltage Input Voltage ratings Frequency Protection degree Weight [kg (lbs.)]
Motor rating
Note2)
(HP) (kW)
Current [A] (110% over current) (HP) Motor rating (kW) Current [A] (150% over current)
4.9 (10.8)
22.9 28.2 33.5 20 25 30 15 18.5 22 60 74 88 110% 1 Minute (Normal Duty) 10 15 20 25 7.5 11 15 18.5 33 44 54 68 150% 1 Minute (Heavy Duty) 0.01~120 Hz 200~230V Note3) 3200~230V (-15%~+10%) 50/60 Hz ( 5%) IP00 / UL Open Note4) 6 (13.2) 13 (28.7) 13.5 (29.8) 20 (44.1)
20 (44,1)
055
9.6 7.5 5.5 12
075
12.7 10 7.5 16
110
19.1 15 11 24
150
23.9 20 15 30
185
220
300
370
450
550
750
900
Fan or pump load Output ratings General load Frequency Voltage Input Voltage ratings Frequency Protection degree Weight [kg (lbs.)]
Motor rating
Note2)
(HP) (kW)
Current [A] (110% over current) (HP) Motor rating (kW) Current [A] (150% over current)
31.1 35.9 48.6 59.8 72.5 87.6 121.1 145.8 25 30 40 50 60 75 100 125 18.5 22 30 37 45 55 75 90 39 45 61 75 91 110 152 183 110% 1 Minute (Normal Duty) 5.5 7.5 10 15 20 25 30 40 50 60 75 100 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 8.8 12 16 22/24 28/30 34/39 44/45 150% 1 Minute (Heavy Duty) 0.01~120 Hz 380~480V Note3) 3380~480V (-15%~+10%) 50/60 Hz ( 5%) IP20 / UL Type1 IP00 / UL Open Note4) 4.9 (10.8) 6 (13.2) 6 (13.2) 12.5 (27.6) 13 (28.7) 20 (44.1) 20 (44.1) 27 (59.5) 27 (59.5) 29 (64) 42 (92.6) 43 (94.8) 19.5 (43.9) 19.5 (42.9) 26.5 (58.3) 26.5 (58.3) 39 (86) 40 (88.2) 42 (92.6) 67 (147.4) 68 (149.9)
1100
178 150 110 223 125 90 183
1320
210 200 132 264 150 10 223
1600
259 250 160 325 200 132 264
2200
2800
3150
488 400 315 613 350 280 547
3750
582 500 375 731 400 315 613
4500
699 600 450 877 500 375 731
Fan or pump load Output ratings General load Frequency Voltage Input Voltage ratings Frequency Protection degree DCL Weight [kg (lbs.)]
Motor rating
(HP) (kW)
Current [A] (110% over current) (HP) Motor rating (kW) Current [A] (150% over current)
344 436 300 350 220 280 432 547 110% 1 Minute (Normal Duty) 250 300 160 220 325 432 150% 1 Minute (Heavy Duty) 0.01~120 Hz 380~480V Note3) 3380~480V (-15%~+10%) 50/60 Hz ( 5%) IP00 / UL Open Note4) 200 (441.9) 200 (441.9)
101 (222.7)
380 (837.7)
Note 1) Rated capacity (v 3VI) is based on 220V for 200V class and 460V for 400V class. 2) Indicates the maximum applicable capacity when using a 4-Pole LS motor. 3) Maximum output voltage will not exceed the input voltage. An output voltage less than the input voltage may be programmed if necessary. 4) IP20/UL Type1 with optional conduit, it can be modified to UL Type1.
iP5A
Standard Specifications
Common Specifications (External)
Keypad Remote
32 character display LCD keypad Download and Upload available 2m, 3m and 5m long keypad cable enables users Remote cable to control the inverter from a distant area To enhance the regenerative braking performance, DB resistor Optional All units
Dynamic braking
DB unit Conduit for
it makes the inverter to accelerate/decelerate rapidly If it need a regenerative braking, it is used with DB resistor
Conduit option
15~90kW Install it to fit for NEMA TYPE 1 Enclosure or IP20 (20~125HP) All series DEVICENET optional communication card (Above S/W V10) All series
PROFIBUS
LS485/MODBUS_RTU
LonWorks
BACNet
MODBUS_TCP
Metasys_N2
CCLink
CANopen
10
Wiring
For 5.5~30kW (7.5~40HP) Main Power Circuit
P2 (+) N (-)
U V W
Motor
Control Circuit
Programmable Digital Input 1 (Speed L) Programmable Digital Input 2 (Speed M) Programmable Digital Input 3 (Speed H) Fault Reset (RST) Inverter Disable (BX) Jog Frequency Reference (JOG) Forward Run Command (FX) Reverse Run Command (RX) Common Terminal
V+ M1 M2 M3 M4 M5 M6 M7 M8 CM A1 C1 A2 C2 A3 C3 A4 C4
RS485 Signal RS485 Common Max. output voltage: 12V Source max.: 30mA Sink max.: 20mA
Analog Power Source (+12V) Frequency Reference (0~12V, V1S: -12~12V) Frequency Reference Common Terminal Frequency Reference (0~20mA or 4~20mA) Analog Power Source (-12V)
+ + -
V1 5G I V-
S0 S1 5G
Output Frequency Meter Output Voltage Meter Common for Output Meter Signal
3A 3C 3B
A0 B0 5G
CC+ CM
NT 5G
Note 1) 5G is Common Ground for Analog Input / Output. 2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input.
11
iP5A
Wiring
For 37~90kW (50~125HP) / 315~450kW (400~600HP) Main Power Circuit
P2 (+) N (-)
U V W
Motor
Control Circuit
Programmable Digital Input 1 (Speed L) Programmable Digital Input 2 (Speed M) Programmable Digital Input 3 (Speed H) Fault Reset (RST) Inverter Disable (BX) Jog Frequency Reference (JOG) Forward Run Command (FX) Reverse Run Command (RX) Common Terminal
V+ M1 M2 M3 M4 M5 M6 M7 M8 CM A1 C1 A2 C2 A3 C3 A4 C4
RS485 Signal RS485 Common Max. output voltage: 12V Source max.: 30mA Sink max.: 20mA
Analog Power Source (+12V) Frequency Reference (0~12V, V1S: -12~12V) Frequency Reference Common Terminal Frequency Reference (0~20mA or 4~20mA) Analog Power Source (-12V)
+ + -
V1 CM I V-
S0 S1 5G
Output Frequency Meter Output Voltage Meter Common for Output Meter Signal
3A 3C 3B
A0 B0 CM
Frequency Reference (Pulse: 0~100kHz) Common for Frequency Reference (Pulse)
CC+ CM
ET 5G
Note 1) 5G is Common Ground for Analog Meter Output (SO, S1) and External motor thermal detection (ET). 2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input. 3) DC Reactor is built basically in inverters for 15~280kW.
12
Motor
Control Circuit
Programmable Digital Input 1 (Speed L) Programmable Digital Input 2 (Speed M) Programmable Digital Input 3 (Speed H) Fault Reset (RST) Inverter Disable (BX) Jog Frequency Reference (JOG) Forward Run Command (FX) Reverse Run Command (RX) Common Terminal
V+ M1 M2 M3 M4 M5 M6 M7 M8 CM A1 C1 A2 C2 A3 C3 A4 C4
RS485 Signal RS485 Common Max. output voltage: 12V Source max.: 30mA Sink max.: 20mA
Analog Power Source (+12V) Frequency Reference (0~12V,V1S: -12~12V) Frequency Reference Common Terminal Frequency Reference (0~20mA or 4~20mA) Analog Power Source (-12V)
+ + -
V1 CM I V-
S0 S1 5G
Output Frequency Meter Output Voltage Meter Common for Output Meter Signal
3A 3C 3B
A0 B0 CM
Frequency Reference (Pulse: 0~100kHz) Common for Frequency Reference (Pulse)
CC+ CM
ET 5G
Note 1) 5G is Common Ground for Analog Meter Output (SO, S1) and External motor thermal detection (ET). 2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input. 3) DC Reactor is built basically in inverters for 15~280kW.
13
iP5A
Wiring
For 15~30kW (20~40HP) Built-in DCL Type
DC Reactor
3 AC Input 50/60 Hz
U V W
Motor
DC Reactor
3 AC Input 50/60 Hz
U V W
Motor
14
(+)
R(L1) S(L2) T(L3) G P1
Jumper
(+)
P2
(--)
N U V W
(+)
R(L1) S(L2) T(L3) P1
Jumper
(+)
P2
(--)
N U V W
(+)
G R(L1) S(L2) T(L3) P
(--)
N U V W G
(+)
R(L1) S(L2) T(L3) P
(-)
N U V W
(+)
R(L1) S(L2) T(L3)
Note) P1 (+) is not provided for wiring.
(--)
N U V W
P2
Symbol
R, S, T (L1, L2, L3) G P1 (+), P2 (+) P2 (+), N (-) or P (+), N (-) U, V, W AC Line Voltage Input Earth Ground
Description
External DC Reactor [P1 (+)-P2 (+)] Connection Terminals (Jumper must be removed). DB Unit [P2 (+)-N (-)] Connection Terminals 3 Phase Power Output Terminals to Motor
15
iP5A
Inverter Capacity
U, V, W 5.5 8 14 22 38 38 60 3.5 3.5 5.5 8 14 22 38 60 100 150 200 250 325 2200 2250
AWG or kcmil R, S, T U, V, W 10 8 6 4 2 2 1/0 12 12 10 8 6 4 2 1/0 4/0 300 400 500 700 10 8 6 4 2 2 1/0 12 12 10 8 6 4 2 1/0 4/0 300 400 500 700 2400 2500
200V Class
15kW (20HP) 18.5kW (25HP) 22kW (30HP) 30kW (40HP) 5.5kW (7.5HP) 7.5Kw (10HP) 11 kW (15HP) 15 kW (20HP) 18.5kW (25HP) 22~30kW (30~40HP)
400V Class
37~55kW (50~75HP) 75~90kW (100~125HP) 110~132kW (150~200HP) 160kW (250HP) 220kW (300HP) 280kW (350HP) 315kW (400HP) 375kW (500HP) 450kW (600HP)
2400 2500
Note) Apply the rated torque to terminal screws. Loose screws can cause of short circuit or malfunction. Tightening the screw too much can damage the terminals and cause a short circuit or malfunction. Use copper wires only with 600V, 75 ratings. For 7.5~11kW 240V type inverters, R (L1), S (L2), T (L3) and U, V, W terminals are only for use with insulated ring type connector.
16
3A
3C
3B
A1
C1
A2
C2
A3
C3
A4
C4
C+ M1
CM CM
CM2
M6 M3
24 24
M7 M4
M8 M5
A0 V+
B0 V1
5G 5G
5P V-
S0 I
S1 NT
3A
3C
3B
A1
C1
A2
C2
A3
C3
A4
C4
C+ M1
CM CM
CM2
M6 M3
24 24
M7 M4
M8 M5
CM V+
NC V1
5G CM
5G V-
ET I
S0 A0
S1 B0
17
iP5A
Type
Symbol
M1, M2, M3 FX [M7] RX [M8] JOG [M6]
Name
Programmable Digital Input 1, 2, 3 Forward Run Command Reverse Run Command Jog Frequency Reference Defines programmable digital inputs.
Description
(Factory setting: Multi-step frequency 1, 2, 3) Forward run when closed and stopped when open. Reverse run when closed and stopped when open. Runs at jog frequency when the jog signal is on. The direction is set by the FX (or RX) signal. When the BX signal is ON, the output of the inverter is turned off. When motor uses an electrical brake to stop, BX is used to turn off the output signal. Take caution when BX signal is off (Not turned off by latching) and FX signal (or RX signal) is on. If so, motor continues to run. Used for fault reset. Common terminal for NPN contact input and also common for the external 24V supply. Common 24V terminal for PNP contact input. Can be also used as a 24Vdc external power supply (Maximum output : +24V, 50mA) Power supply for analog frequency setting. Maximum output: +12V, 100mA, -12V, 100mA. Used by a DC 0~12V or -12~12V input to set the frequency reference. (Input impedance is 20 k) Used by a 0-20mA input to set the frequency reference. (Input impedance is 249) Used by a pulse input to set the frequency reference. Common terminal for analog frequency reference signal. Motor thermal sensor input. Used to prevent motor from overheating by using a NTC or PTC thermal sensor. Common terminal for external motor thermal detection. RS485 signal (See RS485 communication in manual for more details.) Common ground. Terminal for RS485 interface. Voltage output for one of the following: Output frequency, output current, output voltage, DC link voltage. Default is set to output frequency. (Maximum output voltage and output current are 0-12V and 1mA). Energizes when a fault is present. (AC250V, 1A: DC30V, 1A) Fault: 3A-3C closed (3B-3C Open) Normal: 3B-3C closed (3A-3C Open) Defined by programmable digital output terminal settings (AC250V, 1A: DC30V, 1A)
BX [M5]
Inverter Disable
RST [M4] CM
Fault Reset Sequence Common (NPN) / 24V Com. Sequence Common (PNP) / Ext. +24Vdc supply Analog Power Source (+12V,-12V) Frequency Reference (Voltage) Frequency Reference (Current) Frequency Reference (Pulse) Frequency Reference Common Terminal External Motor Thermal Detection Common for NT (or ET) RS485 signal High, Low RS485 common Programmable Voltage Output Fault Contact Output Programmable Digital Output
Input Signal
24
V+, VV1 Analog Frequency Setting A0, B0 5G (~30kW) CM (37kW~) External Motor Thermal Detection RS485 Terminal NT (~30kW) ET (37kW~) 5G C+, CCM S0, S1,5G I
Voltage
Output Signal
18
19
iP5A
Programming Keypad
LCD Loader
Mode Button moves you through seven program groups: DRV [Mode] FUN1 [ENT] DRV
Enter Button is used to enter changed data within a parameter. DRV [ENT] APP [MODE] DRV
[SHIFT] This button is used to move cursor across display in programming mode. [ESC] This button is used to move the program code to DRV 00 from any program code. Reverse Run Button Reverse Run LED blinks when drive Accels or Decels.
Forward Run Button Forward Run LED blinks when drive Accels or Decels.
20
Drive Group
FU1 Group
FU2 Group
I/O Group
Note) This figure shows group and code navigation through LCD display keypad. It can be different from actual display due to the group addition or code change.
21
iP5A
Parameter Description
DRV Group
CODE Comm. Addr Description
Command Frequency (Output Frequency during motor run, Reference Frequency during motor stop), Output Current(LCD) Acceleration 5.5~90kW (7.5~125HP) Time 110~450kW (150~600HP) Deceleration 5.5~90kW (7.5~125HP) Time 110~450kW (150~600HP)
Setting Range
Factory Default
DRV-00 Note1)
9100
Cmd. Freq
0 to FU1-30 [Hz]
0 [Hz]
DRV-01 DRV-02
9101 9102
0 to 6000 [sec] 0 to 6000 [sec] 0 (Keypad) 1 (Fx/Rx-1) 2 (Fx/Rx-2) 3 (Int. 485) 0 (Keypad-1) 1 (Keypad-2) 2 (V1) 3 (V1S) 4 (I) 5 (V1+I) 6 (Pulse) 7 (Int. 485) 8 (Ext. PID) 0 to FU1-30 [Hz] * [A] * [rpm] * [V]
DRV-03
9103
Drive Mode
DRV-04
9104
Freq Mode
0 (Keypad-1)
DRV-05 DRV-06 DRV-07 DRV-08 DRV-09 DRV-10 DRV-11 DRV-12 DRV-13 DRV-14 Note2) DRV-15 Note2) DRV-16 DRV-18 Note2) DRV-19 DRV-20 Note3) DRV-91 Note4)
9105 9106 9107 9108 9109 910A 910B 910C 910D 910E 910F 9110 9112 9113 9114 915B
Step Frequency 1 Step Frequency 2 Step Frequency 3 Output Current Motor Speed DC link Voltage User Display Selection Current Trip Display Motor Direction Target/Output Frequency Display Reference/Feedback Frequency Display Speed Unit Selection PID Parameter AD Parameter EXT-PID Parameter Drive Mode 2
Step freq-1 Step freq-2 Step freq-3 Current Speed DC link Vtg User disp Fault Use Only 7-Segment Keypad Tar. Out. Freq. Ref. Fbk. Freq. Hz/Rpm Disp Pid Parameter AD Parameter Ext Pid Para Drive Mode2
* 0 (Forward)/1 (Reverse) * [Hz] * [Hz] Hz or Rpm * [Hz] AD [%] 0 (Keypad) 1 (Fx/Rx-1) 2 (Fx/Rx-2) 0 (Keypad-1) 1 (Keypad-2) 2 (V1) 3 (V1S) 4 (I) 5 (V1+I) 6 (Pulse)
10 [Hz] 20 [Hz] 30 [Hz] * [A] * [rpm] * [V] Output voltage [V] * 0 * [Hz] * [Hz] [Hz] * [Hz] AD % 1 (Fx/Rx-1)
* * * * * * *
DRV-92 Note4)
915C
Frequency Mode 2
Freq Mode2
0 (Keypad-1)
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 1) The speed unit is changed from [Hz] to [%] when DRV-16 is set to [Rpm]. Only User Unit will be displayed when APP-02 is set to [Yes] and when APP-06 is set to either I, V1 or Pulse and when one of I/O-86~ I/O-88 is set to either [Speed], [Percent], [Bar], [mBar], [kPa] or [Pa]. Output Frequency is displayed in DRV-00 during the Inverter is running. User Unit reference is displayed in DRV-00 during the Inverter is not running. 2) DRV-15, DRV-18 will appear when APP-02 [Process PI Mode] is set toYes . Also User Unit is displayed when one of I/O-86~I/O-88 is set to either [Speed], [Percent], [Bar], [mBar], [kPa] or [Pa]. 3) DRV-20 will appear when APP-80 [Ext Process PI Mode] is set toYes . 4) DRV-91/92 will appear only when one of I/O-20~27 is set to [Main drv] and DRV- 03/04 is set to [int485].
22
FU1 GROUP
CODE
FU1-00
Comm. Addr
9200
Description
Jump to Desired Code #
Setting Range
1 to 74 (Use Only LCD Keypad) (None) (Fwd prev) (Rev prev) (Linear) (S-curve) (U-curve) (Linear) (S-curve) (U-curve) 0 to 100 [%] 0 to 100 [%] 0 1 (No) (Yes) 1 to 50 [%] 1 to 100 [%] 0 (Accel) (Dc-start) (Flying-start) 0 to 60 [sec] 0 to 150 [%] 0 (Decel) (Dc-brake) (Free-run) (Flux-brake) 0.1 to 60 [sec] 0.1 to 60 [Hz] 0 to 60 [sec] 0 to 200 [%] 0 1 (No) (Yes) 40 to 120 [Hz] 40 to 120 [Hz] 30 to 120 [Hz] 0.1 to 10 [Hz] 0 1 (No) (Yes) 0 to FU1-35 FU1-34 to FU1-30 1 2 3 1 2
Factory Default
1
FU1-01
9201
Run Prevention
Run Prevention
1 2 0
0 (None)
FU1-02
9202
Acceleration Pattern
Acc. Pattern
1 2 0
0 (Linear)
FU1-03
9203
Deceleration Pattern Start Curve for S-Curve Accel/Decel Pattern End Curve for S-Curve Accel/Decel Pattern
Dec. Pattern
1 2
0 (Linear)
Start Curve End Curve Pre-Heat Mode Pre Heat Level Pre Heat Perc Start Mode DcSt Time DcSt Value
Pre-Heat Pre-Heat Value Pre-Heat Duty Start Mode Starting DC Injection Braking Time Starting DC Injection Braking Value
FU1-23
9217
Stop Mode
Stop Mode
0 (Decel)
FU1-24 FU1-25 FU1-26 FU1-27 FU1-28 FU1-29 FU1-30 FU1-31 FU1-32 FU1-33 FU1-34 FU1-35
Note7)
9218 9219 921A 921B 921C 921D 921E 921F 9220 9221
DC Injection Braking On-delay Time DC Injection Braking Frequency DC Injection Braking Time DC Injection Braking Value Safety Stop Power Source Freq Maximum Frequency Base Frequency Starting Frequency Frequency Limit Selection Low Limit Frequency High Limit Frequency
DcBlk Time DcBr Freq DcBr Fime DcBr Value Safety Stop Line Freq Max Treq Base Treq Start Treq Freq Limit F-limit Lo F-limit Hi
0.1 [sec] 5 [Hz] 1 [sec] 50 [%] 0 (No) 60 [Hz] 60 [Hz] 60 [Hz] 0.5 [Hz] 0 (No) 0.5 [Hz] 60 [Hz]
Note8)
9222 9223
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 5) Only displayed when FU1-02, FU1-03 is set to [S-Curve]. 6) Only displayed when FU1-20 is set to [DC-start]. 7) Only displayed when FU1-23 is set to [DC-break]. 8) Only displayed when FU1-33 is set toYes .
23
iP5A
Parameter Description
FU1 GROUP
CODE Comm. Addr
9228
Note9)
Description
Setting Range
(Linear) (Square) (User V/F) 0 to FU1-30 0 to 100 [%] 0 to FU1-30 0 to 100 [%] 0 to FU1-30 0 to 100 [%] 0 to FU1-30 0 to 100 [%] 73 to 115.0 [%] 0 to 600 [V] (None) (Manual) (Auto) 0 to 30 [%] M kWh 0 to 160 [Degree] 0 to 160 [Degree] (No) (Yes) 5 to 100 [%] 0.5 to 10.0 [sec] (No) (Yes) FU1-62 to 200 [%] 50 to FU1-61 (Maximum 150%) (Self-cool) (Forced-cool) 30 to 110 [%] 0 to 30 [sec] (No) (Yes) 30 to 150 [%] 0 to 60 [sec] 000 to 111 (Bit Set) 000 to 111 (Bit) 30 to 150 [%] 0 to FU1-30 (Max freq) (Delta freq) (0.01 sec)
Factory Default
0 (Linear) 15 [Hz] 25 [%] 30 [Hz] 50 [%] 45 [Hz] 75 [%] 60 [Hz] 100 [%] 100.0 [%] 0 [V] 0 (None) 0 [%] * * * 1 [Yes] 5 [%] 3.0 [sec] 1 (Yes) 150 [%] 120 [%] 0 (Selfcool) 110 [%] 10 [sec] 0 (No) 120 [%] 60 [sec] 100 000 (Bit) 100 [%] 0 [Hz] 0 (Max freq) 1 (0.1 sec)
FU1-40 FU1-41 FU1-42 FU1-43 FU1-44 FU1-45 FU1-46 FU1-47 FU1-48 FU1-49 FU1-50 FU1-51 FU1-52 Note10) FU1-54 FU1-55 FU1-56 FU1-57 FU1-58 FU1-59 FU1-60 FU1-61 FU1-62 FU1-63 FU1-64 FU1-65 FU1-66 FU1-67 Note11) FU1-68 FU1-69 FU1-70 FU1-71 FU1-72 FU1-73 FU1-74
Volts/Hz Pattern User V/FFrequency 1 User V/FVoltage 1 User V/FFrequency 2 User V/FVoltage 2 User V/FFrequency 3 User V/FVoltage 3 User V/FFrequency 4 User V/FVoltage 4 Input Voltage Adjustment Motor Rated Voltage Energy Save Energy Save % Integrating Wattmeter Inverter Temperature Motor Temperature No Motor Selection Trip Current Level Trip Time Setting Electronic Thermal Selection Electronic Thermal Level for 1 Minute Electronic Thermal Level for Continuous Characteristic Selection (Motor Type) Overload Warning Level Overload Warning Time Overload Trip Selection Overload Trip Level Overload Trip Delay Time Input/Output Phase Loss Protection Stall Prevention Mode Selection Stall Prevention Level Accel/Decel Change Frequency Reference Frequency for Accel and Decel Accel/Decel Time Scale
9229 922A 922B 922C 922D 922E 922F 9230 9231 9232 9233 9234 9236 9237 9238 9239 923A 923B 923C 923D 923E 923F 9240 9241 9242 9243 9244 9245 9246 9247 9248 9249 924A
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 9) FU1-41~48 only displayed when FU1-40 is set toUser V/F. 10) Only displayed when FU1-51 is set toManual . 11) Only displayed when FU1-66 is set toYes .
24
FU2 GROUP
CODE
FU2-00 FU2-01 FU2-02 FU2-03 FU2-04 FU2-05 FU2-06 FU2-07 FU2-08 Note12) FU2-10 FU2-11 FU2-12 FU2-13 FU2-14 FU2-15 FU2-16 FU2-20 FU2-21 FU2-22 FU2-23 Note14) FU2-24 FU2-25 FU2-26 Note15)
Note13)
Comm. Addr
9300 9301 9302 9303 9304 9305 9306 9307 9308 930A 930B 930C 930D 930E 930F 9310 9314 9315 9316 9317 9318 9319 931A
Description
Jump to Desired Code # Last Trip 1 Last Trip 2 Last Trip 3 Last Trip 4 Last Trip 5 Erase Trips Dwell Frequency Dwell Frequency Frequency Jump Selection Jump Frequency 1 Jump Frequency 1 Jump Frequency 2 Jump Frequency 2 Jump Frequency 3 Jump Frequency 3 Power ON Start Selection Restart after Fault Reset Speed Search Selection P Gain During Speed Search I Gain During Speed Search Number of Auto Retry Delay Time before Auto Retry
Setting Range
1 to 95 (Use Only LCD Keypad) By pressing [PROG] and [] key, the frequency, current, and operational status at the time of fault can be seen. (No) (Yes) 0 to 10 [sec] FU1-32 to FU1-30 (No) (Yes) 0 to FU2-12 FU2-11 to FU1-30 0 to FU2-14 FU2-13 to FU1-30 0 to FU2-16 FU2-15 to FU1-30 (No) (Yes) (No) (Yes) 0000 to 1111 (Bit Set) 0 to 9999 0 to 9999 0 to 10 0 to 60 [sec] (0.75kW) (1.5kW) (2.2kW) (3.7kW) (5.5kW) (7.5kW) (11.0kW) (15.0kW) (18.5kW) (22.0kW) (30.0kW) (37.0kW) (45.0kW) (55.0kW) (75.0kW) (90.0kW) (110.0kW) (132.0kW) (160.0kW) (220.0kW) (280.0kW) (315.0kW) (375.0kW) (450.0kW) 2 to 12 0 to 10 [Hz] 1 to 200 [A] 0.5 to 200 [A] 70 to 100 [%]
Factory Default
40 0 (None) 0 (None) 0 (None) 0 (None) 0 (None) 0 (No) 0 [sec] 5 [Hz] 0 (No) 10 [Hz] 15 [Hz] 20 [Hz] 25 [Hz] 30 [Hz] 35 [Hz] 0 (No) 0 (No) 0000 200 500 0 1 [sec]
FU2-40
9328
Motor Select
Number of Motor Poles Rated Motor Slip Rated Motor Current (RMS) No Load Motor Current (RMS) Motor Efficiency
4 *Depending on FU2-40
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 12) Only displayed when FU2-07 is set to [1~10 sec]. 13) Only displayed when FU2-10 is set toYes . 14) Only displayed when FU1-23 is set to [DC-break]. 15) Only displayed when FU1-33 is set toYes .
25
iP5A
Parameter Description
FU2 GROUP
CODE
FU2-46 FU2-47 FU2-48
Comm. Addr
932E 932F
Description
Load Inertia Gain for Motor Speed Display
Setting Range
Factory Default
0 100 [%] 5 [kHz] 4 [kHz] 3 [kHz] 0 (Normal 1)
FU2-49
FU2-60 FU2-61 Note16) FU2-62 FU2-63 FU2-64 FU2-65 FU2-66 FU2-67 FU2-68 FU2-69 FU2-80 FU2-81 FU2-82 FU2-83 FU2-84 FU2-85 FU2-87 FU2-90 FU2-91 FU2-92
FU2-93
FU2-94 FU2-95
0 to 8 1 to 1000 [%] 5.5~22kW 0.7~15 [kHz] 30kW 0.7~10 [kHz] 9330 Carrier Frequency Carrier Freq 37~75kW 0.7~4 [kHz] 90~450kW 0.7~3 [kHz] 0 (Normal 1) 9331 PWM Type Selection PWM Mode 1 (Normal 2) 2 (Low leakage) 0 (V/F) 933C Control Mode Selection Control Mode 1 (Slip compen) 2 (Sensorless) 0 (No) 933D Auto Tuning Selection Auto Tuning 1 (Yes) 0 to (depending on FU2-40) 933E Stator Resistance of Motor Rs [ohm] 0 to (depending on FU2-40) 933F Leakage Inductance of Motor Lsigma [mH] * Automatically set corresponding to motor rating. If different, check motor rating setting. 9340 Pre-excitation Time Pre Ex Time 0 to 60 [sec] 9341 P Gain for Sensorless Control SL P-Gain 0 to 9999 9342 I Gain for Sensorless Control SL I-Gain 0 to 9999 0 (Manual) 9343 Manual/Auto Torque Boost Selection Torque Boost 1 (Auto) 9344 Torque Boost in Forward Direction Fwd Boost 0 to 15 [%] 9345 Torque Boost in Reverse Direction Rev Boost 0 to 15 [%] 9350 Power On Display Power On Disp 0 to 12 1 (Watt) 9351 User Display Selection User Disp 0 (Voltage) 9352 Software Version S/W Version Ver X.XX 9353 Last Trip Time Last Trip Time X:XX:XX:XX:XX:X 9354 Power On Time On-Time X:XX:XX:XX:XX:X 9355 Run-time Run-Time X:XX:XX:XX:XX:X 9357 Power Set Power Set 0.1~400 [%] 0 (Default) 935A Parameter Display Para. Disp 1 (All Para) 2 (Diff Para) 0 (No) 935B Read Parameter Para. Read 1 (Yes) 0 (No) 935C Write Parameter Para. Write 1 (Yes) 0 (No) 1 (All Groups) 2 (DRV) 3 (FU1) 935D Initialize Parameter Para. Init 4 (FU2) 5 (I/O) 6 (EXT) 7 (COM) 8 (APP) 935E Parameter Write Protection Para. Lock 0 to 9999 0 (No) 935F Parameter Save Para. Save 1 (Yes)
0 (V/F) 0 (No) *Depending on FU2-40 *Depending on FU2-40 1 [sec] 1000 100 0 (Manual) 2 [%] 2 [%] 0 0 (Voltage) Ver X.XX
0 (No)
0 0 (No)
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 16) Only FU2-61~66 displayed when FU2-60 is set to [Sensorless].
26
I/O GROUP
CODE
I/O-00 I/O-01 Note17) I/O-02 I/O-03 I/O-04 I/O-05 I/O-06 I/O-07 I/O-08 I/O-09 I/O-10 I/O-11 I/O-12 I/O-13 I/O-14 I/O-15 I/O-16
Comm. Addr
9400 9401 9402 9403 9404 9405 9406 9407 9408 9409 940A 940B 940C 940D 940E 940F 9410
Description
Jump to Desired Code # Filtering Time Constant for V1 Signal Input V1 Input Minimum Voltage Frequency Corresponding to V1 Input Minimum Voltage V1 Input Minimum Voltage V1 Input Maximum Voltage Filtering Time Constant for I Signal Input I Input Minimum Current Frequency Corresponding to I Input Minimum Current Filtering Time Constant for I Signal Input Frequency Corresponding to I Input Maximum Current Pulse Input Method Pulse Input Filter Pulse input Minimum Frequency Frequency Corresponding to I/O-13 Pulse Input Maximum Frequency Frequency Corresponding to I/O-15 Pulse input Minimum Frequency
Setting Range
1 to 98 (LCD Keypad Only) 0 to 9999 [msec] 0 to 12 [V] 0 to FU1-30 [Hz] 0 to 100.00 [**] 0 to 12 [V] 0 to FU1-30 [Hz] 0 to 100.00 [**] 0 to 9999 [msec] 0 to 20 [mA] 0 to FU1-30 [Hz] 0 to 100.00 [**] 0 to 20 [mA] 0 to FU1-30 [Hz] 0 to 100.00 [**] (A+B) (A) 0 to 9999 [msec] 0 to 10 [kHz] 0 to FU1-30 [Hz] 0 to 100.00 [**]
Note18) Note18) Note18) Note18) Note18)
Factory Default
1 10 [msec] 0 [V] 0 [Hz] 10 [V] 60 [Hz] 10 [msec] 4 [mA] 0 [Hz] 20 [mA] 60 [Hz] 1 (A) 10 [msec] 0 [kHz] 0 [Hz] 10 [kHz]
P Pulse x2 P Freq y2 0
0 to 100 [kHz] 0 to FU1-30 [Hz] 0 to 100.00 [**] (None) (Half of x1) (Below x1) (None) (FreeRun) (Stop) 0.1 to 120 [sec] 0 1 2 (Speed-L) (Speed-M) (Speed-H) (XCEL-L) (XCEL-M) (XCEL-H) (Dc-Brake) (2nd Func) 1 2 0
Note18)
60 [Hz]
I/O-17
9411
Wire Broken
0 (None)
I/O-18
9412
Operating Selection at Loss of Freq. Reference Waiting Time after Loss of Freq. Reference
Lost Command
1 2
0 (None)
I/O-19
9413
Time Out
1.0 [sec]
I/O-20
9414
M1 Define
3 4 5 6 7
0 (Speed-L)
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 17) When DRV-04 is set to either V1, V1S, I or V1+I or Pulse, only selected item codes are displayed in I/O-1~I/O-19. 18) Only user unit displayed when APP-02 or APP-80 is set to [Yes], after APP-06 is set to one of I, V, Pulse, after then when one of I/O-86~I/O-88 is set to either speed, percent, Bar, mBar, kPa, Pa.
27
iP5A
Parameter Description
I/O GROUP
CODE Comm. Addr Description LCD Keypad Display
8 9 10 11 12 13 14 15 16 17 18 19 I/O-20 9414 Programmable Digital Input TerminalM1 Define 20 M1 Define 21 22 23 24 25 26 27 28 29 30 31 32 33 34 I/O-21 I/O-22 I/O-23 I/O-24 I/O-25 I/O-26 I/O-27 9415 9416 9417 9418 9419 941A 941B Programmable Digital Input TerminalM2 Define Programmable Digital Input TerminalM3 Define Programmable Digital Input TerminalM4 Define Programmable Digital Input TerminalM5 Define Programmable Digital Input TerminalM6 Define Programmable Digital Input TerminalM7 Define Programmable Digital Input TerminalM8 Define M2 Define M3 Define M4 Define M5 Define M6 Define M7 Define M8 Define
Setting Range
(Exchange) (-Reserved-) (Up) (Down) (3-Wire) (Ext Trip) (Pre-Heat) (iTerm Clear) (Open-loop) (Main-drive) (Analog hold) (XCEL stop) (P Gain2) (-Reserved-) (Interlock1) (Interlock2) (Interlock3) (Interlock4) (Speed_X) (RST) (BX) (JOG) (FX) (RX) (ANA_CHG) (Pre-Excite) (Ext PID Run) Same as I/O-20 Same as I/O-20 Same as I/O-20 Same as I/O-20 Same as I/O-20 Same as I/O-20 Same as I/O-20
Factory Default
0 (Speed-L)
28
CODE
I/O-28 I/O-29 I/O-30 Note19) I/O-31 I/O-32 I/O-33 I/O-34 I/O-35 I/O-36 I/O-37 I/O-38 I/O-39 I/O-40 I/O-41 I/O-42 I/O-50 I/O-51 I/O-52 Note20) I/O-53 I/O-54 I/O-55 I/O-56 I/O-57 I/O-58 I/O-59 I/O-60 I/O-61 I/O-62 I/O-63
Comm. Addr
941C 941D 941E 941F 9420 9421 9422 9423 9424 9425 9426 9427 9428 9429 942A 9432 9433 9434 9435 9436 9437 9438 9439 943A 943B 943C 943D 943E 943F
Description
Terminal Input Status Filtering Time Constant for Programmable Digital Input Terminals Jog Frequency Setting Step Frequency 4 Step Frequency 5 Step Frequency 6 Step Frequency 7 Step Frequency 8 Step Frequency 9 Step Frequency 10 Step Frequency 11 Step Frequency 12 Step Frequency 13 Step Frequency 14 Step Frequency 15 Acceleration Time 1 (for Step speed) Deceleration Time 1 (for Step speed) Acceleration Time 1 (for Step speed) Deceleration Time 2 Acceleration Time 3 Deceleration Time 3 Acceleration Time 4 Deceleration Time 4 Acceleration Time 5 Deceleration Time 5 Acceleration Time 6 Deceleration Time 6 Acceleration Time 7 Deceleration Time 7
Setting Range
00000000000/11111111111 2 to 1000 [msec]
Factory Default
00000000000 15 10 [Hz] 40 [Hz] 50 [Hz] 40 [Hz] 30 [Hz] 20 [Hz] 10 [Hz] 20 [Hz] 30 [Hz] 40 [Hz] 50 [Hz] 40 [Hz] 30 [Hz] 20 [sec] 20 [sec] 30 [sec] 30 [sec] 40 [sec] 40 [sec] 50 [sec] 50 [sec] 40 [sec] 40 [sec] 30 [sec] 30 [sec] 20 [sec] 20 [sec]
0 to FU1-30
I/O-70
9446
S0 Output Selection
S0 Mode
S0 Output Adjustment S1 Output Selection S1 Output Adjustment Frequency Detection Level Frequency Detection Bandwidth
I/O-76
944C
Aux Mode1
0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] (Frequency) (Current) (Voltage) (DC link Vtg) (Ext PID Out) 10 to 200 [%] Same as I/O-70 10 to 200 [%] 0 to FU1-30 [Hz] 0 to FU1-30 [Hz] (None) (FDT-1) (FDT-2) (FDT-3) (FDT-4) (FDT-5) (OL) (IOL)
0 (Frequency)
0 (None)
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 19) I/O-30~I/O-34 displayed only when one of I/O-20~I/O-27 is set to either JOG, Speed_L, Speed_M, Speed_H. I/O-35~I/O-42 displayed only when one of I/O-20~I/O-27 is set to Speed_X. 20) I/O-52~I/O-63 displayed only when one of I/O-20~I/O-27 is set to either XCEL_L, XCEL_M, XCEL_H. 21) I/O-74~I/O-75 displayed only when one of I/O-76~I/O-79 is set to either FDT-1~FDT5.
29
iP5A
Parameter Description
I/O GROUP
CODE Comm. Addr Description LCD Keypad Display
8 9 10 11 12 13 14 15 16 17 18 19 20
Setting Range
(Stall) (OV) (LV) (OH) (Lost Command) (Run) (Stop) (Steady) (INV line) (COMM line) (SSearch) (Ready) (MMC) Same as I/O-76 Same as I/O-76 Same as I/O-76 000 to 111 [bit] 00000000/11111111 0 to 9999 0 to 9999 0 (Power On Fan) 1 (Run Fan) 2 (Temper-Fan) 0 to 70 [] 0 (Speed) 1 (Percent) 2 (Bar) 3 (mBar) 4 (kPa) 5 (Pa) Same as I/O-86 Same as I/O-86 1 to 250 0 (1200 bps) 1 (2400 bps) 2 (4800 bps) 3 (9600 bps) 4 (19200 bps) 0 (None) 1 (FreeRun) 2 (Stop) 0.1 to 120 [sec] 2 to 1000 [msec] 00000000000/11111111111 1 to 1000 000 to 111 [bit] 0 to 255 [8C]
Factory Default
I/O-76
944C
Aux Mode1
0 (None)
Programmable Digital Output Terminal Define Programmable Digital Output Terminal Define Programmable Digital Output Terminal Define Fault Output Relay Setting (3A, 3B, 3C) Terminal Output Status Waiting time after Fault Output Relay On Waiting time after Fault Output Relay Off Fan Con Sel (37~90kW) Fan Temp (37~90kW)
Aux Mode2 Aux Mode3 Aux Mode4 Relay Mode Out Status Relay On Relay Off Fan Mode Fan Temper
I/O-86
9456
V1 Unit Sel
0 (Speed)
Current Input User Unit Selection Pulse Input User Unit Selection Inverter Number
0 (Speed) 0 (Speed) 1
I/O-91 Note22)
945B
Baud Rate
3 (9600 bps)
Operating Methodat Loss of Freq. Reference Waiting Time after Loss of Freq. Reference Communication Response Delay Time A or B Contact Input Time Overheat Trip Selection Motor Overheat Trip Temperature
COM Lost Cmd COM Time Out Delay Time In No/Nc Set In Check Time OH Trip Sel MO Trip Temp
0 (None) 1.0 [sec] 5 [msec] 00000000000 1 [msec] 010 [bit] 110 [8C]
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 22) 38400 bps can be set only when the external communication option card is installed. 23) Only I/O-92 ~ I/O-93 displayed when DRV-03/04 is set to [int485].
30
APP GROUP
CODE
APP-00 APP-01 APP-02 APP-03 Note25) APP-04 Note26)
Note24)
Comm. Addr
9700 9701 9702 9703 9704
Description
Jump to Desired Code # Application Mode Selection PID Operation Selection PID F Gain Selection PID Auxiliary Reference Mode Selection
Setting Range
1 to 99 (LCD Keypad Only) (None) (MMC) (No) (Yes) 0 to 999.9[%] (No) (Yes) (Keypad-1) (Keypad-2) (V1) (V1S) (I) (V1+I) (Pulse) (Int. 485) (Ext. PID) (I) (V1) (Pulse) 0 to 999.9 [%] 0 to 32.0 [sec] 0 to100 [msec] 0.00 to FU1-30 FU1-32 to APP-10 0.0 to 999.9 [%] 0.0 to 999.9 [%] 0.0 to 100.0 [%] (No) (Yes) (No) (Yes) 0 to 6000 [sec] 0 to 6000 [sec] 30 to FU1-30 [Hz] (Linear) (Square) (User V/F) 0 to 15 [%] 0 to 15 [%] 30 to 150 [%] FU2-28 to 200 [%] 50 to FU2-27 (Max 150%) 1 to 200 [A] * 1 to 4 * 0 to 7 0 to FU1-30
Factory Default
1 0 (None) 0 (No) 0.0 [%] 0 (No)
APP-05 Note27)
9705
2 (V1)
APP-06 APP-07 APP-08 APP-09 APP-10 APP-11 APP-12 APP-13 APP-14 APP-15 APP-17 APP-20 Note28) APP-21 APP-22 APP-23 APP-24 APP-25 APP-26 APP-27 APP-28 APP-29 APP-40 Note29) APP-41 APP-42 APP-43 APP-44
9706 9707 9708 9709 970A 970B 970C 970D 970E 960F 9711 9714 9715 9716 9717 9718 9719 971A 971B 971C 971D 9728 9729 972A 972B 972C
PID Feedback Signal Selection P Gain for PID Control I Gain for PID Control D Gain for PID Control High Limit Frequency for PID Control Low Limit Frequency for PID Control PID Output Scale PID P2 Gain P Gain Scale PID Output Inverse PID U Curve Feedback Select 2nd Acceleration Time 2nd Deceleration Time 2nd Base Frequency 2nd V/F Pattern 2nd Forward Torque Boost 2nd Reverse Torque Boost 2nd Stall Prevention Level 2nd Electronic Thermal Level for 1 minute 2nd Electronic Thermal Level for Continuous 2nd Rated Motor Current Number of Auxiliary Motor Run Display Aux. Motor Start Selection Operation Time Display on Auto Change The Number of Aux Motor Start Frequency of Aux. Motor 1
PID F/B PID P Gain PID I Time PID D Time PID Limit-H PID Limit-L PID Out Scale PID P2-Gain P Gain Scale Out Inverse PID U Fbk 2nd Acc Time 2nd Dec Time 2nd Base Freq 2nd V/F 2nd F-Boost 2nd R-Boost 2nd Stall 2nd ETH 1min 2nd ETH Cont 2nd R-Curr Aux Mot Run Starting Aux Auto Op Time Nbr Aux s Start Freq 1
0 (I) 1.0 [%] 10.0 [sec] 0.0 [msec] 60 .00 [Hz] 0.5 [Hz] 100.0 [%] 100.0 [%] 100.0 [%] 0 (No) 0 (No) 5 [sec] 10 [sec] 60 [Hz] 0 (Linear) 2 [%] 2 [%] 100 [%] 130 [%] 120 [%] 3.6 [A] * 1 * 4 49.99 [Hz]
0 1 0 1
0 1 2
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 24) MMC (Multi Motor Control) function is applied to inverters only for 5.5~90kW (7.5~125HP). 25) Only APP-03~APP-17 displayed when APP-02 is set to [Yes] (5.5~90kW/7.5~125HP). Only APP-03~APP-17 and APP-63~APP-65 displayed when APP-2 is set to [Yes] (110~450kW/150~600HP). 26) If APP-04 is set to no, DRV-04 setting will be reference of process PID. And APP-05 setting will be ignored. 27) If APP-04 is set, APP-04 will appear. And APP-05 setting value will be reference of process PID, DRV-04 setting will be ignored. 28) Only APP-20~APP-29 displayed only when one of I/O-20~I/O-27 is set to either 2nd Func . 29) Only APP-40~APP-71 displayed when APP-01 is set to [MMC].
31
iP5A
Parameter Description
APP GROUP
CODE
APP-45 APP-46 APP-47 APP-48 APP-49 APP-50 APP-51 APP-52 APP-53 APP-54 APP-55 APP-56 APP-57 APP-58 APP-59 APP-60 APP-61 APP-62 APP-63 APP-64 APP-65 APP-66 APP-67 APP-68 APP-69 APP-71 APP-74 APP-75 APP-76 APP-80
Comm. Addr
972D 972E 972F 9730 9731 9732 9733 9734 9735 9736 9737 9738 9739 973A 973B 973C 973D 973E 973F 9740 9741 9742 9743 9744 9745 9747 974A 974B 974C 9750
Description
Start Frequency of Aux. Motor 2 Start Frequency of Aux. Motor 3 Start Frequency of Aux. Motor 4 Start Frequency of Aux. Motor 5 Start Frequency of Aux. Motor 6 Start Frequency of Aux. Motor 7 Stop Frequency of Aux. Motor 1 Stop Frequency of Aux. Motor 2 Stop Frequency of Aux. Motor 3 Stop Frequency of Aux. Motor 4 Stop Frequency of Aux. Motor 5 Stop Frequency of Aux. Motor 6 Stop Frequency of Aux. Motor 7 Delay Time before Operating Aux Motor Delay Time before Stopping Aux Motor Accel Time when Number of Pump Decreases Decel Time when Number of Pump Increases PID Bypass Selection Sleep Delay Time Sleep Frequency Wake-Up Level Auto Change Mode Selection Auto Change Time Auto Change Level Inter-Lock Selection Pressure Difference for Aux Motor Stop PrePID Reference Frequency PrePID Exit Level PrePID Stop Delay Ext PID Operation Selection
Setting Range
Factory Default
49.99 [Hz] 49.99 [Hz] 49.99 [Hz] 49.99 [Hz] 49.99 [Hz] 49.99 [Hz] 20.00 [Hz] 20.00 [Hz] 20.00 [Hz] 20.00 [Hz] 15.00 [Hz] 15.00 [Hz] 15.00 [Hz] 5.0 [sec] 5.0 [sec] 2.0 [sec] 2.0 [sec] 0 (No) 60.0 [sec] 0.00 [Hz] 35.0 [%] 0 72:00 20.0 [Hz] 0 (No) 2 [%] 0 0 600 0 (No)
0 to FU1-30
APP-81 Note30) APP-82 APP-83 APP-85 APP-86 APP-87 APP-88 APP-89 APP-90 APP-91 APP-92 APP-93 APP-95 APP-97
9751 9752 9753 9755 9756 9757 9758 9759 975A 975B 975C 975D 975F 9761
Ext PID Reference Signal Selection Ext PID Reference Level Ext PID Feedback Signal Selection P Gain for ExtPID I Time for ExtPID D Time for ExtPID High Limit Frequency for ExtPID Control Low Limit Frequency for ExtPID Control ExtPID Output Scale ExtPID P2 Gain ExtPID P Gain Scale ExtPID F Gain ExtPID Output Inverse ExtPID Loop Time
Ext Ref Sel Ext Ref Perc Ext Fbk Sel ExtPID P Gain ExtPID I Time ExtPID D Time ExtPID lmt-H ExtPID lmt-L ExtPID Scale Ext P2 Gain Ext P Scale ExtPID F Gain ExtOut Inverse Ext Loop Time
0 1
0.0 to 999.9 [sec] 0.0 to 999.9 [sec] 0 to 600.0 [sec] 0 to 600.0 [sec] (No) (Yes) 0.0 to 9999 [sec] 0 to FU1-30 [Hz] 0.0 to 100.0 [%] 0, 1 (Aux), 2 (Main) 00:00 to 99:00 FU1-32 to FU1-30 [Hz] (No) (Yes) 0 to100 [%] 0 to FU1-30 0 to 100.0 [%] 0 to 9999 (No) (Yes) (I) (V1) (Pulse) (Key-Pad) 0 to 100.00 [%] (I) (V1) (Pulse) 0 to 999.9 [%] 0 to 32.0 [sec] 0 to 2000 [msec] 0 to 100.00 [%] 0 to 30.00 [%] 0 to 999.9 [%] 0 to 999.9 [%] 0 to 100.0 [%] 0 to 999.9 [%] (No) (Yes) 50 to 200 [msec]
3 (Key-Pad) 50.00 [%] 0 (I) 1.0 [%] 10.0 [sec] 0 [msec] 100.00 [%] 0 [%] 100.0 [%] 100.0 [%] 100.0 [%] 0.0 [%] 0 (No) 100 [msec]
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 30) Only APP-81~APP-97 displayed when APP-80 is set to [Yes].
32
Trial Run
Operation Example (1)
V/F Control + Analog Voltage Input (V1) + Operation via Terminal (FX/RX) Operation condition Control mode: V/F control Frequency command: 50 [Hz] analog input via V1 terminal Accel/Decel time: Accel15 [sec], Decel25 [sec] Drive mode: Run/Stop via FX/RX terminal, Control terminal: NPN mode
3P AC INPUT R (L1) S (L2) T (L3) G S0 M8 (RX) M7 (FX) M6 M5 M4 M3 M2 M1 CM Potentiometer 2 [kohm], 1/2W V+ V1 5G 3A 3C 3B 5G S1 U V W
Wiring
IM
S/W
Step
1 2 3 4 5
Parameter setting
Control Mode Selection Drive Mode Frequency Mode 50 [Hz] Freq Command Setting Accel/Decel Time
Code
FU2-60 DRV-3 DRV-4 DRV-0 DRV-1 DRV-2 Set it to 0 (V/F). Set it to Fx/Rx-1.
Description
Set V1 Analog input value in frequency mode. Set freq command 50 [Hz] via V1 (Potentiometer). Set Accel time to 15 [sec] in DRV-2. Set Decel time to 25 [sec] in DRV-3. Motor starts to rotate in forward direction at 50Hz with Accel time 15 [sec] when
Terminal FX
I/O-26
FX terminal is turned ON. Motor decelerates to stop with Decel time 25 [sec] when FX terminal is turned OFF. When RX terminal is turned ON motor starts to rotate in Reverse direction
Terminal RX
I/O-27
at 50 [Hz] with Accel time 15 [sec]. When it is OFF, motor decelerates to stop with Decel time 25 [sec].
33
iP5A
Trial Run
Operation Example (2)
V/F control + Analog input (V1S) + Operation via terminal FX/RX Operation condition Control mode: V/F control Frequency command: Setting 50 [Hz] via Analog input (V1S) Accel/Decel time: Accel time 15 [sec], Decel time 25 [sec] Drive mode: Run/Stop via FX/RX, Control terminal: NPN mode
3P AC INPUT R (L1) S (L2) T (L3) G S0 M8 (RX) M7 (FX) M6 M5 M4 M3 M2 M1 CM Potentiometer 2 [kohm], 1/2W V+ V1 V3A 3C 3B 5G S1 U V W
Wiring
IM
S/W
Step
1 2 3 4 5
Parameter setting
Control Mode Selection Drive Mode Frequency Mode Operating Frequency Command 50 [Hz] Setting Accel/Decel Time Setting
Code
FU2-60 DRV-3 DRV-4 DRV-0 DRV-1 DRV-2 Set it to 0 (V/F).
Description
Set it to 1 (Fx/Rx-1). Set it to 3 (V1S). Set 50 [Hz] via potentiometer (V1S). Set accel time to 15 [sec] in DRV-1 with decal time to 25 [sec] in DRV-2. When FX terminal is turned ON, motor rotating in forward direction starts
FX Terminal (M7)
IO-26
running at 50 [Hz] for 15 [sec]. When FX terminal is turned OFF, motor decelerates to stop for 25 [sec]. When RX terminal is turned ON, motor rotating in reverse direction starts
RX Terminal (M8)
IO-27
running at 50 [Hz] for 15 [sec]. When RX terminal is turned OFF, motor decelerates to stop for 25 [sec].
34
Dimensions
SV055iP5A (200/400V Class)
DRV
FU1
FU2
I/O
EXT
LC-200
MODE PROG ENTER
LE-200
RUN SHIFT
ESC SHIFT
STOP REV
RESET
FWD
PROG ENT
C1
STOP
RESET
RUN
C2
C3
7.5
W2 W1
H2 H1
D1
mm (inches)
Model
SV055iP5A-2/4
W1
150 (5.91)
W2
130 (5.12)
H1
284 (11.18)
H2
269 (10.69)
D1
156.5 (6.16)
C1
24 (0.98)
C2
24 (0.98)
C3
24 (0.98)
Enclosure Type
IP20 UL Type 1
DRV
FU1
FU2
I/O
EXT
LE-200
LC-200
MODE PROG ENTER
RUN SHIFT
ESC SHIFT
STOP REV
RESET
FWD
PROG ENT
STOP
RESET
RUN
SV150~300 iP5A-2/4
C1 C2 C3
H1 H2
7.5
W3 W2 W1
W3
D1
Model
SV075iP5A-2/4 SV110iP5A-2/4 SV150iP5A-2/4 SV185iP5A-2/4 SV220iP5A-2/4 SV300iP5A-2/4
W1
W2
W3
6 (0.23) 6 (0.23) 9 (0.35) 9 (0.35) 9 (0.35) 9 (0.35)
H1
H2
D1
C1
C2
C3
Enclosure Type
IP20 UL Type 1 IP20 UL Type 1 IP00 UL Open IP00 UL Open IP00 UL Open IP00 UL Open
200 (7.87) 180 (7.09) 200 (7.87) 180 (7.09) 250 (9.84) 230 (9.06) 250 (9.84) 230 (9.06) 304 (11.97)284 (11.18) 304 (11.97)284 (11.18)
284 (11.18)269 (10.69) 182 (7.16) 35 (1.37) 24 (0.98) 35 (1.37) 284 (11.18)269 (10.69) 182 (7.16) 35 (1.37) 24 (0.98) 35 (1.37) 385 (15.16)370 (14.57) 201 (7.91) 385 (15.16)370 (14.57) 201 (7.91) 460 (18.11)445 (17.52) 234 (9.21) 460 (18.11)445 (17.52) 234 (9.21) -
35
iP5A
Dimensions
SV150~300iP5A (UL Type 1 or UL Open Type with Conduit Option used, 200V/400V Class)
W1 W2 Note) Mounting NEMA 1 conduit option to the 15~90kW (20~125HP) Open Type meets NEMA 1 but does not comply with UL Enclosed Type 1. To that end, please purchase UL Type 1 product.
LC-200
MODE PROG ENTER
ESC SHIFT
STOP REV
RESET
FWD
H2 H1 H3
9 7.5
W3
Model
SV150iP5A-2/4 SV185iP5A-2/4 SV220iP5A-2/4 SV300iP5A-2/4
W1
250 (9.84) 250 (9.84) 304 (11.97) 304 (11.97)
W2
230 (9.06) 230 (9.06) 284 (11.18) 284 (11.18)
H1
200.8 (7.9) 200.8 (7.9) 236 (9.29) 236 (9.29)
H2
385 (15.16) 385 (15.16) 460 (18.11) 460 (18.11)
H3
370 (14.57) 370 (14.57) 445 (17.52) 445 (17.52)
D1
454.2 (17.88) 454.2 (17.88) 599.2 (23.59) 599.2 (23.59)
D2
201 (7.91) 201 (7.91) 234 (9.21) 234 (9.21)
C3
146 (5.74) 146 (5.74) 177.5 (6.98) 177.5 (6.98)
W1 W2
D1
LC-200
MODE PROG ENTER
ESC SHIFT
STOP REV
RESET
FWD
H1 H2
W3
Model
SV150, 185iP5A-4L SV220, 300iP5A-4L
W1
250 (9.84) 260 (10.23)
W2
186 (7.32) 220 (8.66)
W3
7 (0.28) 7 (0.28)
H1
403.5 (15.88) 480 (18.89)
H2
392 (15.43) 468.5 (18.44)
D1
261.2 (10.28) 268.6 (10.57)
36
D2
D1
SV150~SV300 iP5A (Built-in DCL Type, UL Type 1 or UL Open Type with Conduit Option used, 400V Class)
W1 W2
LC-200
MODE PROG ENTER
ESC SHIFT
STOP REV
RESET
FWD
H1
H2
W3
Model
SV150, 185iP5A-4L SV220, 300iP5A-4L
W1
250 (9.84) 260 (10.23)
W2
186 (7.32) 220 (8.66)
W3
7 (0.28) 7 (0.28)
H1
H2
D1
D2
188.4 (7.42) 188.8 (7.43)
475.5 (18.72) 392 (15.43) 261.2 (10.28) 552 (21.73) 468.5 (18.44) 268.6 (10.57)
LC-200
MODE PROG ENTER
ESC SHIFT
STOP REV
RESET
FWD
H1 H2
D1 W3 W2 W1 W3
Model
SV370, 450iP5A-4 SV550iP5A-4 SV370, 450iP5A-4L (Built-in DCLType) SV550iP5A-4L (Built-in DCL Type)
W1
300 (11.81) 300 (11.81) 300 (11.81) 300 (11.81)
W2
190 (7.48) 190 (7.48) 190 (7.48) 190 (7.48)
W3
9 (0.35) 9 (0.35) 9 (0.35) 9 (0.35)
H1
534 (21.02) 534 (21.02) 684 (26.92) 684 (26.92)
H2
D1
515 (20.28) 265.6 (10.46) 515 (20.28) 292.6 (11.52) 665 (26.18) 265.6 (10.46) 665 (26.18) 292.6 (11.52)
D2
D1
37
iP5A
Dimensions
SV370~550iP5A (UL Type 1 or UL Open Type with Conduit Option Used, 400V Class)
W1 W2 Note) Mounting NEMA 1 conduit option to the 15~90kW (20~125HP) Open Type meets NEMA 1 but does not comply with UL Enclosed Type 1. To that end, please purchase UL Type 1 product.
LC-200
MODE PROG ENTER
ESC SHIFT
STOP REV
RESET
FWD
H1
H2
W3
Model
SV370, 450iP5A-4 SV550iP5A-4 SV370, 450iP5A-4L SV550iP5A-4L
W1
300 (11.81) 300 (11.81) 300 (11.81) 300 (11.81)
W2
190 (7.48) 190 (7.48) 190 (7.48) 190 (7.48)
W3
9 (0.35) 9 (0.35) 9 (0.35) 9 (0.35)
H1
642 (25.28) 642 (25.28) 792 (31.18) 792 (31.18)
H2
515 (20.28) 515 (20.28) 665 (26.18) 665 (26.18)
D1
D2
265.6 (10.46) 163.4 (6.43) 292.6 (11.52) 190.4 (7.5) 265.6 (10.46) 163.4 (6.43) 292.6 (11.52) 190.4 (7.5)
LC-200
MODE PROG ENTER
ESC SHIFT
STOP REV
RESET
FWD
H1 H2
W3
W2 W1
W3
D1
Model
SV750, 900iP5A-4 SV750, 900iP5A-4L (Built-in DCL Type)
W1
370 (14.57) 370 (14.57)
W2
220 (8.66) 220 (8.66)
W3
9 (0.35) 9 (0.35)
H1
610 (24.02) 760 (29.92)
H2
586.5 (23.09) 736.6 (28.99)
D1
337.6 (13.29) 337.6 (13.29)
38
D2
D1
SV750, 900iP5A (UL Type 1 or UL Open Type with Conduit Option used, 400V Class)
W1 W2 Note) Mounting NEMA 1 conduit option to the 15~90kW (20~125HP) Open Type meets NEMA 1 but does not comply with UL Enclosed Type 1. To that end, please purchase UL Type 1 product.
LC-200
MODE PROG ENTER
ESC SHIFT
STOP REV
RESET
FWD
H1
H2
W3
D2
D1
mm (inches)
Model
SV750, 900iP5A-4 SV750, 900iP5A-4L (Built-in DCL Type)
W1
370 (14.57) 370 (14.57)
W2
220 (8.66) 220 (8.66)
W3
9 (0.35) 9 (0.35)
H1
767.5 (30.22) 917.5 (36.12)
H2
586.5 (23.09) 736.5 (28.99)
D1
337.6 (13.29) 337.6 (13.29)
D2
223.4 (8.8) 223.4 (8.8)
Enclosure Type
IP20 UL Type 1 IP20 UL Type 1
mm (inches)
Model
SV1100, 1320iP5A-4L SV1600iP5A-4L
W1
510 (20.08) 510 (20.08)
W2
381 (15.00) 381 (15.00)
W3
11 (0.43) 11 (0.43)
H1
H2
D1
Enclosure Type
IP00 UL Open IP00 UL Open
768.5 (30.26) 744 (29.29) 422.6 (16.64) 844 (33.23) 819.5 (32.26) 422.6 (16.64)
mm (inches)
Model
SV2200, 2800iP5A-4L
W1
690 (27.17)
W2
581 (22.87)
W3
14 (0.55)
H1
H2
D1
Enclosure Type
IP00 UL Open
mm (inches)
Model
SV3150, iP5A-4L SV3750, 4500iP5A-4L
W1
772 (30.39) 922 (36.30)
W2
500 (19.69) 580 (22.83)
W3
13 (0.51) 14 (0.55)
H1
H2
D1
Enclosure Type
IP00 UL Open IP00 UL Open
1140.5 (44.90) 1110 (43.70) 442 (17.40) 1302.5 (51.28)1271.5 (50.06) 495 (19.49)
39
iP5A
DB Unit
SV150DBU-2 SV220DBU-2 SV037DBH-2 SV037DBH-2, 2set SV150DBU-4 SV220DBU-4 SV037DBH-4
Dimension
Group 1. Group 2. Group 1.
Group 2.
CM G P
OH N N B2 G
Description
Ground terminal
G P/B1 B1
B2
B1
Group 2 -
Group 3 -
B2
Terminals
N P CM OH*
Terminals
G B2 B1 N P
Description
Connect to inverter terminal N Connect to inverter terminal P1 OH common Over Heat Trip output terminal (Open Collector output: 20mA, 27V DC)
Connect to DB Resistors B2 Connect to DB Resistors B1 Connect to inverter terminal N Connect to inverter terminal P1
40
DB Resistor
TH2 TH1
DB Unit
B2 B1 P
Short
B2 B1
G N
P1 (+)
P2 (+)
N (-)
Motor
M1 M2 M3 M4 M5 M6 M7 M8 CM
Max. output voltage: 12V Source max.: 30mA Sink max.: 20mA
S0 S1 5G
Output Frequency Meter Output Voltage Meter Common for output meter signal
3A 3C 3B
Common Terminal
DB resistor terminal
B1, B2
Description
Wire terminal properly based on wiring block diagram. Connect a DB resistor to the DB Unit s B1, B2 terminals. Thermal sensor terminal of DB resistor. Normal temperature (Ambient): Contact ON (TH1-TH2 closed) DB resistor overheated: Contact OFF (TH1-TH2 Open). Wire it to the inverter terminal defined as External Trip.
TH1, TH2
41
iP5A
4-M5 Mounting
IM
B1 B2 G B2 B1 N P
185
192
OHT
POWER
RUN
12.5
125 150
12.5
3.5
172
68.5
42
Group 2
(Unit: mm)
80
RESET POWER 245 OHT OCT 258 RUN 231.5 12 5.5 80 123 130 5
15 27
75
43
iP5A
44
External DB Resistor
iP5A do not have built-in DB resistor on power stack as factory installation. External DB Unit and Resistor (Optional) should be installed. See the following table for more details (ED: 5%, Continuous Braking Time: 15 sec). If Enable duty (%ED) is increased to 10%, use external DB resistor having twice Wattage rating.
Applied motor capacity (kW/HP)
5.5/7.5 7.5/10 11/15 15/20 18.5/25 22/30 30/40 5.5/7.5 7.5/10 11/15 15/20 18.5/25 22/30 30/40 37/50 45/60 55/75 75/100 90/125
[W]
700 1000 1400 2000 2400 2800 6400 700 1000 1400 2000 2400 2800 6400 6400 9600 9600 12800 12800
Type
Type3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 -
[W]
800 1200 2400 2400 3600 3600 1000 1200 2000 2400 3600 3600 -
Type
Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 -
200V
400V
Peripheral Device
MCCB (Molded Case Circuit Breaker) and MC (Magnetic Contactor)
Voltage Motor [kW]
5.5 7.5 11 15 18.5 22 30
Inverter Model
SV055iP5A-2 SV075iP5A-2 SV110iP5A-2 SV150iP5A-2 SV185iP5A-2 SV220iP5A-2 SV300iP5A-2
200V Class
45
iP5A
Peripheral Device
MCCB (Molded Case Circuit Breaker) and MC (Magnetic Contactor)
Voltage Motor [kW]
5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 220 280 315 375 450
Inverter Model
SV055iP5A-4 SV075iP5A-4 SV110iP5A-4 SV150iP5A-4 SV185iP5A-4 SV220iP5A-4 SV300IP5A-4 SV370iP5A-4 SV450iP5A-4 SV550iP5A-4 SV750iP5A-4 SV900iP5A-4 SV1100iP5A-4 SV1300iP5A-4 SV1600iP5A-4 SV2200iP5A-4 SV2800iP5A-4 SV3150iP5A-4 SV3750iP5A-4 SV4500iP5A-4
400V Class
AC Input Fuse
Voltage Motor [kW]
5.5 7.5 11 15 18.5 22 30 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 220 280 315 375 450
Inverter Model
SV055iP5A-2 SV075iP5A-2 SV110iP5A-2 SV150iP5A-2 SV185iP5A-2 SV220iP5A-2 SV300iP5A-2 SV055iP5A-4 SV075iP5A-4 SV110iP5A-4 SV150iP5A-4 SV185iP5A-4 SV220iP5A-4 SV300IP5A-4 SV370iP5A-4 SV450iP5A-4 SV550iP5A-4 SV750iP5A-4 SV900iP5A-4 SV1100iP5A-4 SV1300iP5A-4 SV1600iP5A-4 SV2200iP5A-4 SV2800iP5A-4 SV3150iP5A-4 SV3750iP5A-4 SV4500iP5A-4
AC Reactor [mH]
0.39 0.28 0.20 0.15 0.12 0.10 0.07 1.22 1.14 0.81 0.61 0.45 0.39 0.287 0.232 0.195 0.157 0.122 0.096 0.081 0.069 0.057 0.042 0.029 0.029 0.024 0.024
DC Reactor [A]
30 40 59 75 96 112 160 15 20 30 38 50 58 80 98 118 142 196 237 289 341 420 558 799 799 952 952
[mH]
1.37 1.05 0.74 0.57 0.49 0.42 0.34 5.34 4.04 2.76 2.18 1.79 1.54 1.191 0.975 0.886 0.753 0.436 0.352 Built-in Built-in Built-in Built-in Built-in 0.090 0.076 0.064
[A]
29 38 56 71 91 107 152 14 19 29 36 48 55 76 93 112 135 187 225
200V Class
400V Class
46
For your safety, please read user's manual thoroughly before operating. Contact the nearest authorized service facility for examination, repair, or adjustment. Please contact qualified service technician when you need maintenance. Do not disassemble or repair by yourself!
Safety Instructions
Any maintenance and inspection shall be performed by the personnel having expertise concerned.
Europe Middle East South West Asia South East Asia CIS America
+82-2-2034-4376 / [email protected] +82-2-2034-4901 / [email protected] +82-2-2034-4645 / [email protected] +82-2-2034-4707 / [email protected] +82-2-2034-4913 / [email protected] +82-2-2034-4377 / [email protected]
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: [email protected]
LS Industrial Systems Beijing Office Beijing, China Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: [email protected]
Specifications in this catalog are subject to change without notice due to continuous product development and improvement.
2010. 03