Data Sheet Lockshield Valve Type RLV - With Facility For Connection To Drain Tap
Data Sheet Lockshield Valve Type RLV - With Facility For Connection To Drain Tap
Data Sheet Lockshield Valve Type RLV - With Facility For Connection To Drain Tap
Application
Lockshield valve type RLV - with facility for connection to drain tap
RLV straight
RLV angle
Drain tap
By means of a RLV lockshield valve every radiator can be shut off individually to allow trouble-free maintenance or repair without affecting other radiators in the system. RLV lockshield valves are available in angle versions as well as straight versions. Finish: Nickel plated. RLV lockshield valves can be preset to limit the max. water flow within the following setting area: RLV 10: kvs = 1.8 m3/h RLV 15: kvs = 2.5 m3/h RLV 20: kvs = 3.0 m3/h
Factory setting is fully open valve. Dimensions correspond to DIN 3842-1. Accessories for RLV: - a drain tap for draining or filling of the radiator - a brass handwheel, used when radiators with RLV lockshield valves are removed. In order to avoid deposition and corrosion the composition of the hot system water must be in accordance to the VDI 2035 guide line (Verein Deutscher Ingenieure).
Principle
Flow limitation: kv-values (m3/h) for number of turns 1.5 0.9 2 1.2 1.3 1.8 2.5 1.5 1.7 2.2 3.0 1.6 1.9 2.4 3.5 1.7 2.1 2.6 4.0 1.8 2.3 2.8 kvs 1.9 2.5 3
System Radiator 0.25 0.5 0.75 1.0 3/8 1/2 3/4 3/8 1/2 3/4 0.15 0.35 0.45 0.6 0.2 0.2 0.4 0.4
RLV can be connected to PEX, AluPEX, steel or copper tubings by Danfoss compression fittings.
DKCD
Accessories
Product
Drain tap with 3/4" hose nozzle
Code no.
003L0152
Brass handwheel - temporarily replacement for the thermostat when the radiator is drained
013G3300
Mounting
RLV The RLV lockshield valve is intended for mounting on the outlet of the radiator. To enable subsequent draining of the radiator water, the lockshield valve should be mounted with its cover towards the front. Drain tap For mounting and operation of the drain tap, the following procedure is recommended: 1. Shut off the radiator inlet valve. As a safety precaution the thermostatic sensor should be replaced by a Danfoss manual shut off handle, code no. 013G3300.
2. Remove the cover and shut off the valve by means of a 6 mm Allen key. 3. Mount the drain tap and align the drain branch, which can revolve in any direction. 4. Open the valve for draining.
Setting
Setting of max. water flow: - Close the valve by means of a 6 mm Allen key. - Regulate the water flow by opening the valve. The capacity diagrammes on page 3 show the water flow at 1/4 - 4 turns and for fully open valve (kvs).
DKCD
Capacity
RLV DN 10
[mWg]
Q [l/h]
RLV DN 15
[mWg]
Q [l/h]
RLV DN 20
[mWg]
Q [l/h]
DKCD
Construction
Materials in contact with water Valve body and other metal parts O-ring Ms 58 EPDM
1. Cover 2. Guide sleeve 3. Shut-off cone 4. Valve body 5. Union nut 6. Nipple
Dimensions
D Rp / Rp / Rp /
d2 R / R / R /
H1 57 63 63
H2 40 41 40
L1 51 53 61
L2 75 80 92
L3 27 30 34
L4 51 57 65
L5 23 27 30
S1 22 27 32
S2 27 30 37
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in speci cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
DKCD