Product

Data

5F,H Compressors
05FY,HY Compressor Units
07FY,HY Condensing Units
P701 Condensers
5 to 150 Nominal Tons

5F, 5H COMPRESSORS

5F,H BARE
COMPRESSORS

5F,H
BASE-MOUNTED
COMPRESSORS

Carlyle Series 5F and 5H open-drive


compressors, used on Carrier compressor units and condensing units,
have been the workhorses of the air
conditioning and refrigeration industry for more than 50 years.
Series 5F and 5H are offered as bare
compressors and also as factoryassembled compressors, factoryassembled 05FY and 05HY compressor units, and factory-assembled
07FY and 07HY condensing units
with P701 condensers. Complete systems include motor, drive arrangement, control panel, and condenser
as required. Or, all components may
be ordered as separate sale items for
field assembly and installation.

Features/Benefits
The traditionally high quality of Carlyle
5F and 5H compressors provide efficient, reliable operation with unsurpassed performance, whatever the
application.

Series 5F, 5H Standard


Features
05FY,HY
COMPRESSOR
UNITS

07FY,HY
CONDENSING
UNITS

Copyright 2002 Carrier Corporation

3-year compressor warranty


used with most refrigerants
5 to 150-ton range
high operating efficiency
50 years of proven reliability
multi-drive application
multi-speed range
multi-motor/voltage combinations
multi-condenser combinations
multi-control-panel designs
factory assembled system or separate components for field assembly
6-week maximum availability

Form 5F,H-3PD

Custom-tailored systems
To fit your job requirements, Carrier
compressor and condensing units and
Carlyle open-drive compressors are
available in any combination. Customized selection enables you to order one
factory-assembled system that fits your
application, regardless of strict specifications and special power needs. For
field installation, you can also select
bare or base-mounted compressors
and order the balance of the system
components as separate items or supply your own.
Select quality by ordering:
5F and 5H Bare Compressors
5F and 5H Base-Mounted
Compressors
05FY and 05HY Compressor Units
07FY and 07HY Condenser Units

The 5F,H compressors


Use the 5F,H line of open compressors
to build a system tailored to your
equipment needs. These compressors
come in 12 sizes, ranging from 5 to
150 tons of cooling, so you can select
just the configuration you need. The
compressors building block design
lets you choose water-cooled, aircooled, or evaporative condensers.
The 5F,H compressors can use
Refrigerants 134a, 22 or 507/404A.
The compressor base accommodates
several motor sizes, with either belt or
direct drive, to fill both refrigerant and
job requirements.
Consider these additional advantages when choosing a 5F,H compressor:

operation, in turn, increases energy


efficiency and lowers utility bills.
Internal pressure capacity control is
standard on 5F40-5H126 units. External unloading, either pneumatic or
electric, can also be special ordered.
The 5F20 and 5F30 units offer external pressure unloading as an accessory
feature.

Save on maintenance costs:


A large-capacity, manually reversible oil pump, an automatic pressure
regulator, and an oil-filtering system
provide positive pressure lubrication for extended compressor life.
On all units, the oil passes through a
fine-mesh screen before reaching
the oil pump. A full-flow filter,
standard equipment on 5H120,
126 units, ensures clean flow of the
large-volume oil charge in these
compressors.

Suction gases stay in contact with


cylinder sleeve to keep oil cool and
reduce cylinder wear.
Simple field maintenance and
replacement of components such as
cylinder liners, pistons, and bearings
minimize field service costs and
equipment downtime.
A refined, 2-piece shaft/seal assembly virtually eliminates seal leakage.
Its carbon ring and neoprene bellows combine to provide a tight seal
against a highly polished seat. An oil
bath completely surrounds the seal
assembly, yielding maximum reliability over a wide temperature
range.
Efficient crankcase heater design
prevents both accumulation of liquid
refrigerant in the crankcase during
shutdown and the consequent dilution of the compressors oil supply.

Save on first costs:


With automatic, unloaded starting,
expensive high-torque motors are
unnecessary, reducing your initial
expense.

Save on operating costs:


The design of the crankcase casting
cylinder heads and valve plates
allows a smooth, unrestricted refrigerant flow through the compressor,
resulting in greater operating
efficiency.
As suction pressure changes, capacity control automatically reduces
compressor capacity to as low as
25% of full design load, reducing
horsepower requirements and
demand charges. This part-load

1 Fine Mesh Suction Screen


2 Precision-Ground Valve Plate Assembly
with Swedish Steel Ring Valves
3 Internal Capacity Control System
4 Time-Proven Shaft Assembly
5 Removable Cylinder Liners
6 Forged-Steel Connection Rods with
Replaceable Bearing Inserts

Oil-Level Sight Glass


Oil Drain
Reversible Oil Pump
Statically and Dynamically
Balanced Crankshaft
11 Unrestrictive Suction Gas Inlet
7
8
9
10

Features/Benefits (cont)
The P701 water-cooled
condensers

P701 AX condensers offer the


following features:

Totaline P701 water-cooled condensers are specifically designed for applications where high efficiency is desired
and economy is a prime consideration.
These condensers offer you maximum
adaptability in most comfort and process cooling applications. Available
sizes range in capacity from 5 to
400 tons of heat rejection and are all
shell-and-tube type condensers. Each
can be custom-matched with compressors charged with your choice of
Refrigerants 134a, 22, or 507/404A.
The P701 condensers serve as refrigerant reservoirs when a system is
not operating, eliminating the need for
separate receivers.

Large condenser models for fresh


water applications
Tubes made of high performance
copper with enhanced design, roller
expanded into multiple-grooved
tube sheet
Flange quality steel tube sheet precision machined for superior sealing
Condenser heads are cast iron or
fabricated steel
All water side connections are
female pipe thread except 12 in.,
14 in. and 16 in. which have
flanges
Adjustable nozzles for ease of
packaging
The refrigerant side is constructed
to the latest edition of the ASME
Section VIII Div 1 code and
stamped accordingly
Refrigerant side pressure is designed
for 350 PSI at 250 F
Water side design pressure is
150 PSI at 150 F

P701 CX condensers offer


the following features:
Small condenser models for fresh
water applications
Tubes made of high performance
copper with enhanced design, roller
expanded into multiple-grooved
tube sheet
Flange quality steel tube sheet precision machined for superior sealing
Condenser heads constructed of
nodular iron offer multi-pass design
for controlled cooling water velocity
All water side connections are
female pipe thread
The refrigerant side is constructed
to the latest edition of the ASME
Section VIII Div 1 code and
stamped accordingly
Refrigerant side pressure is designed
for 350 PSI minimum at 250 F
Water side design pressure is
300 PSI minimum at 150 F

Marine condensers offer the


following features:
Special order condensers for sea
water or brackish water applications
Tubes made of 90% copper, 10%
nickel with high performance
enhanced design, roller expanded
into grooved tube sheet
Tube sheet made of 90% copper,
10% nickel and precision machined
for superior sealing
Condenser heads constructed of
cast bronze to withstand corrosive
effects of sea water
Single pass 14 in. and 16 in. heads
are fabricated from steel and are
epoxy coated

All water side connections are


female pipe thread except 12 in.,
14 in. and 16 in. which have
flanges
The refrigerant side is constructed
to the latest edition of the ASME
Section VIII Div 1 code and
stamped accordingly
Refrigerant side is dual rated for
450 PSI at 150 F or 350 PSI at
250 F
Water side design pressure is
150 PSI at 150 F

Compressor and condensing


units
From a wide selection of compressors,
condensers, and accessories, Carrier
now provides a completely factoryassembled compressor unit that you
can combine with either a remote condenser or a factory-assembled condensing unit. Included in the factoryassembled compressor units (05FY,
05HY) are the compressor, steel base,
motor, control panel, and accessories.
The factory-assembled condensing
units (07FY,07HY) consist of all features of the compressor unit above
plus a condenser. On both the factoryassembled compressor unit and the
condensing unit, the required interconnecting wiring is included to minimize
field start-up time and costs. The
factory-assembled condensing units
also include the interconnecting
piping.

Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Physical Data and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-10
Field-Installed Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12,13
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13-24
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26,27

Model number nomenclature


05

HY

080

401

Type of Unit
05 Compressor
07 Condenser

Product
Modification

Type of Compressor
FY 5F Compressor
HY 5H Compressor

V-Ph-Hz
101 575-3-60
401 208-3-60
501 230-3-60
601 460-3-60

Compressor (Refer to
Bare Compressor Data
in Physical Data and
Dimensions Section)

Motor Horsepower
B 7-1/2 G 30
C 10
H 40
D 15
J 50
E 20
K 60
F 25

Drive Type
D Direct
B Belt

L 75
M 100
N 125
P 150

BARE COMPRESSOR

Direct
Drive
BASE-MOUNTED
COMPRESSOR
Belt
Drive

Direct
Drive
COMPRESSOR
UNITS
Belt
Drive

Direct
Drive
CONDENSING
UNITS
Belt
Drive

Included with units.


Available as accessories.
Not included.

5F20, 5F30
5F40
5F60
5H40-5H86
5H120, 5H126
5F40
5F60
5H40-5H86
5H120, 5H126
5F20, 5F30
5F40
5F60
5H40-5H80
5H120
05FY040
05FY060
05HY040-05HY086
05HY120-05HY126
05FY020, 05FY030
05FY040
05FY060
05HY040-05HY080
05HY120
07FY040
07FY060
07HY040-07HY086
07HY120, 07HY126
07FY020, 07FY030
07FY040
07FY060
07HY040-07HY080
07HY120
NOTES:
1. All units operate at 1750 rpm.
2. All components require final alignment in the field (at job site).
3. Electrical panel control voltage 115-1-60. Transformer not supplied.
4. All units are supplied with across-the-line starting.

Vibration isolators

Motor fastening set

Coupling guard

Coupling

Compressor flywheel

Motor pulley and belts

Belt guard

Mufflers

Partial-flow oil filter

Full-flow oil filter

Dual pressure switch

Oil safety switch

Compr internal relief valve

Crankcase heater relay

Crankcase heaters

Equalizer coverplates

Crankcase equalizers

Capacity control

Water-cooled oil cooler

Water-cooled heads

Shutoff valves

Control panel

Motor starter

Compressor motor

Condenser

Steel base

Compressor

COMPONENT PARTS

Physical data and dimensions

BARE COMPRESSORS
COMPRESSOR
OPER WT (lb)
COMPRESSOR
Nom Hp
Displ Cfm at 1750 Rpm
Cylinders
Oil (pt)
Bore (in.)
Stroke (in.)
Max Rpm
Min Rpm
Min Rpm, Cap. Control
High-Side Max Pressure
Low-Side Max Pressure
DIMENSIONS (in.)
A
B
C
Between
D
Mtg Hole CL
E
CONNECTIONS (in.)
Suction (ODF)
Discharge (ODF)

5F

5H

5H

20
175

30
215

40
355

60
400

40
610

60
795

80
1115

120
1580

46
610

3-10
19.0
2
5

5-15
29.8
3
5.5

7.5-20
39.8
4
12

10-30
59.6
6
13

20-50
92.4
4
18

30-75
138.4
6
21

40-100
184.7
8
41

60-150
276.8
12
61

40-60
115.5
4
18

21/2
2

31/4
23/4
1750
400 (Required for proper lubrication)
800
900
1100
900
800
400 psig
245 psig

600

700

800

900

157/8
183/4
183/4
53/4
10

18
207/8
18
53/4
10

211/2
19
201/8
12
8

231/2
21
241/2
137/16
8

301/2
241/2
29
151/2
11

311/2
271/4
297/8
17
11

437/8
241/2
32
29
11

47
273/8
347/8
29
11

11/8
7/
8

15/8
13/8

15/8
13/8

21/8
15/8

25/8
21/8

31/8
31/8

31/8
31/8

41/8
41/8

66
795

86
1115

60-100 75-125
173.0 231.0
6
8
21
41

126
1580
125-200
346.0
12
61

37/16

900

1100

900

301/2
241/2
29
151/2
11

311/2
271/4
297/8
17
11

437/8
241/2
32
29
11

47
273/8
347/8
29
11

25/8
21/8

31/8
31/8

31/8
31/8

41/8
41/8

LEGEND
Hp Horsepower
ODF Outside Diameter Female

Physical data and dimensions (cont)


P701 CX FRESH WATER CONDENSERS
A
B
C

E
ODF GAS
INLET
I

RELIEF
VALVE
F

1-19/32

WATER
CONNECTIONS
6-5/8
7-1/2

J LIQUID OUTLET (OPPOSITE SIDE)


1/8 NPT
VENT

2-7/32
WATER
INLET H

WATER
OUTLET
H

2
1/8 NPT
VENT

PHYSICAL DATA AND DIMENSIONS (in.)


UNIT
P7010605CX
0607CX
0610CX
0615CX
0620CX

279/16
279/16
399/16
519/16
519/16

233/4
233/4
353/4
473/4
473/4

31/2
31/2
31/2
31/2
31/2

2
2
2
2
2

163/8
163/8
283/8
403/8
403/8

LEGEND
FPT Female Pipe Thread
NPT National Pipe Thread
ODF Outside Diameter Female

F
FPT
1/
2
1/
2
1/
2
1/
2
1/
2

G
413/16
413/16
413/16
413/16
413/16

H
FPT
1
1
11/4
11/4
11/4

I
ODF
15/8
15/8
15/8
15/8
15/8

J
ODF
11/8
11/8
11/8
11/8
11/8

WEIGHT
(lb)
100
105
130
160
170

P701 AX FRESH WATER CONDENSERS


B
C

F
GAS P
INLET

M
SAFETY

A
WATER
OUTLET END
(1-PASS ONLY)

WATER
CONNECTIONS
R LIQUID OUTLET
(OPPOSITE SIDE)

S
WATER
OUTLET

S
WATER
OUTLET

S
WATER
INLET

J
L

S
WATER
INLET

S
WATER
OUTLET
(FAR END)

G
4-PASS

2-PASS

1-PASS

S
WATER
INLET

NOTE: Water inlet is on opposite end.

PHYSICAL DATA AND DIMENSIONS (in.)


UNIT
P7010625AX
0630AX
0840AX
0850AX
1065AX
1075AX
1290AX
12110AX
12140AX
12150AX
12200AX
14140AX
14165AX
14210AX
14270AX
14290AX
16200AX
16210AX
16230AX
16300AX
16360AX
16400AX

A
DIA
65/8
65/8
85/8
85/8
103/4
103/4
123/4
123/4
123/4
123/4
123/4
14
14
14
14
14
16
16
16
16
16
16

6313/16
6313/16
66
78
691/8
811/8
69
81
108
108
132
69
81
1153/8
1393/8
1393/8
69
81
81
1201/2
1441/2
1441/2

21/32
21/32
31/8
31/8
411/16
411/16
45/8
45/8
61/8
61/8
61/8
51/8
51/8
911/16
911/16
911/16
51/8
51/8
51/8
123/8
123/8
123/8

31/2
31/2
31/2
31/2
33/4
33/4
43/16
43/8
43/8
43/8
43/8
43/8
43/8
45/8
45/8
45/8
45/8
47/8
47/8
47/8
47/8
47/8

523/8
523/8
523/8
643/8
52
64
5015/16
627/16
867/16
867/16
1103/16
507/16
627/16
8511/16
10911/16
10911/16
4911/16
613/16
613/16
845/8
1085/8
1085/8

37/8
37/8
37/8
37/8
4
4
45/8
415/16
415/16
415/16
53/16
415/16
415/16
57/16
57/16
57/16
57/16
511/16
511/16
61/4
61/4
61/4

413/16
413/16
513/16
513/16
67/8
67/8
77/8
77/8
77/8
77/8
77/8
81/2
81/2
81/2
81/2
81/2
91/2
91/2
91/2
91/2
91/2
91/2

71/2
71/2
911/16
911/16
133/4
133/4
153/4
153/4
153/4
153/4
153/4
177/8
177/8
177/8
177/8
177/8
197/8
197/8
197/8
197/8
197/8
197/8

11/2
11/2
17/8
17/8
21/4
21/4
25/8
25/8

41/2
41/2

5
5
5

25/8
25/8
313/32
313/32
41/4
41/4
51/4
51/16
51/16
51/16
51/16
59/16
59/16
57/16
57/16
57/16
61/2
67/16
67/16
57/8
57/8
57/8

M
FPT
1/
2
1/
2
1/
2
1/
2
1/
2
1/
2
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4

N
65/16
65/16
75/16
75/16
83/8
83/8
93/8
93/8
93/8
93/8
93/8
10
10
10
10
10
11
11
11
11
11
11

P
R
S WEIGHT
ODF ODF
(lb)
15/8 11/8
2
170
21/8 13/8
2
195
1
3
1
2 /8 1 /8 2 /2
300
21/8 13/8 21/2
340
25/8 15/8
3
460
25/8 15/8
3
475
25/8 15/8
4
590
31/8 21/8
4
665
31/8 21/8
6*
855
1
1
3 /8 2 /8
6*
890
35/8 21/8
6*
1060
31/8 21/8
4*
895
35/8 21/8
4*
1410
41/8 25/8 6
1240
41/8 25/8 6
1420
41/8 25/8 6
1480
35/8 21/8
5*
1220
1
5
4 /8 2 /8
5*
1190
41/8 25/8
5*
1360
51/8 31/8 8
1723
51/8 31/8 8
1825
51/8 31/8 8
2085

LEGEND
FPT Female Pipe Thread
ODF Outside Diameter Female
*125 lb flat face flange.
150 lb raised face flange.

Physical data and dimensions (cont)

COMPRESSOR UNIT, DIRECT DRIVE (DD)

COMPRESSOR UNIT, BELT DRIVE (BD)

COMPRESSOR UNITS
5F

COMPRESSOR
OPER WT (lb)
BD
DD
COMPRESSOR
Nom Hp
Displ Cfm at 1750 Rpm
Cylinders
Oil (pt)
Bore (in.)
Stroke (in.)
Max Rpm
Min Rpm
Min Rpm, Cap. Control
High-Side Max Pressure
Low-Side Max Pressure
DIMENSIONS (in.)
BD
A
B
C
DD

A
B
C

5H

30

40

60

40

60

80

120

46

66

86

126

390

430

645
610

730
695

1045
1010

1225
1195

1780
1840

2345
2340

1010

1195

1840

2340

3-10
19.0
2
5

5-15
29.8
3
5.5

7.5-20
39.8
4
12

10-30
59.6
6
13

20-50
92.4
4
18

30-75
138.4
6
21

40-100
184.7
8
41

60-100
173.0
6
21

75-125
231.0
8
41

125-200
346.0
12
61

21/2
2

60-150 40-60
276.8
115.5
12
4
61
18
31/4

23/4
1750
400 (Required for proper lubrication)
800
900
1100
900
800
400 psig
245 psig

600

700

800

900

455/8
23
31

455/8
23
31

61
29
30

61
29
303/4

703/8
313/4
371/4

7115/16
323/4
38

78
451/8
577/8

80
49
46

603/4
29
30

611/8
29
303/4

7213/16
29
377/8

771/4*
29
341/2

943/4
35
46

975/8
35
457/8

LEGEND
BD Belt Drive
DD Direct Drive
*Length is 735/8 in. when using a 326T Frame or smaller motor.

5H

20

37/16

900

1100

900

7213/16
29
377/8

771/4
29
359/16

943/4
35
46

975/8
35
457/8

NOTES:
1. Operating weights include water and refrigerant. Unit is not factory
charged. Weights do NOT include motor.
2. Dimensions shown are 1 in. and are shown with the largest control box. Actual height and width may be less based on hp and voltage of control box. Full dimensional drawings available on request
for standard units. Certified drawings, which are specific to a unit
model number and show in depth detail, are available at an additional charge.
3. Base-mounted compressor dimensions are in the table on page 10.

CONDENSING UNIT DIMENSIONS

CONDENSING UNITS
DRIVE
COMPR
COND
P701
OPER WT (lb)
A
B
C
DRIVE
COMPR
COND
P701
OPER WT (lb)
A
B
C

DRIVE
COMPR
COND
P701
OPER WT (lb)
A
B
C
DRIVE
COMPR
COND
P701
OPER WT (lb)
A
B
C
DRIVE
COMPR
COND
P701
OPER WT (lb)
A
B
C

BELT (07FY,HY)
5F20

5F30

5F40

5F60

5H40

5H60

5H80

0610CX

0620CX

0620CX

0625CX

0840AX

0850AX

1065AX

0850AX

1065AX

1290AX

1290AX

12110AX

12140AX

14210AX

515
46
26
31

555
52
26
31

590
52
26
31

1090
69
267/8
423/8

1360
695/8
267/8
49

1845
81
311/2
661/2

2085
761/2
311/2
661/2

2055
811/8
327/16
725/8

2295
765/8
327/16
725/8

2520
765/8
327/16
725/8

3120
79
441/4
737/8

3180
85
441/4
737/8

3515
1153/8
441/4
737/8

3820
108
441/4
737/8

BELT (07FY,HY) (cont)


5H120
1290AX 12110AX 12140AX 14210AX
3720
79
48
741/8

3795
85
48
741/8

5F40

4085
108
48
741/4

4370
1153/8
48
741/4

5F60

DIRECT (07FY,HY)
5H46

5H40

5H60

0625CX

0840AX

0850AX

0850AX

1065AX

1065AX

1290AX

12110AX

1065AX

1290AX

12110AX

12140AX

1010
69
25
411/4

1190
70
25
471/4

1515
78
25
471/4

1735
837/8
301/2
73

2020
793/8
301/2
73

2020
793/8
301/2
73

2155
791/4
301/2
73

2225
851/4
301/2
73

2155
793/8
301/2
73

2320
791/4
301/2
73

2870
851/4
301/2
73

2930
108
301/2
73

DIRECT (07FY,HY) (cont)


5H80

5H66

5H86

1290AX

12110AX

12140AX

14210AX

1290AX

12110AX

12140AX

14210AX

12110AX

12140AX

14210AX

16230AX

2320
791/4
301/2
73

2870
851/4
301/2
73

2930
108
301/2
73

3235
116
301/2
73

3060
94
313/4
767/8

3120
94
313/4
767/8

3445
108
313/4
747/8

3950
1153/8
313/4
747/8

3120
94
313/4
767/8

3445
108
313/4
747/8

3750
1153/8
313/4
747/8

4360
94
313/4
767/8

DIRECT (07FY,HY) (cont)


5H120

5H126

12110AX

12140AX

14210AX

16230AX

14210AX

16230AX

3700
975/8
41
84

4000
975/8
41
84

4260
1153/8
41
84

4870
975/8
41
84

4260
1153/8
41
84

4870
975/8
41
84

NOTES:
1. Operating weights include water and refrigerant. Unit is not factory charged.
Weights do NOT include motor.

2. Dimensions shown are 1 and are shown with the largest control box. Actual
height and width may be less based on hp and voltage of control box. Full
dimensional drawings available on request for standard units. Certified
drawings, which are specific to a unit model number and show in depth
detail, are available at an additional charge.

Physical data and dimensions (cont)


DIRECT DRIVE UNIT BASES

BELT DRIVE UNIT BASES

B width dimension not shown in this view.

BASE-MOUNTED COMPRESSOR
COMPRESSOR
DIMENSIONS (in.)
BD
A
B
C
DD

A
B
C

5F

5H

30

40

60

40

60

80

120

46

66

86

126

381/4
205/8
281/2

381/4
205/8
281/2

481/8
251/8
255/8

481/8
261/4
303/4

573/4
311/4
371/4

591/4
243/8
341/16

651/4
451/8
421/4

671/8
48
431/2

481/8
211/2
241/2

481/4
211/2
303/4

593/8
241/2
371/4

607/8
273/8
3315/16

811/2
313/4
421/4

847/8
313/4
431/2

593/8
241/2
371/4

607/8
273/8
3315/16

811/2
313/4
421/4

847/8
313/4
431/2

LEGEND
BD Belt Drive
DD Direct Drive
NOTE: Dimensions shown are 1-inch.

10

5H

20

Field-installed accessories
300
200
100
0

80
60
40
20
0

80
60
40
20
0

400
500
600

100 120
140
160
180
200

100 120
140
160
180
200

CARRIER CONTROL PANEL

EQUALIZER COVERPLATE

40
80
160

200

WATER-COOLED OIL
COOLER (ACCESSORY)

120

Enhance your systems capabilities and


performance with the many quality
accessories available for the 5F,H line.
Carrier control panel (32C) for
05FY, 05HY, 07FY, or 07HY compressor and condensing units allows
precision monitoring and control of
compressor functions such as start-up
and operation, oil pressure, and shortcycle protection. Eliminates timeconsuming and costly field fabrication.
All control panels meet NEMA
(National Electrical Manufacturing
Association) requirements for enclosures (see current literature for details).
Water-cooled heads protect compressor by keeping heads cool when
compression ratios or discharge gas
temperatures are high (see ratings).
Partial-flow oil filter (available for
5H40 through 5H86 compressors)
helps prolong service life of the equipment. This filter supplements filtration
provided by the fine-mesh screen furnished as standard equipment on all
compressors.
Water-cooled oil cooler removes
excessive heat resulting from highly
super-heated suction gas or high compression ratios to prevent oil breakdown and increase life expectancy of
compressor and its components.
Crankcase equalizer coverplate
provides easy points for interconnecting gas and oil equalizer lines, for
equalizing pressures in compressor
crankcases on the same circuit.
Couplings connect ends of drive shaft
and driven unit, transmit torque, and
allow for a small amount of shaft misalignment. Couplings prevent damage
to bearings and seals and absorb compressor vibrations to prolong service
life.
Belt-drive package (motor pulley,
belts, and compressor flywheel) is available for compressor operation at
1750 rpm or at 1450 rpm with
1750 rpm motors. All components are
precision matched to provide optimum compressor performance with
minimum wear.
Crankcase heater and relay (separate items) prevent refrigerant from
diluting oil during shutdown to ensure
proper compressor lubrication.
Muffler attenuates sound and gas pulsations, resulting in low sound levels.
Vibration isolators prevent transmission of vibration to building
structure and provide unobtrusive
operation.
Motor fastening set to mount motor
to compressor base.

PARTIAL-FLOW OIL
FILTER (ACCESSORY)

11

Selection procedure (with example)


Performance data is given for Refrigerants 134a, 22, and
507/404A for all units.

Compressor unit
I Determine job requirements.
Example:
Given:
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . R-22
Cooling Load . . . . . . . . . . . . . . . . . . . . . 38 Tons
Saturated Suction Temp (SST) . . . . . . . . . . . .40 F
Saturated Discharge Temp (SDT) . . . . . . . . .120 F
II Select compressor unit.
Enter ratings table for desired refrigerant at
the required suction (SST) and discharge (SDT)
temperatures.
Example:
Enter ratings table for R-22, page 16. Read down
the table under 40 F SST and 120 F SDT to find a
compressor with the capacity to meet the 38-ton
load requirement. Select a 5H40 compressor.
III Obtain complete compressor performance
data from ratings table.
In this example, when selecting a condenser (air
cooled or water cooled), it must be able to handle
the Total Heat of Rejection (THR) of 47.5 tons. All
THR ratings equal 12,000 Btuh/ton. The brake
horsepower (BHP) of the motor required is 44.5
and a 50 horsepower motor or larger should be
chosen.

SST
40

COMPRESSOR PERFORMANCE
5H40
SDT
CAP.
BHP
120
38.0
44.5

THR
47.5

IV Consult rating notes for capacity adjustment


factors which may be required (pages 13,
23 and 24).

Condensing unit selection


When selecting a condensing unit, the rated compressor
capacity must be corrected to compensate for the available
refrigerant subcooling. A P701 condenser nominally provides 2F of refrigerant subcooling while the compressor
ratings are based on 15 F subcooling. The capacity rating
should be adjusted by .5% for each degree of subcooling
difference for R-22 and .6% for R-134a or R-507/404A.
Since there is a 13 F difference, the capacity must
be reduced by 6.5% for R-22 or 7.8% for R-134a or
R-507/404A.
I Determine job requirements.
Example:
Given:
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . R-22
Cooling Load . . . . . . . . . . . . . . . . . . . . . 17 Tons
Saturated Suction Temp (SST) . . . . . . . . . . . .40 F
Saturated Discharge Temp (SDT) . . . . . . . . .105 F

12

II Select compressor unit.


The load requirement must be corrected to utilize
the rating tables for unit selection.
Corrected Required Capacity = Required Load/
.935
Example:
Load Requirement
= 17 Tons
Corrected Required Capacity = 17 Tons/.935
= 18.2 Tons
Enter rating table for R-22. Under 40 F SST and
105 F SDT, select a 5F40 compressor. This selection meets the job requirements. Use direct interpolation where job requirements fall between the
values shown.
III Correct compressor unit rating for 2 F of
refrigerant subcooling available from the
P701 condenser.
Actual Capacity = Rated Capacity x .935
Actual THR
= Actual Capacity
+ (Rated BHP x .212)*
*The .212 multiplier is used to determine heat of
compression (in tons) for an open drive compressor.
Example:
Actual Capacity = 18.2 x .935
= 17 Tons
Actual THR
= 17 Tons + (17.3 x .212)
= 17 + 3.7
= 20.7 Tons
NOTE: Brake horsepower requirements are not
affected by variations in system subcooling.
IV Corrected compressor unit performance.
COMPR
5F40

SST
40

SDT
105

CAP.
17

BHP
17.3

THR
20.7

V Select condenser.
1. Determine the GTD (Greatest Temperature Difference), which is the temperature difference
between the entering water temperature and the
saturated discharge temperature. In this example,
20 F will be used which is typical.
2. Enter the condenser capacity and flow rate tables
for the desired GTD and THR. Convert THR to
Btuh by multiplying by 12,000. It is recommended to stay within the upper third of the condenser table selected. A P701-0625AX
condenser meets the job requirements.
NOTE: See condenser selection recommendations on page 13.
3. The required gpm for this example is 37 and the
pressure drop is 1.32 psid.
VI Consult rating notes for capacity adjustment
factors which may be required (pages 13, 23
and 24).

Selection notes
Compressor and condensing units
1. Saturated Suction Temperature The saturated
suction temperature used in selection of a compressor
or condensing unit should be the saturated temperature at the compressor. To obtain proper unit selection, line losses should be considered (suction and/or
discharge line loss).
2. R-22 applications require an oil cooler when (absolute) pressure ratio is greater than 5.0; oil cooler and
water-cooled heads required when discharge temperature is greater than 250 F.
R-134a applications require an oil cooler and watercooled heads when the discharge temperature is
greater than 275 F.
R-507/404A applications require an oil cooler when
the SST is less than 20 F and require an oil cooler

and water-cooled heads when the discharge temperature is greater than 275 F.
3. Condensing Unit Selection There are a number
of condensers that may be selected for each compressor for each refrigerant listed. Selection of the proper
condenser may depend on several factors:
a. Water flow rate
b. Pumping head
c. Condensing unit efficiency
d. First cost
Selecting a larger condenser provides for better operation under adverse conditions such as high condenser fouling or high entering-water temperatures. Unit capacity and
efficiency can also be increased at nominal flow rates over
utilization of a smaller condenser. Final selection should be
based on the present and future job requirements and individual job economics.

Performance data
Rating notes
Compressor and condensing units
1. Compressor ratings are based on 1750 rpm and
15 F subcooling.
2. Compressor performance must be adjusted for condensing units which provide a nominal 2 F of refrigerant subcooling (see Condensing Unit Selection).
3. Refrigerant temperatures shown are saturated temperatures corresponding to pressures indicated at
compressor. Actual gas temperatures are higher
because of superheat.
4. Capacities are based on actual suction gas temperatures to the compressor of 65 F for R-134a and
R-507/404A (this assumes superheat is obtained
from liquid-suction interchanger or in evaporator).
Capacity corrections for other than rated suction gas
temperatures may be obtained from Rating Basis and
Capacity Multipliers table, page 23.
5. Capacities for R-22 are based on 15 F suction gas
superheat, which normally occurs because of expansion valve operation and line losses. R-22 ratings can
be used without adjustment.
6. The discharge line loss on all 07FY, 07HY condensing units is negligible. The saturated discharge temperature (SDT) is therefore equal to the saturated
condensing temperature (SCT).
7. THR is in tons and equals 12,000 Btuh/ton.

Base condensers
1. The capacities listed in the Condenser Capacity and
Flow Rate tables are based on 105 SCT (Saturated
Condensing Temperature). When operating at other
SCTs between 90 F and 135 F, the change in condenser capacity is minimal. Contact your Carrier Factory Sales Representative for the exact capacity, if
required. Also, all the data points available in hard
copy format for R-22 are not available for R-134a
and R-507/404A. You can either interpolate or contact your Carrier Factory Sales Representative.
2. GPM shown in Condenser Capacity and Flow Rate
tables are based on .0005 total fouling factor. For
other fouling factors contact your Carrier Factory
Sales Representative.
3. Stay within the GPM shown in the tables. A GPM
below those listed can cause tube fouling and above
those listed can cause tube erosion.
4. Saturated Condensing Temperature (SCT) = Saturated Discharge Temperature (SDT) Discharge Line
Loss (F). Discharge line loss may occur when the condenser is remote from compressor.
5. Condenser nominal tons equals 14,400 Btuh. This
equates to 12,000 Btuh/ton at the evaporator plus
an additional 20% for heat of compression.

13

Performance data (cont)


CONDENSER CAPACITIES
UNIT
P701-

NOMINAL
TONS

LETTER
CODE

THR
(Btuh)

GPM

PRESSURE
DROP (PSI)

NO.
PASSES

SURFACE
(sq ft)

0605CX
0607CX
0610CX
0615CX
0620CX
0625AX
0630AX
0840AX
0850AX
1065AX
1075AX
1290AX
12110AX
12140AX
12150AX
12200AX
14140AX
14165AX
16200AX
14210AX
16210AX
16230AX
14270AX
14290AX
16300AX
16360AX
16400AX

5
7.5
10
15
20
25
30
40
50
65
75
90
110
140
150
200
140
165
200
210
210
230
270
290
300
360
400

A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
S
T
U
V
W
X
Y
Z

87,846
119,869
174,765
273,709
353,820
371,578
437,433
608,148
770,641
944,411
1,155,961
1,312,300
1,645,759
2,027,756
2,187,086
2,967,634
2,037,996
2,518,541
2,902,774
3,086,396
3,196,081
3,544,948
3,922,026
4,224,263
4,374,171
5,298,332
5,935,269

15
22.5
30
45
60
75
90
120
150
195
225
270
330
420
450
600
420
495
600
630
630
690
810
870
900
1080
1200

4.8
7.4
5.1
11.0
13.5
4.7
5.2
4.5
7.5
5.2
7.6
6.0
9.6
2.1
2.1
4.1
5.6
8.4
5.5
2.3
7.9
7.8
4.8
4.9
2.2
4.2
4.2

6
6
4
4
4
2
2
2
2
2
2
2
2
1
1
1
2
2
2
1
2
2
1
1
1
1
1

6.1
7.5
11.8
17.6
21.9
22.3
26.1
37.1
45.0
55.7
67.5
78.0
94.5
127.5
139.6
175.6
120.7
146.2
170.9
197.3
184.5
206.9
229.2
248.4
279.2
313.3
351.5

LEGEND
THR Total Heat of Rejection
NOTES:
1. Nominal tons per ARI standards. ARI Standards include 105 F
condensing temp, 85 F inlet cooling water, 14,400 Btuh/ton, .0005
total fouling factor with R-22 service.
2. P701-0615CX, P701-0620CX, P701-1290AX, P701-12110AX,
P701-14165AX and P701-16210AX units have excessive velocity
at ARI Standard flow rate. Flow rate shown is within acceptable
velocity limits.

14

PUMP
DOWN
(lb)
17.0
15.7
24.1
31.2
27.1
39.3
35.9
70.4
84.8
111.2
134.2
158.5
191.5
257.7
246.6
309.8
160.7
194.2
201.9
261.3
264.7
244.0
345.8
328.3
328.3
447.4
412.5

3. Pump down capacities based on 80% of free shell volume with


R-22 at 90 F (per ARI standards).
4. Consult Totaline sales representative for marine condenser
capacities.
5. Pressure drop is in psi. To convert to feet, multiply by 2.31.
6. Letter code refers to the condenser size shown as the last digit for
an 07FY/HY. New letter codes are current as of 3/1/2001.

COMPRESSOR RATINGS; R-134a


COMPRESSOR
SST
SDT
90
100
105
10
110
120
135
90
100
105
20
110
120
135
90
100
105
30
110
120
135
90
100
105
40
110
120
135

Cap.
2.9
2.7
2.5
2.4
2.1
1.8
3.9
3.6
3.4
3.2
2.9
2.5
5.0
4.6
4.4
4.3
3.9
3.3
6.4
5.9
5.7
5.5
5.0
4.4

5F20
Bhp
4.0
4.2
4.3
4.4
4.5
4.5
4.5
4.8
4.9
5.0
5.2
5.4
4.8
5.2
5.4
5.6
6.0
6.3
5.0
5.6
5.8
6.1
6.6
7.2

COMPRESSOR
SST
SDT
90
100
105
10
110
120
135
90
100
105
20
110
120
135
90
100
105
30
110
120
135
90
100
105
40
110
120
135

Cap.
20.6
18.7
17.8
16.9
15.2
12.6
27.4
25.1
24.0
22.9
20.7
17.5
35.7
32.9
31.5
30.2
27.5
23.6
45.7
42.3
40.7
39.0
35.8
31.0

5H60
Bhp
27.8
29.4
30.1
30.6
31.5
32.1
30.8
33.2
34.3
35.3
36.9
38.7
33.0
36.4
37.9
39.3
41.9
45.0
34.4
38.7
40.7
42.7
46.3
50.9

Bhp
Cap.
SDT
SST
THR

THR
3.8
3.6
3.4
3.3
3.1
2.7
4.8
4.6
4.4
4.3
4.0
3.6
6.0
5.7
5.6
5.4
5.1
4.7
7.4
7.1
6.9
6.8
6.4
5.9

THR
26.5
25.0
24.2
23.4
21.9
19.4
33.9
32.2
31.3
30.4
28.6
25.8
42.7
40.6
39.6
38.5
36.4
33.2
53.0
50.5
49.3
48.1
45.6
41.8

Cap.
4.4
4.0
3.8
3.6
3.2
2.7
5.8
5.4
5.1
4.9
4.4
3.7
7.5
6.9
6.7
6.4
5.8
4.9
9.5
8.9
8.5
8.2
7.5
6.5

Cap.
25.6
23.4
22.2
21.1
18.9
15.8
34.0
31.2
29.9
28.5
25.8
21.9
44.3
40.9
39.2
37.5
34.2
29.4
56.7
52.5
50.5
48.5
44.5
38.5

LEGEND
Brake Horsepower
Capacity (Tons)
Saturated Discharge Temperature (F)
Saturated Suction Temperature (F)
Total Heat of Rejection (Tons)

5F30
Bhp
6.0
6.3
6.4
6.5
6.7
6.7
6.6
7.1
7.3
7.5
7.8
8.1
7.1
7.8
8.1
8.4
8.9
9.5
7.4
8.3
8.7
9.1
9.8
10.7
5H66
Bhp
36.2
38.3
39.2
39.9
41.1
41.8
40.1
43.3
44.6
45.9
48.1
50.4
43.1
47.4
49.4
51.3
54.6
58.7
44.8
50.4
53.1
55.6
60.3
66.3

THR
5.7
5.4
5.2
5.0
4.7
4.1
7.2
6.9
6.7
6.5
6.1
5.4
9.0
8.6
8.4
8.1
7.7
7.0
11.1
10.6
10.4
10.1
9.5
8.7

Cap.
5.8
5.3
5.1
4.8
4.3
3.6
7.7
7.1
6.8
0.7
5.9
5.0
10.0
9.3
8.9
8.5
7.8
6.7
12.7
11.9
11.4
11.0
10.1
8.8

5F40
Bhp
7.9
8.3
8.5
8.6
8.8
8.9
8.7
9.4
9.6
9.9
10.3
10.7
9.4
10.3
10.7
11.0
11.7
12.5
9.8
10.9
11.5
12.0
13.0
14.2

5H80
THR Cap. Bhp
33.3 27.5 36.8
31.5 25.0 39.0
30.5 23.8 39.8
29.6 22.6 40.5
27.6 20.2 41.5
24.6 16.8 42.1
42.5 36.5 41.1
40.4 33.5 44.3
39.3 32.0 45.6
38.3 30.5 46.8
36.0 27.6 48.9
32.6 24.1 51.0
53.4 47.5 44.4
50.9 43.8 48.8
49.7 42.0 50.8
48.4 40.2 52.6
45.8 36.7 55.8
41.8 31.5 59.7
66.2 60.9 46.1
63.2 56.4 52.0
61.8 54.2 54.6
60.3 52.0 57.1
57.2 47.7 61.7
52.6 41.3 67.5

THR
7.5
7.1
6.9
6.6
6.2
5.5
9.6
9.1
8.8
8.6
8.1
7.3
12.0
11.4
11.2
10.9
10.3
9.4
14.8
14.2
13.9
13.5
12.8
11.8

THR
35.3
33.3
32.2
31.2
29.0
25.7
45.2
42.9
41.7
40.5
38.0
34.2
56.9
54.2
52.8
51.4
48.5
44.1
70.6
67.4
65.8
64.1
60.8
55.6

Cap.
8.7
8.0
7.6
7.2
6.5
5.4
11.6
10.6
10.2
9.7
8.8
7.5
15.0
13.9
13.3
12.8
11.7
10.0
19.2
17.8
17.1
16.4
15.1
13.2

Cap.
34.1
31.1
29.6
28.1
25.1
20.9
45.3
41.6
39.7
37.9
34.3
29.1
59.0
54.4
52.2
49.9
45.5
39.1
75.6
70.0
67.3
64.6
59.2
51.3

5F60
Bhp
11.7
12.3
12.6
12.8
13.1
13.2
13.0
14.0
14.4
14.7
15.4
16.0
14.0
15.3
15.9
16.5
17.5
18.7
14.5
16.3
17.1
17.9
19.3
21.2

5H86
Bhp
47.9
50.6
51.8
52.8
54.3
55.2
53.2
57.3
59.2
60.9
63.7
66.7
57.1
62.9
65.5
68.0
72.5
77.7
59.3
66.9
70.5
73.8
80.0
87.9

THR
11.2
10.6
10.2
9.9
9.2
8.2
14.3
13.6
13.2
12.8
12.1
10.9
18.0
17.1
16.7
16.3
15.4
14.0
22.2
21.2
20.7
20.2
19.2
17.6

Cap.
13.7
12.5
11.9
11.3
10.1
8.3
18.3
16.8
16.0
15.3
13.8
11.6
23.8
21.9
21.0
20.1
18.3
15.7
30.4
28.2
27.1
26.0
23.9
20.7

THR Cap.
44.3 41.3
41.8 37.6
40.5 35.8
39.3 34.0
36.7 30.4
32.6 25.2
56.6 54.8
53.7 50.3
52.3 48.1
50.8 45.9
47.8 41.5
43.2 35.1
71.1 71.4
67.8 65.9
66.1 63.2
64.4 60.5
60.9 55.1
55.6 47.3
88.1 91.3
84.2 84.7
82.2 81.4
80.2 78.1
76.2 71.6
69.9 62.1

5H40
Bhp THR
18.7 17.7
19.5 16.6
19.7 16.1
19.8 15.5
19.8 14.3
20.1 12.6
20.7 22.7
22.0 21.4
22.5 20.8
22.8 20.1
23.4 18.8
24.4 16.8
22.6 28.6
24.5 27.1
25.3 26.4
26.0 25.6
27.1 24.1
29.1 21.9
23.6 35.4
26.4 33.8
27.5 32.9
28.6 32.1
30.5 30.3
33.5 27.8

5H120
Bhp
THR
54.7
52.9
57.9
49.9
59.3
48.3
60.4
46.8
62.2
43.6
63.4
38.7
60.7
67.7
65.5
64.2
67.7
62.4
69.6
60.6
73.0
57.0
76.6
51.4
65.2
85.2
71.8
81.1
74.9
79.1
77.8
77.0
83.0
72.7
89.2
66.2
67.9 105.7
76.5 100.9
80.6
98.5
84.4
96.0
91.6
91.1
100.8
83.4

Cap.
17.1
15.5
14.7
13.9
12.5
10.3
22.7
20.8
19.8
18.9
17.1
14.4
29.5
27.2
26.1
24.9
22.7
19.5
37.7
34.9
33.6
32.2
29.6
25.6

Cap.
51.2
46.7
44.4
42.2
37.8
31.4
68.0
62.5
59.7
57.0
51.5
43.6
88.6
81.8
78.4
75.1
68.4
58.7
113.3
105.1
101.0
97.0
88.9
77.1

5H46
Bhp THR
24.3 22.2
25.7 20.9
26.3 20.3
26.8 19.6
27.6 18.3
28.1 16.3
26.8 28.4
28.9 26.9
29.9 26.2
30.7 25.4
32.3 23.9
33.8 21.6
28.8 35.6
31.6 33.9
32.9 33.0
34.2 32.2
36.5 30.5
39.2 27.8
30.0 44.0
33.6 42.1
35.3 41.1
37.0 40.1
40.1 38.1
44.2 35.0

5H126
Bhp
74.0
77.6
78.6
79.2
80.1
81.9
80.6
85.9
87.8
89.4
92.1
97.2
84.5
91.8
94.7
97.4
102.5
111.4
87.5
97.2
101.4
105.4
113.2
126.3

THR
67.0
63.1
61.1
59.0
54.7
48.7
85.1
80.7
78.3
75.9
71.1
64.3
106.5
101.3
98.5
95.7
90.2
82.3
131.9
125.7
122.5
119.3
112.9
103.9

NOTE: An oil cooler is recommended for all long stroke compressors


(5H46, 66, 86, 126).

15

Performance data (cont)


COMPRESSOR RATINGS; R-22
COMPRESSOR
5F20
SST
SDT Cap. Bhp
6.3
7.1
90
5.9
7.6
100
5.6
7.8
105
20
5.4
8.0
110
4.9
8.3
120
4.1
8.6
135
8.0
7.4
90
7.5
8.1
100
7.2
8.4
105
30
6.9
8.6
110
6.3
9.1
120
5.3
9.5
135
10.0
7.4
90
9.4
8.3
100
9.1
8.7
105
40
8.7
9.1
110
8.0
9.7
120
6.8 10.4
135
12.3
7.2
90
11.6
8.4
100
11.2
8.9
105
50
10.8
9.3
110
10.0 10.1
120
8.6 11.0
135
COMPRESSOR
SST
SDT
90
100
105
20
110
120
135
90
100
105
30
110
120
135
90
100
105
40
110
120
135
90
100
105
50
110
120
135

Bhp
Cap.
SDT
SST
THR

Cap.
46.0
42.5
40.8
39.2
36.0
31.6
57.6
53.6
51.6
49.6
45.7
40.2
70.9
66.2
63.9
61.5
56.9
50.1
85.9
80.5
77.8
75.1
69.6
61.5

5H60
Bhp
47.5
50.6
52.1
53.6
56.6
60.8
49.9
54.0
56.0
58.0
62.1
68.0
51.3
56.4
59.0
61.6
66.8
74.6
51.6
57.9
61.0
64.2
70.7
80.4

THR
7.8
7.5
7.3
7.1
6.7
5.9
9.6
9.2
9.0
8.8
8.2
7.4
11.6
11.2
10.9
10.7
10.1
9.0
13.9
13.4
13.1
12.8
12.1
10.9

Cap.
9.5
8.8
8.5
8.1
7.4
6.4
12.0
11.2
10.8
10.4
9.6
8.3
15.0
14.1
13.6
13.1
12.1
10.7
18.4
17.4
16.9
16.3
15.2
13.5

5F30
Bhp
10.5
11.3
11.6
11.9
12.4
13.0
10.9
12.0
12.5
12.9
13.6
14.4
11.1
12.4
13.0
13.6
14.5
15.7
10.8
12.5
13.2
13.9
15.2
16.7

5H66
THR Cap. Bhp
56.0 57.1 61.8
53.2 52.8 65.8
51.9 50.7 67.8
50.5 48.6 69.8
48.0 44.8 73.5
44.5 39.9 78.8
68.2 71.5 64.9
65.0 66.5 70.2
63.5 64.0 72.9
61.9 61.6 75.5
58.9 56.9 80.7
54.6 50.6 88.3
81.8 88.0 66.7
78.2 82.2 73.4
76.4 79.3 76.7
74.6 76.4 80.1
71.1 70.8 86.9
65.9 63.0 96.9
96.8 106.5 67.1
92.8 99.9 75.3
90.8 96.5 79.4
88.7 93.2 83.5
84.6 86.6 91.9
78.6 77.3 104.5

THR
70.2
66.7
65.0
63.4
60.4
56.7
85.3
81.4
79.5
77.6
74.0
69.4
102.1
97.7
95.6
93.4
89.3
83.6
120.8
115.8
113.4
110.9
106.1
99.4

LEGEND
Brake Horsepower
Capacity (Tons)
Saturated Discharge Temperature (F)
Saturated Suction Temperature (F)
Total Heat of Rejection (Tons)
Oil cooler and water-cooled heads required.

16

THR
11.7
11.2
10.9
10.6
10.0
9.1
14.3
13.8
13.5
13.1
12.5
11.4
17.3
16.7
16.4
16.0
15.2
14.0
20.7
20.0
19.7
19.3
18.4
17.0

Cap.
12.6
11.7
11.3
10.8
9.9
8.4
16.0
14.9
14.4
13.8
12.7
10.9
20.0
18.7
18.1
17.4
16.1
14.0
24.6
23.1
22.4
21.6
20.1
17.6

5F40
Bhp
14.0
15.0
15.4
15.9
16.6
17.6
14.6
15.9
16.6
17.1
18.2
19.6
14.7
16.5
17.3
18.0
19.4
21.3
14.3
16.5
17.5
18.5
20.3
22.7

5H80
Cap. Bhp
61.3 63.1
56.7 67.2
54.4 69.2
52.2 71.1
47.8 74.8
41.7 79.3
76.9 66.3
71.5 71.7
68.8 74.4
66.1 77.0
60.8 82.2
53.1 89.1
94.6 68.1
88.4 75.0
85.2 78.4
82.1 81.8
75.8 88.5
66.3 98.0
114.5 68.6
107.4 76.9
103.8 81.1
100.1 85.3
92.8 93.7
81.5 105.9

THR
15.6
14.9
14.6
14.2
13.4
12.1
19.1
18.3
17.9
17.5
16.6
15.1
23.1
22.2
21.7
21.3
20.2
18.5
27.6
26.6
26.1
25.6
24.4
22.4

Cap.
19.0
17.7
17.0
16.3
14.9
12.8
24.1
22.5
21.7
20.9
19.2
16.7
30.0
28.2
27.3
26.3
24.3
21.4
36.9
34.8
33.7
32.6
30.4
26.9

5F60
Bhp
20.9
22.5
23.2
23.8
24.6
25.4
21.6
23.9
24.9
25.7
27.0
28.3
21.7
24.7
26.0
27.1
28.9
30.8
21.0
24.8
26.4
27.9
30.3
32.9

THR
23.5
22.5
21.9
21.4
20.1
18.2
28.7
27.6
27.0
26.3
24.9
22.7
34.6
33.4
32.8
32.0
30.5
27.9
41.4
40.1
39.3
38.5
36.8
33.9

Cap.
30.6
28.3
27.2
26.1
24.0
21.2
38.4
35.7
34.4
33.1
30.5
27.0
47.3
44.2
42.6
41.1
38.0
33.7
57.3
53.7
51.9
50.1
46.5
41.3

5H40
Bhp
31.9
33.9
34.9
35.9
37.7
39.9
33.5
36.2
37.5
38.8
41.4
44.7
34.4
37.8
39.5
41.2
44.5
49.2
34.7
38.8
40.9
43.0
47.1
53.1

THR
37.4
35.5
34.6
33.7
32.0
29.7
45.5
43.4
42.4
41.3
39.3
36.5
54.6
52.2
51.0
49.8
47.5
44.1
64.6
61.9
60.6
59.2
56.5
52.6

Cap.
37.9
35.0
33.5
32.2
29.9
27.8
47.6
44.2
42.5
40.9
38.0
34.9
58.6
54.7
52.7
50.9
47.4
43.3
71.0
66.6
64.4
62.2
58.1
53.0

5H46
Bhp
41.5
44.1
45.3
46.6
49.0
52.3
43.5
47.0
48.7
50.4
53.8
58.6
44.8
49.2
51.4
53.6
58.0
64.4
45.0
50.4
53.2
55.9
61.4
69.6

THR
46.7
44.3
43.2
42.1
40.3
38.9
56.8
54.1
52.8
51.6
49.4
47.4
68.1
65.1
63.6
62.2
59.7
57.0
80.6
77.3
75.6
74.0
71.1
67.7

THR
74.7
71.0
69.1
67.3
63.7
58.5
90.9
86.7
84.6
82.5
78.2
72.0
109.0
104.3
101.8
99.4
94.5
87.1
129.1
123.7
121.0
118.2
112.6
104.0

Cap.
76.2
70.4
67.5
64.8
59.5
52.8
95.4
88.7
85.3
82.0
75.6
66.9
117.3
109.6
105.7
101.8
94.2
83.4
142.0
133.2
128.7
124.2
155.3
102.3

5H86
Bhp
82.1
87.4
90.0
92.5
97.0
101.7
86.2
93.3
96.7
100.1
106.5
114.4
88.6
97.5
101.9
106.3
114.8
125.9
89.2
100.0
105.5
110.9
121.5
136.1

THR
93.6
88.9
86.6
84.4
80.1
74.4
113.7
108.5
105.9
103.3
98.2
91.2
136.1
130.3
127.3
124.4
118.5
110.1
160.9
154.4
151.1
147.8
141.1
131.2

Cap.
92.1
85.2
81.8
78.4
71.8
62.3
115.4
107.3
103.3
99.3
91.4
79.6
141.9
132.6
127.9
123.2
113.8
99.6
171.8
161.1
155.7
150.3
139.3
122.6

5H120
Bhp
94.3
100.4
103.4
106.3
112.1
120.3
99.0
107.1
111.1
115.1
123.1
134.7
101.8
112.0
117.1
122.2
132.5
147.9
102.4
114.9
121.2
127.5
140.3
159.5

THR
112.1
106.5
103.7
101.0
95.6
87.9
136.4
130.1
126.9
123.7
117.5
108.2
163.5
156.4
152.8
149.2
141.9
131.0
193.5
185.5
181.4
177.4
169.1
156.4

Cap.
114.4
105.6
101.4
97.3
89.5
79.7
143.3
133.1
128.1
123.2
113.7
101.0
176.1
164.5
158.6
152.9
141.6
125.9
213.1
199.8
193.1
186.4
173.2
154.3

5H126
Bhp
122.6
130.6
134.5
138.2
145.2
153.6
128.7
139.3
144.6
149.7
159.5
172.5
132.3
145.6
152.3
158.9
171.8
189.7
133.1
149.4
157.5
165.8
181.9
204.9

THR
140.4
133.3
129.9
126.6
120.3
112.3
170.6
162.7
158.8
155.0
147.6
137.7
204.2
195.4
191.0
186.6
178.0
166.1
241.3
231.5
226.6
221.6
211.8
197.8

NOTE: An oil cooler is recommended for all long stroke compressors


(5H46, 66, 86, 126).

COMPRESSOR RATINGS; R-507/404A


UNIT
SST SDT
90
100
40 105
110
90
100
20
105
110
90
100
0 105
110
90
100
20 105
110

Cap.
1.0
0.8
0.7
0.6
2.1
1.9
1.8
1.7
3.9
3.5
3.4
3.2
6.6
6.0
5.8
5.5

5F20
Bhp
3.5
3.3
3.2
3.1
5.0
5.1
5.1
5.1
6.3
6.6
6.7
6.8
7.4
7.9
8.1
8.4

UNIT
SST SDT
90
40 100
105
110
90
100
20 105
110
90
100
0 105
110
90
100
20
105
110

Cap.
7.6
6.2
5.5
4.7
15.5
14.0
13.2
12.4
27.7
25.4
24.3
23.1
46.3
42.6
40.7
38.8

5H60
Bhp
22.1
21.3
20.9
20.5
33.1
33.3
33.4
33.4
42.6
44.3
45.0
45.8
50.2
53.8
55.4
57.0

Bhp
Cap.
SDT
SST
THR

THR
1.8
1.5
1.4
1.3
3.2
3.0
2.9
2.8
5.2
4.9
4.8
4.6
8.2
7.7
7.5
7.3

THR
12.2
10.7
9.9
9.1
22.5
21.1
20.3
19.5
36.8
34.8
33.8
32.8
57.0
54.0
52.5
50.9

Cap.
1.5
1.3
1.1
0.9
3.2
2.9
2.7
2.5
5.8
5.3
5.1
4.8
9.9
9.1
8.7
8.3

Cap.
9.4
7.8
6.9
6.0
19.3
17.5
16.5
15.5
34.5
31.6
30.2
28.7
57.5
52.9
50.6
48.2

5F30
Bhp
5.1
4.9
4.8
4.7
7.5
7.5
7.5
7.5
9.4
9.8
9.9
10.1
11.0
11.7
12.1
12.4

THR
2.6
2.3
2.1
1.9
4.8
4.5
4.3
4.1
7.8
7.4
7.2
7.0
12.3
11.6
11.3
10.9

5H66
Bhp THR
28.7 15.5
27.7 13.6
27.2 12.7
26.7 11.8
43.0 28.5
43.3 26.7
43.4 25.7
43.5 24.7
55.5 46.2
57.7 43.9
58.7 42.6
59.6 41.3
65.3 71.3
70.0 67.7
72.2 65.9
74.2 64.0

LEGEND
Brake Horsepower
Capacity (Tons)
Saturated Discharge Temperature (F)
Saturated Suction Temperature (F)
Total Heat of Rejection

Cap.
2.1
1.7
1.5
1.3
4.3
3.9
3.6
3.4
7.8
7.1
6.8
6.4
13.3
12.2
11.6
11.0

Cap.
10.1
8.3
7.3
6.3
20.7
18.7
17.7
16.6
37.0
33.9
32.4
30.8
61.8
56.8
54.3
51.8

5F40
Bhp
6.8
6.5
6.3
6.2
10.0
10.0
10.0
10.0
12.5
13.0
13.2
13.4
14.6
15.6
16.1
16.5

THR
3.5
3.1
2.8
2.6
6.4
6.0
5.8
5.5
10.4
9.9
9.6
9.3
16.3
15.5
15.0
14.6

5H80
Bhp THR
29.2 16.3
28.1 14.3
27.6 13.2
27.1 12.1
43.8 30.0
44.1 28.1
44.2 27.0
44.2 26.0
56.5 49.0
58.7 46.4
59.7 45.0
60.7 43.7
66.6 75.9
71.4 72.0
73.6 69.9
75.7 67.9

Cap.
3.1
2.5
2.2
1.9
6.5
5.8
5.5
5.2
11.7
10.7
10.2
9.7
19.9
18.2
17.4
16.6

Cap.
12.6
10.3
9.1
7.9
25.9
23.3
22.0
20.6
46.0
42.2
40.2
38.2
76.7
70.5
67.4
64.3

5F60
Bhp
10.2
9.7
9.4
9.2
14.9
14.9
14.9
14.9
18.7
19.4
19.8
20.1
21.8
23.3
24.1
24.8

THR
5.3
4.6
4.2
3.8
9.6
9.0
8.7
8.3
15.6
14.8
14.4
14.0
24.5
23.2
22.5
21.8

5H86
Bhp THR
37.9 20.6
36.5 18.1
35.8 16.7
35.2 15.4
57.0 37.9
57.4 35.5
57.6 34.2
57.7 32.9
73.5 61.6
76.5 58.4
77.9 56.7
79.2 55.0
86.7 95.1
93.0 90.3
95.9 87.8
98.6 85.2

Cap.
5.0
4.1
3.6
3.1
10.3
9.3
8.8
8.2
18.5
16.9
16.2
15.4
30.9
28.4
27.1
25.9

Cap.
15.2
12.5
11.1
9.6
31.1
28.1
26.5
24.9
55.5
50.9
48.6
46.2
92.7
85.2
81.5
77.7

5H40
Bhp
14.9
14.4
14.1
13.9
22.2
22.4
22.4
22.5
28.6
29.7
30.2
30.7
33.6
36.0
37.1
38.2

5H120
Bhp
43.3
41.6
41.0
40.2
65.3
65.8
65.9
66.0
84.3
87.7
89.2
90.7
99.5
106.7
110.0
113.2

THR
8.2
7.2
6.6
6.1
15.1
14.1
13.6
13.0
24.5
23.2
22.6
21.9
38.0
36.0
35.0
34.0

THR
24.4
21.4
19.8
18.2
45.0
42.1
40.5
38.9
73.4
69.5
67.5
65.4
113.8
107.9
104.8
101.7

Cap.
6.2
5.1
4.5
3.9
12.8
11.6
10.9
10.2
22.9
21.0
20.0
19.0
38.3
35.2
33.7
32.1

Cap.
18.9
15.6
13.8
11.9
38.6
34.9
33.0
31.0
68.9
63.2
60.3
57.3
114.9
105.8
101.1
96.4

5H46
Bhp
19.4
18.7
18.3
18.0
28.9
29.1
29.1
29.2
37.1
38.6
39.2
39.9
43.7
46.8
48.2
49.6

THR
10.3
9.0
8.4
7.7
18.9
17.7
17.1
16.4
30.8
29.2
28.4
27.5
47.6
45.1
43.9
42.6

5H126
Bhp
56.4
54.3
53.2
52.3
85.0
85.5
85.7
85.9
109.7
114.1
116.1
118.0
129.3
138.7
143.1
147.2

THR
30.8
27.1
25.1
23.0
56.7
53.1
51.2
49.2
92.2
87.4
84.9
82.4
142.4
135.2
131.5
127.7

NOTES:
1.
Shaded ratings require an oil cooler and water-cooled
heads.
2. An oil cooler is recommended for all long stroke compressors
(5H46, 66, 86, 126).
3. Oil cooler required when SST is below 20 F.

17

Performance data (cont)


CONDENSER CAPACITY AND FLOW RATES
R-22 (at 105 F) CONDENSING TEMPERATURE WITH .0005 TOTAL FOULING FACTOR
UNIT
P701-

0605CX

0607CX

0610CX

0615CX

0620CX

0625AX

0630AX

0840AX

0850AX

1065AX

GPM

4
7
10
13
16
19
22
8
11
14
17
20
23
26
10
15
20
25
30
35
40
15
20
25
30
35
40
45
15
20
25
30
35
40
45
25
35
45
55
65
75
85
30
40
50
60
70
80
90
40
60
80
100
120
140
50
70
90
110
130
150
100
120
140
160
180
200
220

0.4
1.2
2.3
3.7
5.5
7.5
9.9
1.1
2.0
3.1
4.4
6.0
7.8
9.7
0.7
1.5
2.5
3.7
5.2
6.9
8.8
1.5
2.6
3.8
5.4
7.1
9.0
11.2
1.1
1.8
2.8
3.8
5.1
6.5
8.1
0.7
1.2
1.9
2.7
3.7
4.8
6.0
0.7
1.2
1.8
2.5
3.4
4.3
5.3
0.6
1.3
2.2
3.3
4.5
6.0
1.1
1.9
3.0
4.4
5.9
7.6
1.6
2.2
2.9
3.7
4.6
5.6
6.6

LEGEND
GPM Gallons Per Minute
GTD Greatest Temperature Difference (F)
P
Change In Pressure (psi)

18

15 GTD
25,876
40,573
52,268
61,854
69,544
76,284
81,725
47,149
59,478
69,930
78,722
86,329
92,626
98,283
62,373
85,363
104,246
120,229
133,498
144,917
154,191
97,523
122,585
144,524
163,696
180,523
195,650
208,992
101,136
128,374
153,231
175,497
195,393
213,379
229,519
143,279
182,367
214,674
241,762
265,014
283,919
300,803
170,758
209,945
242,650
271,334
295,532
317,239
335,480
231,569
309,640
372,012
422,189
463,073
500,930
296,824
378,460
445,812
502,450
548,504
587,833
497,687
558,019
609,337
655,460
694,609
731,968
764,169

TOTAL HEAT OF REJECTION AT SPECIFIED GTD (F)


20 GTD
25 GTD
30 GTD
35 GTD
34,346
42,623
50,894
59,047
53,575
66,384
79,002
91,433
68,835
85,046
100,906
116,676
80,982
100,018
118,330
136,385
91,211
112,212
132,917
153,006
99,334
122,457
144,354
165,956
106,541
130,963
153,913
177,705
62,256
77,174
91,893
106,399
78,384
96,924
115,096
133,011
91,849
113,217
134,266
155,035
103,175
126,925
150,325
173,419
112,806
138,858
164,108
189,023
121,152
148,694
176,400
202,651
128,605
157,814
186,617
213,715
82,660
102,457
122,287
141,818
112,618
139,447
165,852
191,893
137,064
169,356
201,201
232,648
157,722
194,628
230,151
265,167
174,765
215,383
254,191
292,454
189,123
232,616
274,693
317,053
202,443
248,020
292,947
337,309
129,183
160,807
191,540
222,649
161,948
200,943
239,541
277,305
190,575
235,938
280,611
324,664
215,528
266,356
316,465
365,659
237,619
293,047
347,672
401,108
256,985
316,774
374,406
432,610
273,709
336,575
398,539
459,727
134,027
166,805
199,111
231,647
170,328
211,585
252,256
292,405
202,435
251,179
299,427
346,631
231,510
286,665
341,092
394,800
257,457
318,265
378,366
437,215
280,670
346,918
411,868
475,987
301,699
372,792
441,714
509,707
189,183
234,342
278,853
322,685
239,870
296,448
352,230
407,298
281,873
347,257
412,496
475,260
316,860
389,648
462,572
532,195
346,304
426,315
502,128
580,044
371,578
456,014
539,267
617,577
391,753
483,509
569,523
654,414
225,374
279,128
332,028
384,176
276,499
341,625
405,807
468,118
319,222
393,855
466,584
537,416
356,215
438,635
519,889
597,581
386,982
477,015
564,243
647,069
415,518
508,451
603,921
694,287
437,433
537,756
636,707
729,719
305,830
378,918
450,965
521,942
408,013
504,258
597,595
689,529
487,692
603,017
713,803
819,900
552,832
681,449
806,061
924,384
608,148
745,178
880,222
1,013,523
651,392
799,425
941,663
1,082,025
392,331
486,264
578,850
670,228
498,635
616,474
731,993
845,905
585,635
723,306
857,721
987,383
656,782
808,565
958,209
1,105,984
717,949
884,783
1,046,464
1,200,062
770,641
947,107
1,117,473
1,285,647
655,475
808,070
958,376
1,106,650
731,538
904,525
1,070,705
1,229,850
799,341
986,472
1,165,035
1,341,130
856,550
1,054,440
1,249,623
1,434,672
912,222
1,117,768
1,320,333
1,520,285
955,731
1,170,825
1,388,102
1,592,145
996,751
1,225,710
1,445,627
1,650,631

40 GTD
67,175
103,691
131,981
154,717
172,113
187,291
200,067
120,699
150,692
175,071
195,531
213,636
228,576
240,462
160,973
217,417
263,167
299,727
330,227
357,244
379,093
252,631
314,905
368,164
414,241
453,874
488,748
520,228
263,717
332,450
393,631
447,790
495,867
538,365
576,875
365,918
460,716
537,191
600,918
650,648
694,849
738,299
435,634
529,518
609,117
674,205
732,076
779,467
826,329
591,910
780,189
927,725
1,045,822
1,139,022
1,220,703
760,485
958,367
1,118,374
1,247,414
1,357,777
1,451,868
1,249,634
1,391,588
1,514,993
1,617,293
1,708,533
1,793,632
1,865,118

NOTES:
1. Total heat of rejection is in Btuh.
2. GTD is the difference between the condensing temperature and
the inlet water temperature.
3. P is in psi. To convert to feet, multiply by 2.31.

CONDENSER CAPACITY AND FLOW RATES (cont)


R-22 (at 105 F) CONDENSING TEMPERATURE WITH .0005 TOTAL FOULING FACTOR (cont)
UNIT
P701-

1075AX

1290AX

12110AX

12140AX

14140AX

12150AX

14165AX

12200AX

16200AX

14210AX

GPM

100
120
140
160
180
200
220
125
150
175
200
225
250
125
150
175
200
225
250
200
275
350
425
500
575
150
200
250
300
350
400
450
225
300
375
450
525
600
675
100
175
250
325
400
475
175
275
375
475
575
675
175
275
375
475
575
675
300
400
500
600
700
800
900

1.8
2.5
3.3
4.2
5.2
6.2
7.4
1.5
2.1
2.7
3.5
4.4
5.3
1.7
2.3
3.1
3.9
4.8
5.8
0.6
1.0
1.6
2.2
2.9
3.7
0.9
1.5
2.2
3.1
4.1
5.2
6.5
0.6
1.0
1.5
2.1
2.8
3.5
4.3
0.5
1.3
2.5
4.0
5.8
7.9
0.5
1.1
1.8
2.8
3.9
5.1
0.6
1.3
2.4
3.6
5.1
6.9
0.6
1.1
1.6
2.2
2.9
3.7
4.5

LEGEND
GPM Gallons Per Minute
GTD Greatest Temperature Difference (F)
P
Change In Pressure (psi)

15 GTD
549,242
620,641
684,010
740,636
790,161
832,768
873,638
647,708
727,950
801,122
865,203
920,475
973,062
709,443
806,243
891,444
968,319
1,036,223
1,100,217
1,001,127
1,227,329
1,409,736
1,556,958
1,679,131
1,785,789
837,468
1,024,922
1,180,023
1,315,964
1,429,599
1,531,322
1,615,835
1,115,708
1,340,371
1,528,485
1,676,685
1,814,346
1,925,912
2,012,271
653,019
1,020,301
1,311,461
1,545,317
1,734,022
1,888,436
1,036,407
1,443,277
1,761,534
2,009,806
2,216,727
2,389,837
1,024,624
1,420,618
1,734,267
1,975,785
2,176,714
2,344,233
1,517,254
1,830,461
2,083,261
2,304,057
2,480,970
2,637,269
2,785,070

TOTAL HEAT OF REJECTION AT SPECIFIED GTD (F)


20 GTD
25 GTD
30 GTD
35 GTD
723,666
894,725
1,064,037
1,229,536
816,646
1,008,988
1,195,572
1,379,434
898,961
1,108,478
1,310,356
1,514,172
970,480
1,193,714
1,413,701
1,630,852
1,031,523
1,272,666
1,502,922
1,730,059
1,091,177
1,341,161
1,587,674
1,821,717
1,143,861
1,399,460
1,662,009
1,910,686
851,897
1,052,844
1,247,755
1,443,202
957,665
1,181,564
1,399,753
1,612,247
1,050,925
1,293,509
1,529,077
1,764,923
1,130,819
1,392,139
1,645,384
1,895,198
1,202,857
1,480,758
1,754,871
2,014,720
1,270,146
1,556,383
1,838,443
2,116,837
935,822
1,158,675
1,378,012
1,593,021
1,061,146
1,311,985
1,559,368
1,798,741
1,172,494
1,449,312
1,717,584
1,982,106
1,270,209
1,567,302
1,860,345
2,142,651
1,362,848
1,676,315
1,985,238
2,290,194
1,441,382
1,772,096
2,103,464
2,420,017
1,315,969
1,625,774
1,931,178
2,229,385
1,608,045
1,982,676
2,352,045
2,704,787
1,845,046
2,265,246
2,687,795
3,087,802
2,033,727
2,491,961
2,954,691
3,388,991
2,198,496
2,682,488
3,173,108
3,657,631
2,324,867
2,855,407
3,362,094
3,862,159
1,104,779
1,367,476
1,625,473
1,880,768
1,348,299
1,664,135
1,978,055
2,282,311
1,550,353
1,915,099
2,265,790
2,611,549
1,718,611
2,120,895
2,504,871
2,883,491
1,868,143
2,299,754
2,708,794
3,129,046
1,991,541
2,444,151
2,890,336
3,330,900
2,112,964
2,578,846
3,049,759
3,490,559
1,467,119
1,813,040
2,150,604
2,483,462
1,756,172
2,165,306
2,568,678
2,953,928
1,998,193
2,460,469
2,898,293
3,348,127
2,187,086
2,689,272
3,184,458
3,649,584
2,353,276
2,883,226
3,405,512
3,921,048
2,497,970
3,060,678
3,598,318
4,128,647
2,630,528
3,200,063
3,780,874
4,354,531
863,988
1,075,136
1,284,549
1,488,236
1,346,893
1,668,492
1,985,663
2,298,685
1,723,877
2,132,322
2,526,493
2,921,219
2,022,692
2,497,840
2,954,947
3,405,763
2,273,809
2,788,416
3,295,339
3,795,567
2,472,537
3,036,448
3,592,558
4,130,103
1,370,530
1,699,143
2,022,971
2,342,462
1,900,667
2,348,235
2,789,344
3,217,610
2,314,216
2,845,078
3,367,805
3,883,355
2,641,826
3,243,681
3,836,775
4,422,170
2,911,067
3,566,859
4,213,194
4,851,251
3,112,286
3,841,096
4,524,378
5,198,771
1,354,070
1,678,702
1,998,149
2,313,249
1,871,931
2,313,491
2,741,744
3,171,255
2,273,442
2,797,067
3,312,944
3,821,973
2,589,891
3,183,902
3,769,536
4,325,191
2,848,763
3,496,108
4,134,381
4,734,756
3,057,721
3,760,097
4,434,731
5,063,607
1,993,877
2,462,665
2,920,225
3,371,081
2,402,416
2,965,530
3,496,911
4,036,389
2,732,006
3,359,473
3,977,847
4,588,129
3,012,589
3,710,107
4,382,864
5,015,617
3,250,710
3,990,250
4,700,497
5,401,112
3,459,476
4,224,991
4,979,263
5,700,870
3,625,707
4,453,153
5,243,277
6,023,187

40 GTD
1,392,800
1,560,856
1,710,591
1,838,835
1,954,402
2,052,717
2,145,306
1,632,703
1,827,351
1,997,960
2,141,908
2,271,172
2,379,001
1,806,411
2,038,119
2,243,254
2,428,676
2,582,240
2,732,636
2,516,832
3,052,573
3,482,486
3,817,573
4,108,083
4,322,409
2,130,479
2,582,434
2,952,835
3,257,263
3,527,334
3,745,417
3,937,867
2,804,138
3,347,060
3,755,280
4,132,598
4,430,503
4,652,365
4,881,361
1,694,373
2,607,208
3,304,471
3,850,932
4,289,800
4,637,316
2,657,876
3,639,661
4,392,400
4,978,075
5,451,971
5,865,201
2,623,657
3,587,662
4,309,151
4,873,334
5,327,175
5,721,592
3,815,758
4,569,118
5,166,653
5,670,941
6,092,993
6,413,044
6,740,668

NOTES:
1. Total heat of rejection is in Btuh.
2. GTD is the difference between the condensing temperature and
the inlet water temperature.
3. P is in psi. To convert to feet, multiply by 2.31.

19

Performance data (cont)


CONDENSER CAPACITY AND FLOW RATES (cont)
R-22 (at 105 F) CONDENSING TEMPERATURE WITH .0005 TOTAL FOULING FACTOR
UNIT
P701-

16210AX

16230AX

14270AX

14290AX

16300AX

16360AX

16400AX

GPM

200
275
350
425
500
575
650
225
300
375
450
525
600
675
300
400
500
600
700
800
900
300
425
550
675
800
925
475
625
775
925
1075
1225
1375
475
625
775
925
1075
1225
475
625
775
925
1075
1225
1375

1
1.8
2.8
4
5.3
6.9
8.5
1.1
1.8
2.7
3.7
4.9
6.2
7.7
0.8
1.4
2.1
2.8
3.7
4.8
5.9
0.7
1.4
2.2
3.1
4.3
5.5
0.7
1.2
1.7
2.3
3.0
3.8
4.7
1.0
1.6
2.4
3.2
4.2
5.3
0.8
1.4
2.0
2.7
3.6
4.5
5.5

LEGEND
GPM Gallons Per Minute
GTD Greatest Temperature Difference (F)
P
Change In Pressure (psi)

20

15 GTD
1,194,350
1,507,268
1,770,094
1,991,883
2,173,887
2,342,974
2,486,054
1,343,705
1,658,124
1,926,815
2,154,179
2,351,561
2,528,836
2,680,047
1,659,847
2,024,956
2,325,370
2,576,282
2,807,096
2,982,903
3,163,790
1,696,427
2,163,318
2,546,440
2,851,064
3,118,233
3,331,512
2,316,169
2,749,165
3,111,810
3,395,270
3,659,895
3,872,697
4,074,876
2,518,292
3,013,394
3,416,332
3,769,142
4,056,344
4,311,940
2,605,621
3,139,915
3,592,864
3,965,169
4,284,368
4,569,570
4,839,239

TOTAL HEAT OF REJECTION AT SPECIFIED GTD (F)


20 GTD
25 GTD
30 GTD
35 GTD
1,578,641
1,956,273
2,329,709
2,698,111
1,985,089
2,456,183
2,916,566
3,375,334
2,323,697
2,868,324
3,400,202
3,924,854
2,608,452
3,215,109
3,805,374
4,387,800
2,850,585
3,506,490
4,153,270
4,780,925
3,060,496
3,766,791
4,436,244
5,096,548
3,232,073
3,965,846
4,689,412
5,404,144
1,774,662
2,199,194
2,619,003
3,034,096
2,186,147
2,704,940
3,212,311
3,717,051
2,533,533
3,126,145
3,715,226
4,286,501
2,834,521
3,489,889
4,135,715
4,764,872
3,088,477
3,793,499
4,498,966
5,173,593
3,310,041
4,079,235
4,797,247
5,532,731
3,509,005
4,293,092
5,098,519
5,861,381
2,189,338
2,709,603
3,218,407
3,724,199
2,659,408
3,283,509
3,892,882
4,493,714
3,048,255
3,768,927
4,461,273
5,124,368
3,382,754
4,164,316
4,921,708
5,668,965
3,655,656
4,506,963
5,312,992
6,108,043
3,899,223
4,781,048
5,660,710
6,487,671
4,119,905
5,036,865
5,940,587
6,832,761
2,238,151
2,771,577
3,295,118
3,812,421
2,846,526
3,519,423
4,171,405
4,814,028
3,337,925
4,106,608
4,863,922
5,611,202
3,733,082
4,601,424
5,442,767
6,241,750
4,070,090
4,987,248
5,891,008
6,783,032
4,356,253
5,341,138
6,312,257
7,246,436
3,039,869
3,759,339
4,445,216
5,137,081
3,604,853
4,434,163
5,264,683
6,057,206
4,054,506
5,000,040
5,894,968
6,777,151
4,458,625
5,458,362
6,443,346
7,390,511
4,783,503
5,860,457
6,922,151
7,909,981
5,032,227
6,173,035
7,298,037
8,373,584
5,286,951
6,479,584
7,615,195
8,735,819
3,311,712
4,096,515
4,860,189
5,618,421
3,954,287
4,880,307
5,771,694
6,672,864
4,477,293
5,505,721
6,535,813
7,519,583
4,924,974
6,062,656
7,140,653
8,248,700
5,308,452
6,514,437
7,648,327
8,822,102
5,615,111
6,864,968
8,096,719
9,312,672
3,432,065
4,247,606
5,052,103
5,838,210
4,124,948
5,103,101
6,050,035
6,983,882
4,709,650
5,794,296
6,862,846
7,917,186
5,186,929
6,409,377
7,575,035
8,725,168
5,611,293
6,918,043
8,155,234
9,375,599
5,988,678
7,324,212
8,671,764
9,938,639
6,301,762
7,704,446
9,086,817
10,451,466

40 GTD
3,062,287
3,823,536
4,442,995
4,963,190
5,378,156
5,748,665
6,077,054
3,442,551
4,210,543
4,850,302
5,385,954
5,862,392
6,259,915
6,581,106
4,218,564
5,086,777
5,798,307
6,407,079
6,893,203
7,346,606
7,664,767
4,323,115
5,448,155
6,326,541
7,061,758
7,664,521
8,169,269
5,802,897
6,838,959
7,647,698
8,325,127
8,884,406
9,436,001
9,801,754
6,367,262
7,540,194
8,490,628
9,252,776
9,925,908
10,514,506
6,613,309
7,905,841
8,958,654
9,818,054
10,580,803
11,254,399
11,800,277

NOTES:
1. Total heat of rejection is in Btuh.
2. GTD is the difference between the condensing temperature and
the inlet water temperature.
3. P is in psi. To convert to feet, multiply by 2.31.

CONDENSER CAPACITY AND FLOW RATES (cont)


R-134a (at 105 F) CONDENSING TEMPERATURE WITH .0005 TOTAL FOULING FACTOR
UNIT
P7010605CX
0607CX
0610CX
0615CX
0620CX
0625AX
0630AX
0840AX
0850AX
1065AX
1075AX
1290AX
12110AX
12140AX
14140AX
12150AX
14165AX
12200AX
16200AX
14210AX
16210AX
16230AX
14270AX
14290AX
16300AX
16360AX
16400AX

GPM
GTD
THR
P

GPM
4
22
8
26
10
40
15
42
15
45
25
85
30
90
40
140
50
150
100
220
100
220
125
250
125
250
200
575
150
450
225
675
100
475
175
675
175
675
300
900
200
650
225
675
300
900
300
925
475
1375
475
1225
475
1375

LEGEND
Gallons Per Minute
Greatest Temperature Difference (F)
Total Heat of Rejection
Change In Pressure (psi)

P
0.43
9.69
1.08
9.55
0.69
8.57
1.50
9.64
1.07
7.88
0.65
5.83
0.71
5.16
0.61
5.83
1.04
7.41
1.55
6.44
1.75
7.21
1.45
5.17
1.62
5.71
0.57
3.61
0.86
6.32
0.61
4.20
0.47
7.74
0.47
4.97
0.58
6.71
0.62
4.42
1.00
8.25
1.04
7.48
0.81
5.68
0.73
5.37
0.69
4.53
0.97
5.13
0.82
5.33

TOTAL HEAT OF REJECTION AT SPECIFIED GTD (F)


15 GTD
40 GTD
P
THR
THR
25,765
0.44
66,796
80,103
10.06
194,621
46,790
1.12
119,453
96,365
9.90
234,015
62,074
0.71
159,840
151,198
8.93
369,084
96,870
1.56
251,118
197,657
10.04
490,954
100,679
1.11
262,189
226,118
8.18
565,547
142,136
0.68
361,781
294,664
6.12
717,671
169,332
0.74
430,974
328,979
5.41
804,474
229,741
0.64
585,906
487,215
6.10
1,186,682
294,477
1.08
752,237
576,477
7.77
1,414,060
491,308
1.62
1,231,276
748,299
6.75
1,811,718
543,235
1.83
1,371,900
857,022
7.56
2,089,682
640,243
1.51
1,610,509
949,116
5.38
2,331,313
702,533
1.68
1,781,996
1,081,660
5.95
2,670,390
989,938
0.60
2,484,282
1,746,399
3.84
4,222,703
829,800
0.89
2,106,140
1,583,375
6.60
3,828,377
1,102,892
0.64
2,759,028
1,966,220
4.46
4,725,153
648,134
0.49
1,684,102
1,852,532
8.09
4,517,159
1,029,404
0.49
2,632,546
2,340,751
5.27
5,700,528
1,017,399
0.61
2,597,916
2,295,546
7.02
5,557,759
1,500,798
0.65
3,767,346
2,723,529
4.65
6,531,613
1,184,433
1.04
3,029,886
2,421,220
8.66
5,912,984
1,331,505
1.08
3,406,100
2,629,070
7.83
6,410,453
1,644,295
0.85
4,168,315
3,074,944
6.00
7,495,165
1,681,478
0.76
4,269,982
3,264,221
5.66
7,943,303
2,288,601
0.73
5,705,596
3,961,437
4.80
9,566,629
2,490,601
1.03
6,270,314
4,191,020
5.45
10,215,657
2,579,947
0.86
6,522,230
4,703,510
5.64
11,464,852
NOTES:
1. Total heat of rejection is in Btuh.
2. GTD is the difference between the condensing temperature and
the inlet water temperature.
3. P is in psi. To convert to feet, multiply by 2.31.

21

Performance data (cont)


CONDENSER CAPACITY AND FLOW RATES (cont)
R-507/404A (at 105 F) CONDENSING TEMPERATURE WITH .0005 TOTAL FOULING FACTOR
UNIT
P7010605CX
0607CX
0610CX
0615CX
0620CX
0625AX
0630AX
0840AX
0850AX
1065AX
1075AX
1290AX
12110AX
12140AX
14140AX
12150AX
14165AX
12200AX
16200AX
14210AX
16210AX
16230AX
14270AX
14290AX
16300AX
16360AX
16400AX

GPM
GTD
THR
P

22

GPM
4
22
8
26
10
40
15
42
15
45
25
85
30
90
40
140
50
150
100
220
100
220
125
250
125
250
200
575
150
450
225
675
100
475
175
675
175
675
300
900
200
650
225
675
300
900
300
925
475
1375
475
1225
475
1375

LEGEND
Gallons Per Minute
Greatest Temperature Difference (F)
Total Heat of Rejection
Change In Pressure (psi)

P
0.43
9.69
1.08
9.56
0.69
8.57
1.50
9.64
1.07
7.88
0.65
5.83
0.71
5.17
0.61
5.83
1.04
7.41
1.55
6.44
1.75
7.21
1.45
5.17
1.62
5.71
0.57
3.61
0.86
6.32
0.61
4.20
0.47
7.74
0.47
4.97
0.58
6.71
0.62
4.42
1.00
8.25
1.04
7.48
0.81
5.69
0.73
5.37
0.69
4.53
0.98
5.14
0.82
5.33

TOTAL HEAT OF REJECTION AT SPECIFIED GTD (F)


15 GTD
40 GTD
P
THR
THR
25,582
0.44
66,021
76,649
10.07
186,012
46,132
1.12
117,295
92,293
9.91
223,811
61,395
0.71
157,440
145,885
8.93
353,223
96,015
1.56
247,451
191,905
10.05
471,557
99,591
1.11
258,740
220,172
8.19
547,035
140,108
0.68
355,018
283,698
6.13
680,343
166,854
0.74
422,296
317,371
5.41
764,927
226,617
0.64
575,438
469,123
6.12
1,133,013
290,154
1.08
737,603
556,359
7.78
1,346,139
481,415
1.62
1,195,454
719,947
6.75
1,727,631
532,609
1.83
1,339,365
827,576
7.57
2,001,385
626,889
1.51
1,563,267
916,892
5.39
2,235,009
690,314
1.69
1,742,825
1,048,796
5.96
2,558,547
969,692
0.60
2,419,279
1,675,473
3.84
4,013,472
816,842
0.89
2,060,332
1,513,513
6.61
3,655,576
1,083,086
0.64
2,693,371
1,883,280
4.46
4,481,024
643,291
0.49
1,663,120
1,788,919
8.10
4,326,399
1,016,231
0.49
2,588,503
2,253,177
5.28
5,402,854
1,004,120
0.61
2,553,079
2,208,564
7.02
5,299,788
1,471,001
0.65
3,670,893
2,612,665
4.65
6,258,033
1,168,653
1.04
2,974,120
2,333,933
8.67
5,653,432
1,313,736
1.08
3,343,356
2,530,572
7.84
6,139,566
1,616,728
0.85
4,073,584
2,958,091
6.01
7,149,523
1,655,375
0.76
4,184,727
3,144,178
5.67
7,586,650
2,238,728
0.73
5,565,050
3,792,706
4.80
9,070,571
2,441,137
1.03
6,123,263
4,031,866
5.45
9,774,892
2,534,088
0.86
6,380,518
4,524,881
5.65
10,936,480
NOTES:
1. Total heat of rejection is in Btuh.
2. GTD is the difference between the condensing temperature and
the inlet water temperature.
3. P is in psi. To convert to feet, multiply by 2.31.

STANDARD RATINGS FOR COMPRESSORS

COMPR
5F20
5F30
5F40
5F60
5H40
5H46
5H60
5H66
5H80
5H86
5H120
5H126

REFRIGERANT
R-22

R-134a
Cap.
(tons)
2.9
4.4
5.9
8.8
13.8
17.1
20.7
25.8
27.6
34.3
41.5
51.5

THR
(tons)
4.0
6.1
8.1
12.1
18.8
23.9
28.6
36.0
38.0
47.8
57.0
71.1

Bhp
5.2
7.8
10.3
15.4
23.4
32.3
36.9
48.1
48.9
63.7
73.0
92.1

Cap.
(tons)
8.3
12.6
16.7
25.1
39.9
49.1
59.6
73.9
79.4
98.6
119.2
147.9

R-507/404A
THR
(tons)
10.4
15.7
20.8
31.3
49.4
61.4
73.7
92.4
98.2
123.0
147.4
184.5

Bhp
10.9
16.2
21.6
32.2
49.0
63.7
73.4
95.5
97.5
126.8
145.9
189.7

Cap.
(tons)
2.3
3.5
4.7
7.1
11.4
14.1
17.1
21.3
22.8
28.4
34.3
42.3

THR
(tons)
3.6
5.4
7.2
10.8
17.0
21.4
25.4
32.2
33.9
42.8
50.8
64.0

Bhp
5.9
8.8
11.6
17.4
26.4
34.3
39.3
51.2
52.1
68.0
77.8
101.2

STANDARD RATING CONDITIONS


REFRIGERANT
R-22
R-134a
R-507/404A

SST
45
20
10

SDT
130
120
105

LEGEND
Bhp Brake Horsepower
Cap. Capacity
RGT Return Gas Temp to
Compr (F)
SC Liquid Subcooling (F)

SDT Saturated Discharge


Temp (F)
SST Saturated Suction
Temp (F)
THR Total Heat Rejection
(tons)

RGT
65
65
65

SC
15
15
5

RPM
1750
1750
1750

NOTE: The refrigerant ratings closely


correspond to standard air conditioning
and refrigeration conditions in which
these compressors are typically applied.

RATING BASIS AND CAPACITY MULTIPLIERS


SAT. SUCT
TEMP
(F)

RATED SUCT
GAS TEMP
(F)

40
20
0

65
65
65

10

65

20

65

30
40

65
65

40
0.790

20
0.830
0.830

CAPACITY MULTIPLIERS
R-507/404
Actual Suction Gas Temp to Compr (F)
0
10
20
30
40
0.870
0.890
0.910
0.930
0.950
0.870
0.890
0.910
0.930
0.950
0.870
0.890
0.910
0.930
0.950

0.890
0.910
0.930
0.950

0.950
0.959
0.968
0.977

0.910
0.930
0.950

0.960
0.969
0.978

0.970
0.979
0.987

R-134a
50
0.970
0.970
0.970
0.970
0.986
0.970
0.987
0.987
0.992

60
0.990
0.990
0.990
0.990
0.995
0.990
0.996
0.996
0.997

65
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000

23

Performance data (cont)


5F,H RATING LIMITS
REFRIGERANT
R-134a
R-22
R-507/404A

SST
Minimum Maximum
0
50
40
50
60
50

MULTIPLYING FACTORS FOR


OTHER THAN 1750 RPM

SDT
Minimum Maximum
80
145
80
135
80
120

RPM
CAPACITY
BHP

1450
0.835
0.798

1160
0.674
0.602

LEGEND
Bhp Brake Horsepower

LEGEND
SDT Saturated Discharge Temp (F)
SST Saturated Suction Temp (F)

CONDENSING UNIT MAXIMUM LIQUID LIFT


TEMP DIFF (F)
SDT ENT WATER TEMP
15
20
25
30
35
40

HEIGHT (ft)*
R-134a
R-22, 507/404A
30
52
37
64
43
75
49
85
53
93
57
99
58
61
62

45
50
55

103
107
110

LEGEND
SDT Saturated Discharge Temperature (F)
*Maximum allowable vertical distance from condenser to evaporator
sections (with evaporator located above condenser. Location of compressor is irrelevant, since it contacts gases only at suction and
discharge).

CAPACITY CONTROL REDUCTION STEPS


100
COMPR
SIZE

5F20*
5F30*
5F40, 5H40,46
5F60, 5H60,66
5H80, 86
5H120,126

CONTROL
CYL

1
1
3
4
6
8

871/2

831/3

100

90

86

2
3
4
6
8
12

10

CAP. STEPS (% Full Load Cap.)


75
662/3
621/2
50
% Full Load Bhp
80
74
71
60
Number of Active Cylinders

*5F20 and 5F30 compressors available with or without one cylinder for unloading. Two controlled cylinders (to 331/3%)
available on request for 5F30 only.

24

371/2

331/3

25

50

45

38

Typical piping and wiring


FIELD-ASSEMBLED UNIT (See Notes)

*Field-supplied refrigerant circuit components.


NOTES:
1. Piping and wiring are field supplied.
2. Motor and control panel are factory supplied on the
05FY,HY compressor units and 07FY,HY condensing
units.
3. Wiring and piping shown are general points-of-connection
guides only and are not intended for or to include all
details for a specific installation.
4. All wiring must comply with applicable local and national
codes.
5. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for
details.

25

Guide specifications 05FY,HY


05FY,HY Open-Direct-Drive and
Open-Belt-Drive Reciprocating
Compressor Unit
HVAC Guide Specifications
Size Range: 5 to 150 Tons
Carrier Part Numbers: 05FY,HY
Part 1 General
1.01 SYSTEM DESCRIPTION
Compressor unit utilizing direct driven or belt driven
reciprocating type refrigerant compressor.
1.02 QUALITY ASSURANCE
A. Unit performance shall be rated according to ARI 520
latest edition, comply with ANSI/ASHRAE 15 latest
revision Safety Code, NEC, and ASME Code.
B. Compressors will be factory run tested to ensure
proper performance.
C. Motor and control panel shall be UL listed and
NEMA approved.
1.03 DELIVERY, STORAGE AND HANDLING
Unit will be stored and handled according to manufacturers instructions.
Part 2 Products
2.01 EQUIPMENT
A. General:
Factory assembled single piece, refrigerant compressor unit. Contained within the package shall be an
open-drive reciprocating compressor, motor and
drive package, control package, structural steel
base, wiring, piping, controls, and special features
required prior to field start-up.
B. Compressors:
Reciprocating open-drive type only, with shutoff
valves, automatically reversible positive displacement oil pump, oil charge, crankcase heater with
relay (standard on 05FY040 and above), and suction
pressure actuated cylinder unloaders.
C. Motor and Drive Package:
1. Motor shall be NEMA T-frame only with operating speed of 1750 rpm.
2. Open-Direct-Drive Package shall include motorto-compressor coupling and guard, shims and
fastening set.
Open-Belt-Drive Package shall include belt
guard, motor pulley and belts, fastening set, and
compressor flywheel.

26

D. Controls and Safeties:


1. Included in the control panel are power and
control terminal blocks, contactors, control
relays, on/off switch, pressure gages for oil, discharge, and suction pressure. Unit designed to
start with controlled cylinders unloaded.
Factory-assembled control box to be tested and
mounted on structural base. Controls capable of
interlocking with evaporator, condenser, or
cooling tower fans.
2. Safeties in the control box include high, low,
and oil pressure switches, timer to prevent compressor short cycling, overload relays or circuit
breakers, and control circuit fuse.
E. Electrical Requirements:
All control and power wiring between control box
and compressor shall be factory assembled.
F. Special Features:
Certain standard features are removed and replaced
by those features designated by *. Consult your local
Carrier sales office for amending specifications.
1. Water-Cooled Condenser:
Shell and tube with integral finned copper tubes
for field installation. Shall be factory tested to
comply with ASME Code for unfired pressure
vessels, ARI Standard 450 for condensers, and
ANSI/ASHRAE 15 Safety Code. Equipped
with pressure relief, liquid line shutoff, and connection for water regulating valve.
2. Discharge Muffler:
Discharge line muffler for noise reduction.
3. Vibration Isolators:
To prevent transmission of vibration to building.
4. Water-Cooled Oil Cooler:
Water-cooled oil cooler to reduce oil temperature during operation.
* 5. Water-Cooled Cylinder Heads:
Used to reduce unit operating temperature.
* 6. Partial-Flow Oil Filter:
Controls the amount of contaminants within
the operating oil charge. Partial flow type for
safety.

Guide specifications 07FY,HY


07FY,HY Open-Direct-Drive and
Open-Belt-Drive Reciprocating
Water-Cooled Condensing Unit
HVAC Guide Specifications
Size Range: 5 to 150 Tons
Carrier Part Numbers: 07FY,HY
Part 1 General
1.01 SYSTEM DESCRIPTION
Condensing unit utilizing direct drive or belt driven
reciprocating type refrigerant compressor and
water-cooled condenser.
1.02 QUALITY ASSURANCE
A. Unit performance shall be rated in accordance to ARI
520 latest edition, comply with ANSI/ASHRAE 15
latest revision Safety Code, NEC, and ASME Code.
B. Compressors will be factory run tested to ensure
proper performance.
C. Motor and control panel shall be UL listed and
NEMA approved.
1.03 DELIVERY, STORAGE AND HANDLING
Unit will be stored and handled according to manufacturers instructions.
Part 2 Products
2.01 EQUIPMENT
A. General:
Factory assembled single piece, refrigerant compressor unit. Contained within the package shall be an
open-drive reciprocating compressor, motor and
drive package, control package, structural steel
base, wiring, piping, controls and special features
required prior to field start-up.
B. Compressors:
Reciprocating open-drive type only, with shutoff
valves, automatically reversible positive displacement
oil pump, oil charge, crankcase heater with relay, and
suction pressure actuated cylinder unloaders.
C. Motor and Drive Package:
1. Motor shall be NEMA T-frame only with operating speed of 1750 rpm.
2. Open-Direct-Drive Package shall include motorto-compressor coupling and guard, shims, and
fastening set.
Open-Belt-Drive Package shall include belt
guard, motor pulley and belts, fastening set, and
compressor flywheel.

D. Condenser:
Shell and tube with integral finned copper tubes.
Shall be factory tested to comply with ASME Code
for unfired pressure vessels, ARI Standard 450 for
condensers, and ANSI/ASHRAE 15 Safety Code.
Equipped with pressure relief, liquid line shutoff, and
connection for water regulating valve.
E. Controls and Safeties:
1. Included in the control panel are power and
control terminal blocks, contactors, control
relays, on/off switch, pressure gages for oil, discharge, and suction pressure. Unit designed to
start with controlled cylinders unloaded.
Factory-assembled control box to be tested and
mounted on structural base. Controls capable of
interlocking with evaporator or cooling tower
fans.
2. Safeties in the control box include high, low,
and oil pressure switches, timer to prevent compressor short cycling, overload relays or circuit
breakers, and control circuit fuse.
F. Electrical Requirements:
All control and power wiring between control box
and compressor shall be factory assembled.
G. Special Features:
Certain standard features are removed and replaced
by those features designated by *. Consult your local
Carrier sales office for amending specifications.
1. Vibration Isolators:
To prevent transmission of vibration to building.
2. Water-Cooled Oil Cooler:
Water-cooled oil cooler to reduce oil temperature during operation.
* 3. Water-Cooled Cylinder Heads:
Used to reduce unit operating temperature.
* 4. Partial-Flow Oil Filter:
Controls the amount of contaminants within
the operating oil charge. Partial flow type for
safety.
5. Discharge Muffler:
Used for noise reduction. Standard on the
07HY040 and larger.

27

Carrier Corporation Syracuse, New York 13221

7-02

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 2 4 4
New Book 3
Pg 28
Catalog No. 520-522
Printed in U.S.A.