PROJECT : CLIENT :CLIENT'S CONSULTANT :CONTRACTOR :-

PACKAGE4 INDOOR SUBSTATIONS-NEW & MODIFICATIONS OCP Uhde Spie Maroc

LIGHTNING PROTECTION CALCULATION FOR PJ-TPP BUILDING ( REFERENCE : IS 2309 ) Symbol / Formulae / Description / Parameter References A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION i) Input Data :a) Dimensions of Building / Structure
Length of the Building Width of the Building Height of the Building L ( Refer the Relevant Layout W Drawings of the Building / H Structure ) N Ng A B C D E Ac P ( Refer Fig. 1 of IS 2309 ) ( Refer Clause 8.1.2 of ( Refer Table 1A of IS 2309 ) ( Refer Table 1B of IS 2309 ) ( Refer Table 1C of IS 2309 ) ( Refer Table 1D of IS 2309 ) ( Refer Table 1E of IS 2309 ) = (L x W) + 2 (L x H) + 2(W x H) + 3.14 H2 = = = = = = = = = = =

Value

Unit

60.00 28.00 23.00

m m m

b)

Lightning Flash Density & Weighing Factors


Number of Thunderstorm Days / Year Lightning Flash Density (Flashes to Ground /km2/year) Weighting Factor A ( Use of Structure ) Weighting Factor B ( Type of Construction ) Weighting Factor C ( Content of Consequential Effects ) Weighting Factor D ( Degree of Isolation ) Weighting Factor E ( Type of Country ) 100 No. of Days / Year 9.2 Nos./km2/year 1 0.8 1 0.4 0.3 7389.06 Meter2 0.067979 Times per year 0.096000 0.006526 6.5260E-03

ii)

Calculations :Collection Area ( Refer Clause 8.1.2 of IS 2309 ) Probable Number of Strikes to Building / Structure per Year ( Refer Clause 8.1.2 of IS 2309 ) Overall Multiplying Factor Overall Risk Factor Calculated

= Ac x Ng x 10-6 times/year = = AxBxCxDxE Overall Multiplying = Factor x P = = ie

Rf-C

iii)

Maximum Acceptable Overall Risk Factor:Maximum Acceptable Overall Risk Factor Rf-A ( Refer Clauses 8.1.3 & 8.1.6 of IS 2309 ) =
ie

0.000001
1.000E-06

iv)

Result / Conclusion :Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor > Hence, Lightning Protection is Required.

B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS Calculations (As per Clause 12.2.3 of IS-2309):Ab = ( L x W ) Base Area of Structure P = 2(L+W) Perimeter of Structure i) For Base Area (Ab) < 100m2
a) Number of Down Conductors Required = For Ab < 100m2

= = =

1680 Meter2 176 Meter 1 Nos

ii)

For Base Area (Ab) > 100m2


b) Based on Base Area of Structure:Number of Down Conductors Required c) Based on Parimeter of Structure:Number of Down Conductors Required = 1+(Ab-100)/300 = 6 Nos

= P/30 = 6 Nos. Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309) = Hence, Required Number of Down Conductors 6 Nos.

REVISION DETAILS

Rev.
R0

Date

Drg/Doc. No.

Remarks
First Submission

Prepared

Reviewed

Approved