E175e PDF
E175e PDF
E175e PDF
Addendum
For the latest information on commissioning this actuator see the addendum starting on p78. Click HERE to go to addendum.
Publication number E175E Date of issue 07/04
The Rotork Setting Tool allows actuator control, indication and protection functions to be configured to suit site requirements. It is essential that all the actuator settings are checked for compatibility with the process and control system requirements before the actuator is put into service. Please read this publication. When Rotork personnel or nominated agents are contracted to carry out site commissioning and/or acceptance, documentation of commissioned actuator configuration can be made available for customer records.
This manual covers IQT range actuators: * IQT - Operation of isolating/regulating 1/4 turn valves. * IQTM - Operation of modulating 1/4 turn valves. * IQTF - Operation of part-turn and slow speed multi-turn valves. It provides instruction on: * Manual and electrical (local and remote) operation. * Preparation and installation of the actuator onto the valve. * Commissioning and adjustment of the Primary Settings for correct valve operation. * Commissioning and adjustment of the Secondary Settings to suit site-specific control and indication requirements. * Maintenance Troubleshooting. * Sales and Service.
THE ROTORK IQT RANGE THE FIRST 1/4 TURN VALVE ACTUATOR THAT YOU CAN COMMISSION AND INTERROGATE WITHOUT REMOVING ELECTRICAL COVERS.
Using the supplied infra-red Setting Tool to access the actuator set up procedures, point and shoot setting of torque levels, position limits and all other control and indication functions can be made safely, quickly and conveniently, even in hazardous locations. The IQT allows commissioning and adjustment to be carried out with the main power supply to the actuator switched on or off. Standard diagnostics access information about the control system, valve and actuator status in the form of display icons and help screens. Instantaneous valve torque and position can be monitored on the actuator with a single key press of the Setting Tool. The on board Datalogger captures operational and valve torque data enabling informed maintenance choices to be made. IQ Insight software for PC allows the Datalogger to be interrogated, as well as the complete actuator set up to be configured and recorded. The actuator containing the Setting Tool will be identified with a yellow label on the terminal cover. Visit our web site at www.rotork.com for more information on the IQT and other Rotork actuator ranges.
Refer to Publication E185E for repair, overhaul and spare part instructions.
CONTENTS
Page Page
1 Page
2 3 3 3 3 4 5 7 7 7 7 7 8 8 8 8 8 8 9
6 Cable Connections
6.1 6.2 6.3 6.4 6.5 Earth/Ground Connections Removing Terminal Cover Cable Entry Connecting to Terminals Replacing Terminal Cover
3.1 Operating by Hand 3.2 Operating Electrically 3.3 Display Local Indication 3.4 Display Alarm Indication
10 10 10 10 10 10 11 11 12 13 13 13 13 14 14 14
15 16 25 27 60 62 64 69 71 72 73
7 Commissioning
7.1 The Setting Procedure 7.2 The Setting Tool 7.3 Entering the Actuator Setting Procedure 7.4 Setting Mode Password 7.5 New Password 7.6 Checking Mode 7.7 Procedure Branch Crossroad 7.8 The Actuator Display Setting/Checking Mode 7.9 Returning to Valve Position Display
12 IQ Approvals
This manual is produced to enable a competent user to install, operate, adjust and inspect Rotork IQT range valve actuators. The electrical installation, maintenance and use of these actuators should be carried out in accordance with the National Legislation and Statutory Provisions relating to the safe use of this equipment, applicable to the site of installation. For the UK: Electricity at Work Regulations 1989 and the guidance given in the applicable edition of the IEE Wiring Regulations should be applied. Also the user should be fully aware of his duties under the Health and Safety Act 1974. For the USA: NFPA70, National Electrical Code is applicable. The mechanical installation should be carried out as outlined in the manual and also in accordance with relevant standards such as British Standard Codes of Practice. If the actuator has nameplates indicating that it is suitable for installation in Hazardous Gas Areas then the actuator is suitable for use in Zone 1 and Zone 2 (or Div 1 and Div 2) explosive atmospheres only. It should
Enclosure Materials
IQT actuators are manufactured from aluminium alloy with stainless steel fasteners. The user must ensure that the operating environment and any materials surrounding the actuator cannot lead to a reduction in the safe use of, or the protection afforded by, the actuator. Where appropriate the user must ensure the actuator is suitably protected against its operating environment. Should further information and guidance relating to the safe use of the Rotork IQT range of actuators be required, it will be provided on request.
Thermostat Bypass
If the actuator is configured to bypass the thermostat, when using the ESD function, the hazardous area certification will be invalidated.
Storage
If your actuator cannot be installed immediately store it in a dry place until you are ready to connect incoming cables. If the actuator has to be installed but cannot be cabled it is recommended that the plastic transit cable entry plugs are replaced with metal plugs which are sealed with PTFE tape. The Rotork double-sealed construction will preserve internal electrical components perfectly if left undisturbed. It is not necessary to remove any electrical compartment covers in order to commission the IQT actuator. Rotork cannot accept responsibility for deterioration caused on-site once the covers are removed. Every Rotork actuator has been fully tested before leaving the factory to give years of trouble free operation, providing it is correctly commissioned, installed and sealed.
WARNING
With respect to handwheel operation of Rotork electric actuators, under no circumstances should any additional lever device such as a wheel-key or wrench be applied to the handwheel in order to develop more force when closing or opening the valve as this may cause damage to the valve and/or actuator or may cause the valve to become stuck in the seated/backseated position.
When the selector is locked in the Local or Remote positions the Stop facility is still available. The selector can also be locked in the Stop position to prevent electrical operation by Local or Remote control.
Do not operate the actuator electrically without first checking, using the infra-red Setting Tool, that at least the Primary Settings have been made (refer to Section 8
page 15).
Fig. 3.1
Local Control
With the red selector positioned at Local (anti-clockwise) the adjacent black knob can be turned to select Open or Close. To Stop, turn red knob clockwise.
Remote Control
Rotate the red selector to the Remote position (clockwise), this gives remote
control only for Open and Close but local Stop can still be used by turning the red knob anti-clockwise.
The liquid crystal display screen has 2 modes of position indication: 1. Valve position power on 2. Valve position power off On power up the actuators liquid crystal display screen is back-lit with a soft amber light and one of the indicator lamps will be on, dependent on position. The display screen will show percentage open or an end of travel symbol. (See Figs 3.3, 3.4 and 3.5) As standard, red lamp signifies valve open, yellow intermediate, and green lamp signifies valve closed. Open and closed colour functions can be reversed on request.
Open
Red indicator and open symbol displayed
Closed
Green indicator and closed symbol displayed
Fig. 3.3
Mid Travel
Yellow indicator and percentage open value displayed
Fig. 3.5 With the main power supply switched off, the liquid crystal display screen is powered by a battery and continues to display actuator position. However, the battery does not support screen backlighting, or position indicator lamps.
6 5
Fig. 3.2 The Actuator Display The display consists of: 1. 2. 3. 4. 5. 6. Red position indication lamp Yellow position indication lamp Green position indication lamp Liquid crystal display screen (LCD) Infra-red sensors Infra-red signal confirmation indicator (Red)
Fig. 3.4
The valve alarm icon, Fig 3.6, is displayed when a valve problem causes the actuator to trip-off due to the configured torque value being developed (refer to [tC]/[tO] pages 20/21).The possible causes are: Valve tight or obstructed in mid travel. Valve stuck or jammed Valve process conditions changed (increase in pressure, flow etc.) Once the actuator has tripped off on torque, electrical operation in the same direction is inhibited. The icon will remain displayed until movement in the opposite direction takes place. The valve alarm icon will not be displayed when stopping at end of travel for valves configured to torque seat or torque back seat at end of travel (refer to [C2]/[C3] pages 18/19).
Control Alarm
Local and Remote operation will be inhibited while an active ESD or interlock signal is present (refer to [A1] ESD Action page 30, [A8] External Interlocks page 32 and Conditional Control [A9] page 32.) Investigate the operational conditions of the actuator remote control system.
Fig. 3.7 The control system alarm icon, Fig 3.7, is displayed when the remote control system maintains an active ESD or interlock signal (the ESD, interlock function or conditional control having been enabled.)
Valve Alarm
Fig. 3.6
Try handwheel operation of the valve to feel for stiffness (refer to page 3).
Actuator Alarm
Battery Alarm
The actuator checks the battery status at approximately 10 minute intervals. After replacing a battery the alarm icon will continue to be displayed until the next check indicates the battery is healthy. This may take up to 10 minutes.
Fig. 3.8 The actuator alarm icon, Fig. 3.8, is displayed when an active actuator alarm is present. Electrical operation will be inhibited while an alarm is present. The possible causes are: Transformer thermostat tripped Battery low on power up* Power supply fault *see Battery Alarm (To identify the specific cause of the alarm refer to Help Screens).
Fig. 3.9 The battery alarm icon, Fig. 3.9, is displayed when the actuator detects its battery as being low, discharged or missing. If, on power up, the actuator detects a discharged battery and actuator power loss inhibit feature [OS] is enabled (refer to page 58), both battery and actuator alarm icons (Fig.3.8 and 3.9) will be displayed. Electrical operation will be inhibited. When the battery alarm icon is displayed, the battery should be replaced immediately (refer to page 62).
Fig. 4.1
Fig. 4.2 The range of IQT drive bushes is shown in figure 4.3. Please refer to publication E110E for maximum stem acceptance details.
Fig. 4.3
WARNING:
Do not lift the actuator and valve combination via the actuator. Always lift the valve/actuator assembly via the valve.
Fig. 5.1
Fig. 5
WARNING:
The actuator should be fully supported until full valve stem engagement is achieved and the actuator is secured to the valve flange.
Secure actuator to valve with four fixing bolts. Check that the cast groove in actuator base is not obstructed see Fig 5.1. Its purpose is to protect the actuator in the event of a product leak from the valve stem/gland packing. Check base fixing bolts are tight.
The IQT stop bolts are located below the terminal compartment. Stop bolt adjustment allows +/- 5 variation of travel at each end position. Screwing bolts in reduces movement, out increases movement. For clockwise closing valves the right hand bolt is the closed stop as shown with spanner in fig 5.2. The left is the open stop. Stop bolts are factory set to give a nominal 90 travel.
Fig. 5.2
10
Cable Connections
6.1 Earth/Ground Connections
A lug with a 6mm diameter hole is cast adjacent to the conduit entries for attachment of an external protective earthing strap by a nut and bolt. An internal earth terminal is also provided, however it must not be used alone as the protective Earth Connection.
Ensure all power supplies are isolated before removing actuator covers.
Check that the supply voltage agrees with that stamped on actuator nameplate. A switch or circuit breaker must be included in the wiring installation of the actuator. The switch or circuit breaker shall be mounted as close to the actuator as possible and shall be marked to indicate that it is the disconnecting device for that particular actuator. The actuator must be protected with overcurrent protection devices rated in accordance with Rotork publication No. E135E Electric motor performance data for IQT range actuators.
WARNING: Actuators for use on phase to phase voltages greater than 600V a.c.must not be used on supply systems such as floating, or earth-phase systems, where phase to earth voltages in excess of 600V a.c. could exist.
11
Commissioning
2. Secondary Functions
Settings covering the control, indication and optional equipment functions.
All IQT actuator functions are configured before dispatch to Rotork standard default settings unless alternatives have been specified with the order. Should difficulty be encountered during commissioning the default settings can be reinstated, returning the actuator configuration to its original manufactured state. Site commissioning can then begin again (refer to Section 9.17).
The default function should be used with caution as settings selected after manufacture may be essential for the safe operation of the valve and/or plant.
P? cr
50
This may be an open or closed symbol or a percentage open value. Refer to Section 10.
y y
PC
Ir
Ic
Primary Functions
Direction Limit Actions Torque Values Limit Positions
Secondary Functions
Indication Contacts Control Mode Options Help Screens Defaults
1.
Primary Functions
Settings for end of travel limit actions, torque values, limit positions etc.
12
4 6
3 5 7
Name
1.
Key* 2. y Key*
3. - Key
Instruction
Display next function down Display next function across Decrease/change displayed functions value or option setting Increase/change displayed functions value or option setting Enter displayed value or option setting
* Pressing the two arrow keys together returns the actuator display to the position
13
PRESS THE
y KEY.
The display will change to [PC]. Using the + or - key scroll through the available passwords until the desired password is displayed.
PRESS THE
KEY.
PRESS THE
KEY.
Password Display, Checking Mode Once the procedure has been entered in the required mode
Two setting bars will appear and will remain visible on every function display screen.
Password Changed to [IE] Default Password, Setting Mode Enabled The Actuator Function Settings can be protected by the Use of a Password NOTE: The new password becomes effective the next time setting mode is entered.
14
Tool + or - keys will cause the setting to be changed. In checking mode the settings cannot be altered. In setting mode, once displayed, a new setting can be entered into the actuator memory by pressing the key. The setting will flash off and back on, confirming its selection.
To access the Primary Function settings press the arrow key (refer to Section 8 Commissioning Primary Functions page 15). To access the Secondary Function settings press the arrow y key (refer to Section 9 Commissioning Secondary Functions page 25).
The y arrow key will always display the NEXT function on the SAME level and will wrap around the functions on the same level. The actuator display indicator lamps will continue to indicate valve position. Actuator functions are displayed in code form in the top portion of the liquid crystal display screen. The setting for the displayed function is shown in the lower portion of the screen. Depending on the actuator function displayed, its setting may be an option or a value. In setting mode the Setting
TOP PORTION
Function e.g. tC = Torque Close
2. 3. 4.
y arrow keys
LOWER PORTION
Function Setting e.g. Value = 40% Typical Actuator Function Display Setting Mode Enabled
Press the arrow key until the display returns to position. With any actuator function screen displayed, select Remote control using the red Local/Stop/Remote selector.
15
Settings and operation must be verified by electric operation and function test of the actuator to ensure correct operation.
16
50
P?
y y y
Ic
Position Display (This may be an open or closed symbol or a % open value.) Torque and Position Display
PC
Ir
Password
cr
c1
tC
y y y
c2 tO LO
c3
Direction to Close
Limit Closed
LC
50
y Limit Open
Position Display
C1
17
Direction to Close
Using the + or - key, display character conforming to correct closing direction. Having ensured that the display corresponds to the established closing direction
Manually operate actuator and valve to establish correct closing direction. If the handwheel labelling is found to be incorrect please apply to Rotork for conversion labels.
PRESS THE
KEY.
The displayed option will flash, indicating that it has been set.
50
P?
[C] in the Setting Field Indicating Clockwise to Close
PRESS THE
y KEY.
cr
PC
Ir
Ic
c1
tC
y y y
c2 tO LO
c3
LC
50
C2
18
Close Action
Using the + or - key, display the desired option.
IQT actuators are designed to stop at the end of travel by torque limitation against the actuator stop bolts. Stop bolts should therefore be set to the precise stopping position required, refer to section 5.6. IQTF actuators can be configured to close on torque or limit. Refer to valve manufacturers instructions.
50
P?
NOTE: When set to close on torque, the actuator will apply the value of torque as set for [tC] in seating the valve (refer to [tC] page 20).
cr
PC
Ir
Ic
[Ct] in the Setting Field Indicating Close on Torque - defualt setting.
c1
tC
y y y
c2 tO LO
c3
LC
50
[CL] in the Setting Field Indicating Close on Limit Having selected the required option
PRESS THE
KEY.
The displayed option will flash, indicating that it has been set.
PRESS THE
y KEY.
C3
19
Open Action
50
Using the + or - key display the desired option.
IQT actuators are designed to stop at the end of travel by torque limitation against the actuator stop bolts. Stop bolts should therefore be set to the precise stopping position required, refer to section 5.6. IQTF actuators can be configured to close on torque or limit. Refer to valve manufacturers instructions.
P?
cr
PC
Ir
Ic
c1
tC
y y y
c2 tO LO
c3
LC
50
PRESS THE
KEY.
The displayed option will flash, indicating that it has been set.
PRESS THE
y KEY.
tC
20
The value of torque available in the close direction can be configured. Refer to valve manufacturer for recommended value. The closing torque value can be varied between 40% and Rated, in 1% increments.
PRESS THE
KEY.
40% of Rated Torque
The displayed value will flash, indicating that it has been set. Should the set value of torque be developed in closing, the actuator will torque trip and stop.
50
P?
PRESS THE
y KEY.
99% of Rated Torque
cr
PC
Ir
c1
tC
y y y
c2 tO LO
c3
Rated Torque
LC
50
tO
21
The value of torque available in the open direction can be configured. Refer to valve manufacturer for recommended value.
PRESS THE
KEY.
Rated
50
P?
BOOST SHOULD NOT BE SELECTED WHEN THE ACTUATOR HAS BEEN CONFIGURED TO OPEN ON TORQUE (refer to [C3] page 19)
cr
PC
Ir
Ic
unless back seating at Rated torque is acceptable. Using the + and - keys display the recommended torque value. In the absence of a recommended torque value, try a low setting and increase until satisfactory valve operation is achieved. 40% Boost In checking mode, on pressing the key after reviewing open torque setting, the display will revert to valve position. 99%
c1
tC
y y y
c2 tO LO
c3
LC
NOTE: Rated torque is quoted on the actuator nameplate. Boost torque is at least 140% of Rated torque. PRESS THE KEY.
50
The displayed value will flash, indicating that it has been set.
LC
LO
50
22
P?
Limit Closed
P?
cr
PC
Ir
Ic
Limit Open Move valve manually to the open position. Allow for overrun by winding actuator output closed by two handwheel turns.
cr
PC
Ir
Ic
Move valve manually to the closed position. Allow for overrun by winding actuator output open by two handwheel turns.
c1
c1
PRESS THE
KEY.
tC
y y y
c2 tO LO
c3
PRESS THE
KEY.
tC
y y y
c2 tO LO
c3
The two bars will flash and the closed indicator lamp will illuminate, indicating closed limit position has been set.
LC
The two bars will flash and the open indicator lamp will illuminate, indicating open limit position has been set.
LC
PRESS THE
y KEY.
50
PRESS THE
KEY.
50
To check closed limit position hand wind valve open until the amber lamp illuminates. Wind valve back closed until the closed lamp illuminates.
The open symbol (refer to Fig. 3.3. page 4) should now appear.
NOTE: When in checking mode Set Limit Closed [LC] does not appear.
AA
cr
P?
23
Speed Setting
IQT operating time can be adjusted between 25% and 100% of the maximum time (50% and 100% for IQT2000). IQT are factory set at the maximum speed. IQTM actuators are dispatched with the minimum speed set. To access speed setting [AA] screen, bus system [OP] has to be set to [On], using the + and - key. After this setting, proceed to screen [AA].
50 Positional Display
% Speed
25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Fig 8.2
Hex Setting
19 1E 23 28 2D 32 37 3C 41 46 4B 50 55 5A 5F 64
y y
PC
IrDA comms
Ir
Cell Phone
Ic
ESD Action
r1 r2 r3 r4
With [AA] displayed Use the + and - key to select the required actuator operating time. The settings are displayed in hexadecimal and can be related to the actuator speed as shown in Fig 8.2.
Primary Functions
OE A1
PRESS THE
KEY.
The displayed value will flash, indicating that it has been set.
CPT Folomatic Remote Control Remote Control Source Bus System
Option Selection
OI
OF
Od
OP [On]
PA
All speed settings are adjustable in unit increments of hexadecimal. Any value of hex outside of the range stated will not be accepted into the actuator memory.
AA
24
P?
If the procedure has been followed as described, the positional display will indicate that the actuator is in the open position.
cr
PC
Ir
Ic
Select Remote control momentarily, using the red selector to exit setting procedure and then select required control: Local, Stop or Remote. With the correct settings made electric operation can now be carried out safely.
c1
tC
y y y
c2 tO LO
c3
LC
50
25
Settings and operation must be verified by electric operation and function test of the actuator to ensure correct operation.
Fig. 9
26
cr
P?
50 Positional Display
y y
PC
IrDA comms
Ir
Cell Phone
Ic
d1 H1 OE A1
r1 r2 r3 r4
y y y y y y y y
Value
r1 r2 r3 r4
A2
y y y y y y y
Contact Form
r1 r2 r3 r4
A3
Primary Functions
ESD Action
y y y
A4
y y y
A5
Bus System
y y y
A6
Interrupter Timer
y y y
2-wire Control
A7
y y y
External Interlocks
A8
Power Loss Inhibit
Conditional Control
A9
At
CPT
OI
OF
Od
OP
OJ
Or
OS
- If OE, OF, OP, or OJ are fitted and selected ON their appropriate set-up screens will be inserted here. H2 d2 H3 H4 H5 H6 H7 H8
H9
9.1
SECONDARY FUNCTIONS CONTENTS
page 9.0 9.1 9.2 9.3 9.4 9.5 9.6 9.7 9.8 9.9 9.10 9.11 9.12 9.13 9.14 9.15 9.16 9.17 9.18 10.0 10.1 10.2 Commissioning Secondary Functions Accessing the Secondary Settings Indication Contacts S1, S2, S3 and S4 Control Mode Configuration Option Extra Indication Contacts S5S8 Option CPT (Current Position Transmitter) Option Folomatic Remote Control Remote Control Source Bus System Option Pakscan Bus System Option Modbus Bus System Option Profibus DP Bus System Option DeviceNet Bus System Positioning Control Settings Option Interrupter Timer Setting Tool Local Control Inhibit Operation After Power Loss Actuator Type Setting Default Options Default Options Maintenance,Monitoring and Troubleshooting Help Screens IrDA Diagnostics and Configuration 25 27 28 30 33 34 35 38 39 43 47 51 54 56 58 58 59 60 61 62 64 69
Having established that the Primary Functions have been correctly set, the Secondary Functions can now be configured to suit site control and indication requirements. It is possible to move through the various Secondary Functions as shown in Fig. 9.1 using the y and keys. The actuator wiring diagram will indicate any options fitted. Options Setting Tool Local Control [Or] and Power Loss Inhibit [OS] are standard features, their use being optional.
27
In order to display the Secondary Functions it is necessary to press the key until [Cr] appears. If you have chosen to enter Secondary Functions in the checking mode the display will be as Fig. 9.2. If you have chosen to enter Secondary Functions in the setting mode the display will be as Fig. 9.3 (refer to Section 7).
Fig. 9.2
Fig. 9.3
9.2
r1
Contact S1 - Function
r1
28
Contact S1 - Value
Indication contacts S1 [r1], S2 [r2], S3 [r3] and S4 [r4] may each be set to trip for any one of the following functions:
PRESS THE
KEY.
When the S contact function is set to [P0], the required intermediate position value must be set.
Code Function
[CL] [OP] [Po] [tC] [tO] [tt] [tl] [dC] [dO] [d?] [St] [bA] [HA] [bL] [LS] [Ol] [Cl] [lL] [ES] [LP] [Lo] [rE] [AA] closed end position open end position intermediate position torque trip close torque trip open torque trip any position torque trip mid travel actuator closing actuator opening actuator rotating motor stalled battery low hand operation blinker local stop open interlock close interlock interlock active ESD signal lost phase local selected remote selected actuator alarm *
The displayed function will flash indicating that it has been set.
The S contact form can be set normally open [no] or normally closed [nc]. The procedures for setting up contacts S2, S3 and S4 are the same as those shown for S1.
PRESS THE
KEY.
The displayed value will flash indicating that it has been set. Contact S1 Configured to Trip at Valve Closed Limit
Unless specified with order, the default settings for indication contacts are as follows: S1 [CL] closed end position [no] S2 [OP] open end position [no] S3 [CL] closed end position [nc] S4 . [OP] open end position [nc]
* Contact alarm indication will operate under the same conditions as the display alarm indication icons (refer to page 5 for information).
PRESS THE
y KEY.
Value Set to Indicate 25% Open
PRESS THE
y KEY.
r1
29
Use the + or - keys to select between [nO] (normally open) and [nC] (normally closed).
PRESS THE
KEY.
The displayed option will flash indicating that it has been set.
PRESS THE
KEY.
9.3
A1
ESD Action
A2
A3
30
The Control Mode Configuration affects how the actuator will respond under conditions of emergency shut down, local control, remote control interlocks, and 2-wire remote control. Also included is an unseating torque switch bypass function. Unless specified with order, the control mode configuration will be set as shown for default configuration on page 60. If it is necessary to change the configuration follow the instructions in this section. There are 10 configurable control functions: A1 ESD action A2 ESD contact type A3 ESD thermostat bypass A4 ESD override interlock A5 ESD override local stop A6 Maintained local control A7 2-wire remote control A8 External interlocks A9 Conditional Control At Torque switch bypass.
An active ESD signal applied to the actuator will override any existing or applied local or remote control signal. ESD can be configured to override the transformer thermostat, active interlocks or local stop selection. Refer to A3, A4 and A5. The default action under an active ESD signal is to stay put [SP]. Press the + or - key to select the required ESD action: [CL] Close on ESD [SP] Stay put on ESD [OP] Open on ESD
The default setting for ESD Contact Type is [nO]. The actuator responds to a remote control ESD signal derived from a normally open contact making. For ESD, where a remote control ESD signal is derived from a normally closed contact breaking, the signal being removed, press the + or - key. The display will change to [nC].
The default setting for Thermostat Bypass is [OF] during ESD. The thermostats remain in circuit and enabled during ESD. The thermostats can be bypassed during ESD as a factory set, hard-wired option only. Contact Rotork for information.
PRESS THE
KEY.
Danger: Actuator hazardous area certification is invalidated while the thermostats are bypassed.
A3 should be set to reflect the factory set configuration of thermostat bypass. During an ESD event: [A3]=[OF] thermostats enabled [A3]=[On] thermostats bypassed
The displayed option will flash indicating that it has been set.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Actuator Responds to a Remote, Normally Open ESD Contact Making (Signal Applied) Note: If Folomatic analogue control is required A2 must be set to [nO]. ESD Set to Close
A4
A5
A6
A7
31
The default setting for ESD Override Interlocks is [OF]. ESD action will not override an active interlock applied to the actuator. If an applied ESD signal is required to override active interlocks causing the ESD action as set for A1, press the + or - key. The display will change to [On].
The default setting for ESD Override Local Stop is [OF]. ESD will not override local stop when selected. If an applied ESD signal is required to override local stop causing the ESD action as set for A1, press the + or key. The display will change to [On].
The default setting for Local Actuator Pushbutton control is self-maintained [On]. If non-maintained actuator pushbutton control is required (jogging, inching, push to run), press the + or - key. The display will change to [OF].
The default setting for 2-wire Remote Control is Stayput [SP]. If a open and closed remote control signal are applied simultaneously the actuator will stayput (stop if running). Refer to actuator wiring diagram or publication E120E. Use the + or - key to select the required priority: [OP] Open [SP] Stay put [CL] Close
PRESS THE
KEY.
PRESS THE
KEY.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set.
The displayed option will flash indicating that it has been set.
The displayed option will flash indicating that it has been set.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. ESD Override Local Stop Off ESD Override Interlock Off Self-Maintained Local Control
A8
External Interlocks
A9
Conditional Control
At
32
Actuators are delivered with the interlock facility disabled [OF] Refer to the actuator wiring diagram or publication E120E for interlock control circuits. To enable remote external interlocks press the + or - key. The display will change to [On].
PRESS THE
KEY.
Where a high level of safety integrity is required, Conditional Control can be configured. In this mode two discreet signals are required for remote operation. Remote control will be conditional on both a control signal (open or close) and the appropriate interlock signal being applied simultaneously. Failure of either or a spurious signal will not cause operation. Interlocks [A8] must be set [On]. Interlock signals are not required for local operation. The default setting for conditional control is [OF]. To enable conditional control press the + or - key.The display will change to [On].
The default setting for Torque Switch Bypass is [OF], the torque switches are not bypassed during the unseating movement. To bypass the torque switches during the unseating movement press the + or - key. The display will change to [On].
PRESS THE
KEY.
The displayed option will flash indicating that it has been set.
The displayed option will flash indicating that it has been set. The torque switches will be bypassed from closed limit to 5% open when opening and from open limit to 95% when closing. Bypassing the torque switches makes torque in excess of rated and up to actuator stall available for unseating a sticky valve. Outside these positions the torque setting will revert to the values set for [tC], see page 20 and [tO] page 21.
PRESS THE
Interlocks Disabled Note: If interlocking is required in only one direction, it will be necessary to connect a link between the actuator terminals associated with the other direction.
KEY.
The displayed option will flash indicating that it has been set.
9.4
OE
33
Extra indication contacts S5 [r5], S6 [r6], S7 [r7] and S8 [r8] are available as an option. Check actuator circuit diagram for inclusion. When the Extra Contact Option is included the set-up procedure and available contact functions for S5 S8 are identical to S1S4 (refer to Section 9.2 page 28). Unless specified with order the default setting for the extra indication contacts will be as follows: S5 [r5] Close limit indication S6 [r6] Open limit indication S7 [r7] Torque trip mid travel S8 [r8] Remote control selected
The action of turning on the Extra Contact Option makes an additional series of set-up screens available
Enabled Disabled Extra Contact Set-up Displays Press the + or - key to select the Extra Contact Option set-up screens [On].
PRESS THE
KEY.
The displayed option will flash indicating that it has been set.
9.5
34
Setting instructions for actuators including a CPT providing 4-20 mA analogue position feedback.
The CPT is an optional extra. It may be internally or externally powered. Check wiring diagram for inclusion and connection details.
With [HI] Displayed, the (CPT) 20mA Output will Correspond to Actuator Fully Open If 20mA is required to correspond to actuator closed use the + or - key to change to [LO].
PRESS THE
KEY.
The displayed option will flash indicating that the option has been set.
9.6
OI
Folomatic Feedback
9.4
35
Setting instructions for actuators including a Folomatic (proportional) Controller for use in (analogue) valve position control. The Folomatic is an optional control device. Check actuator wiring diagram for inclusion. Before setting the parameters for Option Folomatic ensure Remote Control Source [Od] has been selected to [bo] in Section 9.7.
Folomatic set-up screens can be turned OFF to provide extra security. Once selected ON the option function displays allow commissioning of the Folomatic to be undertaken.
Before commissioning of the Folomatic functions can begin, the Folomatic Feedback must be set to suit the applied set point signal.
The action of turning on the Folomatic option makes an additional series of settings available.
With [HI] displayed, an increasing set point signal will correspond to valve opening. If a high set point signal is required to correspond to valve closing use the + or - key to change to [LO].
PRESS THE
KEY.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the key to access the Folomatic set-up displays.
The displayed option will flash indicating that it has been set. If setting [OI] is modified after commissioning the Folomatic, it will be necessary to recommission the Folomatic. Press the y key to access the Folomatic set-up display [OF].
FI
Fr
FL
FH
36
Using the + or - key select [ l] for current set point signal or [ U] for voltage set point signal.
Using the + or - key select [05], [10] or [20] to correspond with the set point signals within the range of 05mA or volts, 010mA or volts or 020mA or volts (i.e. 420mA).
to correspond with the LOW set point signal. Current Mode Selected
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the
PRESS THE
KEY.
Valve Closed on LOW Signal Valve Open on HIGH Signal
The displayed option will flash indicating that it has been set. Press the
PRESS THE
KEY.
PRESS THE
KEY.
The displayed value will flash indicating that it has been set. Press the
The displayed value will flash indicating that it has been set. Press the
Fd
Deadband Adjustment
Ft
FA
FF
37
Failsafe Action
If the actuator hunts or responds unnecessarily to a fluctuating set point signal the deadband must be increased. If more accurate control is required the deadband may be decreased. Use the + or - key to select the deadband width. Range 0099 corresponds to 09.9% of setpoint signal. NOTE: Maximum deadband is 9.9% of valve stroke. Normally minimum deadband should not be less than 1%.
The motion inhibit timer introduces a delay in the actuator response to a rapidly fluctuating set point signal, preventing unnecessary movement. Once the system stabilises the actuator will respond to steady changes in the set point signal as necessary. Use + or - key to adjust motion inhibit time in seconds: range 099. Normally it is recommended that motion inhibit time should not be set to less than 5 seconds (refer to note on page 58).
Use + or - key to enable [On] or disable [OF] action on loss of set point signal. [On] Failsafe as determined by [FF]. [OF] Failsafe to position corresponding to low set point.
Failsafe action when [FA] enabled. Use + or - key to select, on loss of set point signal: [Lo] move valve to position corresponding to minimum set point. [SP] stayput on loss of set point. [Hl] move valve to position corresponding to maximum set point.
Enabled
PRESS THE
KEY.
The displayed option will flash indicating that it has been set.
PRESS THE
KEY.
PRESS THE
KEY.
PRESS THE
KEY.
The displayed value will flash indicating that it has been set. Press the
The displayed value will flash indicating that it has been set. Press the
The displayed option will flash indicating that it has been set. Commissioning of the Folomatic is now complete. Remote control may be selected.
9.7
Od
38
The available forms of remote control are listed below: Standard hardwired control Analogue control-Option Folomatic Network control including: Option Pakscan Option Modbus Option Profibus The setting for Remote Control Source will depend on the type of remote control required and the option specified and fitted. Check actuator circuit diagram for remote control form.
The setting of Remote Control Source will be determined by the option that has been fitted, if any. [rE] Standard hardwired remote control. [bO] Option Folomatic. [OP] Options Pakscan, Profibus, Modbus, Foundation Fieldbus or DeviceNet. [OF] All remote control disabled (Actuator available for local control only).
PRESS THE
KEY.
The displayed option will flash indicating that it has been set.
9.8
PA
Pakscan Address
Pb
39
Setting instructions for actuators including an optional Pakscan Field Control Unit check wiring diagram for inclusion.
The actuator Pakscan Field Control Unit must be allocated a unique loop address. The actuator must be in Loopback for its address to be set or changed. Loopback can be achieved in two ways: 1. 2. Turn OFF the master station. Isolate the actuator from the 2-wire control loop.
Before setting the parameters for Option Pakscan ensure Remote Control Source [Od] has been selected to [oP] in Section 9.7.
Pakscan set-up screens can be turned off to provide extra security. The action of turning screens on or off does not affect its operation. Pakscan Set-up Screens ON
The actuator Pakscan Field Control Unit baud rate must be set to the loop baud rate. For a Pakscan 2-wire control loop the selected baud rate must be common to the master station and all the field control units included in the loop. The actuator must be in Loopback for its baud rate to be set or changed. Loopback can be achieved in two ways: 1. 2. Turn OFF the master station. Isolate the actuator from the 2-wire control loop.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the key to display the Pakscan set-up screens.
Using the + or - keys display the required loop address. Address to be set within the range 01F0 Hexadecimal. (refer to table on page 72).
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the
Pb
PF
40
Using the + or - keys display the required baud rate. 01 = 110 baud 03 = 300 baud 06 = 600 baud 12 = 1200 baud 24 = 2400 baud
The IQT actuator has the facility to accept 4 auxiliary inputs (AUX1AUX4). These are used when supplementary remote control or digital auxiliary inputs are required in addition to the standard control and feedback features incorporated into the Pakscan card. It is also possible to have a combination of both remote control and volt-free inputs to provide, for example, open and close control as well as a high and low tank level alarm indication, supplied via an external transducer. The hexadecimal number displayed under PF can be considered as a software mask. It is this mask that tells the Pakscan card what type of input to expect, control or input signal, and what form the input will be, normally open or normally closed (refer to page 72 for Binary, Hexadecimal and Decimal Conversion Table). To decipher the mask the number needs to be split into two separate hexadecimal characters, each of which can be sub-divided into 4 binary bits. The first 4 bits represent the function and the second 4 represent the input source (known as invert). Pictorially this can be represented as:
Bits
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the
When used for remote control of the actuator bits 4 to 1 of the function character have been designated as follows: Bit 4 (AUX4) Bit 3 (AUX3) Bit 2 (AUX2) Bit 1 (AUX1) ESD Stop/Maintain Close Open
(When used for digital signal inputs they are simply designated as AUX 4 to AUX 1)
PF
Rules
41
Examples
1. The full range of remote controls is needed. Open and Close are NO and ESD and Stop/maintain is NC. Aux I/P Function Invert 4321 1111 0011 =F =3 i.e. set [PF] to [F3]
2. Open and close control is required along with 2 inverted digital signal inputs (Note that with this setting the open and close commands will be maintained.) Aux I/P Function Invert 4321 0011 0011 =3 =3 i.e. set [PF] to [33]
3. ESD Control
When using ESD (aux input 4), the ESD contact mode setting [A2] should be set to the default value of [nO]. The [A1]ESD direction setting should be set to either Open or Close the valve (refer to page 30).
3. Only an ESD input is needed. The requirement is for push to run control with a NO contact input. Aux I/P Function Invert 4321 1100 1000 =C =8 i.e. set [PF] to [C8]
4. Stop/Maintain Control
When energised this will make the Aux input Open/Close/ESD control push-to-run, (non-maintained). When de-energised, the Aux input Open/Close/ESD control will be maintained.
PF
PP
Setting [PP] is not used by Pakscan. Entered settings will be ignored.
42
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. If Pakscan positioning control is required, return to the position display by pressing and y keys together. Display [OF] (refer to page 54).
9.9
PA
Modbus Address
Pb
43
Modbus Baudrate
Setting instructions for actuators including an optional Modbus RTU module check wiring diagram for inclusion.
The Modbus module must be allocated a unique address. To set the address the Modbus module must be isolated from the host by disconnecting the RS485 highway or turning off the host device. Using the + or - keys display the required address.
Before setting the parameters for Option Modbus ensure Remote Control Source [Od] has been selected to [oP] in Section 9.7.
Modbus module set-up screens can be turned off to provide extra security. The action of turning screens on or off does not affect its operation.
The Modbus module must be set to the RS485 highway baudrate. To set the baudrate the Modbus module must be isolated from the host by disconnecting the RS485 highway or turning off the host device. Using the or keys display the required baudrate: [01] [03] [12] [48] [19] 110 300 1200 4800 19200 [06] [24] [96] [38] 600 2400 9600 38400
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the key to display the Modbus set-up screens.
Address to be set within the range 01 to F7 Hexadecimal (refer to page 72 for conversion). If an address value outside this range is entered, the address set will revert to 01 (for 00) or F7 (for value above F7).
2400 Baud
PRESS THE
KEY.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the
The displayed option will flash indicating that it has been set. Press the
PF
44
The IQT actuator has the facility to accept 4 auxiliary inputs (AUX1 AUX4). These are used when supplementary remote control or digital auxiliary inputs are required in addition to the standard control and feedback features incorporated into the Modbus module. It is also possible to have a combination of both remote control and volt-free inputs to provide, for example, open and close control as well as a high and low tank level alarm indication, supplied via an external transducer. The hexadecimal number displayed under PF can be considered as a software mask. It is this mask that tells the Modbus module what type of input to expect, control or input signal, and what form the input will be, normally open or normally closed (refer to page 72 for Binary, Hexadecimal and Decimal Conversion Table). To decipher the mask the number needs to be split into two separate hexadecimal characters, each of which can be sub-divided into 4 binary bits. The first 4 bits represent the function and the second 4 represent the input source (known as invert). Pictorially this can be represented as: Left side hex character Aux 4 to 1 (function) 4321 Right side hex character AUX 4 to 1 (Invert) 4321
Any function bit set to 0 indicates that the particular aux input is to be treated as a digital signal for field status reporting, e.g. a level switch or motor running status. If the corresponding invert bit is set to a 0, an open contact is reported as a logic 1 and a closed contact is reported as a logic 0 (i.e. this will invert the input). If the corresponding invert bit is set to a 1, an open contact is reported as a logic "0" and a closed contact is reported as a logic 1 (i.e. this gives a noninverting input).
Bits
When used for remote control of the actuator bits 4 to 1 of the function character have been designated as follows: Bit 4 (AUX4) Bit 3 (AUX3) Bit 2 (AUX2) Bit 1 (AUX1) ESD Stop/Maintain Close Open
3. ESD Control
When using ESD (aux input 4), the ESD contact mode setting [A2] should be set to the default value of [nO]. The [A1]ESD direction setting should be set to either Open or Close the valve (refer to page 30).
(When used for digital signal inputs they are simply designated as AUX 4 to AUX 1.)
PF
PP
45
Modbus Parity
4. Stop/Maintain Control
When energised this will make the Aux input Open/Close control push-to-run. When de-energised, the Aux input Open/Close control will be maintained. ESD is always push to run (non maintained).
Where Modbus parity bit detection is used the module must be set with the parity bit setting of the host. Using the + or - keys display the required parity bit: [no] No parity bit [En] Even parity bit [Od] Odd parity bit
Examples
1. The full range of remote controls is needed. Open and Close are NO and ESD and Stop/maintain is NC. Aux I/P 4 3 2 1 Function 1 1 1 1 Invert 0011 =F = 3 i.e. set [PF] to [F3]
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the
2. Open and close control is required along with 2 inverted digital signal inputs. (Note that with this setting the open and close commands will be maintained.) Aux I/P 4 3 2 1 Function 0 0 1 1 Invert 0011 =3 = 3 i.e. set [PF] to [33]
PRESS THE
KEY.
The displayed option will flash indicating that it has been set.
3. Only an ESD input is needed. The requirement is for push to run control with a NO contact input. Aux I/P 4 3 2 1 Function 1 1 0 0 Invert 1000 =C = 8 i.e. set [PF] to [C8]
Continued
46
For Modbus module positioning settings and action on loss of signal setting [OF] (refer to page 54). If Modbus positioning control and action on loss of communication are required, return to the position display by pressing and y keys together. Display [OF] (refer to page 54).
9.10
PA
47
Profibus Address
Setting instructions for actuators including an optional Profibus DP module check wiring diagram for inclusion.
The Profibus DP module must be allocated a unique address. To set the address the Profibus module must be isolated from the host by disconnecting the RS485 highway or turning off the host device. Using the + or - keys display the required address.
Before setting the parameters for Option Profibus ensure Remote Control Source [Od] has been selected to [oP] in Section 9.7.
Profibus module set-up screens can be turned off to provide extra security. The action of turning screens on or off does not affect its operation.
PRESS THE
KEY.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the key to display the Profibus set-up screens.
Address to be set within the range 01 to 7E Hexadecimal (refer to page 72 for conversion). If an address value outside this range is entered, the address set will revert to 01 (for 00) or 7E (for value above 7E).
The displayed option will flash indicating that it has been set. Press the
y to display [Pb].
Pb
Profibus Proflags 2
PF
48
Proflags 2 setting determines the port used for communication and whether the host has the ability to change the Profibus module address. Using the + or - keys display the required setting: Set: [01] [03] [06] [12] Port 2 1 2 1 Host address change disabled disabled enabled enabled Port 1, Host Enabled
The IQT actuator has the facility to accept 4 auxiliary inputs (AUX1AUX4). These are used when supplementary remote control or digital auxiliary inputs are required in addition to the standard control and feedback features incorporated into the Profibus module. It is also possible to have a combination of both remote control and volt-free inputs to provide, for example, open and close control as well as a high and low tank level alarm indication, supplied via an external transducer. The hexadecimal number displayed under PF can be considered as a software mask. It is this mask that tells the Profibus module what type of input to expect, control or input signal, and what form the input will be, normally open or normally closed (refer to page 72 for Binary, Hexadecimal and Decimal Conversion Table). To decipher the mask the number needs to be split into two separate hexadecimal characters, each of which can be sub-divided into 4 binary bits. The first 4 bits represent the function and the second 4 represent the input source (known as invert). Pictorially this can be represented as: Left side hex character Aux 4 to 1 (function) 4321 Right side hex character AUX 4 to 1 (Invert) 4321
PRESS THE
KEY.
The displayed option will flash indicating that it has been set.
The default setting is [12]. On failure to establish communication the setting will cycle between [12] and [06] at 41/4 minute intervals until communication is established.
The power to the actuator must now be cycled in order for the Proflags 2 setting to take effect.
Press the
When used for remote control of the actuator bits 4 to 1 of the function character have been designated as follows: Bit 4 (AUX4) Bit 3 (AUX3) Bit 2 (AUX2) Bit 1 (AUX1) ESD Stop/Maintain Close Open
(When used for digital signal inputs they are simply designated as AUX 4 to AUX 1.)
PF
Rules
49
Examples
1. The full range of remote controls is needed. Open and Close are NO and ESD and Stop/maintain is NC. Aux I/P 4 3 2 1 Function 1 1 1 1 Invert 0011 =F = 3 i.e. set [PF] to [F3]
2. Open and close control is required along with 2 inverted digital signal inputs. (Note that with this setting the open and close commands will be maintained.) Aux I/P 4 3 2 1 Function 0 0 1 1 Invert 0011 =3 = 3 i.e. set [PF] to [33]
3. Only an ESD input is needed. The requirement is for push to run control with a NO contact input. Aux I/P 4 3 2 1 Function 1 1 0 0 Invert 1000 =C = 8 i.e. set [PF] to [C8]
3. ESD Control
When using ESD (aux input 4), the ESD contact mode setting [A2] should be set to the default value of [nO]. The [A1]ESD direction setting should be set to either open or close the valve (refer to page 30).
4. Stop/Maintain Control
When energised this will make the Aux input Open/Close control push to run When de-energised, the Aux input Open/Close control will be maintained. ESD is always push to run (non maintained).
PF
PP
Setting [PP] is not used by Profibus. Entered settings will be ignored.
50
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. If Profibus positioning control and action on loss of communication are required, return to the position display by pressing and y keys together. Display [OF] (refer to page 54).
PA
DeviceNet Address
Pb
51
DeviceNet Baudrate
The DeviceNet module must be allocated a unique address. Using the + or - keys display the required address. Address to be set within the range 01 to 3F Hexadecimal. See page 72 for conversion. If an address value outside this range is entered, the address set will revert to 01 (for 00) or 3F (for value above 3F).
The DeviceNet module must be set to the DeviceNet highway baudrate. Using the + or - keys display the required baudrate: [01] 125 k baud [03] 250 k baud [06] 500 k baud
PRESS THE
KEY.
PRESS THE
KEY.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the key to display the DeviceNet set up displays.
The displayed option will flash indicating that it has been set. Press the
The displayed option will flash indicating that it has been set. Press the
PF
Press the
52
The IQT actuator has the facility to accept 4 auxiliary inputs (AUX1AUX4). These are used when supplementary remote control or volt free digital auxiliary inputs are required in addition to the standard control and feedback features incorporated into the DeviceNet module. It is also possible to have a combination of both remote control and volt free inputs to provide, for example, open and close control as well as a high and low tank level alarm indication, supplied via an external transducer. The hexadecimal number displayed under PF can be considered as a software mask. It is this mask that tells the DeviceNet module what type of input to expect, control or input signal, and what form the input will be, normally open or normally closed. To decipher the mask the number needs to be split into two separate hexadecimal characters, each of which can be sub-divided into 4 binary bits. The first 4 bits represent the function and the second 4 represent the input source (known as invert). Pictorially this can be represented as: Left side hex character Aux 4 to 1 (function) 4321 Right side hex character AUX 4 to 1 (Invert) 4321
Bits
When used for remote control of the actuator bits 4 to 1 of the function character have been designated as follows: Bit 4 (AUX4) Bit 3 (AUX3) Bit 2 (AUX2) Bit 1 (AUX1) ESD Stop/Maintain Close Open
3. ESD Control
When using ESD (aux input 4), the ESD contact mode setting [A2] should be set to the default value of [nO]. The [A1]ESD direction setting should be set to either open or close the valve (refer to page 30).
(When used for digital signal inputs they are simply designated as AUX 4 to AUX 1.)
PF
AA
53
DeviceNet Parity
4. Stop/Maintain Control
When energised this will make the Aux input Open/Close control push-to-run. When de-energised, the Aux input Open/Close control will be maintained. ESD is always push to run (non maintained).
Examples
1. The full range of remote controls is needed. Open and Close are NO and ESD and Stop/maintain is NC. Aux I/P 4 3 2 1 Function 1 1 1 1 Invert 0011 =F = 3 i.e. set [PF] to [F3]
PRESS THE
KEY.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the
The displayed option will flash indicating that it has been set.
2. Open and close control is required along with 2 inverted digital signal inputs. (Note that with this setting the open and close commands will be maintained.) Aux I/P 4 3 2 1 Function 0 0 1 1 Invert 0011 =3 = 3 i.e. set [PF] to [33]
3. Only an ESD input is needed. The requirement is for push to run control with a NO contact input. Aux I/P 4 3 2 1 Function 1 1 0 0 Invert 1000 =C = 8 i.e. set [PF] to [C8]
9.12
OF
FL
FH
54
If the system control strategy for Pakscan, Modbus or Profibus requires intermediate valve travel positioning, certain control parameters need to be checked: the Limited Range Position Settings, the Motion Inhibit Time and its Deadband. There are an additional two Action on Loss of Signal parameters relating only to Modbus and Profibus systems that also need to be checked. Limited Range Positioning is a selectable option whereby positioning limits, 0% and 100%, can be at different positions to those used for digital Closed and Open limit commands. Limited range positioning can be set using the [FL] and [FH] screens. It should be noted that the actuator will respond to a digital Open or Close host command by moving the valve to the set limits irrespective of settings made for positioning control. Settings for Deadband and Motion Inhibit Time affect accuracy and response time.
Bus system positioning control set-up screens can be suppressed to provide extra security. Use the + or - key to turn on the positioning set-up screens.
[FL] is the position to which the actuator will move if a 0% command is sent and is the position at which the actuator will report 0% to the host. The default setting is for 0% to be the Close limit. If altered, it is possible that the position indicated by the actuator display will differ to that indicated by the host. Use the + or - key to select the desired valve position for a 0% command.
[FH] is the position to which the actuator will move if a 100% command is sent and is the position at which the actuator will report 100% to the host. The default setting is for 100% to be the Open limit. If altered, it is possible that the position indicated by the actuator display will differ to that indicated by the host. Use the + or - key to select the desired valve position for a 100% command.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the key to display Bus System Positioning Control Settings. Once [FI] is displayed, press the to display [FL]. 0% DV = Valve Closed 100% DV = Valve Open
y key
PRESS THE
KEY.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the
The displayed option will flash indicating that it has been set. Press the
Fd
Ft
FA
FF
55
All positioning commands are subject to a deadband tolerance. The deadband sets the expected positioning accuracy of the actuator and is dependent on various factors including, actuator output speed, number of turns and valve torque. If the deadband is set too low the valve may hunt around the set point. Use the + or - key to display the required setting: [00] to [99] 0% to 9.9% of valve stroke.
MIT sets the minimum time between successive position commands being actioned. It is used in situations to reduce the number of starts per hour and to smooth out fluctuations if continuous positioning is implemented. Setting the longest possible time while maintaining acceptable control will maximise the life of the motorised valve. Use the + or - key to display the required setting: [02] to [99] 2 to 99 seconds.
Modbus, Profibus & DeviceNet modules can be set to respond on loss of host communication by positioning the valve. Modbus checks for a loss of general highway communications whereas Profibus checks for a loss of communications addressed specifically to itself. The default setting is off [OF] and the default timeout is 255 sec. Use the + or - key to display the required setting: [On] Failsafe determined by setting [FF] [OF] No failsafe action
Modbus, Profibus & DeviceNet failsafe action when [FA] is enabled. Use the + or - key to display the required setting: [Lo] Close valve [SP] Stay put [HI] Open valve
Failsafe Close
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. 2.5% Deadband 5 Second MIT
PRESS THE
KEY.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the
The displayed option will flash indicating that it has been set. Press the
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the
9.13
OJ
9.13
56
When fitted, the timer will be made available for operation. The Interrupter cannot be enabled or disabled using the Setting Tool.
The default for timer direction is [CL], timer operation will start in closing and stop in opening pulsing operation around the close position. If pulsing operation is required to stop in closing and start in opening around the open position, use the + or - key. The display will change to [OP].
Using the + or - key select the position for the TIMER TO START WHEN THE VALVE IS CLOSING. [ ][ ] [01] to [99] [ ] = valve closed = percentage open = valve open
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Interrupter Timer Interrupter Timer Disabled Enabled When the timer option is available an additional series of settings can be accessed by pressing the key. Timer Set to Start Pulsing when Closing Valve Reaches 25% Open
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Pulsed Operation Around the Closed Position NOTE: Instructions [JC] and [JO] are for timer operation around the Closed position. For timing around the Open position, read stop for start [JC] and start for stop [JO]. Press the If the timing is not required in the closing stroke select [JC] to [ ] [ ] valve closed position. Press the
NOTE: If the timer option is not available pressing the key will not access setting.
Press the key to display interrupter timer set-up screens.
JO
Jn
Contactor On Time
JF
JE
57
Using the + or - key select the position for the TIMER TO STOP WHEN THE VALVE IS OPENING. [ ][ ] [01] to [99] [ ] = valve closed = percentage open = valve open
Using the + or - key select the actuator run period in the range 199 seconds.
Using the + or - key select the actuator stop period in the range 199 seconds.
The interrupter timer may be overridden when the actuator is under ESD signal command. This will mean the actuator will run to limit without stop/start action under ESD command. Refer to A1A3 (refer to page 30 for ESD settings).
The default for ESD override interrupter timer is [OF]. The interrupter timer will continue stop/start action during ESD action.
PRESS THE
Timer Set to Stop Pulsing when Opening Valve Reaches 25% Open
KEY.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. Press the
The displayed option will flash indicating that it has been set. Press the y key to display [JE] (refer to note on Page 58).
+ or - to display [On].
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. If timing is not required in the opening stroke select [JO] to [ ] [ ]. Press the ESD Override Timer OFF
PRESS THE
KEY.
The displayed option will flash indicating that it has been set.
Example
An actuator fitted with the interrupter timer and set as the example shown in these instructions would operate at: Rated speed from full Open to 25% Open. /6 rated speed from 25% Open to Fully Closed and from Fully Closed to 25% Open.
1
Note
With a Folomatic option fitted and the Interrupter Timer enabled, the Folomatic Motion Inhibit Timer must be adjusted to the same time as that set for the Interrupter Timer contactor off. Failure to do so will cause the actuator response to defer to the lower time which may cause control or process problems. For ON and OFF times in excess of 99 seconds apply to Rotork.
9.14
58
The displayed option will flash indicating that it has been set. With the red control selector in Local, the Setting Tool control keys are active (refer to page 12).
The default setting for this protection option is disabled [OF]. When disabled it is important that the actuator is not manually operated during a power failure if the battery is low as changes in position cannot be tracked - refer to page 6 for battery level status display. Should this occur the limits must be reset before electric operation takes place- refer to LC/LO page 27. Locking the hand auto lever can prevent manual operation - refer to 3.1 page 2.
PRESS THE
KEY.
The displayed option will flash indicating that it has been set. When protection is enabled, on power up if a low battery is detected, the actuator will inhibit electrical operation and display Power Loss Inhibit via actuator alarm display (refer to page 6) and the monitor relay will deenergise. Limits must reset and the battery replaced refer to page 65.
59
cr
P?
50 Positional Display
y y
PC
IrDA comms
Ir
Cell Phone
With [Ab] displayed Use the + and - key to select the required actuator type. The selectable values are related to actuator type as follows: Value 1 3 6 12 24 Type IQT125 IQT250 IQT500 IQT1000 IQT2000
Ic
ESD Action
r1 r2 r3 r4
Primary Functions
OE A1
PRESS THE
CPT Folomatic Remote Control Remote Control Source Bus System
KEY.
The displayed value will flash, indicating that it has been set. Any value of hex outside of the range stated will not be accepted into the actuator memory.
Option Selection
OI
OF
Od
IQT Speed Setting
OP PA
AA
Actuator Type
Ab
9.17
60
All IQT functions are configured to a set of Rotork default (standard) settings before despatch, see the table opposite. When requested, alternative settings specified with the order will be used. When site commissioning takes place, entered settings overwrite Rotork defaults and these current settings are used for operation along with the remaining unadjusted defaults. Should difficulty be encountered during commissioning the default settings can be reinstated, returning the actuator configuration to its original manufactured state. Site commissioning must then begin again. There are two levels of default: d1 Rotork standard or customer specified primary and secondary settings. d2 Limit positions only factory set limits.
Primary Functions
NOTE:
Settings associated with control options Folomatic, Pakscan, Modbus Profibus and Foundation Fieldbus are not affected by d1 or d2. Functions will remain as set.
If d1 is entered, all Primary and Secondary Functions except limit positions will return to their default setting. See the table opposite for Rotork standard settings. Primary setting (except limits) and secondary settings must then be checked and reset as required (refer to Primary Functions page 15 and Secondary Functions page 25). If d2 is entered the limits will be reset, with the actuator positioned at 50%. Limits must then be reset to the suit the valve (refer to Primary Functions page 15).
Secondary Functions
[CI]/[nO] Close, Normally Open [OP]/[nO] Open, Normally Open [CI]/[nC] Close, Normally Closed [OP]/[nO] Open, Normally Closed [SP] [nO] [OF] [OF] [OF] [On] Stay put on ESD Normally Open (make for ESD) Thermostats Active during ESD Interlocks Active during ESD Local Stop Active during ESD Maintains in Local Control
9.17
61
The Rotork standard default settings are subject to change without notice.
PRESS THE
KEY.
The setting bars will flash, indicating the [d1] default settings have been reinstated. To reinstate factory set limits (actuator positioned at 50%) with [d2] displayed,
PRESS THE
KEY.
The setting bars will flash, indicating the [d2] default limits have been reinstated.
[d1] Displayed
[d2] Displayed
10
62
Maintenance
Every Rotork actuator has been fully tested before dispatch to give years of trouble-free operation providing it is installed, sealed and commissioned in accordance with the instructions given in this publication. The IQT actuators unique double sealed, non-intrusive enclosure provides complete protection for the actuator components. Covers should not be removed for routine inspection as this may be detrimental to the future reliability of the actuator. The electrical control module cover is bonded by the Rotork quality control seal. It should not be removed as the module contains no site-serviceable components. All electrical power supplies to the actuator must be isolated before any maintenance or inspection is carried out, except replacement of the battery. Electrical supplies must be isolated before actuator covers are removed refer to Battery replacement instructions.
WARNING:
The battery holder in the actuator gearcase also protects the user from the hazardous live connections inside the actuator and therefore it must not be damaged. The actuator must be isolated or disconnected if the battery holder has to be removed from the actuator gearcase. A unique circuit has been incorporated into the battery function of the IQT, effectively reducing the overall drain and significantly increasing the battery life. Tests show for a typical actuator, a battery life of 7 years can be expected. Allowing for a conservative margin, Rotork recommend that the battery should be replaced every 5 years. Battery level status is indicated by an icon on the actuator display, refer to Section 3.4 Alarm Indication (refer to page 5). If the battery icon is displayed the battery must be replaced.
Battery Replacement
If the actuator is located within a hazardous area permission must be obtained in the form of a hot work permit or other local regulation before removal and/or replacement of the battery. Removal of the battery with the main electrical power switched off will result in stored Datalogger records being lost. It is therefore recommended that the battery is replaced with the main electrical supply to the actuator switched on. If main electrical power is not available or if main power has been switched off while the battery was discharged, it is recommended that the actuator limits be checked after battery replacement (refer to Section 8 Commissioning Primary Functions).
Battery Removal
The actuator must be selected to Stop using the red selector (refer to page 3). Access to the battery is via a labelled sealing plug situated on the main gearcase near the handwheel hub.
10
63
Use an 8mm Allen key to remove the sealing plug, ensuring the O ring seal remains on the plug. Disconnect the battery wiring loom from the battery terminals. Using the black pull strap, lift the battery out of the rubber sealing pocket.
Oil
The IQT range are factory filled with 80% Texaco Texamatic 9330 automatic transmission fluid (ATF) and 20% Kerosene. Equivalent ATF lubricants meeting the Dexron 2 or Mercon specification may be used. For operating ambient temperatures below -20C / -4F, 20% kerosene by volume should be added. IQT actuators do not require regular oil changes (refer to Weights and Measures Section 11, page 71).
Example shows 19% (of rated) torque at 50% open position. Display torque range: [00] to [99]% of rated torque in 1% increments. For values of torque above 99% the display will indicate [HI]. Display position range: [ ][ ] [01] to [99] [ ] = valve closed = percentage open = valve open
Fig. 10
Battery Types
For European hazardous area certified actuators (ATEX) use an Ultralife U9VL lithium manganese dioxide battery only. For FM and CSA certified enclosures use an Ultralife U9VL lithium manganese dioxide battery. Equivalent, UL recognised, batteries may be used. For watertight (WT) actuator enclosures use an Ultralife U9VL lithium manganese dioxide battery or any equivalent 9V battery.
PRESS THE
KEY.
The display will split, the top indicating the instantaneous torque (as a % of rated), the bottom indicating the measured position (% open).
For a stationary actuator the display will indicate the actual torque value as applied by the actuator. To keep the torque + position display active press the + or - keys. The display will remain active for approximately 5 minutes from the last key operation.
10
64
Troubleshooting
The IQT range of actuators is the worlds first that can be commissioned and interrogated without removing electrical covers. Help Screen diagnostics enable fast and complete fault finding to be carried out. With power off, the actuator display is not backlit. Position indicator lamp not illuminated. With mains power on, the actuators display should be backlit (refer to Section 3.3 page 4 The Actuator Display). Check that 3 phase supply is available and is of the correct voltage as stated on the actuator nameplate. Measure voltage phase to phase across terminals 1, 2 and 3 of the actuator terminal bung. With power Off, the actuator does not display position. With mains power off the actuator battery supports position indication liquid crystal display only.
H4 Monitor remote control inputs to the actuator. H5 Monitor remote interlocks local control inputs and motor thermostats. H6 Monitor torque switch status and IR Setting Tool communication for vandal proof applications. H7 Monitor travel limits, centre column and position limit status. H8 Monitor the actuators positionsensing devices. H9 Rotork use only. Help screen bars shown are undefined and may be ON, OFF or flashing.
H1
H2
BATTERY LOW ON POWER UP
Bar ON = Low battery detected On Power Up. If [OS] is selected [On] (set as default ) the actuator operation will be inhibited when powered up with a discharged battery (refer to [OS] page 58). The battery should be replaced at the earliest opportunity (refer to section 10).
65
H1
Phase Loss Position Error Local Controls Error Battery Low on Power-up
H2
ESD Active Low Battery Battery Discharged
LOW BATTERY
Bar ON = Battery level low. Bar OFF = Battery OK. Bar ON when the battery is low but still able to support the necessary actuator functions. The battery should be replaced at the earliest possible opportunity.
Help Screen 1
BATTERY DISCHARGED
Bar ON = Battery Discharged. Bar ON when the battery is no longer able to support actuator functions under loss of power conditions. The battery must be replaced (refer to Section 10) and limit positions reset (refer to [LC] and [LO] section 8).
POSITION ERROR
Bar ON = Current Position Error Present. During power up the actuator position processor compares the current position to that stored in the eeprom. If there is a discrepancy this is shown as a current position error. Re-setting of both actuator limits should now be carried out (refer to section 8).
PHASE LOSS
Bar ON = Phase Lost (3 Phase Actuators Only). Loss of third monitored power supply phase connected to actuator terminal 3.
H3
H4
H5
REMOTE CLOSE 1
Bar OFF = Remote Close Signal Present. ESD 1 Bar OFF = ESD signal present.
66
H3
Clockwise Limit Anti Clockwise Limit Inhibit ESD 2 Remote Close 2
H4
Remote Maintain 2 Remote Open 1 Remote Close 1 ESD 1 Remote Open 2 Remote Maintain 1
Local Stop not Selected Thermostat Tripped Local Open not Present
H5
Open Interlock Close Interlock Local not Selected
REMOTE MAINTAIN 1
Bar OFF = Remote Maintain signal present. Bar ON = Remote Maintain not present and/or Remote Stop active.
Help Screen 3
REMOTE OPEN 2
Bar OFF = Remote Open signal present from BUS option pcb.
CLOCKWISE LIMIT
Bar ON = Actuator has reached clockwise limit of travel.
Help Screen 4 All remote signals designated with 1 are standard hard wired remote inputs. When a Pakscan, Profibus or Foundation Fieldbus card is fitted, remote control inputs are designated with a 2.
Help Screen 5
REMOTE CLOSE 2
Bar OFF = Remote Close signal present from BUS option pcb.
OPEN INTERLOCK
Bar ON = Open Interlock Active. (Actutator disabled) Unauthorised Open electrical operation can be prevented by interlocking the actuator (Open) control with an external interlock contact. If external interlocks are not required the interlock function must be selected OFF.
ANTI-CLOCKWISE LIMIT
Bar ON = Actuator has reached Anti-clockwise limit.
ESD 2
Bar OFF = ESD signal present from BUS option pcb.
INHIBIT
Bar ON = Actuator inhibited.
REMOTE OPEN 1
Bar OFF = Remote Open Signal Present.
Possible Causes:
Phase Loss (3 phase only). Power Loss Inhibit (page 58). Internal Failure.
REMOTE MAINTAIN 2
Bar OFF = Remote Maintain signal present from BUS option pcb.
H5
H6
Torque Switch Status & IR Setting Tool Comms for Vandal Proof Applications
67
CLOSE INTERLOCK
Bar ON = Close Interlock Active. (Actuator disabled) Unauthorised Close electrical operation can be prevented by interlocking the actuator (Close) control with an external interlock contact. If external interlocks are not required the interlock function must be selected OFF.
IR Remote Control not Selected IR Local Control Disabled IR Closed Signal not Present IR Open Signal not Present
H6
Local Controls not Fitted
Help Screen 6 When actuators are supplied for Vandal Proof applications the local control knobs are removed to prevent unauthorised operation. The local control functions are then carried out by using the Infra-red Setting Tool.
This latching of the event protects the actuator and valve from repeated hammering against the obstruction as a response to a maintained control signal. To de-latch the actuator it must be reversed. (For actuator torque adjustment, refer to [tC ] and [tO] section 8)
H6
Torque Switch Status & IR Setting Tool Comms for Vandal Proof Applications cont.
H7
H3
68
H7
Relay 4 Relay 3 Open Limit Close Relay 2 Relay 1 Actuator Moving
H8
Position Sensor A Position Sensor B
Help Screen 7
Help Screen 8
OPEN LIMIT
Bar ON = Actuator has reached open limit.
POSITION SENSOR A
Senses output rotation. Used for the position sensing circuit. Correct operation of the sensor is indicated by the bar being ON and OFF alternately. When the motor is running, ON and OFF bit duration should be equal.
CLOSE LIMIT
Bar ON = Actuator has reached Close limit.
ACTUATOR MOVING
Bar ON = Actuator moving.
POSITION SENSOR B
Senses output rotation. Used for the position sensing circuit. Correct operation of the sensor is indicated by the bar being ON and OFF alternately. When the motor is running, ON and OFF bit duration should be equal.
10.2
10.2
69
IQ Insight software tool for PC has been developed to enable the actuator configuration and onboard datalogger to be reconfigured and analysed. To enable communication with IQ Insight the actuator IrDA interface must be enabled. A PC running IQ Insight software may be located at the actuator or, using a cell phone link, at a remote site (for information on IQ Insight see www.rotork.com).
Using IQ Insight software tool, remote diagnostics can be enabled using a cell phone located at the actuator to transmit and receive data to and from a remote PC running IQ Insight software. The cell phone must be IrDA compatible and have access to a transmit/receive data line (contact your cell phone manufacturer and service provider). (For information on IQ Insight software refer to publication E111E). The actuator IrDA feature must be enabled (refer to [Ir] IQ Insight IrDA Comms). Before starting, the cell phone must be configured for "data" as opposed to voice and be positioned in direct line of sight to the actuator display, no more than 0.5m (2ft) from the display.
PRESS THE
KEY.
To enable remote diagnostics use the + or - key. The display will change to [On].
PRESS THE
KEY.
The actuator display will automatically return to indicating the current position. The actuator will search for a compatible IrDA device within range for approximately 30 seconds. On establishing communication, the actuator display will indicate the symbol shown below.
10.2
70
NOTE: The use of a notebook PC or cell phone with actuators located in hazardous areas will be subject to local regulations.
The cell phone must be kept within range for the duration of the remote diagnostic session. If communication is not established or is lost, after 30 seconds the actuator will stop searching. To resume remote cell phone diagnostics the process outlined above must be started again. It is the responsibility of the user to seek guidance and permission. The IQ Setting Tool is certified Intrinsically Safe (IS) and therefore can be used in defined hazardous areas (refer to page 12). Diagnostic devices are available for local configuration, analysis and transportation of actuator data to other areas. Contact Rotork for further information.
11
Oil
71
The IQT range are factory filled with 80% Texaco Texamatic 9330 automatic transmission fluid (ATF) and 20% Kerosene. Equivalent ATF lubricants meeting the Dexron 2 or Mercon specification may be used. For operating ambient temperatures below -20C / -4F, 20% kerosene by volume should be added.
72
64 100 65 101 66 102 67 103 68 104 69 105 6A 106 6B 107 6C 108 6D 109 6E 110 6F 111 70 112 71 113 72 114 73 115 74 116 75 117 76 77 78 79 7A 7B 7C 7D 7E 7F 118 119 120 121 122 123 124 125 126 127
AA 170 AC 172 AD 173 AE AF B0 B1 B2 B3 B4 B5 B6 B7 B8 B9 BA BB BC BD BE BF 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191
CA 202 CC 204 CD 205 CE CF D0 D1 D2 D3 D4 D5 D6 D7 D8 D9 DB 206 207 208 209 210 211 212 213 214 215 216 217 219
12
73
IQ Approvals
USA hazardous Area FM. Class 1, Division 1, Groups C, D, E, F, G hazardous areas.
Factory Mutual - Explosionproof to NEC Article 500. Temperature -30C to +60C (-22F to +140F). *Option -40C to +60C (-40F to +40F). *Alternative for Group B hazardous area. Temperatures as for Groups C and D.
Refer to actuator nameplate for unit specific approval details European Hazardous area
EExd IIB T4. ATEX (94/9/EC) II 2GD CENELEC Norm EN50014 and EN50018 Temperature -20C to +70C (-4F to +158F). *Option -30C to +70C (-22F to +158F). *Option -40C to +70C (-40F to +158F). *Option -50C to +40C (- 58F to +104F).
International Non hazardous WT: Standard watertight, BS EN 60529 :1992, IP68, 7 metres/72 hours.
Temperature -30C to +70C (-22F to +158F). *Option -40C to +70C (-40F to +158F). *Option -50C to +40C (-58F to +104F).
Canada Non hazardous CSA WT: Canadian Standard Association Watertight. Wiring and components complying with CSA Enclosure 4 and 4X.
Temperature -30C to +70C (-22F to +158F). *Option -40C to +70C (-40F to +158F). *Option -50C to +40C (-58F to +104F).
Rotork can supply actuators to national standards not listed above. For details please contact Rotork.
If your Rotork actuator has been correctly installed and sealed, it will give years of trouble-free service. Should you require technical assistance or spares, Rotork guarantees the best service in the world. Contact your local Rotork representative or the factory direct at the address on the nameplate, quoting the actuator type and serial number.
Algeria Tel: + 213 6 37 4854 Fax: + 213 6 37 2613 E-Mail: Argentina Tel: +54 11 4755 5560/4753 7533 Fax: +54 11 4755 5560/4753 7533 E-Mail: [email protected] Australia Rotork Company HQ Tel: +61 3 53 381566 Fax: +61 3 53 381570 E-Mail: [email protected] Australia Brisbane Rotork Company Tel: +61 7 3373 2050 Fax: +61 7 3255 5388 E-Mail: Australia Sydney Rotork Company Tel: +61 2 9 567 2735 Fax: +61 2 9 567 2739 E-Mail:
Australia Western Australia Agent Tel: +61 8 9314 1827 Fax: +61 8 9314 1837 E-Mail: [email protected] Austria Agent Tel: +43 7224 66008 Fax: +43 7224 66008 E-Mail: [email protected] Bahrain Rotork Regional Office Tel: +973 791 976 Fax: +973 791 976 E-Mail: [email protected] Bahrain Agent Tel: +973 727790 Fax: +973 727811 E-Mail: [email protected] Belgium Agent Tel: +32 2 7263300 Fax: +32 2 7263633 E-Mail: [email protected] Bolivia Agent Tel: +591 3 532615 Fax: +591 3 552528 E-Mail: [email protected] Brazil Agent Tel: +55 71 235 6588 Fax: +55 71 235 3299 E-Mail: [email protected]
Brunei Agent Tel: +673 3 336122 Fax: +673 3 336142 E-Mail: [email protected] Canada Rotork Company HQ Tel: +1 403 569 9455 Fax: +1 403 569 9414 E-Mail: [email protected] Canada Edmonton Rotork Company Tel: +1 780 449 6663 Fax: +1 780 449 6578 E-Mail: [email protected] Canada Montreal Rotork Company Tel: +1 514 355 3003 Fax: +1 514 355 0024 E-Mail: [email protected] Canada S.W. Ontario Rotork Company Tel: +1 519 337 9190 Fax: +1 519 337 0017 E-Mail: [email protected] Canada Toronto Rotork Company Tel: +1 905 602 5665 Fax: +1 905 602 5669 E-Mail: [email protected]
Caribbean (Puerto Rico) Agent Tel: +1 787 751 4415 Fax: +1 787 250 1842 E-Mail: Chile Agent Tel: +56 2 441 1033/699 2001 Fax: +56 2 441 1023 E-Mail: [email protected] China North/Beijing Rotork Company Tel: +86 10 6497 4142/94590 Fax: +86 10 6499 4591 E-Mail: [email protected] China Shanghai Rotork Company Tel: +86 21 6478 5015 Fax: +86 21 6478 5035 E-Mail: [email protected] China Sichuan Rotork Branch Tel: +86 28 6521191 Fax: +86 28 6521056 E-Mail: [email protected] China (South) Guangzhou Rotork Branch Tel: +86 20 81320500 Fax: +86 20 81320499 E-Mail: [email protected]
China Hong Kong Rotork Company Tel: +852 2520 2390 Fax: +852 2528 9746 E-Mail:[email protected] Colombia Agent Main Office Tel: +57 1 621 27 40 Fax: +57 1 621 25 61 E-Mail: [email protected] Costa Rica Agent Tel: +506 228 8630/1 Fax: +506 289 4350 E-Mail:[email protected] Croatia Agent Tel: +385 1 4 577 217 Fax: +385 1 4 577 220 E-Mail: Cyprus Agent Tel: +357 2 434131 Fax: +357 2 433416 E-Mail: [email protected] Czech Republic Agent Tel: +420 5 48321534 Fax: +420 5 48216240 E-Mail:
Denmark Agent Tel: +45 32531777 Fax: +45 32530504 E-Mail: Ecuador Agent Tel: +593 2 222 585 Fax: +593 2 569 950 E-Mail: [email protected] Egypt Agent Tel: +20 2 2574830/2573456 Fax: +20 2 2575695 E-Mail: [email protected] Finland Agent Tel: +358 9 350 7410 Fax: +358 9 374 3590 E-Mail: France Rotork Company Tel: +33 1 43 11 15 50 Fax: +33 1 48 35 42 54 E-Mail: (name)@rotork.fr Germany Rotork Company Tel: +49 2103 95876 Fax: +49 2103 54090 E-Mail: [email protected] Greece Agent Tel: +30 1 6549433/6536610 Fax: +30 1 6517810 E-Mail: [email protected]
Hungary Agent Tel: +36 76 495932 Fax: +36 76 495936 E-Mail: [email protected] India Bangalore Rotork Factory Tel: +91 80 8395576 Fax: +91 80 8391601 E-Mail: [email protected] India Calcutta Rotork Branch Tel: +91 33 282 3306 Fax: +91 33 282 3473 E-Mail: [email protected] India Chennai Rotork Company Tel: +91 44 625 4219/625 8136 Fax: +91 44 625 7108 E-Mail: [email protected] India Mumbai Rotork Branch Tel +91 22 5584578 Fax: +91 22 5584540 E-Mail: [email protected] India New Delhi Rotork Branch Tel +91 11 5616305 Fax: +91 11 5502840 E-Mail: [email protected]
Indonesia Rotork Company Tel +62 21 5806764 Fax: +62 21 5812757 E-Mail: [email protected] Ireland (Northern) Agent Tel: +44 28 90 841004 Fax: +44 28 90 841007 E-Mail: [email protected] Ireland (Southern) Dublin Agent Tel: +353 1 2952182 Fax: +353 1 2953713 E-Mail: [email protected] Italy Rotork Company Tel: +39 02 45703300 Fax: +39 02 45703301 E-Mail: [email protected] Japan Osaka Rotork Company Tel: +81 728 35 7555 Fax: +81 728 35 7548 E-Mail: Japan Tokyo Rotork Company HQ Tel: +81 3 3294 8551 Fax: +81 3 3294 6460 E-Mail: [email protected]
Jordan Agent Tel: +962 6 581 9982 Fax: +962 6 582 5818 E-Mail: [email protected] Korea (South) Rotork Company Tel: +82 331 265 0962 Fax: +82 331 265 1369 E-Mail: [email protected] Kuwait Agent Tel: +965 241 5921 Fax: +965 241 2485 E-Mail: [email protected] Latvia Agent Tel: +371 7 315086/315087 Fax: +371 7 315084 E-Mail: [email protected] Libya Agent Tel: +218 21 47 72628/78598 Fax: +218 21 47 72782 E-Mail: [email protected] Lithuania Agent Tel: +370 7 202410 Fax: +370 7 207414 E-Mail: [email protected]
Malaysia East Malaysia Agent Tel: +60 85 410079 Fax: +60 85 419484 E-Mail: Malaysia West Malaysia Rotork Company Tel: +60 3 7880 9198 Fax: +60 3 7880 9189 E-Mail: [email protected] Mexico Agent Tel: +52 5 559 2959/2777 Fax: +52 5 575 1092 E-Mail: [email protected] Netherlands Rotork Company Tel: +31 10 414 6911 Fax: +31 10 414 4750 E-Mail: [email protected] New Zealand Auckland Agent North Island Tel: +64 9 634 0456 Fax: +64 9 625 2678 E-Mail: New Zealand Christchurch Agent South Island Head Office Tel: +64 3 353 4665 Fax: +64 3 353 4666 E-Mail:
New Zealand Wellington Agent North Island Tel: +64 4 477 5070 Fax: +64 4 477 5049 E-Mail: Nigeria Agent Tel: +234 1 4522955/523225 Fax: +234 1 4522887 E-Mail: [email protected] Norway Stavanger Agent HQ Tel: +47 51 844204 Fax: +47 51 844102 E-Mail: Norway Bergen Agent Sales Office/Workshop Tel: +47 56 312900 Fax: +47 56 312910 E-Mail: Norway Oslo Agent Sales Office Tel: +47 67 906120 Fax: +47 67 906472 E-Mail: Oman Agent Tel: +968 601438 Fax: +968 699446 E-Mail:[email protected]
Pakistan Agent Tel: +92 21 5861509/5861510 Fax: +92 21 5874674 E-Mail: [email protected] Peru Agent Tel: +51 1 330 7728 Fax: +51 1 330 7728 E-Mail: [email protected] Philippines Manila Agent Tel: +63 2 7312610/7326125 Fax: +63 2 7312610 E-Mail:[email protected] Poland Agent Tel: +48 22 723 1770 Fax: +48 22 723 1780 E-Mail: Portugal Agent Tel: +351 21 486 43 25 Fax: +351 21 483 57 17 E-Mail:[email protected] Qatar Agent Tel: +974 44 19603 Fax: +974 44 19604 E-Mail:[email protected]
Romania Agent Tel: +40 44 114187/114664 Fax: +40 44 114664 Manual E-Mail:[email protected] Russia Rotork Company Tel: +7 095 229 24 63 Fax: +7 503 234 91 25 E-Mail: [email protected] Saudi Arabia Agent/J.V. Tel: +966 3 833 1661 Fax: +966 3 833 9369 E-Mail: Saudi Arabia Rotork Company Tel: +966 3 858 1464 Fax: +966 3 858 1464 E-Mail: [email protected] Singapore Rotork Company Tel: +65 4571233 Fax: +65 4576011 email: South Africa Rotork Company Tel: +27 11 453 9741-3 Fax: +27 11 453 9894 E-Mail: Spain Rotork Company Tel: +34 94 676 60 11 Fax: +34 94 676 60 18 E-Mail:[email protected]
Sweden Partille Agent Head Office Tel: +46 53 3763952 Fax: +46 53 3763955 E-Mail:[email protected] Sweden Saffle Agent Local Office Tel: +46 533 763952 Fax: +46 533 763955 E-Mail:[email protected] Syria Agent Tel: +963 31 230 289 Fax: +963 31 237 867 E-Mail: Taiwan Agent Tel: +886 2 2577-1717 Fax: +886 2 2577-5588 E-Mail:[email protected] Thailand Rotork Company Tel: +66 2 272 7165-6 Fax: +66 2 272 7167 E-Mail:[email protected] Trinidad Agent Tel: +1 868 6524889/6523422 Fax: +1 868 6522651 E-Mail:[email protected]
Turkey Agent Tel: +90 216 327 34 71 Fax: +90 216 327 34 72 E-Mail:[email protected] U.K. Head Office, Tel: +44 1225 733200, Fax +44 1225 333467 E-mail: [email protected] United Arab Emirates Agent Tel: +971 2 632 5111 Fax: +971 2 621 1934 E-Mail: [email protected] United States of America Rotork Company HQ Rochester Tel: +1 716 328 1550 Fax: +1 716 328 5848 E-Mail:[email protected] United States of America Rotork Company Duluth Tel: +1 770 623 6301 Fax: +1 770 623 6124 E-Mail:[email protected] United States of America Chicago & Mid West Rotork Company Tel: +1 815 436 1710 Fax: +1 815 436 1789 E-Mail:
United States of America Houston Rotork Company Tel: +1 713 7825888 Fax: +1 713 7828524 E-Mail: United States of America New York City Rotork Company Tel: +1 716 328 1550 Fax: +1 716 328 5848 E-Mail:[email protected] United States of America North East Rotork Company Tel: +1 814 835 8349 Fax: +1 814 835 8909 E-Mail: United States of America Northern California Rotork Company Tel: +1 707 769 4880 Fax: +1 707 769 4888 E-Mail: United States of America Northwest Area Rotork Company Tel: +1 253 838 5500 Fax: +1 253 838 5400 E-Mail: [email protected] United States of America Philadelphia Rotork Company Tel: +1 609 223 1926 Fax: +1 609 223 9012 E-Mail: [email protected]
United States of America South Central Region Rotork Company Tel: +1 972 459 4957 Fax: +1 972 745 2041 E-Mail: [email protected] United States of America Southern California Rotork Company Tel: +1 949 348 2913 Fax: +1 707 769 4888 E-Mail: Venezuela & N. Antilles Rotork Company HQ Tel: +58 2 212 5232/4208 Fax: +58 2 212 8050 E-Mail: [email protected] Venezuela & N. Antilles Cagua Rotork Company Tel: +58 4 4635911 Fax: +58 4 4635911 E-Mail: Venezuela & N. Antilles Maracaibo Rotork Company Tel: +58 61 579315/492611 Fax: +58 61 579315 E-Mail:[email protected] Venezuela & N. Antilles Puerto La Cruz Rotork Company Tel: +58 281 268 0759 Fax: +58 281 266 3554 E-Mail:
Vietnam Agent Tel: + 84 8 84 62525 Fax: + 84 8 8423218 E-Mail:[email protected] Yemen Agent Tel: +967 1 272988 Fax: +967 1 271890 E-Mail:[email protected]
Addendum to:
IQT Range Installation and Maintenance Instructions Battery Failsafe information
Charger : The IQT battery failsafe is despatched with the batteries in a charged state, however once the IQT is connected to AC power the batteries will automatically begin charging to bring them to the float charge state. For correct battery charging, the IQT supply voltage must not be less than 90% of nominal. Charging Timetypically 4 hours from a discharged state (depending on ambient temperature). Charge state - Tri-colour LED indication in IQT main display* fig 2 RedBattery charge depleted < 80%Boost charge AmberBattery charge low 80% to 100%Overcharge charge GreenBattery fully charged Float charge * AC Power ON indication. When AC supply is OFF, LED status indication is approximate due to termination of battery charging. Protection : DC power supplyFuses FS 3 and FS4 are rated at 20A, automobile type ATO Fast acting.
Charge/control Fuses FS1 and FS2 are rated 2A, 20mm quick blow. The battery supply will auto disconnect at 20V or 30 minutes after AC supply is removed from the actuator to prevent damage caused by deep discharge of batteries. Maintenance : Ensure the two vents located in the battery pack cover are not removed, plugged or covered. The batteries are sealed lead acid type and require no maintenance. Refer to E175E for IQT range maintenance.
Fig. 1
Fig. 2
houses the battery pack and charging/control circuitry and care must be taken that it does not drop. Ensure the two 20A fuses located in a plastic bag are kept safely - DO NOT FIT The cover is restrained with an external chain to support its weight (5.5 Kg approx) and prevent interconnecting cables being damaged. The battery failsafe cover assembly is supported by the restraining chain during commissioning. 2. Set control Links. Figure 4 Referring to the label, locate PCB links LK1 and LK2. Links determine required action on loss of AC supply to the actuator. Using pliers, fit links LK1 and LK2 in required positions. Links bridge between pins 1-2 or 23 and must be set for the desired action as detailed in table the below: *The direction required for failsafe operation and ESD contact form (if being used) is set with the IQT setting tool. Refer to 6, page 4.
LK1 LK2 Required action 1-2 1-2 Failsafe on loss of supply, ESD [A2] set [NO]* 2-3 1-2 Failsafe on loss of supply, ESD [A2] set [NC]* 1-2 2-3 Stayput waiting for command (30 Min max) 3. Connect ESD/Interlock control wiring. Figure 5 If the control of the IQT actuator with AC supply switched ON requires emergency shut down and/or interlocks, ESD and/or interlock field wiring must be connected to the green terminal plug located on the battery pack assembly. If ESD and/or interlocks do not form part of the IQT control scheme then no wiring is necessary. Remove plug by pulling it straight up and connect field wiring for ESD and/or interlocks as indicated on the label and actuator wiring diagram. Once connected, re-fit the wired plug into its socket. The plug and socket are polarised, ensuring they cannot be mated incorrectly. Fig. 4 Fig. 6 Fig. 3 Fig. 5
Tighten the 4 fixing bolts using a 6mm allen key. Set up of the battery pack is now complete. To enable failsafe operation, settings within the IQT actuator must now be made. 6. IQT Actuator failsafe Settings. The actuator can be operated by standard remote control signals (open/close/interlocks/ESD) under AC supply control. On AC supply loss, the actuator will automatically perform an ESD using battery power. For the required failsafe operation, using the supplied Infra-red Setting Tool, set secondary settings [A1], [A2] and [A4] for the desired failsafe action. Refer to publication E175E IQT Range Installation instructions, page 30, [A1] ESD Action, [A2] ESD contact type and [A4] ESD override interlocks actuator settings must be checked and/or set . Switch ON AC supply power to the IQT actuator. Refer to table below for settings
Failsafe action on loss of AC supply Close (no user ESD) Open (no user ESD) Close ESD = N/O contact, makes for ESD Open ESD = N/O contact, makes for ESD Close ESD = N/C contact, breaks for ESD Open ESD = N/C contact, breaks for ESD
LK1* 1-2
LK2* 1-2
[A1] [CL]
[A2] [NO]
[A4] [OF]
1-2
1-2
[OP]
[NO]
[OF]
1-2
1-2
[CL]
[NO]
[OF]
Fig. 7 4. Fit Battery Fuses. Figure 6 Referring to the label, locate 20A fuses FS3 and FS4 holders located on the battery pack assembly. Remove 20A fuses from the plastic bag and fit into fuse holders FS3 and FS4 as shown. 5. Refit Cover. Figure 7 Make sure cover O ring is fitted and the cover spigot is lightly greased. Refit cover making sure no field or interconnecting wires are trapped between cover and gearcase.
1-2
1-2
[OP]
[NO]
[OF]
2-3
1-2
[CL]
[NC]
[OF]
2-3
1-2
[OP]
[NC]
[OF]
NOTE. If ESD is being used for AC supply control the user must decide if ESD is to override local stop. If ESD override local stop is required set [A5] to [NO]. Testing To test the failsafe function, switch off AC supply to IQT actuator. Actuator will perform the set failsafe function. Refer to section 2, page 4 of this addendum.
ATTENTION: RED PLASTIC PLUGS IN CONDUIT ENTRIES ARE FOR TRANSIT ONLY. FOR LONG TERM PROTECTION FIT SUITABLE METAL PLUGS. ATTENZIONE: I TAPPI IN PLASTICA ROSSA PER L'ENTRATA CAVI SONO SOLO TEMPORANEI. PER UNA PROTEZIONE PERMANENTE PREGO SOSTITUIRLI CON APPOSITI TAPPI METALLICI. ATENCION: LOS TAPONES ROJOS DE PLASTICO EN LAS ENTRADAS DE CABLE SON UNICAMENTE PARA TRANSPORTE. PARA PROTECCION PERMANENTE COLOCAR TAPONES METALICOS APROPIADOS. ACHTUNG: DIE ROTEN PLASTIKSTOPFEN SIND NUR FR DEN TRANSPORT GEEIGNET. FR DAVERHAFTEN SCHUTZ SIND DIESE GEGEN GEEIGNETE BLINDSTOPFEN AUSZTAUSCHEN. ATTENTION: LES BOUCHONS PLASTIQUES ASSURENT UNE PROTECTION TEMPORAIRE. POUR UNE PROTECTION DEFINITIVE UTILISER DES BOUCHONS METALLIQUES.
As we are continually developing our products, the design of Rotork actuators is subject to change without notice. The latest product and technical information is available at our website: www.rotork.com. The name Rotork is a registered trade mark. Rotork recognises all registered trade marks.