12 Electrical Design Basis PDF
12 Electrical Design Basis PDF
12 Electrical Design Basis PDF
0
REV.
06.12.2007
DATE PREPARED BY CHECKED BY PREPARED BY
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
Safety to personnel and equipments. Reliability of service. Minimum fire risk. Ease of maintenance and convenience of operation. Adequate provision for future expansion and modification. Maximum interchangeability of equipments. Automatic protection of all electrical equipments through selective relaying system. Fail safe features. Hook-up provisions with existing facilities, wherever required. Adequate provision for future expansion and modification.
1.1 Site Conditions All electrical equipments and accessories / materials are to be suitable for installation and operation under dusty, humid, corrosive and hostile environment with special degree of hazards. Min / Max ambient temperatures, RH, Height from MSL and other related environmental parameters for site are mentioned elsewhere in bid package.
1.2 General Safety The electrical system should incorporate safety margins to ensure that the installation is safe under all operating conditions, including those associated with the start up and shut down of equipment and throughout intervening shut down periods. The emphasis in equipment specification shall be on operability, prevention of accident / fault and functionality for the intended design life. All insulating materials specified for the equipment should be non-toxic.
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
1.3 Fire Integrity All cable penetrations through firewalls, switchgear room walls, control room walls, and between safe and hazardous area (from close to open or open to close) have to be sealed using multi cable transits to maintain fire integrity and prevent gas migration.
The applicable specifications as drawn by the above organizations / institutions are also mentioned in the corresponding equipment standard specifications. In the event of conflict between codes and standards being used, the most stringent one has to be followed. Where Indian standards do not exist or equipment is supplied by foreign manufacturer, relevant international standards shall be applicable.
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
Incase of any conflict amongst the above, the more stringent shall be followed. The following factors shall be considered for proper selection of equipments for use in hazardous area: Area classification i.e. Zone-0, 1 or 2. Gas group classification: The characteristics of the gas or vapor involved in relation to the ignition current or minimum ignition energy and safe gap data. Temperature classification: The ignition temperature of gas or vapor involved or the lowest value of ignition temperature if more than one combustible material is present. Environmental conditions in which equipments are to be installed: The selected
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001 ELECTRICAL DESIGN BASIS DOCUMENT NO.: OESG/ARP/ELECT/0012 Page No.: 4 of 32
REV. 0
electrical equipments shall be suitably protected against corrosive and solvent agents, water & moisture ingress, thermal and mechanical stresses as determined by the environmental conditions. The types of protections generally used for electrical equipments in hazardous areas are as follows : Zone 0 Zone 1 Zone 2 Intrinsically Safe, Type of Protection i. Intrinsically Safe, Type of Protection i. Flameproof equipment, Type of protection d. Pressurized enclosure, Type of protection p Sand filled equipment, Type of protection q. Other electrical apparatus specifically designed for zone 1,s. Protection as suitable for Zone-0 and 1. Increased Safety protection e.
Electrical equipments to be used in hazardous area shall possess type test certificates from one of the following recognized testing and certifying authorities: CMRI CCE UL FM BASEEFA : : : : : Central Mining Research Institute. Chief Controller of Explosives (Indian). Underwriters Laboratories Inc. (USA). Factory Mutual Research Corporation (USA). British Approvals Service for Electrical
Equipment in Flameproof Atmospheres. PTB RIIS : : Physikalisch Technische Boundesantalt (Germany). Research Institute of Industrial Safety (JAPAN).
All equipments falling in the hazardous area shall be intrinsically safe (type i), or flameproof / explosion proof (type d). Only in case for any application, when equipments of such protection classification are not available, other types of protections can be considered as indicated in the table below: Zone 1 2 Type of Protection p, q, s p, q, s, e
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
The temperature of exposed surface of any equipment (including electrical) installed in hazardous area shall not exceed the minimum ignition temperature of the gases involved, subject to a maximum of 2000C (Temp. Class T3). In addition to above, the equipments to be used in classified areas must have type test certificates from CMRI or any other testing agency as above and must also be approved by DGMS. Any other statutory approval, if required in view of Clause 5.0 of this document, will also be the responsibility of the contractor. Besides all indigenous equipments to be used in classified areas shall have valid BIS license as required by statutory authorities. The copies of the BIS certificates with the DGMS approval certificates shall be furnished during documentation review. It is the contractors responsibility to obtain all statutory approvals including the DGMS approval for the plant. NOTE: 1.0 2.0 Electrical equipment installation in Zone-0 area shall be avoided. Switchgear room, the outdoor switchyard, housing for
emergency power generator set shall be located in safe area. 3.0 Overhead power lines passing through hazardous area shall be avoided. 4.0 Equipments / items installed in battery room shall be suitable for Zone 1, Gas group II C.
REV. 0
State Electricity Rules / Regulations laid down by Chief Electrical Inspector of State. Any other applicable rules / regulations of central / state / local statutory body. Note: Special attention is to be paid to chapter X of IE rules, while designing electrical system in oil mines.
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
TRANSFORMER MOTOR
INCOMER
RELAY MV HV HV MV PMCC HV PMCC (REF:- ANSI / IEEE (250 V (650 V (250 V / IEC 37.2) POWER DISTR. (650 V (650 V < HV < HV < MV < HV < MV 33 kV) 33 kV) 650 V) 33 kV) 650 V) IDMTL O/C (51) IDMTL E/F (51N) BACK UP E/F (51N) (SECONDARY SIDE NEUTRAL) MOTOR PROTECTION RELAY WITH LOCKED ROTOR FEATURE (50, 51, 50N, 46, 49, 50L/R) INSTANT. REST.E/F SECONDARY SIDE (50N) INST.O.C (50) INSTANT.EF. (R) (50N) TRIPPING RELAY (86) TRIP CKT SUPERVISION (95) TFMR AUX. RELAY (63TX) UNDERVOLTAGE WITH TIMER (27,2) YES YES (7) YES NO YES YES YES (4) YES (4, 8) YES YES YES (4) YES (4,9) NO
YES
YES
NO
NO
NO
NO
NO
YES
NO
NO
NO
NO
NO NO NO
NO NO NO NO YES (4) NO NO
NO NO NO NO YES YES NO
NO NO NO NO YES NO NO
YES
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
Note: (1) (2) (3) (4) (5) (6) (7) (8) For transformers rated 5 MVA and above. For motors rated 1500 KW and above. For critical / long feeders. These relay functions can be substituted by inherent releases. Wherever Auto-transfer feature is provided. Provide INST E/F 50N for transformers with primary delta. Provide IDMTL E/F 51N for transformer with primary star. MV outgoing feeders and motor starters shall be provided with sensitive earth leakage protection. ELCB shall be used for all feeders up to 63A rating and motor starters up to 7.5KW rating. For rating higher than these CBCT and Earth leakage relay and timer along with indication lamps shall be provided. (9) MV incomers shall be provided with CBCT operated sensitive earth fault protection with time delay. (10) CBCT ratio shall be selected to suit earth leakage relay setting range. CBCT and relay setting shall be suitably selected to achieve required sensitivity as per OISD norms. (11) Sensitive earth fault relay with built-in adjustable timer with suitable settings to achieve required sensitivity shall be provided in transformer secondary neutral circuit. (12) Suitable neutral displacement relays along with necessary PTs (with open delta windings) also be provided to sense earth fault in the system and give alarm / indications. (13) Contactors units used as MV (up to 650 volt) motor starters incorporate the following protective devices: MCCB for short circuit. Earth fault protection as per scheme for feeder protection as per note-8 above. Over load relay with built-in single phase preventor. (14) Motors rated 75 kW and above shall be provided with motor protection relay.
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
6.2 Generator Protection The protections generally used for generators are as under. However the actual protective requirements shall vary from case to case, depending on the rating, excitation system, operation, type of prime mover etc. 87 G- Differential protection (For 1500 kW) 51 N- Stator earth fault Rotor earth fault 51V- Voltage controlled over current 32- Reverse power (For parallel operation) 40- Field failure 46- Unbalanced loading protection (Negative sequence) 49 T- Stator winding temperature protection (For 500 kW ) 81- Under/over frequency protection Over / under voltage protection 86 Lock out relay
When generator with unit transformer is employed besides individual equipment protection, the following additional protections are required: i) ii) Transformer over-fluxing protection. Overall generator unit transformer differential protection. In installations where generator is operating in parallel with grid, special protection such as out of step relay shall be required. 6.3 Capacitor banks Protection The protective requirements of HV capacitors provided for power factor correction are as follows. IDMTL over current for protection against short circuits. Instantaneous earth fault. Neutral phase displacement. Under / Over voltage. Fuses for individual capacitor units (internal element fuses and external expulsion type fuses). The capacitor bank feeders shall generally be tripped on bus under / over voltage
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
conditions and necessary interlock shall be provided for re-switching to take care of capacitor residual voltage. MV capacitors of smaller ratings shall be protected with MCCBs. Capacitor banks above 125 kVAR shall be protected by ACB. Feeder to capacitor panel at PMCC shall have protections like IDMTL O/C, IDMTL E/F, & Trip Relay. The continuous current rating of fuses and switching devices for capacitors should be 30 % higher than the normal full load current.
6.4 DC Feeders (110V DC, 24V DC) Protection MCCBs / MCBs used for DC incomer feeders and DC distribution feeders are to be provided with short circuit and overload protection as a minimum.
7.1 An earthing system as per IS 3043 shall be installed in each plant area for system neutrals, all electrical equipments and steel frame buildings. Each earthing system shall consist of G.I. pipe electrodes, G.I. earthing flats of sizes as required in a common loop to interconnect all earth rods. All major structural steel, stacks, vessels and process equipment likely to become charged with static electricity shall be solidly connected to the earthing system. The overall resistance of earth grid shall be less than 1.0 ohm. Soil resistively survey shall be carried out by the contractor for design of earth grid. The earth network conductor shall be sized to carry maximum earth fault current without undue rise in temperature. All electrical equipments shall have two separate & distinct connections to earth grid. 7.2 Lightning protection system shall be provided for equipment, structures, Tankages (Existing & New) and buildings as per OISD std.180 and IS 2309 with independent earthing system of earth resistance less than 5 ohms.
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
Lightning protection with independent earthing system shall be provided for oil storage tanks and separator vessels by use of lightning protection masts around such storage tanks and separator vessels as per OISD 180. The lightning protection network shall be bonded with the main earthing network below ground, minimum at two points. 7.3 For HV system each lightning arrestor shall be connected to a separate copper plate earthing located as close as possible to it and within the fenced area of each set of arrestors. The three numbers of earthings for each set of arrester shall be spaced about 5 meters apart so that they are all within the enclosing fence. Each of these earthings shall be interconnected. 7.4 An earthing schedule giving the type / sizes of earthing conductors for different equipments is given below. Required sizes for earthing conductors shall have to be established by design calculations. The sizes given below are indicative and minimum only.
TYPE OF EQUIPMENT BARE GI WIRE/GI WIRE ROPE OR GI STRIP MOTORS UPTO 3.7KW MOTORE 5.5KW TO 30KW & 6mm DIA. WIRE ROPE WELDING 10mm (3/8) DIA , WIRE ROPE
RECEPTACLES MOTORS ABOVE 37KW INCLUDING HT MOTORS BUILDING COLUMNS STORAGE TANK (VERTICAL & HORIZONTAL) LOADING RACKS PIPE RACKS VESSELS & HEAT EXCHANGER SMALL EQUIPMENTS & INSTRUMENTS LIGHTING POWER & INSTRUMENT PANELS 16mm (5/8) DIA, WIRE ROPE 40mm X 5mm STRIP 40mm X 5mm STRIP 40mm X5mm STRIP 10mm (3/8) DIA, WIRE ROPE NUMBER 8 SWG SOLID 10mm (3/8) DIA, WIRE ROPE
MAIN EARTH BUS / LT & HT SWITCHGEAR AS CALCULATED INTERCONNECTIONS/ POWER TRANSFORMER EHV & HV SUBSTATION PUSH BUTTON STATIONS AS CALCULATED NUMBER 8 SWG SOLID
STREET LIGHT POLES / HIGH MAST LIGHT 10mm (3/8) DIA , WIRE ROPE TOWER ELECTRICAL DESIGN BASIS
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
Emergency -
Utilization Category: Electrical loads are divided into following three classes according to use: Continuous Load Intermittent Load Stand-by Load Which draws power at continuous rate. Which draws power as per duty cycle for short duration. Which is connected with power supply and ready to act as and when required.
Load Assessment; All electrical loads are to be developed by the contractor based on estimated load identified in the equipment list. The data sheet should specify maximum power requirement. In evaluating load summary, utilization category is applied as following:
Total Load: i) Continuously Operating Equipment ii) Intermittent Load 100 % of operating load 50 % of the total intermittent load or the largest intermittent load whichever is higher. iii) Stand-by Equipment 10 % of total stand-by load or largest stand-by load, whichever is higher.
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001 ELECTRICAL DESIGN BASIS DOCUMENT NO.: OESG/ARP/ELECT/0012 Page No.: 13 of 32
REV. 0
: :
Utilization / Distribution Voltage Levels: 11/kV : Large motors in plant transmission 440 / 415 Volts 240 V, AC (phase to phase) : : Plant distribution . Lighting as per DGMS guidelines. Switchgear control supply. Anti condensation space heaters, and overhead
convenience outlets. 110 V DC, 2 wire (Battery back-up) : Critical & Exit lights for 1 hour duration, Generator, Breaker Controls / Instrument supply etc. 24 V DC, 2 wire (Battery back-up) : Instrument supply, Fire and Gas detection system etc. 240 V AC, UPS : Communication, Process
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001 ELECTRICAL DESIGN BASIS
Instrument Distributed
control, Control
control,
REV. 0
The shirt circuit levesl for all voltage levels shall be calculated and systems shall be accordingly designed.
REV. 0
tropical environment (50oC temperature and maximum 90% RH for design). Note: Equipment / Switchgear rating indicated anywhere in the bid specification shall be considered as minimum. Exact rating shall be decided by contractor based on actual design calculations plus 10% spare capacity (if spare capacity is not specifically mentioned).
11.2
Transformer
: Delta/Star, 3-phase
Incoming C.B. (LT) : ACB (4 pole). System : Complete system to be grounded as per the statutory requirements. Transformer (Lighting) : Indoor, 415 V / 240 V; Delta/Star, 3-phase, Up to 100 kVA - Non-encapsulated winding (Vacuum resin impregnated dry type)
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001 ELECTRICAL DESIGN BASIS DOCUMENT NO.: OESG/ARP/ELECT/0012 Page No.: 16 of 32
REV. 0
Above 100 kVA- Encapsulated winding (Cast resin dry type) Natural air-cooled type. Insulation: Fup to 100 kVA; Habove 100 Kva Two nos. of lighting transformers are required for each installation. Each lighting transformer shall be sized to take care of the total lighting load of the plant with a provision for 10% extra capacity. Lighting system of the complete installation shall be as per DGMS guidelines as detailed later. Lighting transformers with the MLDB(s) shall be located inside the MV switchgear room. The substation building shall be sized to take care of all the present and future requirements and to maintain adequate clearances between equipments for ease of maintenance. A margin of at least 25% space shall be kept in switch gear rooms and battery rooms for future expansion. HV/MV switch boards shall have provision for future extension from both ends. The following minimum clearances around various equipments and panels shall be maintained: a) Front clearance for switchboard/ panels 2500 mm (HV Switch Board) 2000 mm (MV Switch Boards/ others) b) Rear clearance for panels requiring maintenance from rear 1500 mm (HV Switch Board) 1000 mm (MV Switch Board) c) Rear clearance for panels having access from front only 750 mm
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
d)
Side clearance between two switchboards or from nearest obstruction 1500 mm 750 mm 750 mm 1000 mm
e) f) g) h)
Front clearance for wall mounted equipments Front clearance for operator station/ annunciation / control panel -
2500 mm
i)
Vertical clearance above the top of the highest equipment shall be minimum 1500mm from roof slab. For areas with false ceiling minimum clearance of 750mm shall be provided between top of the equipment and the false ceiling.
11.3
PMCC / MCC / Switchgears All panels shall be single / double front, fully draw-out type. Compartments shall be capable of withdrawing to a test position. This test position isolates the power cables to allow the live commissioning of control circuit. The MV switch boards are provided with a minimum 20% fitted spare motor starters and feeder modules (subject to minimum 01 of each rating and type). Each starter unit have component designed for Type 2 co-ordination as per IEC / IS 13947. All load feeders shall be provided with earth leakage protection. For the PMCC, feeders for more than 400 ampere rating shall be provided with ACB. Feeders up to 400 ampere rating shall be provided with MCCB. All lighting / auxiliary / power panel main incomers will be MCCB. All lighting sub-distribution board incomers up to 63 amperes shall be MCB and beyond 63 amperes MCCB shall be provided. Bus bar and isolating devices are rated at 125% of total design load. Bus bars are generally identified as R, Y & B with phase coloured as red, yellow and blue. All the switchgears are industrial grade equipment installed in freestanding sheet metal cubicles of modular design. All the switchgears are to be installed in a
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001 ELECTRICAL DESIGN BASIS DOCUMENT NO.: OESG/ARP/ELECT/0012 Page No.: 18 of 32
REV. 0
closed naturally ventilated room. All equipment and switchgear ratings are decided based on actual design calculations (actual requirement) and 10% spare capacity (if spare capacity is not particularly mentioned). Cable entry to all panels of H.T. & L.T. switchgear and control panels shall be from bottom. Bus coupler switch gear rating shall be higher of the following: o Largest incoming breaker o Maximum load on either side of bus section o Maximum of current rating of bus- bars on either side of coupler. Switch board components such as breakers, MCCBs, horizontal and vertical bus bars shall be designed to withstand design fault current or maximum fault current at the point of installation, which ever is higher for a minimum period of 1 sec. 11.4 MV Incomers Incomer feeders shall be withdrawable, four pole, air circuit breakers with charging motor, spring release and close mechanism. Breaker close / trip solenoid are fed through 110 Volt D.C. There shall be three positions for the draw out trolley, Full-in, Test and Full-out. 11.5 Power Factor Control Switched capacitor banks with automatic power factor correction relay shall be provided in all installations to improve the power factor. Capacitor banks shall be provided at MV (415 V) and / or HV panels, as per requirement and shall be sized in order to arrive at over all power factor up to 1.0 at each installation. The capacitors impregnation shall be non toxic, non PCB (poly chlorinated biphenyl) type and bio degradable. HV Capacitor banks The banks of ungrounded star connected capacitors shall be mounted out door at least 2.75 meters above ground. Capacitor banks shall be supplied with series reactor and RVT. Series reactors shall be designed to limit in rush current and to suppress harmonics. The banks shall be switched on by vacuum switches with back
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
up protection of VCB. Microprocessor based automatic p.f. correction relay shall also be provided for control.
MV Capacitor banks 415 V, indoor type, delta connected capacitor bank for p.f. control complete with over voltage protection, microprocessor based automatic p.f. correction relay and switching contactors. Capacitor units shall be dry type, mixed di-electric, low loss, long life with over pressure protection device.
11.6
Motors All the motors required by mechanical packages shall meet the requirement of relevant National / International standards. The voltage ratings for motors shall be as below: Rated Voltage in kV ( UN) 415 3.3 UN 6.6 6.6 UN<11 Minimum rated output (kW) 160 > 160 and < 1000 1000
Also all electric motors installed outdoor shall meet the criteria for the hazardous area requirement and the below mentioned criteria in addition to the standard specifications and data sheet for same: Enclosure Insulation Starting : : : TEFC (totally enclosed fan cooled) with IP-55. Class "F" with temperature rise limited to Class "B". Requirement of starters shall depend on SEB regulations. Generally for MV motors Direct on line starters for motors rated below 45 KW & reduced voltage starters for motors rated 45 KW and above shall be required. Starters for from CPP shall be of DOL type. Space heater : For motors rated 15 KW or above. HT Motors to be fed
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
Control
A local / remote selector switch shall be provided to enable field starting of motors from local control station. MCC shall be provided with stay put type of stop button.
Starting torque and minimum torque of the motor shall be compatible with the speed torque curve of driven equipment under specific operating conditions. For DOL start applications, HV motors shall be suitable for starting with 80 % of the rated voltage at the terminals and MV motors with 75 % of the rated voltage at the terminals. For heavy duty drives such as reciprocating compressor, agitator, crusher etc. high starting torque motors (minimum 150 % of rated torque) shall be provided to limit starting current and time. 11.7 UPS & DC Supply UPS and DC supply shall be provided as per project requirement. Separate battery room is to be provided in all switch gear rooms. Generally, the following shall be required: 11.7.1 UPS (for communication, Instrumentation and Control application) Input Output Type Back up time Battery type Capacity : : : : : : 415 Volts 10%, 50 Hz 3%. 240 Volts (AC), 1-phase. Parallel redundant with bypass. 2 hours for full rating of UPS. Sealed Maintenance Free (SMF), VRLA To be decided during detailed engineering (spare capacity of 50 % is to be provided). 11.7.2 UPS (for SCADA application) Input Output Capacity Type : : : : 415 Volts 10%, 50 Hz 3%. 240 Volts (AC), 1-phase. 5 KVA (Min.) Parallel redundant with bypass.
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
: :
04 hours for full rating of UPS. Sealed Maintenance Free (SMF) VRLA
DC supply system shall be provided with charger, SMF batteries, Lead acid and DC distribution board. DC supply shall be sized during detail engineering. a) Output : 110V DC (1 hour battery back up)
To cater to specialty lighting, i.e. critical and exit lights, breaker controls / instrument supply etc. b) Out put : 24V DC (2 hour battery back up)
To cater to instrument / control supply, Process and control PLC, Fire and Gas detection system etc. c) Output : 24 V DC
To cater to the starting requirement of Emergency Gen. sets, Fire water pumps.
11.8
a) Emergency Generator Emergency generator driven by battery started diesel engine with AMF panel shall be provided in all installations. The electrical loads to be fed by emergency generator shall consist of the following as minimum: Complete lighting load. All utilities including air compressor, UPS, DC battery and charger system, Potable water, Service water, Bore well water, etc. Fire fighting equipment including jockey pump but excluding main fire water pumps Diesel fuel handling / transfer system Loads critical for process (as defined in basic bid work), plant and personnel safety Loads essential for safe shut down of the plant
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
Instrumentation and communication systems. Process Loads of installations as mentioned in Power system Philosophy
Annexure- II, enclosed elsewhere in the bid package. 10 % margin for future expansion shall be considered while sizing the generator set. b) Gas engine Generator for installations fed by ASEB supply Gas engine generator shall be sized to meet full power requirement of the installation as follows. i) Continuously Operating Equipment ii) Intermittent Load 100 % of operating load 50 % of the total intermittent load or the largest intermittent load, which ever is higher The total load for sizing of generator shall be sum of i), ii) and additional 10% margin for future.
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
The voltage rating of cables shall be as follows High Voltage Cables Power and Control Cables DC Cables : : : 3.3 / 6.6 / 11 / 22 / 33 KV (as required) 1100 / 600 V 150 V DC
Cable sizing: During detailed engineering all power and control cables are to be identified and sized according to the requirements of Indian and International standards. The sizing calculation takes into account the following factors: System Voltage Connected Load Current Carrying Capacity Voltage Drop Short Circuit withstand criteria Laying conditions
Wherever possible, power cables and control cables are to be routed separately or with adequate spacing to minimize the effects of de-rating. De-rating of cables due to ambient air temperature, ground temperature, grouping & proximity of cables, method of laying (air / underground), thermal resistivity of soil etc. shall be taken into account. De-rating factor of 0.6 or less shall be considered for sizing of all cables.
The minimum value of oxygen index for cables shall be 29 at 27 20 C. The flame retardance properties shall meet the requirements of IS 7098 (1994) applicable to C1 category of cables for all power and control cables (up to and including 1100 Volts). All cables shall be without intermediate joints. The cable sizes selected shall meet the following requirements of voltage drops. Voltage drop:
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
The maximum allowable voltage drop in any feeder under steady state condition at full load is to be maintained as follows Between transformer secondary and HV Switchboard or PCC / PMCC Between HV Switchboard and HV Motor Between PCC / PMCC and remote MCC / Auxiliary Switchboard Between PCC / PMCC and Motors Between remote MCC and Motors From lighting transformer to MLDB in Substation Between MLDB and remote lighting panels Between Lighting points and Lighting panels DC system 1% 3% 2% 5% 3% 0.5 % 2.5 % 2% 3%
The voltage drop at the worst affected pre-loaded bus is not to exceed 15% of nominal voltage during start-up of the largest HV motor and 10% of nominal voltage during start-up of the largest MV motor.
The voltage available at motor terminals during start-up is to be sufficient to ensure positive starting and acceleration or reacceleration to full speed by the motor (even with motor in fully loaded condition, if required) without causing any damage to the motor. However, under no circumstances, the voltage at motor terminals during starting or reacceleration is allowed to fall below 80% of the nominal voltage for HV motors and 75 % of nominal voltage for MV motors.
Cables for capacitor banks shall be sized for 143% of the rated capacitor current.
Minimum cross section of cable conductor: MV Power Cables MV Control Cables Lighting : : : 2.5 mm2 (copper) 2.5 mm2 (copper) 3 x 2.5 mm2 (copper)
One core shall be left as spare in control cables having up to 5 cores. From 7 cores upward about 20% or minimum 2 cores shall be left as spare for future use. Control wiring of the panels shall be carried out with flexible, 1.1kV grade, PVC insulated, switchboard wire with stranded copper conductor of 2.5 mm2. For connecting relay instruments, 1.5 mm2 copper conductors will be acceptable.
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001 ELECTRICAL DESIGN BASIS DOCUMENT NO.: OESG/ARP/ELECT/0012 Page No.: 25 of 32
REV. 0
For lighting circuits of non-industrial buildings following sizes of copper conductor, PVC insulated wire shall be used in concealed PVC conduit system with 2-pole MCBs: For circuit wiring For point wiring : : Minimum 2.5mm2. Minimum 1.5mm2(for 5amp. points).
For Air-conditioner machine circuits 4.0mm2 (Copper conductor) PVC insulated wire shall be used. Cable Glands and Multi Cable Transit (MCT) Frames: Suitable size double compression type glands are supplied for all cables. For entries into Ex(d) enclosures, barrier type (or compound filled) glands are provided. All cable glands and adaptors are made up of nickel plated brass and are fitted with soft sealing nylon washer. Fiber washers are not to be used. Lock nuts are used for entry into sheet steel boxes enclosures. Industrial cable glands are not used on oil / gas installations. All cable glands are to be type tested and certified by appropriate authorities for use in specified hazardous area. Cable transit frames are to be fitted where cables pass through outdoor trays / trenches indoor areas or vice-versa. Such cable transit frames are designed to include 25 % spare capacity for future use. Cable transit frames are to be supplied with test certificates from an accredited independent test authority to confirm adequate fire rating for areas where they are to be installed.
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
a)
Complete cable trays, supports, rack-risers, ducts, trenches and area cabling for all the equipments / loads, termination kits, glands, lugs, markers, tag plates & etc.
b) c)
The cable trays, racks & trenches shall be sized to allow for 20% future cables. Special care is to be taken to the routing and separation of cables to minimize the effect of fire on emergency and essential supplies and production operations. Intrinsically safe circuit cables run in separate trays. Instrument and communication cables shall not be laid along with the power cables. Cabling for fire water system shall be as far as possible taken in exclusive route through underground trench.
d)
In addition the minimum distance between power / control wiring and electronic signal wiring on prolonged cable route will be as follows: Power / Control cable Minimum distance from electronic / signal cable Up to Up to Up to 125 V 300 V 1000 V 150 mm 150 mm 300 mm 450 mm
Above 1000 V e)
Cable ladders / trays are to be manufactured from FRP material with UV protection features. They are heavy duty type having loading criteria, fire withstanding capacity and other properties as detailed in standard specification for FRP cable trays.
f)
The overhead cable trays are installed a minimum 2700 mm. (minimum) above grade level. At road crossings overhead trays shall be installed at 7000 mm. (minimum) above grade level.
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
sheds, storage sheds, laboratory, instrumentation, control room, electrical substation rooms, office complex, gate cabin etc.) of the installation including DC critical lighting in the compressor / pump houses, sub-station, control room etc. and all escape routes as required. For illumination of the complete outdoor area (e.g. open area, street lighting etc.) coming under each plant area, motorized flood lighting high mast(s) (20 mtrs high approximately) shall be provided. Each high mast shall have minimum 12 nos. of 2 x 400W HPSV fixtures. The number of fixtures in each mast including masts exact location shall be worked out during detailed engineering. The dark areas / shadows shall be illuminated with suitable street light / floodlight fixtures. The type and exact number of fixtures required for different locations shall be worked out during detailed engineering and shall fulfill the minimum illumination level criteria. The fixture selection (i.e. flameproof / non-flameproof) shall be based on the area classification. Outdoor fittings in safe areas shall be of weather proof (i.e. IP 55) construction. Corrosion resistant fixtures will be provided in places like chemical storeroom and battery room. A maintenance factor of 0.8 shall be considered for all illumination level calculations. All ballasts shall be low loss type with copper winding and power factor improvement capacitor. The lighting fixtures of various circuits shall be suitably interlaced so that failure of one circuit does not result in complete darkness. Depending upon operational requirements, minimum illumination levels shall be as follows: Illumination in lux Roads Process Areas: Pump houses, dosing shed etc. Main platforms for operation and access stairs 100 60 20
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
Other process areas (pipe racks, injection manifold, filters, tanks, dosing system etc.) Injection Pump Shed Compressor area Non-Process Areas: Laboratory Control room Electrical switch room, DG room, UPS / Charger and battery room Transformer bay, outdoor switchyard Cable cellar Loading-unloading area, Tube-well area Fire water pump house Tank farm area Pipe rack area Flare area Injection header Raw water tank area Lube oil / Grease store Office Stairs / corridors Change rooms, garage etc. Gate cabin & entrance Residential Area: Living area, Toilets Recreation room Canteen
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001 ELECTRICAL DESIGN BASIS
60 100 200
400 400
REV. 0
Under normal operation the above lighting shall be fed by normal power source on 240 V AC supply (SEB or D.G. set supply through lighting transformer). Upon failure of both of above supplies the Critical lighting system will come into function. The minimum illumination level requirements for critical lighting are as below: i ) Near to areas where specific safety operations ( visual tasks) are to be carried out (e.g. control room, subStations, D.G. shed, F. W. / crude oil pump house etc.) ii) Escape Lighting a) b) Escape way (interior) Areas at exit door and at points where it is necessary to emphasize the position of potential hazard, if any. c) Other notified general outdoor areas. : 10 Lux : 30 Lux : 10 Lux : Spot lighting to be provided.
Taller structures shall have aviation obstruction lighting as per statutory regulations (D.G.C.A.).
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
In order to comply with the above statutory requirements, the lighting system for the installations in oil mines under the jurisdiction of DGMS shall be designed on the following basis: a) Phase to phase voltage in the lighting system shall be limited to maximum of 250 V. b) Lighting transformers shall be 415 / 240 V, three phase delta-star connected with neutral point of secondary connected to earth and taps of + 5 % and + 2.5 % on primary. c) Further distribution from lighting transformers to MLDB and LDBs shall be at a voltage of 240 V, 3-phase (3-wire system without neutral). d) All lighting distribution boards and lighting panels shall have three phase buses rated for 240 V, 3-phase and shall be without neutral bus. e) Outgoing circuits from lighting panels shall be controlled by 2 pole MCBs. Earth leakage protection shall also provide isolation in both poles. f) All lighting fixtures and equipments shall be connected between two phases at a voltage 240 V phase to phase. g) Incase of lighting of building within the plant premises, double pole switches or 2-pole MCBs shall be used in the lighting circuits instead of conventional single pole switches. h) All 240 V, 1-phase sockets in plant area as well as in buildings shall also be connected between phases at a voltage of 240 V phase to phase and controlled by 2-pole MCBs or double pole switches.
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0
Explosion proof junction boxes, light fittings, control stations etc. are to be manufactured from copper free cast aluminum alloy (LM 6) with an epoxy finish.
Cable glands should be of nickel plated brass or equivalent. All metal surfaces for all equipments and panels shall be painted after proper surface finish The painting procedure to be followed for all equipments and panels is as described below: All metal surfaces shall be thoroughly cleaned and de-greased to remove mill scale, rust, grease and dirt. Fabricated structures shall be pickled and then rinsed to remove any traces of acid. The under-surface shall be prepared by applying a coat of phosphate paint and a coat of yellow zinc chromate primer. The under-surface shall be made free from all imperfections before undertaking the finished coat. After preparation of the under-surface, the panels shall be spray painted with two coats of epoxy-based final paint or shall be powdercoated. The colour shade of the final paint shall be shade 631 (light grey) as per IS-5. Spray-painted finished panels shall be dried in stoving ovens in a dust-free atmosphere.
All unpainted steel parts shall be cadmium plated or suitably treated to prevent rust and corrosion. All hardware shall be corrosion resistant. All joints and connections of the panel members shall be made of galvanized, zinc passivated or cadmium plated, high tensile strength steel bolts, nuts and washers, secured against loosening.
Onshore Engineering Services New Delhi PROJ: Assam Renewal Project Job No.:OESG-AA-07-001
REV. 0