Circuit Breaker NA
Circuit Breaker NA
Circuit Breaker NA
ACB
NA8
Page C-01
NA8G
Page C-37
NA1
Page C-71
NA8
2. Type designation
N A 8 - /
Shell grade rated current of the breaker Enterprise design code Enterprises air circuit breaker code
3. Operation conditions
3.1 When the ambient air tempeature is -5~+40, the mean value is no greater than +35 within 24 hours. Note: If the upper limit is higher than +40 or lower limit lower than -5 in work, discussions shall be made between the user and the manufacturer. 3.2 Altitude: not higher than 2000m for the installation site. 3.3 When the ambient air temperature is +40, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for example, for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature averaged in that month +20, and special measures shall be taken for the condensation occasionally produced due to temperature change. 3.4 Class of pollution: 3. 3.5 The installation category of the breakers main circuit is IV; when the rated operational voltage of the main circuit is less than or equal to AC400V, the installation category of the control circuit and auxiliary circuit is III, apart from the similarity between the under voltage release coil and the intellectual controllers power transormer primary coil and the breaker; When the rated operational voltage of the major loop is greater than AC400V and less than or equal to AC690V, it is necessary for the control circuit and auxiliary circuit to be isolated from the major loop with an isolating transformer, and the highest operational voltage of the control circuit and auxiliary circuit is AC400V, the installation category of the control circuit and auxiliary circuit being III.
C-01
> >>
NA8
4. Product structure
Body structure
Wiring terminals of the secondary circuit Under voltage release
Shunt release
Closing electromagnet
Press Press
C
Breaker on and energy storage over
Intellectual controller
Operating mechanism
Press
Press
Storage
Fault-breaking indicator reset button OFF pushbutton ON/OFF indication Energy storage handle ON pushbutton Energy storage indication
Intellectual controller
Can release
Drawout structure
Wiring terminals of the secondary circuit
Press Press
Storage
Locking device
Position indication
> >>
C-02
NA8
Connected
Test
Disconnected
Test
Disconnected
Test: the main circuit is disconnected, the safety separator woks well, and the secondary circuit is connected
Connected
(4) Move the breaker body onto the guide rail with a snap
Test
Disconnected
(5) Push the breaker body in, and the turn the breaker body to the working position
C-03
> >>
NA8
5. Main technical parameters
5.1 Main technical parameters
Type NA8-1600 NA8-3200 NA8-6 3 00
Shell grade rated current Inm A Rated current In A Nominal insulation voltage Ui V Rated operational voltage Ue V Rated ultimate short circuit breaking capacity Icu kA Rated service short circuit breaking capacity Ics kA Rated short time withstand current Icw,1s kA Frequency of operation (number of times/h) Number of operations Flashover distance mm Line incoming pattern Weight (3P/4P) Size (3P/4P) Heightwidthdepth Fixed type kg Draw-out type kg Fixed type kg Draw-out type kg
Mechanical life Electric life
1600 200,400,630,800, 1000,1250,1600 1000 400,690 55,30 42,25 42,25 20 3000 1000 0 Wire to enter from the upper or lower part 22/26.5 38/55 320(254/324)251 351(282/352)345
3200 1600,2000,2500,3200 1000 400,(690V In trial production) 100,75 100,75 85,10 3000 500 0 Wire to enter from the upper or lower part 52.5/66.5 98/121 354(422/537)331 431(435/550)445
6300 4000,5000,6300 1000 400,(690V In trial production) 125,85 125,85 100,10 2000 500 0 Wire to enter from the upper or lower part 200 471780445
5.2 Capacity-reducing usage 5.2.1 Capacity-reducing at different temperatures The following table shows the continual current-loading capacity of the circuit breakers and buses in each wiring mode at the corresponding ambient environment temperatures and under the conditions of the satisfaction of conventional heating with a similarity in capacity reducing between the breaker connected in a mixed way and the breaker connected horizontally.
Style Wiring mode Ambient temperature Draw-out type Front/rear horizontal wiring mode -5~40 45 50 55 60 Rear vertical wiring mode -5~40 45 50 55 60
200 400 630 1600 800 1000 1250 1600 1600 3200 2000 2500 3200 4000 6300 5000
200 400 630 800 1000 1250 1550 1600 2000 2500 3200 4000 5000
200 400 630 800 1000 1250 1500 1600 2000 2500 3100 4000 4700
200 400 630 800 950 1150 1450 1600 2000 2450 3000 3900 4600
200 400 550 700 900 1050 1350 1600 1900 2350 2900 3800 4400
200 400 630 800 1000 1250 1600 1600 2000 2500 3200 4000 5000 6300
200 400 630 800 1000 1250 1600 1600 2000 2500 3200 4000 5000 6100
200 400 630 800 1000 1250 1550 1600 2000 2500 3200 4000 4800 6000
200 400 630 800 950 1200 1500 1600 2000 2500 3050 3900 4650 5500
200 400 580 700 900 1100 1450 1600 1950 2400 2900 3800 4500 5200
> >>
C-04
NA8
5.2.2 Capacity-reducing at different altitudes When the altitude is higher than 2000m, there will appear changes in insulation property, cooling performance, pressure, and the performance can be modified in reference to the following table.
Altitude (m) Insulation withstand voltage (V) Insulation voltage (V) Rated operational voltage (V) Rated operational current (A) 2000 3500 1000 690 1In 3000 3000 800 580 0.96In 4000 2500 700 500 0.92In 5000 2000 600 400 0.87In
5.3 Power loss Power loss is the total loss measured when the breaker is charged with the rated current. Power loss Breaker type
NA8-1600
NA8-3200
NA8-6300
5000 6300
Note: The data and parameters in the above technical documentation result from tests and theoretical calculation, and can only be used as a general type selection guide. They cannot replace industrial practical experience or proof test.
5.4 Recommended bus for the breaker and recommendation for users to install the buses Inm(A)
In(A) Thickness (mm) Busbar Width (mm) Number of buses
NA8-1600
200 5 20 1 400 5 50 1 630 5 40 2 800 5 50 2 1000 1250 1600 5 60 2 8 60 2 10 60 2
NA8-3200
1600 2000 6 100 2 6 100 3 2500 5 100 4 3200 10 100 4
NA8-6300
4000 10 100 5 5000 10 100 7 6300 10 100 8
C-05
> >>
NA8
6. Dimensions and connection of the circuit breaker
NA8-1600(In=200A~1250A) Draw-out type (horizontal connection is the default by the factory, vertical one to be made by users themselves)
4P central line
210
36
a
3P central line
1211(3P) 1611(4P) N Pole 60 25 15 35 76 76 76
149
275
7
351
78.5
95
345(Connecting position) 391(Separating position) 282(3P) 352(4P)
74
310
149(3P) 155(4P)
2-8.5
95
In(A)
a(mm) 5 10 15
2-8.510
78.5(3P) 75.5(4P)
35
145(3P) 215(4P)
63
74
Note: If users intend to change the horizontal connection into vertical one on site, they need to replace the upper and lower buses on both sides with the same one as the central bus.
NA8-1600(In=1600A) Draw-out type (horizontal connection is the default by the factory, vertical one to be made by users themselves)
4P central line 3P central line 85
35 15 35 310 101 101 101 80.5
210
36
15
N Pole 275
179
351
63.5
95
435(Connecting position) 481(Separating position)
74
282(3P) 352(4P)
2-8.5
149(3P)
2-8.510
155(4P)
95
35
145(3P) 215(4P)
63
75.5(4P)
78.5(3P)
95
435(Connecting position) 481(Separating position)
74
Note: If users intend to change the horizontal connection into vertical one on site, they need to replace the upper and lower buses on both sides with the same one as the central bus.
> >>
C-06
NA8
NA8-1600(In=200A~1250A) Fixed type (horizontal connection is the default by the factory, vertical one to be made by users themselves)
210 22
4P central line
a 320
76 48.5
76
76
4-8.5 100
a(mm) 5 10 15
237(3P) 307(4P)
48.5(3P) 45.5(4P)
149(3P) 155(4P)
100 251
92
Note: If users intend to change the horizontal connection into vertical one on site, they need to replace the upper and lower buses on both sides with the same one as the central bus.
NA8-1600(In=1600A) Fixed type (horizontal connection is the default by the factory, vertical one to be made by users themselves)
210
22
Separator between phases (to be ordered separately)
15 35
4P central line 3P central line
12-11(3P) 16-11(4P)
3P central line
60 25
320
48.5(3P)
45.5(4P)
100
4-8.5 179
237(3P) 307(4P)
33.5
15
100 341
92
Note: If users intend to change the horizontal connection into vertical one on site, they need to replace the upper and lower buses on both sides with the same one as the central bus.
C-07
> >>
80.5
15
24-11(3P) 32-11(4P)
85 35
NA8
NA8-1600 Draw-out type Size of the hole to be drilled on the panel NA8-1600 Fixed type Size of the hole to be drilled on the panel
220
118
322
120
320
285
C
118
78 118.5
From the center of the mounting hole on the right side of the breaker
From the center of the mounting hole on the right side of the breaker
258
258
217.5(3P) 332.5(4P)
217.5 42 385 18
232
Datum line 1
Dimensions
Datum line 2
199
Dimensions
371 328
11 1117
175
162.5(3P) 277.5(4P)
47
10
Installation dimensions
Datum line 2
14 1117
376
268
14
155
145
18
21.5
97
> >>
C-08
NA8
NA8-3200(In=1600A~2500A) Draw-out type (horizontal connection is the default by the factory)
42
25
78 14
50
11 29
133
115 84
115
115
Datum line 1
445(Connecting position) 492(Separating position)
Note: If users want to change the horizontal connection into vertical one on site, they only have to turn the bus by 90.
42 14 11 78
25
55
115
115
115
Datum line 1
25
57.5
Note: If users want to change the vertical connection into horizontal one on site, they only have to turn the bus by 90.
C 15
78
25
11
29
115 301
115
115
Datum line 1
In(A) 1600,2000 2500 C 20 25 30
29
C-09
16.5
3200
> >>
NA8
NA8-3200(In=3200A) Draw-out type (horizontal connection is the default by the factory)
42
25
133
14
126
126
126
84
Datum line 1
29
11
100
25
Note: If users want to change the horizontal connection into vertical one on site, it is necessary to replace the upper and lower buses for the N and B phases with the same one as the A and C phases.
42
14
11
25
57
100
115
115
115
Datum line 1
25 35.5
Note: If users want to change the vertical connection into horizontal one on site, it is necessary to replace the upper and lower buses for the N and B phases with the different one from the A and C phases.
191
11
200(3P ) 315(4P )
200 1
2 11
163 13
246
44
> >>
C-10
NA8
NA8-3200 Fixed type Size of the hole to be drilled on the panel
412
371 328
150
70.5
200(3P) 315(4P)
200
311 268
86
Datum line 1
Datum line 1
33
78 14 25
50
11 29
133
115
115
115
Datum line 1
47.5
Note: If users want to change the horizontal connection into vertical one on site, they only have to turn the bus by 90.
33 25
14 11 78 55
115
115
115 1
25
Note: If users want to change the vertical connection into horizontal one on site, they only have to turn the bus by 90.
C-11
21
> >>
NA8
NA8-3200(In=1600A~3200A) Fixed type (front connection)
60
78 15
25
11
300
115
115
Datum line 1
33
25
133
14
126
126
126
Datum line 1
47.5
Note: If users want to change the horizontal connection into vertical one on site, it is necessary to replace the upper and lower buses for the N and B phases with the same one as the A and C phases.
33
14 11
25
57
100
115
115
115
25
49
Datum line 1
Note: If users want to change the vertical connection into horizontal one on site, it is necessary to replace the upper and lower buses for the N and B phases with the different one from the A and C phases.
29
11
100
25
> >>
C-12
NA8
NA8-6300 Draw-out type size of the hole to be drilled on the panel
562.5
217.5
42
385
18
232
40
Datum line 1
Dimensions
Datum line 2
199
Dimensions
371 328
175
376
268
1117 145
155
14
Datum line 1
Datum line 1
Installation dimensions
Mounting dimension
11
14
Datum line 1
115 115 115 115 115
55
125
25
25
C-13
50.5
> >>
Datum line 2
97
18
NA8
NA8-6300(In=4000A~5000A) Draw-out type (horizontal connection is the default by the factory)
78
25
11 29
133
25
14
115
115
115
115
115
Datum line 1
124
Note: If users want to change the horizontal connection into vertical one on site, they only have to turn the bus by 90.
14 11
Datum line 1
115
78
115
115
115
115
55
25
Note: If users want to change the vertical connection into horizontal one on site, they only have to turn the bus by 90.
25 97.5 C
29
115 301
115
115
115
C 20 25
23.5
15
78
25
11
> >>
C-14
C-15
SB2 SB1 HL2 HL3 HL4 12
FU
Fault indication
ABC
Connection diagram for the secondary circuit of the NA8-1600 optional standard type intellectual controller
> >>
14 22 47 54 24 28 30 34 36 41 42 44 45 50 53 38 39 48 51 55 26 32 16 18 20
HL1
XT
Breaker body
QF
SAL
Intelligent controller
AX
SA
F DT Q/QY
L1
Control power supply
TA
L2(N)
XT
1 11 25 37 40 27 13 15 17 35 19 21 23 31 33
10
29
43 46
49
52
56
57
FU
+ DC24V -
Main circuit
Intelligent controller
Under Energy storage Power-driven Open Close voltage indication energy storage
On indication
Dtclosing electromagnet Fshunt release Q/QYunder voltage release SALsensitive switch SAtravel switch Menergy storage motor AXauxiliary contact Fufuse SB1ON pushbutton SB2OFF pushbutton HL1~HL4indicator light Type of AX auxiliary contact available for users XTconnection terminal TAcurrent transformer QFbreaker Spower module I. Four groups of changeover II. Five groups of changeover #1#2input (terminals) for intellectual controller auxiliary power supply contacts(default configuation) contacts #4#5#6faulty tripping contact output (#5 is the common terminal, AC250V 5A) 38 39 41 42 44 45 47 38 39 41 42 44 45 47 48
Notes: 1. Four open (contacts) and four close from DF1 to DF8 with a common point available conventionally, two open and two close from DF9 to DF12 with a common point available additionally for Inm=1600 when special order is made for alternating current, four open and four close from DF1 to DF8 with a common point available only for Inm=1600 in case of direct current, contact capacity (DC220V 0.5A). 2. Various control voltages of the 1600 has to be put to #1 and #2 after the power module outputs DC24V. 3. The wiring for the part indicated by dashed lines shall be made by users.
37 40 43 46
37
40
43
46
49
37
40
43
46
49
52
37 39 41
43 45 47
NA8
NA8
Fault indication
ABC
HL1
SB2 SB1
HL2
HL3
HL4
XT
4 12 22 47 54
FU
6 34 36 41 42 44 45 50 53
14 24 28 30 38 39 48 51 26 32
16
18
20
Breaker body
QF
SAL
Intelligent controller
AX
SA
F DT Q/QY
L1
Control power supply
TA
L2(N)
XT
1 11 25 37 40 27 13 15 17 35 19 21 23 31 33
10
29
43
46
49
52
FU
3200 and 6300 shell controller power supply: AC230V and AC400V
+ DC24V -
S
Under Energy storage Power-driven Open Close voltage indication energy storage
3200 and 6300 shell controller power supply: DC220V and DC110V
On indication OFF Auxiliary contact indication available for users AC auxiliary contact for standby application
Main circuit
Intelligent controller
Connection diagram for the secondary circuit of the NA8-3200~6300 optional standard type intellectual controller
Dtclosing electromagnet Fshunt release Q/QYunder voltage release SALsensitive switch SAtravel switch Menergy storage motor AXauxiliary contact Fufuse SB1ON pushbutton SB2OFF pushbutton HL1~HL4indicator light Type of AX auxiliary contact available for users XTconnection terminal TAcurrent transformer QFbreaker Spower module I. Four groups of changeover II. Five groups of changeover #1#2input (terminals) for intellectual controller auxiliary power supply contacts(default configuation) contacts #4#5#6faulty tripping contact output (#5 is the common terminal, AC250V 5A) 38 39 41 42 44 45 47 38 39 41 42 44 45 47 48
Notes: 1. Four open (contacts) and four close from DF1 to DF8 with a common point available conventionally, one open and one close from DF9 to DF10 with a common point available additionally when special order is made for alternating current, contact capacity (DC220V 0.5A). 2. When the controller voltage of 3200 and 6300 shells is AC230V/400V, it can be directly put to #1 and #2; if the voltage is DC220V/110V, it has to be put to #1 and #2 after the power module outputs DC24V. 3. The wiring for the part indicated by dashed lines shall be made by users.
37 40 43 46 37 40 43 46 49 37 39 41 43 45 47 37 39 41 43 45 47 49 51
> >>
C-16
C-17
Profibus-DP ST-4 power module
+ L N PE
FU
L1
PE
Connection diagram for the secondary circuit of the NA8-1600 optional type multifunctional intellectual controller
> >>
+ + +
ST-DP Device
12 13 16 17 18 19 14 15
N
1 + + COM D11 D12 D13 2 3 4 5 6 7 8
ABC
Fault indication
DC24V ST201
SB2 SB1
D02 14 15 16 17 D03 D01 12 13
XT
3 10 54 55
12
14 22 28 32 38 39 48 50 51 53 30
16 24 41 42 44 45 47 26 36
18
20
34
PE
D14 D15 SA D16
QF
SAL
D13
Intelligent controller
AX
F DT Q/QY
TA
Breaker body
XT 9 40 11 13 35 37 15 17 23 29 31 33 27 19 21 25
43
46
49
52
56
57
+ DC24V-
Main circuit
Intelligent controller
Under Energy storage Power-driven Open Close voltage indication energy storage
On indication
DTclosing electromagnet Fshunt release Q/QYunder voltage release SALsensitive switch SAtravel switch Menergy storage motor #1#2Intelligent controller auxiliary supply input AXauxiliary contact Fufuse SB1ON pushbutton #3PE SB2OFF pushbutton HL1~HL4indicator light #4# 5# 6Fault trip contact output XTconnection terminal TAcurrent transformer (# 5 for the public side, AC250V 5A) QFbreaker Spower module ST-DPDevice #7#8#9Auxiliary contact output ST201Relay module(Optional) ST-4Power module(Optional) (#8 for the public side, AC250V 5A) #14#15RS485 communication interface (communication type when) Notes: 1. Four open (contacts) and four close with a common point available #16#17Sub-gate output conventionally, two open and two close with a common point available additionally #18#19Switch output for Inm=1600 when special order is made for alternating current. Four open #26#27Load 1 Alarm (contacts) and four close from DF1 to DF8 with a common point available only for #10#11Load 2 Alarm 1nm=1600 in case of direct current, contact capacity (AC250V 5A). #20#21#22#23ABCNVoltage signal input 2. The wiring for the part indicated by dashed lines shall be made by users. (multi-functional time) (Maximum voltage AC400V) #24#25External transformer input
NA8
37
40
43
46
37
40
43
46
49
37 39 41
43 45 47
FU
NA8
L1
PE Profibus-DP
ST-4 power module
+ L N PE
ST-DP Device
12 13 14 15 16 17 18 19
N
1 + + COM D11 D12 D13 2 3 4 5 6 7 8
ABC
Fault indication
DC24V ST201
SB2 SB1
D02 14 15 16 17 D03 D01 12 13
XT
3 10 54
12
14 22 28 38 48 39 50 53 51 30 32
16 24 41 42 44 45 47 26 36
18
20
34
PE
D14 D15 SA D16
QF
SAL
D13
Intelligent controller
AX
F DT Q/QY
TA
Breaker body
XT 9 11 40 13 35 37 15 17 21 23 29 31 33 27 19 25
43
46
49
52
3200 and 6300 shell controller power supply: AC230V and AC400V
+ DC24V-
3200 and 6300 shell controller power supply: DC220V and DC110V
Intelligent controller Under Energy storage Power-driven Open Close voltage indication energy storage On indication OFF Auxiliary contact indication available for users AC auxiliary contact for standby application
Main circuit
Connection diagram for the secondary circuit of the NA8-3200 and 6300 optional type multifunctional intellectual controller
> >>
DTclosing electromagnet Fshunt release Q/QYunder voltage release SALsensitive switch SAtravel switch Menergy storage motor #1#2Intelligent controller auxiliary supply input AXauxiliary contact Fufuse SB1ON pushbutton #3PE SB2OFF pushbutton HL1~HL4indicator light #4# 5# 6Fault trip contact output XTconnection terminal TAcurrent transformer (# 5 for the public side, AC250V 5A) QFbreaker Spower module ST-DPDevice #7#8#9Auxiliary contact output ST201Relay module(Optional) ST-4Power module(Optional) (#8 for the public side, AC250V 5A) #14#15RS485 communication interface (communication type when) Notes: 1. Four open (contacts) and four close with a common point available #16#17Sub-gate output conventionally, one open and one close with a common point available additionally #18#19Switch output for when special order is made for alternating current. Contact capacity AC250V 5A #26#27Load 1 Alarm 2. When the controller voltage of the 3200 and 6300 shells is AC230V/400V, it #10#11Load 2 Alarm can be directly put to #1 and #2; if the voltage is DC220V/110V, it has to be put to #20#21#22#23ABCNVoltage signal input #1 and #2 after the power module outputs DC24V. (multi-functional time) (Maximum voltage AC400V) 3. The wiring for the part indicated by dashed lines shall be made by users. #24#25External transformer input
37
40
43
46
37
40
43
46
49
37 39 41
43 45 47
C-18
NA8
Connection of the secondary circuit
(5-
7)m
Conductor cross-section S: 2 (0.5~1.2)mm Connecting wire of secondary circuit Special screwdriver for the connection of secondary circuit
Screwless terminal connection system is used for the secondary connection of the breaker. The connection is made by using special flat blade screwdriver and single-core conductor by reference to the connectin diagram for the seondary circuit. Screwless terminal system is used for the connection of the secondary circuit. Insert the special screwdriver into the terminal hole shown in the figure to deform the clamp, insert the conductor into the corresponding terminal hole, and then take out the screwdriver.
C-19
> >>
NA8
8. Intellectual controller and protective characteristics
8.1 User interface of the standard type (M type) and multifunctional type (H type) intellectual controllers.
C
2 4
3
6
7 9 10
11
13
12
Brand CHINT brand LCD window LCD window capable of showing the current for each phase, various setting parameters, rated current, fault current, tripping time, and the like SET key Switch to the set default menu (left arrow key, when it is necessary to move leftwards or rightwards for the set interface). UP key Move the box select menu under the current menu to change the position of said box upwards, and perform the setting of the parameter ADD in the parameter setup menu. RETURN key Exit the current menu and go to the previous menu, or cancel the value of the current setup parameter. ACK key Go to the next menu of the currently selected select box (go to the set state under the set interface, and exit the set state by double pressing the key). DOWN key Move the box select menu under the current menu to change the position of said box downwards, and perform the setting of the parameter SUBTRACT in the parameter setup menu. INQUIRY key Switch to the inquiry default menu (right arrow key, when it is necessary to move leftwards or rightwards for the set interface). IR lamp Over current long time delay fault indication Isd lamp Short-circuit short-time delay fault indication test lamp Button for simulating instantaneous tripping test Ii lamp Short-circuit instantaneous fault indication Ig lamp Asymmetric grounding, neutral line fault indication
> >>
C-20
NA8
8.2 Default interface and menu structure for the multifunctional controller The multifunctional controller provides 4 title menus (measurement menu, parameter setup menu, protection parameter setup menu, history record and maintenance menu) and 1 default menu. Default interface for the multifunctional controller
Current I
C-21
> >>
NA8
1 menu 2 menu 3 menu 4 menu P= 660kW PQS Q= 0kvar S= 660kVA -1.00 Inductive Power factor PFa= 1.00 PFb= 1.00 Instantaneous value PaQaSa PFc= 1.00 Pa= 220kW Qa= 0kvar Sa= 220kVA Power P Pb= 220kW PbQbSb Qb= 0kvar Sb= 220kVA Pc= 220kW PcQcSc Qc= 0kvar Sc= 220kVA P= 660kW PQS Required value Q= 0kvar S= 660kVA P= 661kW Q= 2kvar Maximum S= 662kVA Reset(+/-) Ia Ib IaIb IcIn Ic In Waveform UanUbn Ucn Ucn Ia= 1000A I(A) Ib= 1000A Ic= 1000A In= 1000A Uab= 380V Ubc= 380V U(V) Uca= 380V Uan= 220V Ubn= 220V Ucn= 220V Ia= 0.0% I(%) Ib= 0.0% Ic= 0.0% In= 0.0% THD Uab= 0.0% Ubc= 0.0% Uca= 0.0% U(%) Uan= 0.0% Ubn= 0.0% Ucn= 0.0% Uan Ubn 5 menu
> >>
C-22
NA8
1 menu 2 menu 3 menu 4 menu Ia= 0.0% Ib= 0.0% thd I(%) Ic= 0.0% In= 0.0% Uab= 0.0% Ubc= 0.0% Uca= 0.0% thd U(%) Uan= 0.0% Ubn= 0.0% Ucn= 0.0% Ia FFT THD=0.0% Ia(3,5,7...31)
0.0%
5 menu
3 5 7 9 11...31)
3 5 7 9 11...31)
Ic FFT THD=0.0%
0.0%
3 5 7 9 11...31)
3 5 7 9 11...31)
3 5 7 9 11...31)
3 5 7 9 11...31)
3 5 7 9 11...31)
3 5 7 9 11...31)
C-23
> >>
NA8
8.2.3 Structure of the protection parameter setup menu
1 menu 2 menu 3 menu IR Current protection Long time delay Current protection Delay time Cooling time Definite-time limit Short-time delay 4 menu e.g.=1000A=100%In e.g.=ON e.g.=C1Is@6IR e.g.=3h Operating current e.g.=5000A=5.0IR e.g.=0.1s e.g.=2000A=2.0IR e.g.=C10.Is@6IR 5 menu
Inverse-time limit
Delay time e.g.=10000A=10.0In e.g.=200% e.g.=800A e.g.=0.4s e.g.=6.0 e.g.=600A e.g.=0.1s e.g.=100A e.g.=0.1s e.g.=8.0A e.g.=0.75s e.g.=5.0A e.g.=0.1s e.g.=4.0A e.g.=0.1s
Ground protection
Starting current Starting time Return current Return time Leakage protection Operating current Setup delay time Starting current Electric leakage alarm Starting time Return current Return time Executive mode Unloading value 1 e.g. =I the first method e.g.=800A e.g.=50%tR e.g.=700A e.g.=25%tR Executive mode Startup value Under voltage Starting time Return value Return time Executive mode Startup value
Load monitoring
e.g.=Alarm e.g.=200V e.g.=0.2s e.g.=320V e.g.=60.0s e.g.=Alarm e.g.=480V e.g.=1s e.g.=400V e.g.=60.0s e.g.=Alarm e.g.=10% e.g.=1s e.g.=5% e.g.=60.0s
Voltage protection
Over voltage
Starting time Return value Return time Executive mode Startup value
U unbalanced
> >>
C-24
NA8
8.2.4 Structure of the history record and maintenance menu
1 menu 2 menu e.g. phase sequence alarm, Current alarm inverse power alarm, over frequency alarm Total number of times Number of operations Number of operations Total wear Contact wear Product information Contact wear Zhejiang CHINT electrics co., LTD Under voltage tripping T=0.20s Umax=0V e.g.: 1 Under voltage tripping 2004/06/17 11:24:59 6/17 F=0.00Hz Uab= 0V Ubc= 0V Uca= 0V Tripping record A phase short-circuit definite-time limit T= 0.4s I= 4300A e.g.: 8 (for) short-circuit definite-time limit 2004/05/03 15 : 28 : 25 5/30 Ia= 4300A Ib= 4200A Ic= 4000A In= 150A e.g.: 1 DI (for) DI input alarm 2004/07/16 Di input alarm Di1 2004/07/16 20 : 38 : 45 Alarm logging e.g.: 8 Under voltage alarm 2004/06/20 Note: Up to 8 times of alarms can be recorded e.g.: 1 (for) local switch on 2002/06/18 Position changing record e.g.: 8 (for) testing tripping 2002/06/15 Note: Up to 8 times can be recorded Under voltage alarm Umax= 0V 2004/06/20 22 : 29 : 40 Local switch on 2002/06/18 9 : 30 : 56 Test tripping 2002/06/15 10 : 30 : 20 e.g.:300 e.g.:219(ACK key, Reset) e.g.:120 e.g.:20(ACK key, Reset) 3 menu 4 menu 5 menu
Notes: a. The actual menu will vary depend on the function selected by the user. b. The controller starts screensaver automatically 10min later.
C-25
> >>
NA8
8.3 List of controller functions Standard configuration
Standard type (M type) 1. Quadruple over current protection (for overload, short-time delay time, instantaneous, grounding); grounding corresponds to vector sum (T type); 2. Parameter setup: fixed value keyboard setting function; 3. Current measurement function; 4. Current unbalance rate measurement function; 5. Two test functions: (1) Instantaneous tripping test simulated on the panel; (2) Triple over current, grounding/leakage and operating time tests simulated by software; 6. Fault recording function: 8 times of failures can be recorded; 7. Self-diagnostic function; 8. MCRmake/break function; 9. Alarm logging function; 10. Recording number of operations; 11. Contact wear; 13. Position changing record; 13. Human-machine interface: 2843 LCD; 14. Heat capacity measurement Multifunction type (H type) 1. Quadruple over current protection (for overload, short-time delay time, instantaneous, grounding); grounding corresponds to vector sum (T type); 2. Parameter setup: fixed value keyboard setting function; 3. Current measurement function; 4. Current unbalance rate measurement function; 5. Two test functions: (1) Instantaneous tripping test simulated on the panel; (2) Triple over current, grounding/leakage and operating time tests simulated by software; 6. Fault recording function: 8 times of failures can be recorded; 7. Self-diagnostic function; 8. MCRmake/break function; 9. Communication function: MODBUS protocol; 10. Alarm logging function; 11. Recording number of operations; 12. Contact wear; 13. Position changing record; 14. Human-machine interface: 2843 LCD; 15. Heat capacity measurement
> >>
C-26
NA8
8.4 Characteristic parameters of the standard type intellectual controller Over current protection characteristics
10000 5000
IR=(0.4-1)In
tR=(1~30)s
T(s)
10
I2t on
5 2 1
Isd=1.5~10IR I t off
2
Isd=1.5~10IR
0.5 0.2 0.1 0.05 0.02 0.01 0.2 0.3 0.5 0.6 0.8 1 2 3 4 5 8 10 20 30 40 50 60 80
Ii=2~15)In
1.5
4 5
8 10
20
30
X IR
T(s)
10 5 2 1 0.5 0.2 0.1 0.05 0.02 0.01 0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 10 20 30 I2 t off I2t on
X In
C-27
> >>
NA8
8.4.1 Over current long time delay protection characteristic
Rated current range IR Error Line current I 1.05 IR (0.4~1)In +OFF(Power off) >1.30 IR 10% 1.5 IR 2.0 IR 6.0 IR Operating time tR(s) No actuation within 2h <1h and then actuate 16 9 1 32 18 2 64 36 4 128 72 8 192 108 12 256 144 16 320 180 20 384 216 24 480 270 30 15% Time error
Explanation for parameter setting: Long-time delay operating current continuously adjustable: IR=(0.4~1)In. The long-time delay tripping time represents the inverse-time limit characteristic, and nine optional settings are readily available for tripping time in case of 6IR: tR=(1-2-4-8-12-16-20-24-30)s. Example 1: If it is know that in conditions of I=6IR, the tripping time setting value is 2s, and now the line current I=1.5IR, then the actual tripping time TR can be worked out by: (1.5IR)2TR=(6IR)22. The answer is obtained as TR=32s.
Explanation for parameter setting: The short-circuit short-time delay protection operating current continuously adjustable: Isd=(1.5~10)IR. The short-time delay tripping time can be selected as tsd=(0.1s~1s). When the tripping time is set as inverse-time limit operating characteristic, there are two cases: the case of I1.15Isd and I10IR represents the definite-time limit; the case of I1.15Isd and I10IR represents the inverse-time limit characteristic and the actual tripping time is calculated according to the formula tsd=0.1tR, wherein tR is the long-time delay time, tsd is the short-time delay time. The method for setting the current and time for the short-circuit short-time delay protection is similar to that for over current long time delay protection. 8.4.3 Short-circuit instantaneous protection characteristic
Rated current range Ii (2~15)In +OFF(Power off) Error Line current I 0.85Ii >1.15Ii Operating Characteristics No-action Action
15%
Explanation for parameter setting: The instantaneous protection operating current is continuously adjustable: Ii=(2~15)In. The method for setting the current for the instantaneous protection is similar to that for over current long time delay protection setting.
Note: k is the fault current multiple (I/Ig), I is the fault current, Ig is the setup operating current.
> >>
C-28
NA8
Explanation for parameter setting: The single-phase grounding protection operating current can be adjusted and selected: Ig=(0.2~1)In. The protection delay tripping time can be selected as tg=(0.1s~1s). The case of IkIg or k set to OFF represents the definitetime limit characteristic, tg=0.1s-0.2s-0.3s-0.4s-0.5s-0.6s-0.7s 0.8s-0.9s-1s The case of the current meeting the condition of 1.1Ig IkIg represents the inverse-time limit characteristic and the actual tripping time is calculated according to the formula t=TgkIg/I. In the formula, I is the line current, Tg is the setup delay time, Ig is the setup operating current, t is the operating time, k is the shearing factor. The method for setting the parameter is similar to that for over current long time delay protection. Note: For the intellectual controller, the current settings for the long- and the short-time delay and the instantaneous protection should not come across each other, and the condition of IRIsdIi must be ensured. 8.5 Explanation for auxiliary functions a. Explanation for test conditions When onsite adjustment, periodical inspection or overhaul is made with the controller supported by the breaker, breaking several times is necessary by using the test functions of the controller to check the cooperation of the controller and the breaker. When the breaker on, press the test button, and the intellectual controller will trip instantaneously to cut off the breaker. Note: This function can be used only when onsite adjustment or overhaul for the breaker is made, and shall not be used during the normal operation. Each time before the controller is switched on, it is necessary to press the reset button in the upper position of the controller panel so that the breaker can be switched on again for operation. b. Explanation for fault memory The controller still has the function of fault memory after reset or de-energized to keep a latest historical event for post analysis. Only when there is a new fault again, the original information is cleared with the current latest faulty data saved. For the inquiry method, refer to the above explanation about fault display. 8.6 Explanation for display function When the rated current is greater than or equal to 400A, the primary current shall not be lower than 0.4In for single phase, and 0.2In for three phases for normal operation of the controller. When the rated current is less than 400A, the primary current shall not be lower than 0.8In for single phase, and 0.4In for three phases for normal operation of the controller. Note: When the AC220V S power module is energized, and the voltage falls to AC120V, there will be no display on the controller When the AC380V S power module is energized, and the voltage falls to AC200V, there will be no display on the controller a. Current display Error range for current display: 5% b. Voltage display Error range for voltage display: 1.5%
9. Accessories
9.1 Under voltage release When the under voltage release is not energized, neither power-driven nor manual operation can make the breaker on. For the under voltage release, there are two varieties: instantaneous and time delay operations. The time for the under voltage time delay release is Inm=1600A, the time can be selected from but not adjustable in the range of (0~7)s; Inm=3200A or 6300A, the time can be selected from and adjusted among 0.5s, 1s, 3s and 5s. When, within 1/2 delay time, the power voltage returns to 85%Ue or above, the breaker will not get disconnected. Operating characteristic:
Rated operational voltage Ue(V) Operating voltage (V) Reliable switching voltage (V) Reliable not-switching voltage (V) Power consumption (W) AC230 AC400 (0.35~0.7)Ue (0.85~1.1)Ue 0.35Ue 20VA
9.2 Shunt release After the shunt release is energized, the breaker is switched off instantaneously to allow remote operation. Operating characteristic:
Rated control supply voltage Us(V) Operating voltage (V) Power consumption (W) Breaking time AC230 AC400 (0.7~1.1)Us 200VA (5010)ms 200W DC220 DC110
C-29
> >>
NA8
Shunt release (Inm=3200A6300A) Power operating mechanism (Inm=3200A6300A)
9.3 Closing electromagnet After the motor energy storage is ended, energizing the closing electromagnet will make the energy storage spring force of the operating mechanism to be released instantaneously to rapidly switch the breaker on. Operating characteristic:
Rated control supply voltage Us(V) Operating voltage (V) Power consumption (W) Closing time AC230 AC400 (0.85~1.1)Us 200VA (5010)ms 200W DC220 DC110
9.5 Auxiliary contact (with a common point) Standard type: 4 groups of changeover contacts (default configuration) are provided Special type: 5 groups of changeover contacts 6 groups of changeover contacts (Inm=1600A provided, but not available for DC) 3 N.O. and 3 N.C. 4 N.O. and 4 N.C. (Inm=3200A and 6300A provided) Technical parameters:
Rated voltage (V) AC DC 230 400 220 Rated thermal current Ith(A) 6 0.5 Rated control capacity 300VA 60W
9.4 Power operating mechanism The functions of motor energy storage and automatic energy re-storage after the breaker comes on are available to ensure that the breaker can come on immediately after it gets disconnected. The breaker also allows manual energy pre-storage.
Rated operational voltage Ue(V) Operating voltage (V) Reliable switching voltage (V) Energy storage time Frequency of operation AC230 AC400 (0.85~1.1)Ue 75/150VA <4s At most 3 times in a minute 75/150W DC220 DC110
9.6 Separator between phases The separator is installed between the phases of the line bank to improve the insulating ability between the phases of the breaker.
> >>
C-30
NA8
9.7 Key lock The OFF pushbutton of the breaker can be locked in the position of depress, and at this time, the breaker cannot be closed for operation; after the user selects the option, the factory provides locks and keys; one breaker is provided with one independent lock and one key for the one lock; two breakers, two independent locks and one key for the two locks; three breakers, three same locks and two same keys for the three locks. Note: a. For the air circuit breaker with key interlock, when the key has to be pulled out, it is necessary to first press the OFF key, turn the key anticlockwise, and then pull out the key. b. The key for the 1600 does not work for the 3200 and 6300 shell breakers and vice versa, so be on guard against the distinction between them. 9.11 The drawer type of air circuit breaker about any working position locking device After the breaker body is locked automatically in any working position, it is necessary to turn the key to unlock the matter so that the breaker body can be moved to the next working position by turning the handle. (This function available for 3200 to 6300). 9.12 Mechanical interlock a. Steel cable interlock for two breakers placed horizontally can realize the interlock between circuit breakers of similar or different shells. b. Joint rod interlock for two superimposed brewakers.
9.8 Pushbutton lock It is used to lock the button for opening and closing the breaker with the padlock used for such a purpose. (Padlocks to be provided by users themselves)
b. Interlock with the door for the breaker position (only for the 1600 shell) When the breaker is in the position of connection and test, the cabinet door must not be opened; when the breaker is in the separation position, the cabinet door is allowed to be opened.
9.9 Door frame and lining pad They are installed on the door of the distribution cabinet room to seal it with a protection level of up to IP40. 9.10 Drawer type of air circuit breaker separation position locking device For the separation position of the open frame (draw-out) circuit breaker, a lock rod can be pulled out to lock the matter, and the breaker locked will be unable to be turned towards the TEST or CONNECTION position. Padlocks have to be provided by users themselves.
9.14 Counter The counter counts the number of mechanical operations of the circuit breaker for the user.
C-31
> >>
NA8
Mechanical interlock
2m(max)
Circuit diagram
1QF 0
1QF 2QF
2QF 0 1 0
0 1
Note: a. When it is necessary to bend the steel cable, the transition arc at the bend shall be larger than R120mm, in order to ensure the flexible movement of the steel cable. b. Check the steel cable to see if there is sufficient lubricating oil in it, in order to ensure the flexible movement of the steel cable.
Mounting dimensions of the interlock with the door for the status of the NA8-1600 air circuit breaker (fixed type)
Reset
A direction
A direction
Gusset plate OFF position R60 This panel is to be designed by users themselves ON position Right mounting panel of the circuit breaker Mounting plane
117.6
Mounting hole 59
> >>
C-32
NA8
Mounting panel
OFF position
23 0 0
26 0 0 ON position
10
182
Mounting hole
13.5
45
30.7
Mounting dimensions of the interlock with the door for the status of the NA8-1600 air circuit breaker (draw-out type)
Reset
A direction
A direction
Block breaker drawer right side plate Gusset plate This panel is to be designed by users themselves Mounting panel
R60
150
8.4
Bottom plate of the draw-out socket of the breaker Mounting hole Mounting plane 14
35
C-33
> >>
NA8
OFF position
23 0 0
C
18
26 0 0
ON position
10
96.21
Bottom plate of the draw-out socket of the breaker Mounting hole Mounting plane
80
10. Installation 10.1 Following items to be checked before installation Check the label plate on the breaker panel to see if it conforms to the specifications of the ordered goods. a. Rated current; b. Under voltage release voltage and delay time; c. Shunt release voltage; d. Closing electromagnet voltage; 3. Motor voltage. 10.2 Before installation, operation, maintenance and inspection, you shall read this manual, and consult the manufacturer for questions, if any. 10.3 Preparations before installation Before the breaker is installed, check the insulation resistance of the breaker by using a 1000V megohmmeter according to regulations; when the surrounding media temperature is 255 and the relative humidity is 50%~70%, the insulation resistance shall not be less than 20 megohm. The place with the insulation resistance to be tested includes: the place between various phases and between various phases and the frame when the breaker is closed; the place between in- and out-lines of various phases when the breaker is switched off. 10.4 Installation of the fixed type breaker Place the breaker into the distribution cabinet, and fasten it by using 4 pieces of M6(Inm=1600A) or M10(Inm=3200A or above) bolts and washers. The breaker shall be installed stably with no additional mechanical stress to avoid damage of the breaker or bad contact of the main bus bar. 10.5 Installation of the open frame (draw-out) circuit breaker Take the breaker body out of the draw-out socket, and install the socket in the distribution cabinet, and fasten it by using 4 pieces of M6(Inm=1600A) or M10 (Inm=3200A or above) bolts and washers; the breaker shall be installed stably with no additional mechanical stress to avoid damage of the breaker or bad contact of the main bus bar and the secondary circuit. After the work is completed, mount the body into the draw-out socket. 10.6 The specifications of the wiring copper bars for the primary circuit of the breaker shall meet the copper bar specifications used under the conditions of conventional heating in GB14048.2. 10.7 The breaker shall be grounded substantially.
218
> >>
C-34
NA8
11. Common faults and troubleshooting Listed below are the problems which users may encounter during installation, adjustment, and operation of the breaker, and the possible reasons and elimination methods.
No. Technical problems Possible causes Diagnosis and trouble shooting 1 Check the breaking current and operating time on the intellectual controller; 2 Analyze the operation of the load and power network; 3 Promptly find and shoot the trouble if overload is confirmed; 4 For lack of match between the actual running current and the long time delay operating current, please modify the long-time delay operating current setting for a proper match and protection according to the actual running current; 5 Press the reset button to close the breaker again. 1 Check the breaking current and operating time on the intellectual controller; 2 Promptly find and shoot the trouble if short circuit is confirmed; 3 Check the setting value of the intellectual controller; 4 Check to see whether the breaker is in good condition, and determine whether it can be closed for operation; 5 Press the reset button to close the breaker again. 1 Check the breaking current and operating time on the intellectual controller; 2 Promptly find and shoot the trouble if it is confirmed that there is a grounding fault; 3 If no grounding fault is detected, please determine whether the grounding fault current setting is proper, and can be well matched with the actual protection; if not, the setting shall be modified; 4 Press the reset button to close the breaker again. 1 Check to see if the power voltage is lower than 70%Ue; 2 Check the under voltage release and control unit for fault; Check the working condition of two breakers equipped with mechanical interlock. 1 Whether the under voltage release has been energized; 2 Whether the power voltage is lower than 85%Ue; 3 Whether the under voltage release or control unit malfunctions, if so, the release shall be replaced. Press the reset button to close the breaker again. Put the open frame (draw-out) circuit breaker to the right position by rocking (with it locked in the connection position) Check the contact status of the secondary circuit, and shoot the trouble, if any 1 Check the motor control power supply and see if it is well providing power, and the voltage must be 85%Us; 2 Check the status of the motor energy storage mechanism. 1 Check the power voltage of the closing electromagnet, and it must be 85%Us; 2 if there is any trouble in the closing electromagnet to enable the attracting, it shall be replaced. 1 There may be short circuit current when the matter is switched on, and in this case you shall find and shoot the trouble; 2 Check to see if there is any overload current in the circuit, find and shoot the trouble, if any; 3 Check to see whether the breaker mechanism is in good condition; 4 Check the setting value of the intellectual controller for reasonability, and a resetting process is necessary if not reasonable; 5 Press the reset button to close the breaker again. 1 Check the shunt release circuit for reliable connection and the shunt release for trouble, and the release shall be replaced if the fault is confirmed; 2 Check the operating mechanism for mechanical fault. 1 Check the motor energy storage mechanism control power voltage, and the voltage shall be 85%Us; check the status of the circuit connection; 2 Check the motor; Energy storage mechanism malfunction.
Under voltage release tripping Mechanical interlock action Under voltage release no attracting Reset button fails to reset Open frame (draw-out) circuit breaker fails to be put to the right position by rocking Open frame (draw-out) circuit breaker bad contact for the secondary circuit Breaker fails to pre-store energy
The breaker fails to open in powerdriven mode The breaker fails to open in manual mode Energy failed to be stored in powerdriven mode Cant achieve manual energy storage
Breaker fails to store energy Breaker fails to be pulled out when the open frame (draw-out) circuit breaker is in the SEPARATION position Open frame (draw-out) circuit breaker fails to be put to the CONNECTION position by rocking
Rock rod fails to be pulled out; breaker fails to completely reach the SEPARATION position The drawer has seized up for foreign matters fall in it; damage in the mechanism for putting in by rocking or the gear thereof; position locking device fails to be unlocked Intellectual controller fails to be energized by power supply; improper input voltage for the auxiliary power supply; improper secondary output voltage for the transmitter; unreliable connection between the secondary output terminal of the transmitter and the controller;
Pull out the rock rod. Put the breaker completely to the SEPARATION position by rocking.
Check it for foreign matters and for condition of the rack and gear. Turn the key on the drawer to unlock the matter.
1 Check to see if the intellectual controller power supply is well connected and works well; 2 Cut off the intellectual controller control power supply, and then connect the power supply; If the fault is still present, there may be some troubles in the controller which has to be replaced.
C-35
> >>
NA8
12. Order specification
User Type and size Rated current (In)A NA8-1600 200 400 630 800 1000 1250 1600 Vertical connection 4P Factorys setting values: IR=1In, 2s(6IR); definite-time limit Isd=8IR, 0.4s; inverse-time limit Isd=6IR, tsd=0.2s@6IR, Ii=12In; Ig is off (if it is on, it shall be specially stated, the default value is Ig=0.5In, the inverse-time limit shearing factor is k=OFF, thetime is T=0.4s). If the user has some requirements different from the defaulting, please write the numerical values on the line below. Long-time delay protection IR Setting of the protection parameter Order amount Order date NA8-3200 1600 2000 2500 3200 Front connection Tel NA8-6300 4000 5000 6300
Installation mode Draw-out type Connection mode Horizontal connection Number of poles 3P
Fixed type (no such products for over 4000A) Mixed connection (connection mode to be noted)
Operating current setting: Definite-time limit Inverse-time limit Operating time setting: Definite-time limit Inverse-time limit:0.1tR Operating current setting: Operating current setting: Operating time setting: Inverse-time limt shearing factor k: Multifunctional type DC220V DC110V DC24V In (1~15,OFF)
Short-circuit instantaneous protection Ii Ground protection Ig Intellectual Selecting the type controller Power input Basic function Standard type AC400V AC230V
IR s (0.1,0.2,0.3,0.4,0.5,0.6,0.7,0.8,0.9,1.0); (1.5~6,OFF)
Optional function (this function to be added as required by the user, and to be matched with the controller type)
Over voltage protection Under voltage protection Over frequency protection Under frequency protection Voltage unbalance protection Phase sequence protection Voltage measurement Frequency measurement Measurement of harmonic current Power factor measurement Power measurement Phase sequence detection Voltage unbalance rate measurement Electric energy measurement Contact equivalent Power network history parameter recording function Leakage protection MCR make/break function Load monitoring function Signal contact output function Communication function ZSI regional interlocking protection function
Note: When the product is a multifunctional controller as arranged by the user, the communication function and the like are the basic function configuration. Under voltage release Instantaneous AC400V Time delay s (1-2-3-4-5-6-7s provided for the 1600 shell, optional but not adjustable; 0.5-1-3-5s for the 3200 shell, optional and adjustable) AC230V AC230V AC230V DC220V DC220V DC110V DC110V
Accessories Shunt release AC400V for standard Closing electromagnet AC400V configuration
AC400V AC230V DC220V DC110V Energy storage motor 4 groups of changeover contacts 6 groups of changeover contacts (Inm=1600 not available for DC) Auxiliary contact 3 N.O. and 3 N.C. 4 N.O. and 4 N.C. (Inm=3200 and 6300 provided) One breaker is provided with one independent lock and one key Two breakers are provided with two independent locks and one key (the same key/lock not available for the 1600 and 3200/6300 shell breakers) Two breakers are provided with three independent locks and two keys (the same key/lock not available for the 1600 and 3200/6300 shell breakers) Two-breaker interlock solution Steel cable interlock (can realize the interlock between circuit breakers of similar or different shells) Joint rod interlock (can realize the interlock between similar shells) Door interlock
Mechanical interlock
Note: Extra costs are needed for the optional functions, operational accessories and the like for the breaker.
NA8-1600
NA8-3200
NA8-6300 C-36
> >>
NA8G
2. Type designation
N A 8G - /
No. of poles (pole 3 may be omitted) Frame size rated current Improved product code Design sequence number ACB Company code
3. Operation conditions
3.1 When the ambient air temperature is -5 - +40 , the mean value is no greater than +35 within 24 hours. Note: If the upper limit is higher than +40 or lower limit lower than -5 in work, discussions shall be made between the user and the manufacturer. 3.2 Altitude: not higher than 2000m for the installation site. 3.3 When the ambient air temperature is +40 , the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for example, for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature averaged in that month +20 , and special measures shall be taken for the condensation occasionally produced due to temperature change. 3.4 Class of pollution: 3 3.5 The installation category of the breaker main circuit is IV; when the rated operational voltage of the main circuit is less than or equal to AC400V, The installation category of the control circuit and auxiliary circuit is , apart from the similarity between the under voltage release coil and the intellectual controllers power transformer primary coil and the breaker; When the rated operational voltage of the major loop is greater than AC400V and less than or equal to AC690V, it is necessary for the control circuit and auxiliary circuit to be isolated from the major loop, and the highest operational voltage of the control circuit and auxiliary circuit is AC400V, the installation category of the control circuit and auxiliary circuit being .
C-37
> >>
NA8G
4. Product structure
Body structure
C
ON pushbutton Energy storage motor
Intellectual controller
Operating mechanism
Fault-breaking indicator reset button Energy storage handle Breaking button Making button Energy storage & release indicator
Breaking/Making indicator
> >>
C-38
NA8G
Depress
Depress
Depress
Depress
Depress
Depress
Depress
Depress
Energy storage
Energy storage
Energy storage
Energy storage
Drawout structure
Position indication
Locking device
C-39
> >>
NA8G
Connected
Connected
Test
Disconnected
Connected: both main circuit and secondary circuit are connected
Test
Disconnected
Test: the main circuit is disconnected, the safety separator works well, and the secondary circuit is connected.
Connected
Test
Disconnected
Disconnected: neither main circuit nor secondary circuit is connected
(4)Move the breaker body onto the guide rail with a snap
(5)Push the breaker body in, and turn the break body to the working position
> >>
C-40
NA8G
5. Main technical parameters
5.1 Main technical parameters
Shell grade rated current Inm A
Rated current In A
1600
200,400,630,800, 1000,1250,1600 690 415 690
3200
1600,2000,2500, 2900,3200 1000 415 690 100 65 80 65 80 65 10 3000 1000 0 Wire to enter from the upper or lower port 52.5/66.5 98/121 406(422/537)329 439(435/550)445
6300
4000,5000,6300 6300
1000 415 120 100 100 10 2000 500 0 Wire to enter from the upper or lower port 210/233 439(835/928)501 439928501 233
Rated ultimate short circuit breaking capacity Icu kA 50 25 Rated service short circuit breaking capacity Ics kA Rated short time withstand current Icw,1s kA Frequency of operation (number of times/h) Number of operations Mechanical life Electrical Life 40 20 40 20 20 3000 1000 0 Wire to enter from the upper or lower port fixed type kg draw-out type kg fixed type draw-out type 22/26.5 38/55 320(254/324)258 351(282/352)352
5.2 Capacity-reducing usage 5.2.1 Capacity-reducing at different temperatures The following table shows the continual current-loading capacity of the circuit breakers and buses in each wiring mode at the corresponding ambient environment temperatures and under the conditions of the satisfaction of conventional heating with a similarity in capacity reducing between the breaker connected in a mixed way and the breaker connected horizontally.
Style wiring mode ambient temperature Draw-out type Front/rear horizontal wiring mode
-5~40 200 400 630 1600 800 1000 1250 1600 1600 2000 3200 2500 2900 3200 4000 6300 5000 6300 45 200 400 630 800 1000 1250 1550 1600 2000 2500 2900 3200 4000 5000 6100 50 200 400 630 800 1000 1250 1500 1600 2000 2500 2900 3100 4000 4700 6000 55 200 400 630 800 950 1150 1450 1600 2000 2450 2800 3000 3900 4600 5500 60 200 400 550 700 900 1050 1350 1600 1900 2350 2700 2900 3800 4400 5200
C-41
> >>
NA8G
5.2.2 Capacity-reducing at different altitudes
When the altitude is higher than 2000m, there will appear changes in insulation property, cooling performance, pressure, and the performance can be modified in reference to the following table.
Altitude(m) Insulation withstand voltage(V) Insulation voltage(V) Rated operational voltage(V) Rated operational current(A) 2000 3500 1000 690 1In 3000 3000 800 580 0.96In 4000 2500 700 500 0.92In 5000 2000 600 400 0.87In
5.3 Power loss Power loss is the loss at each pole which is measured when the breaker is charged with the rated current.
Power loss Breaker type
Rated current
200 400 630 800
Draw-out type
115 140 161 215 230 250 460 390 470 600 600 670 550 590 950
Fixed type
45 80 100 110 120 130 220 170 250 260 260 420 -
NA8G-1600
NA8G-3200
NA8G-6300
5000 6300
Note: The data and parameters in the above technical documentation results from tests and theoretical calculation, and can only be used as a general type selection guide.They cannot replace industrial practical experience or proof test. 5.4 Recommended bus for the breaker and recommendation for users to install the buses
Inm(A)
In(A) Thickness(mm) Busbar Width(mm)
NA8G-1600
200 5 20 400 5 50 1 630 5 40 2 800 5 50 2 1000 5 60 2 1250 8 60 2 1600 10 60 2
NA8G-3200
1600 6 100 2 2000 6 100 3 2500 5 100 4 2900 10 100 3 3200 10 100 4
NA8G-6300
4000 10 100 5 5000 10 100 7 6300 10 100 8
Number of buses 1
> >>
C-42
NA8G
6. Dimensions and connection
NA8G-1600 (In=200A ~1250A) Draw-out type (horizontal connection is the default by the factory, vertical one to be made by users themselves).
210
36
a
149 275
7
351
78.5
95
76
2-6.5 2-6.510
149(3P) 155(4P)
95
35
78.5(3P) 75.5(4P)
145(3P) 215(4P)
63
76
310
35
a(mm) 5 10 15
76
76
76
Note: If users intend to change the horizontal connection into vertical one on site, they need to replace the upper and lower buses on both sides with the same one as the central bus.
NA8G-1600 (In=1600A) Draw-out type (horizontal connection is the default by the factory, vertical one to be made by users themselves).
210 36
Separator between phases (to be ordered separately)
15
275
179
351
63.5
95
76
435(Connecting position)
282(3P) 352(4P)
481(Separating position)
Wires connected horizontally
Separator between phases (to be ordered separately)
2-6.5
95
2-6.510
35
149(3P) 155(4P)
145(3P) 215(4P)
63
N pole
2411(3P) 3211(4P)
78.5(3P) 75.5(4P)
95 435(Connecting position)
80.5
76
481(Separating position)
Wires connected vertically
310
101
101
101
Note: If users intend to change the horizontal connection into vertical one on site, they need to replace the upper and lower buses on both sides with the same one as the central bus.
C-43
> >>
NA8G
NA8G-1600 (200A~1250A) Fixed type (horizontal connection is the default by the factory, vertical one to be made by users themselves).
210
22
Separator between phases (to be ordered separately)
a 320
275
281
149
48.5
7 100 251 92
100
4-7
237(3P) 307(4P)
149(3P) 155(4P)
48.5(3P) 45.5(4P)
100 251
92
76
76
76
a(mm) 5 10 15
Note: If users intend to change the horizontal connection into vertical one on site, they need to replace the upper and lower buses on both sides with the same one as the central bus.
NA8G-1600 (In=1600A) Fixed type (horizontal connection is the default by the factory, vertical one to be made by users themselves).
210
35
22
Separator between phases (to be ordered separately)
320
275 281
149(3P)
155(4P)
48.5(3P)
45.5(4P)
100 341
92
100
4-7
N Pole
15
24-11(3P) 32-11(4P)
179
15
237(3P) 307(4P)
80.5
7 33.5
92
Note: If users intend to change the horizontal connection into vertical one on site, they need to replace the upper and lower buses on both sides with the same one as the central bus.
> >>
C-44
NA8G
NA8G-1600 Draw-out type Size of the hole to be drilled on the panel NA8G-1600 Fixed type Size of the hole to be drilled on the panel
220 10-5
220 8-5
120
118
322
320
118
285
78
118.5
From the center of the mounting hole on the right side of the breaker
258
From the center of the mounting hole on the right side of the breaker
258
217.5(3P) 332.5(4P)
240
Datum line 1
Datum line 2
199
371 328
11 11 17
175
155
145
18
1 4 7 111
376
268
14
10
47
162.5(3P) 277.5(4P)
162.5
106
Datum line
Datum line 1
C-45
> >>
21.5
97
Datum line 2
NA8G
NA8G-3200(In=1600A~2500A) Draw-out type (horizontal connection is the default by the factory).
52
25
78 14
50
11 29
C
115 115 115 Datum line
445(Connecting position) 492(Separating position)
Note: If users want to change the horizontal connection into vertical one on site, they only have to turn the bus by 90 NA8G-3200(In=1600A~2500A) Draw-out type (vertical connection to be made by users themselves).
84
133
42 14 11 25
55
78
115
115
115
Datum line
25
Note: If users want to change the vertical connection into horizontal one on site, they only have to turn the bus by 90 NA8G-3200 Draw-out type; Front connection
57.5
C 15
86
25
12-13
29
115
301
115
115
Datum line
C 20 30
2900, 3200
> >>
C-46
NA8G
NA8G-3200(In=2900, 3200A) Draw-out type (horizontal connection is the default by the factory)
52
25
133
14
126
84
126
126
Datum line
42
14 11
25
57
100
115 25
115
35.5
Note: If users want to change the horizontal connection into vertical one on site, it is necessary to replace the upper and lower buses for the N and B phases with the same one as the A and C phases.
11
200(3P) 315(4P)
200
Datum line 1
Datum line 2
163 13
11
402
246
44
29
11
100
25
C-47
> >>
NA8G
NA8G-3200 Fixed type, size of the hole to be drilled on the panel
4 12
371 328
150
72.5
311 268
200(3P) 315(4P)
200
86
Datum line
Datum line
32
112
18.5
86
50
12-13
In(A)
115 115 115 Datum line
a(mm) 20 30
1600~2500 2900~3200
Note: If users want to change the horizontal connection into vertical one on site, they only have to additionally install a vertical bus.
55
32
29 14
11
57
100
115
115
a(mm) 20 30
55 25
45
Note: If users want to change the horizontal connection into vertical one on site, they only have to additionally install a vertical bus.
> >>
C-48
NA8G
NA8G-6300 In=(4000A~5000A) Draw-out type size of the hole to be drilled on the panel
710.5(4P) 617.5(3P) 217.5 391
232
Datum line 2
199
Datum line 1
175
376
1117
268
162.5 47 703(3P)
Datum line 1
106
Datum line 1
818(4P)
NA8G-6300 In=(6300A) Draw-out type size of the hole to be drilled on the panel
710.5
217.5
391
240
Datum line 1
Datum line 2
199
371 328
14
175
155
376
1117
268
21.5 21.5
Datum line 2
145
97
162.5 47 818
Datum line 1
106
Datum line 1
C-49
> >>
18
Datum line 2
145
97
18
NA8G
NA8G-6300(In=4000A~5000A) Draw-out type (vertical connection to be made by users themselves)
29 11 125 115 103
N pole
129.5
105
142
105
142
105 30
57
25 14 10.5
Note: If users want to change the horizontal connection into vertical one on site, they only have to additionally install a vertical bus. NA8G-6300(In=4000A~5000A) Draw-out type (horizontal connection is the default by the factory)
N pole
100
155
210
28-13 20
112
103
30
40
Note: If users want to change the horizontal connection into vertical one on site, they only have to additionally install a vertical bus.
NA8G-6300(In=6300A) Draw-out type (vertical connection to be made by users themselves)
14 11 125 115 103
130 207 130 207 130 30
92
57 25
29
Note: If users want to change the horizontal connection into vertical one on site, they only have to additionally install a vertical bus. NA8G-6300(In=63000A) Draw-out type horizontal connection is the default by the factory
10.5
112 30
Note: If users want to change the horizontal connection into vertical one on site, they only have to additionally install a vertical bus.
92
103
40
20
180
260
> >>
C-50
NA8G
7. Secondary circuit wiring
Connection diagram for the secondary circuit of the NA8G-1600 optional standard type intellectual controller
Fault indication
N A B C
HL1
SB2
SB1
HL2
HL3
HL4
XT
12
14
16
18
20
22
24
26
28
30
32
34
36
38
39
41
42
44
45
47
48
50
51
53
54
55
FU
Breaker body
QF SAL
Intellectual controller
DT
Q/QY
M
DF1 DF2 DF3 DF4 DF5 DF6 DF7 DF8 DF9 DF10 DF11 DF12
L1
TA
SA
XT
10
11
13
15
17
19
21
23
25
27
29
31
33
35
37
40
43
46
49
52
56
FU
+DC24V -
S
Energy
Main circuit
Intellectual controller
Open Close
1 and 2: input (terminals) for intellectual controller auxiliary power supply # # # 4, 5 and 6: faulty tripping contact output ( 5 is the common terminal, AC250V 5A)
Notes: 1. Four open (contacts) and four close from DF1 to DF8 with a common point available conventionally, two open and two close from DF9 to DF12 with a common point available additionally for Inm = 1600 when special order is made for alternating current, four open and four close from DF1 to DF8 with a common point available only for Inm = 1600 in case of direct current, contact capacity (DC220V 0.5A). 2. Various control voltages of the 1600 has to be put # # to 1 and 2 after the power module inputs DC24V. 3. The wiring for the part indicated by dashed lines shall be made by users.
C-51
> >>
NA8G
Connection diagram for the secondary circuit of the NA8G-3200 to 6300 optional standard type intellectual controller
Fault indication
N A B C
HL1
SB2
SB1
HL2
HL3
HL4
XT
12
14
16
18
20
22
24
26
28
30
32
34
36
38
39
41
42
44
45
47
48
50
51
53
54
55
FU
Breaker body
C
SAL
QF
Intellectual controller
DT
Q/QY
M
DF1 DF2 DF3 DF4 DF5 DF6 DF7 DF8 DF9 DF10 DF11 DF12
L1
TA
SA
XT
10
11
13
15
17
19
21
23
25
27
29
31
33
35
37
40
43
46
49
52
56
FU
3200 and 6300 shell controller power supply: AC230V and AC400V
+DC24V -
S
3200, 6300 shell controller power supply: DC220V,DC110V; 1600 shell controller power supply Main circuit Intellectual controller
Under Energy -driven ON OFF storage voltage indication energy indication indication
storage Power
Open Close
1 and 2: input (terminals) for intellectual controller auxiliary power supply # # # 4, 5 and 6: faulty tripping contact output ( 5 is the common terminal, AC250V 5A)
Notes: 1. Four open (contacts) and four close from DF1 to DF8 with a common point available conventionally, one open and one close from DF9 to DF10 with a common point available additionally, contact capacity (DC220V 0.5A) 2. When the controller voltage of the 3200 and 6300 shells is AC230V/400V, it can be directly put to #1 and #2; if the voltage # # is DC220V/110V, it has to be put to 1 and 2 after the power module inputs DC24V. 3. The wiring of the part indicated by dashed lines shall be made by users.
> >>
C-52
NA8G
Connection diagram for the secondary circuit of the NA8G-1600 optional type multifunctional controller
FU L1 N PE Profibus-DP
L N PE
ST-DP Device
12 13 14 15 16 17 18 19
A B C
Fault indication
1 +
3 +
DC24V
D01 D02 14 15
ST201
D03 16 17
SB2
SB1
HL1
Green Red
12 13
HL2
HL3
HL4
XT
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
39
41
42
44
45
47
48
50
51
53
54
55
PE QF
SAL D13 D14 D15 D16 SA
Breaker body
Intellectual controller
DT
Q/QY
M
DF1 DF2 DF3 DF4 DF5 DF6 DF7 DF8 DF9 DF10 DF11 DF12
TA
XT
11
13
15
17
19
21
23
25
27
29
31
33
35
37
40
43
46
49
52
56
+DC24VS
Main circuit
Intellectual controller
Open Close
Under voltage
Power
ON indication
OFF Auxiliary contact available for users AC auxiliary contact for standby application indication
storage
Q/QYunder voltage release DF1 - DF12auxiliary contact XTconnection terminal ST-DP communication module
1 and 2: input (terminals) for intellectual controller auxiliary power supply 3PE # 4, #5 and #6: faulty tripping contact output ( #5 is the common terminal, AC250V 5A) # 7, #8 and #9: auxiliary contact output ( #8 is the common terminal, AC250V 5A) # 10, #11 and #12: auxiliary contact output ( #11 is the common terminal, AC250V 5A) # 14 and #15RS485 communication interfaces (in case of communication type) # 16, #17, #18, #19, #26 and #27: programmable input/output points (DC110V 0.5A, AC250V5A) # 20, #21, #22, and #23: A, B, C, and N voltage signal output (in case of multifunction type) (maximum voltage AC400V) # 24 and #25: to be externally connected to the mutual inductor input
#
Notes: 1. Four open (contacts) and four close from DF1 to DF8 with a common point available conventionally, two open and two close from DF9 to DF12 with a common point available additionally for Inm = 1600 when special order is made for alternating current. Four open (contacts) and four close from DF1 to DF8 with a common point available only for Inm = 1600 in case of direct current, contact capacity (AC250V 5A). 2. The wiring of the part indicated by dashed lines to be made by users.
C-53
> >>
NA8G
Connection diagram for the secondary circuit of the NA8G-3200 and 6300 optional type multifunctional intellectual controller
FU L1 N PE Profibus-DP
L N PE
ST-DP Device
12 13 14 15 16 17 18 19
A B C
Fault indication
1 +
3 +
DC24V
D01 D02 14 15
ST201
D03 16 17
SB2
SB1
C
HL2 HL3 HL4 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55
HL1
Green Red
12 13
XT
10
12
14
16
18
20
22
24
26
28
30
32
PE QF
SAL D13 D14 D15 D16 SA
Breaker body
Intellectual controller
DT
Q/QY
M
DF1 DF2 DF3 DF4 DF5 DF6 DF7 DF8 DF9 DF10 DF11 DF12
TA
XT
11
13
15
17
19
21
23
25
27
29
31
33
35
37
40
43
46
49
52
56
3200 and 6300 shell controller power supply: AC230V and AC400V
+ DC24V -
S 3200, 6300 shell controller power supply: DC220V,DC110V; 1600 shell controller power supply
Power
Main circuit
Intellectual controller
Open Close
Under voltage
ON indication
OFF indication
storage
Q/QYunder voltage release DF1 - DF12auxiliary contact XTconnection terminal ST-DP communication module
1 and 2: input (terminals) for intellectual controller auxiliary power supply 3PE # 4, #5 and #6: faulty tripping contact output ( #5 is the common terminal, AC250V 5A) # 7, #8 and #9: auxiliary contact output ( #8 is the common terminal, AC250V 5A) # 10, #11 and #12: auxiliary contact output ( #11 is the common terminal, AC250V 5A) # # 14 and 15RS485 communication interfaces (in case of communication type) # # 16, 17, #18, #19, #26 and #27: programmable input/output points (DC110V 0.5A, AC250V5A) # 20, #21, #22, and #23: A, B, C, and N voltage signal output (in case of multifunction type) (maximum voltage AC400V) # 24 and #25: to be externally connected to the mutual inductor input
#
Notes: 1. Four open (contacts) and four close from DF1 to DF8 with a common point available conventionally, one open and one close from DF9 to DF10 with a common point available additionally when special order is made for alternating current. Contact capacity AC250V 5A # # 2. When the controller voltage of the 3200 and 6300 shells is AC230V/400V, it can be directly put to 1 and 2; # # if the voltage is DC220V/110V, it has to be put to 1 and 2 after the power module inputs DC24V. 3. The wiring of the part indicated by the dashed lines shall be made by users.
> >>
C-54
NA8G
8. Intelligent controller and protective characteristics
8.1 User interface of the standard type controller
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8
LED window Ig limp IR limp Isd limp Ii limp MENU Pushbutton Pushbutton
LCD window capable of showing the current for each phase, various setting parameters, rated current, fault current, tripping time, and the like Asymmetric grounding, neutral line fault indication Over current long time delay fault indication Short-circuit short-time delay fault indication Short-circuit instantaneous fault indication Successively access to submenus at various levels by pressing the MENU key To inquire the current for each phase at present: recurrently select the contents in the menus at various levels Return to previous menu; the intellectual controller software is reset; RESET key must be pressed after the encoder switch position is adjusted; the intellectual controller faulty tripping results in fault memory which can be cleared only by pressing the RESET key; There are (0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 0.98, 1.0)In, nine settings altogether, for the over current long time delay current multiple setting
RESET Pushbutton
9 10 11 12
IR Knob switch tR Knob switch Isd Knob switch tsd Knob switch Ig Knob switch test Pushbutto n tg Knob switch
There are (1, 2, 4, 8, 12, 16, 20, 24, 30)s, nine settings altogether, for the over current long time delay time setting in case of 6Ir There are (1.5, 2, 2.5, 3, 4, 5, 6, 8, 10)Ir, nine settings altogether, for the short-circuit short-time delay current multiple setting For the short-circuit short-time delay time setting, there are nine settings: the inverse time limit, i.e., I2t on(0.1, 0.2, 0.3, 0.4)s, the definite-time limit, i.e., I2t OFF (0.1 0.2 0.3 0.4)s and X, i.e., closing the short-time delay There are (A, B, C, D, E, F G, H, J), nine settings altogether, for the asymmetric grounding (neutral line) current multiple setting For the typical numerical values thereof, see the characteristic parameter table Button for simulating instantaneous tripping test For the asymmetric grounding (neutral line) time setting, there are nine settings: the inverse time limit, i.e., I2t on(0.1, 0.2, 0.3, 0.4)s, and the definite-time limit, i.e., I2t OFF(0.1 0.2 0.3 0.4)s, and X, i.e., closing the asymmetric grounding (neutral line) Short-circuit instantaneous current multiple setting.
13
14 15
16
Ii Knob switch
C-55
> >>
NA8G
8.2 Default interface and menu structure for the standard type controller The default interface for the standard type controller is described as follows (the current for each phase to be selected by pressing ) Operation method: Press MENU to go to the primary menu, then press selection menu, and than press MENU Go to the secondary menu, press selection menu or modify the parameter, press RESET to return to the previous menu
Default interface for the standard type controller
Primary menu
Secondary menu
Instantaneous value
Magnitude of current
Ia= 1300A Ib= 1400A Maximum Ic= 1380A In= 200A Ig= 0A Current thermal capacitance Long time delay setting current Ir=1600A and long time delay setting time tr=Is@6Ir Short time delay setting current Isd=9600A short time delay setting time tsd=0.4s Instantaneous setting current Ii=16000A Grounding setting current Ig=1600A grounding setting time tg=OFF Instantaneous 10min 20min Long time delay thermal capacitance cooling time = instantaneous 30min 45min 1h 2h 3h Long time delay protection = open Open Close For example: Long time-lag tripping Ib=2894A For example, long time-lag tripping Note: Up to 8 times of failures can be recorded actuation time 12.06s Ir=1600A the event having taken place, the time being 0:21 on the date of 0 0% Simultaneously press MENU and to reset
Protection parameter
Fault recording
Alarm free
45 (default) note: adjustable range from 35 to 60
Notes: a. The actual menu will very depend on the function selected by a user. b. The controller starts screensaver automatically 10min after it is energized.
> >>
C-56
NA8G
8.3 User interface of the multifunctional controller
2 4
5 3 6 8
9 10
11 13 12
1 2
Brand LED window SET key UP key RETURN key ACK key DOWN key INQUIRY key IR limp Isd limp
test
"CHINT" Brand
LCD window capable of showing the current for each phase, various setting parameters, rated current, fault current, tripping time and the like
Switch to the set default menu (left arrow key, when it is necessary to move leftwards or rightwards for the set interface). Move the box select menu under the current menu to change the position of said box upwards, and perform the setting of the parameter ADD in the parameter setup menu. Exit the current menu and go to the previous menu, or cancel the value of the current setup parameter. Go to the next menu of the currently selected select box (go to the set state under the set interface, a nd exit the set state by double pressing the key). Move the box select menu under the current menu to change the position of said box downwards, and perform the setting of the parameter SUBTRACT in the parameter setup menu. Switch to the inquiry default menu (right arrow key, when it is necessary to move leftwards or rightwards for the set interface). Over current long time delay fault indication Short-circuit short-time delay fault indication Button for simulating instantaneous tripping test Short-circuit instantaneous fault indication Asymmetric grounding, neutral line fault indication
4 5 6
8 9 10 11 12 13
Ii limp Ig limp
C-57
> >>
NA8G
8.4 Default interface and menu structure for the multifunctional controller The multifunctional controller provides 4 title menus (measurement menu, parameter setup menu, protection parameter setup menu, and history record and maintenance menu) and 1 default menu.
C
Fifth menu
Ib= 5% Ic= 1%
Ia= 1000A Ib= 1000A Ic= 998A In= 0A Ia= 1050A Ib= 1040A Ic= 1010A In= 0A Reset(+/-)
Uab= 380V Ubc= 380V Instantaneous value Voltage U Mean value Unbalance rate Phase sequence FrequencyF 50Hz EP= 200kWh Total electric energy Electric energy E Input electric energy Output electric energy Electric energy reset EQ= 10kvarh ES= 200kVAh EP= 200kWh EQ= 200kvarh EP= 0kWh EQ= 0kvarh Reset Uca= 380V Uan= 220V Ubn= 220V Ucn= 220V Uav= 380V 0% A,B,C
> >>
C-58
NA8G
Primary menu Secondary menu Third menu P, Q, S Fourth menu P= 660kW Q= 0kvar S= 660kVA -1.00 Power factor Perceptual PFa= 1.00 PFb= 1.00 PFc= 1.00 Instantaneous value Pa, Qa, Sa Pa= 220kW Qa= 0kvar Sa= 220kVA Power P Pb= 220kW Pb, Qb, Sb Qb= 0kvar Sb= 220kVA Pc= 220kW Pc, Qc, Sc Qc= 0kvar Sc= 220kVA P= 660kW P, Q, S Required value Maximum Q= 0kvar S= 660kVA P= 661kW Q= 2kvar S= 662kVA Reset(+/-) Ia IaIb Harmonic H Waveform IcIn Ib Ic In Uan UanUbn Ucn Ucn Ia= 1000A I(A) Ib= 1000A Ic= 1000A In= 1000A Base form U(V) Uab= 380V Ubc= 380V Uca= 380V Uan= 220V Ubn= 220V Ucn= 220V Ia= 0.0% I(%) Ib= 0.0% Ic= 0.0% In= 0.0% THD U(%) Uab= 0.0% Ubc= 0.0% Uca= 0.0% Uan= 0.0% Ubn= 0.0% Ucn= 0.0% Ia= 0.0% thd I(%) Ib= 0.0% Ic= 0.0% In= 0.0% Ubn Fifth menu
C-59
> >>
NA8G
Primary menu Secondary menu Third menu Fourth menu Uab= 0.0% Ubc= 0.0% thd U(%) Uca= 0.0% Uan= 0.0% Ubn= 0.0% Ucn= 0.0%
Ia FFT THD=0.0%
Fifth menu
Ia(3, 5, 7...31)
0.0%
3 5 7 9 11...31)
Ib FFT THD=0.0%
0.0%
3 5 7 9 11...31)
Ic FFT THD=0.0%
0.0%
3 5 7 9 11...31)
In FFT THD=0.0%
0.0%
3 5 7 9 11...31)
3 5 7 9 11...31)
0.0%
3 5 7 9 11...31)
3 5 7 9 11...31)
Uca(3, 5, 7...31)
0.0%
3 5 7 9 11...31)
Current protection
> >>
C-60
NA8G
Primary menu Secondary menu Third menu Definite-time limit Short-time delay Inverse-time limit Instantaneous Operating current Operating current Ground protection Current protection Grounding alarm Delay time Coefficient of earthing Starting current Starting time Return current Return time Leakage protection Operating current Setup delay time Starting current Electric leakage alarm Starting time Return current Return time Executive mode Unloading value 1 Load Monitoring Unloading time 1 Unloading value 2 Unloading time 2 e.g. =I the first method e.g. =800A e.g. =50%tr e.g. =700A e.g. =25%tr Executive mode Startup value Under voltage Starting time Return value Return time Executive mode Startup value Voltage protection Over voltage Starting time Return value Return time Executive mode Startup value U unbalanced Starting time Return value Return time e.g. =Alarm e.g. =200V e.g. =0.2s e.g. =320V e.g. =60.0s e.g. =Alarm e.g. =480V e.g. =1s e.g. =400V e.g. =60.0s e.g. =Alarm e.g. =10% e.g. =1s e.g. =5% e.g. =60.0s Delay time e.g. =10000A=10.0In e.g. =200% e.g. =800A e.g. =0.4s e.g. =6.0 e.g. =600A e.g. =0.1s e.g. =100A e.g. =0.1s e.g. =8.0A e.g. =0.75s e.g. =5.0A e.g. =0.1s e.g. =4.0A e.g. =0.1s Fourth menu Operating current Fifth menu e.g. =5000A=5.0Ir e.g. =0.1s e.g. =2000A=2.0Ir e.g. =C10.Is@6Ir
C-61
> >>
NA8G
Primary menu Secondary menu Third menu Fourth menu A phase short-circuit definite-time limit T= 0.4s I= 4300A
15:28:25 5/30 Ia= 4300A Ib= 4200A Ic= 4000A In= 150A Di input alarm Di1 2004/07/16 20:38:45 ...... Under voltage alarm Umax= 0V 2004/06/20 22:29:40 local switch on 2002/06/18 9:30:56 ...... Test tripping 2002/06/15 10:30:20
Fifth menu
Tripping record
e.g.
1 DI (for) DI input alarm 2004/07/16
Alarm logging
......
Notes: a. The actual menu will very depend on the function selected by the user. b. The controller starts screensaver automatically 10min later. 8.5 List of the controller functions Standard configuration
Standard type (M type) 1.Quadruple over current protection (for overload, short-time delay time, instantaneous, grounding); grounding corresponds to vector sum (T type); 2.Parameter setup: fixed value setting position setting function 3.Current measurement 4.Test function; 5.Fault recording function: 8 times of failures can be recorded; 6.Self-diagnostic function; 7.MCR make/break function; 8.Human-machine interface: 3322 LCD; 9.Heat capacity measurement Multifunction type (H type) 1.Quadruple over current protection (for overload, short-time delay time, instantaneous, grounding); grounding corresponds to vector sum (T type); 2.Parameter setup: fixed value keyboard setting function; 3.Current measurement function; 4.Current unbalance rate measurement function; 5.Two test functions: (1)Instantaneous tripping test simulated on the panel; (2)Triple over current, grounding/leakage and operating time tests simulated by software; 6.Fault recording function: 8 times of failures can be recorded; 7.Self-diagnostic function 8.MCR make/break function 9.Communication function: MODBUS protocol; 10.Alarm logging function; 11.Recording number of operations; 12.Contact wear 13.Position changing record 14.Human-machine interface: 2843 LCD; 15.Heat capacity measurement
> >>
C-62
NA8G
Heat capacity measurement
Standard type (M type) Multifunction type (H type) P Function 1.Voltage measurement; 2.Voltage unbalance measurement; 3.Frequency measurement; 4.Phase sequence measurement; 5.Electric energy measurement; 6.Power measurement; 7.Power factor measurement; 8.Earth-current grounding protection; 9.Leakage protection; 10.Load monitoring function; 11.Quadruple D0 output function; 12.DI input function; 13.Regional interlocking function; 14.Under and over voltage protection; H Function 1.Voltage measurement; 2.Voltage unbalance measurement; 3.Frequency measurement; 4.Phase sequence measurement; 5.Electric energy measurement; 6.Power measurement; 7.Power factor measurement; 8.Earth-current grounding protection; 9.Leakage protection; 10.Load monitoring function; 11.Quadruple DO output function; 12.DI input function; 13.Regional interlocking function; 14.Under and over voltage protection; 15.Measurement of harmonic current; 16.Neutral phase protection
None
8.6 Characteristic parameters of the standard type intelligent controller Over current protection characteristics
10000 5000
IR=(0.4-1)In
TR=(1~30)s
T(s)
10
I2t ON
5 2 1
Isd=1.5~10IR
0.5 0.2 0.1 0.05 0.02 0.01 0.2 0.3 0.5 0.6 0.8 1 2 3 4 5 8 10 20 30 40 50 60 80
Ii=2~15)In
1.5
4 5
8 10
20
30
X IR
T(s)
10 5 2 1 0.5 0.2 0.1 0.05 0.02 0.01 0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 10 20 30 I2 t OFF I2 ON
X In
C-63
> >>
NA8G
8.6.1 Over current long time delay characteristic
Rated current range IR Error
Operating time tR(s) No actuation within 2h 1h and then actuate 16 9 1 32 18 2 64 36 4 128 72 8 192 108 12 256 144 16 320 180 20 384 216 24 480 270 30
(0.4~1)In
10%
15%
Explanation for parameter setting Long-time delay operating current adjustable: IR=(0.4-0.5-0.6-0.7-0.8-0.9-0.95-0.98-1)In, and there are nine settings for option. The long-time delay tripping time represents the inverse-time limit characteristic, and nine optional settings are readily available for tripping time in case of 6IR: tR=(1-2-4-8-12-16-20-24-30)s. For setting, insert a small slotted screwdriver to the knob groove as shown in the right drawing, gently turn it to make the arrow of the knob point at the current and time set as required. As shown in the figure, the over current long time delay protection current setting value IR=0.6Inand the delay tripping time is 2s (in the condition of 6IR).
IR
8 . 9 . 7 . . 95 . 6 . 98 . 5 . 4 1 In
tR (s) 4 2
8 12 16 20 24 1 30 a 6IR
Example 1: If it is known that in condition of I=6IR, the tripping time setting value is 2s, and now the line current I=1.5IR, then the actual tripping time TR can be worked out by: (1.5IR)2TR=(6IR)22. The answer is obtained as TR=32s.
Operating time tsd(s) No actuation Time-delay action 0.1 0.2 0.3 0.4 0.1 0.2 0.3 0.4 anti-time-limit delay:I Tsd=(10IR) tsd
2 2
15%
I 2t ON I 10IR I 2t ON I10IR
15%
Explanation for parameter setting The short-circuit short-time delay protection operating current adjustable: Isd=(1.5-2-2.5-3-4-5-6-8-10)IR, and there are nine settings for option. There are nine settings for the short-time delay tripping time, wherein 4 settings represent the definite-time limit characteristic (i.e., I2t OFF), 4 settings the inverse-time limit characteristic, and 1 setting the function of closing the short-time delay (X). When the tripping time is set as definite-time limit operating characteristic (i.e., the arrow points at the off area), the tripping time can be selected as tsd=0.1s-0.2s-0.3s-0.4s-x (i.e., the function of closing the short-time delay). When the tripping time is set as inverse-time limit operating characteristic (i.e., I2t ON), there are two cases: the case of I1.15Isd and I10IR represents the definite-time limit; the case of I1.15Isd and I10IR represents the inverse-time limit characteristic and the actual tripping time is calculated according to the formula I2Tsd=(10IR)2tsd, wherein I is the line current, Tsd the actual tripping time, and tsd the setting tripping time. The method for setting the current and time for the short-circuit short-time delay protection is similar to that for over current long time delay protection. As shown in the figure, the current for the short-circuit short-time delay protection is 3IR, and the tripping time is set as tsd=0.2s in the setting position of inverse time limit (I2t ON).
Isd 3 4 5 2.5 2 1.5 IR tsd (s)
6 8 10
4 . 4 . . 3 . 3 . 2 . 1 . 2 X . 1 ON OFF 2 It
Example 2: If it is known that the short-time delay setting current is Isd=3IR, then the tripping time is set as tsd=0.2s in the setting position of inverse time limit (I2t ON). Now the current is 7IR in the line current, then the short-time delay tripping time can be worked out by calculation: 1.5Isd=1.153IR=3.45IR Then I=7IR1.15Isd And because I=7IR10IR So according to I2Tsd=(10I)2tsd (7IR)2Tsd=(10IR)20.2 Tsd=0.41s
> >>
C-64
NA8G
8.6.3 Short-circuit instantaneous protection
Rated current range Ii Error
15%
Explanation for parameter setting The instantaneous protection operating current is adjustable: Ii=[2-3-4-6-8-10-12-15-OFF]In, and there are nine settings for option. The method for setting the current for the instantaneous protection is similar to that for over current long time delay protection setting. As shown in the figure, the instantaneous protection current setting value is 8In. 8.6.4 Single-phase grounding fault protection
Rated current range Ig Error Line current I 0.9Ig 1.1Ig (A~J)In +OFF(Power off) I 2T OFF 10% I 2T ON IJ I T ON IJ
2
Ii
6 4 3
2
10 12 15 Off
Operating time tg(s) no-action time - delay action 0.1 0.1 0.2 0.2 0.3 0.3 0.4 0.4
2 2
15%
anti-time-limit delay I Tg = ( J ) tg
Explanation for parameter setting The single-phase grounding protection operating current is adjustable: Ig=(A-B-C-D-E-F-G-H-J)In, and there are nine settings for option. There are nine setting positions for the protective delay tripping time, wherein 4 settings represent the definite-time limit characteristic (i.e., I2t OFF), 4 settings the inverse-time limit characteristic (I2t ON), and 1 setting the function of closing the grounding protection (X). When the tripping time is set as definite-time limit operating characteristic (i.e., the arrow points at the OFF area), the tripping time can be selected as tg=0.1s-0.2s0.3s-0.4s-x (i.e., the function of closing the grounding protection). When the tripping time is set as inverse-time limit operating characteristic (i.e., I2t ON), there are two cases: in the case of I1.1Ig and IJ, the result of the automatic changeover process is the definite-time limit operating characteristic, tg=0.1s-0.2s-0.3s-0.4s; The case of the current meeting the condition of 1.1IgIJ represents the inverse-time limit characteristic and the actual tripping time is calculated according to the formula I2Tg=(J)2tg. In the formula, I is the line current, Tg the actual operating time, J the setting current, and tg the setting tripping time. The method for setting the parameter is similar to that for over current long time delay protection. As shown in the figure, the grounding protection current is CIn and the tripping time setting is tg=0.4s in the setting position of inverse time limit (I2t ON) .
Ig
D C B
F G H
Tg (s)
J
ON
In
4 . 4 . . 3 . 3 . 2 . 1 . 2 X . 1 Off 2 It
Example 3: If it is known that the grounding fault protection setting current for the intellectual controller with a rated current of In=800A is as the setting position of C, the tripping time is set as the inverse time limit 0.4s. Now there is a failure in the circuit, the line current I=400A, then the actual tripping time can be worked out; it can be seen from the table that the result is C=0.4 Ig=CIn=0.4800=320A So I=400A1.1Ig 2 2 According to the formula I Tg=(J) tg (400)2Tg=(1.0800)20.4 Tg=1.6s Note: For the intellectual controller, the current settings for the long- and the short-time delay and the instantaneous protection should not come across each other, and the condition of IRIsdIi must be ensured.
C-65
> >>
NA8G
8.7 Explanation for auxiliary functions a. Explanation for test functions When onsite adjustment, periodical inspection or overhaul is made with the controller supported by the breaker, breaking several times is necessary by using the test functions of the controller to check the cooperation of the controller and the breaker. With the breaker on, press the T key, and the intellectual controller will trip instantaneously to cut off the breaker. Note: This function can be used only when onsite adjustment or overhaul for the breaker is made, and shall not be used during the normal operation. Each time before the controller is switched on, it is necessary to press the reset button in the upper position of the controller panel so that the breaker can be switched on again for operation. b. Explanation for fault memory The controller still has the function of fault memory after reset or de-energized to keep a latest historical event for post analysis. Only when there is a new fault again, the original information is cleared with the current latest faulty data saved. For the inquiry method, refer to the above explanation about fault display 8.8 Explanation for display function When the rated current is greater than or equal to 400A, the primary current shall not be lower than 0.4In for single phase and 0.2In for three phases for normal operation of the breaker. When the rated current is less than 400A, the primary current shall not be lower than 0.8In for single phaseand 0.4In for three phases for normal operation of the breaker. Note: When the AC220V ST power module is energized, and the voltage falls to AC120V, there will be no display on the controller When the AC380V ST power module is energized, and the voltage falls to AC200V, there will be no display on the controller a. Current display Error range for current display: 5% b. Voltage display Error range for voltage display: 1.5%
9. Accessories
9.1 Under voltage release When the under voltage release is not energized, neither power-driven nor manual operation can make the breaker on. For the under voltage release, there are two varieties: instantaneous and time delay operations. The time for the under voltage time delay release is Inm=1600A, the time can be selected from but not adjusted in the range of 0 7s; Inm=3200A or 6300A, the time can be selected from and adjusted among 0.5s, 1s, 3s, and 5s. When, within 1/2 delay time, the power voltage returns to 85%Ue or above, the breaker will not get disconnected. Operating characteristic:
Rated operational voltage Ue(V) Operating voltage(V) Reliable switching voltage(V) Reliable not-switching voltage(V) Power consumption(W) AC230 AC400 (0.35~0.7)Ue (0.85~1.1)Ue 0.35Ue 20VA Under-voltage release (Inm=1600A) Under-voltage release (Inm=3200A, 6300A)
9.2 Shunt release After the shunt release is energized, the breaker is switched off instantaneously to allow remote operation. Operating characteristic:
Rated control supply voltage Us(V) Operating voltage (V) Power consumption (W) Breaking time AC230 AC400 (0.7~1.1)Us 200VA 5010ms 200W DC220 DC110 Shunt release (Inm=1600A) Shunt release (Inm=3200A, 6300A)
9.3 Closing electromagnet After the motor energy storage is ended, energizing the closing electromagnet will make the energy storage spring force of the operating mechanism to be released instantaneously to rapidly switch the breaker on. Operating characteristic:
Rated control supply voltage Us(V) Operating voltage (V) Power consumption (W) Closing time AC230 AC400 (0.85~1.1)Us 200VA 5010ms 200W DC220 DC110 Closing electromagnet (Inm=1600A) Closing electromagne (Inm=3200A, 6300A)
> >>
C-66
NA8G
9.4 Power operating mechanism The functions of motor energy storage and automatic energy re-storage after the breaker comes on are available to ensure that the breaker can come on immediately after it gets disconnected. Operating characteristic:
Rated control supply voltage Us(V) Operating voltage (V) Power consumption (W) Energy storage time Frequency of operation AC230 AC400 (0.85~1.1)Us 75/150VA 4s At most 3 times in a minute DC220 DC110 75/150W
(Inm=1600A)
(Inm=3200A, 6300A )
9.5 Auxiliary contact (with a common point) 4 groups of changeover contacts (2 N.O. and 2 N.C.) are provided for the standard form of auxiliary contacts, and 6 groups of changeover contacts (3 N.O. and 3 N.C.) for the special form (Inm=1600A not available for DC). Technical parameters:
Rated voltage(V) AC DC 230 400 220 Rated thermal current Ith(A) 6 6 Rated control capacity 300VA 60W
(Inm=1600A)
(Inm=3200A, 6300A )
9.6 Separator between phases The separator is installed between the phases of the line bank to improve the insulating ability between the phases of the breaker. 9.7 Key lock The OFF pushbutton of the breaker can be locked in the position of depress, and at this time, the breaker cannot be closed for operation; after the user selects the option, the factory provides locks and keys; one breaker is provided with one independent lock and one key for the one lock; two breakers, two independent locks and one key for the two locks; three breakers, three same locks and two same keys for the three locks. Note: a.For the air circuit breaker with key interlock, when the key has to be pulled out, it is necessary to first press the OFF key, turn the key anticlockwise, and then pull out the key. b.The key for the 1600 does not work for the 3200 and 6300 shell breakers and vise versa, so be on guard against the distinction between them. 9.8 Pushbutton lock It is used to lock the button for opening and closing the breaker with the padlock used for such a purpose. (Padlocks to be provided by users themselves) 9.9 Door frame and lining pad They are installed on the door of the distribution cabinet room to seal it with a protection level of up to IP40. 9.10 Drawer type of air circuit breaker separation position locking device For the separation position of the open frame (draw-out) circuit breaker, a lock rod can be pulled out to lock the matter, and the breaker locked will be unable to be turned towards the TEST or CONNECTION position. Padlocks have to be provided by users themselves. 9.11 The drawer type of air circuit breaker about any working position locking device After the breaker body is locked automatically in any working position, it is necessary to turn the key to unlock the matter so that the break body can be moved to the next working position by turning the handle. (this function available for 3200 to 6300). 9.12 Interlock with the door Interlock with the door for the break status When the breaker is closed, the cabinet door must not be opened; when the breaker is switched off, the cabinet door is allowed to be opened. Interlock with the door for the breaker position When the breaker is in the position of connection and test, the cabinet door must not be opened; when the breaker is the separation position, the cabinet door is allowed to be opened. 9.13 Mechanical interlock Steel cable interlock for two breakers placed horizontally or joint rod interlock for two superimposed breakers.
C-67
> >>
NA8G
10. Installation
10.1 Following items to be checked before installation Check the label plate on the breaker panel to see if it is conform to the specifications of the ordered goods. a.Rated current b.Under voltage release voltage and delay time c.Shunt release voltage d.Closing electromagnet voltage e.Motor voltage 10.2 Before installation, operation, maintenance and inspection, you shall read this manual, and consult the manufacturer for questions, if any. 10.3 Preparations before installation Before the breaker is installed, check the insulation resistance of the breaker by using a 1000V megohmmeter according to regulations; when the surrounding media temperature is 255 and the relative humidity 50% - 70%, the insulation resistance shall not be less than 20 megohm. The place with the insulation resistance to be tested includes: the place between various phases and between various phases and the frame when the breaker is closed; the place between in- and out- lines of various phases. 10.4 Installation of the fixed type breaker Place the breaker into the distribution cabinet, and fasten it by using 4 pieces of M6(In=1600A) or M10(In=3200A or more) bolts and washers. The breaker shall be installed stably with no additional mechanical stress to avoid damage of the breaker or bad contact of the main bus bar. 10.5 Installation of the open frame (draw-out) circuit breaker Take the breaker body out of the draw-out socket, and install the socket in the distribution cabinet, and fasten it by using 4 pieces of M6(In=1600A) or M10(In=3200A or more) bolts and washers; the breaker shall be installed stably with no additional mechanical stress to avoid damage of the breaker or bad contact of the main bus bar. After the work is completed, mount the body into the draw-out socket. 10.6 The specifications of the wiring copper bars for the primary circuit of the breaker shall meet the copper bar specifications used under the conditions of conventional heating in IEC/EN 60947-2 10.7 The breaker shall be grounded substantially.
Under voltage release Tripping Mechanical interlock action Under voltage release No attracting Reset button fails to reset 2 Breaker fails to close
Open frame (draw-out) circuit breaker f ails to be put to the right position by rocking Open frame (draw-out) circuit breaker Bad contact for the secondary circuit Breaker fails to pre-store energy
1 Check the motor control power supply and see if it is well providing power, and the voltage must be 85%Us 2 Check the status of the motor energy storage mechanism.
Put the open frame (draw-out) circuit breaker to the right position by rocking (with it locked in the connection position) 1 Check the power voltage of the closing electromagnet, and it must be higher than or equal to 85%Us 2 If there is any trouble in the closing electromagnet to enable the attracting, it shall be replaced.
> >>
C-68
NA8G
No.
Technical problems
Possible causes
1 There may be short circuit current when the matter is switched on, and in this case you shall find and shoot the trouble 2 Check to see if there is any overload current in the circuit, find and shoot the trouble, if any 3 Check the setting value of the intellectual controller for reasonability, and a re-setting process is necessary if not reasonable 4 Press the reset button to close the breaker again 1 Check the shunt release circuit for reliable connection and the shunt release for trouble, and the release shall be replaced if the fault is confirmed 2 Check he operating mechanism for mechanical fault. 1 Check the motor energy storage mechanism control power voltage, and the voltage shall be 85%Us; check the status of the circuit connection 2 Check the motor Energy storage mechanism malfunction Pull out the rock rod
The breaker fails to open in power-driven mode The breaker fails to open in manual mode
Breaker fails to be pulled out when the open frame (draw-out) circuit breaker is in the SEPARATION position Open frame (draw-out) circuit breaker fails to be put to the CONNECTION position by rocking
Rock rod fails to be pulled out Put the breaker completely Breaker fails to completely reach the SEPERATION position to the SEPERATION position by rocking The "drawer has seized up for foreign matters fall in it; Check it for foreign matters and for condition damage in the mechanism for putting in by rocking or the of the rack and gear Turn the key on the drawer to unlock the matter gear thereof; Position locking device fails to be unlocked Intellectual controller fails to be energized by power supply: 1 Check to see if the intellectual controller power supply is well be connected and works well Improper input voltage for the auxiliary power supply 2 Cut off the intellectual controller control Improper secondary output voltage for the transmitter power supply, and then connect the power supply; Unreliable connection between the secondary output If the fault is still present, there may be some terminal of the transmitter and the controller troubles in the controller which has to be replaced
C-69
> >>
NA8G
12. Specifications for ordering
User Type and size Rated current (In)A NA8G-1600 200 400 630 800 1000 1250 1600 Vertical connection Order amount Order date NA8G-3200 1600 2000 2500 2900 3200 Front connection Tel NA8G-6300 4000 5000 6300(dont have 4P)
Fixed type (no such products for over 4000A) mixed connection (connection mode to be noted) 4P
Factorys setting values: IR=1In, 2s(6IR); Isd=8IR, inverse-time limit 0.4s; Ii=12In; In1200A Ig=800A; In1200A Ig=DIn, OFF If the user has some requirements different from the defaulting, please write the numerical values on the line below Long-time delay protectionIR Setting of the protection Intelligent controller parameter hort-circuit instantaneous protectionIi Ground protectionIg Selecting the type Power input Basic function Optional function (this function to be added as required by the user, and to be matched with the controller type) Standard type AC400V AC230V DC220V Short-circuit short-time delay protectionIsd Operating current setting______In (0.4,0.5,0.6,0.7,0.8,0.9,0.95,0.98,1) Operating time setting______s (1,2,4,8,12,16,20,24,30) Operating current setting______IR (1.5,2,2.5,3,4,5,6,8,10) Operating time setting inverse time______s (0.1,0.2,0.3,0.4,OFF) Operating current setting______In (2,3,4,6,8,10,12,15,OFF) Operating current setting______In See Manual, p. 24 Operating time setting inverse time______s Definite-time limit______s Multifunctional type DC110V DC24V Voltage measurement
Three-section protection against over current Neutral line or grounding fault protection Test function Fault inquiry/memory function Self-diagnostic function
Over voltage protection Under voltage protection Over frequency protection Under frequency protection Voltage unbalance measurement Phase sequence protection Voltage measurement Frequency measurement Measurement of harmonic current Power factor measurement Power measurement Phase sequence detection Voltage unbalance rate measurement Electric energy measurement Contact equivalent Power network history parameter recording function MCR make/break function Load monitoring function Signal contact output function Communication function ZSI regional interlocking protection
Note: when the product is a multifunctional controller as arranged by the user, the communication function and the like are the basic function configuration Accessories for standard configuration Under voltage release Shunt release Energy storage motor Auxiliary contact OFF locking device Instantaneous Time delay______s (1-2-3-4-5-6-7s provided for the 1600 shell, optional but not adjustable; 0.5-1-3-5s for the 3200 and 6300 shell, optional and adjustable) AC400V AC230V AC400V AC400V AC230V AC230V AC230V DC220V DC220V DC220V DC110V DC110V DC110V
2 NO and 2 NC
One breaker is provided with one lock and one key Two breakers is provided with two same locks and one key (the same key/lock not available for the 1600 and 3200/6300 shell breakers) Three breakers is provided with three same locks and two keys (the same key/lock not available for the 1600 and 3200/6300 shell breakers) Two-breaker interlock solution Steel cable interlock Joint rod
Mechanical interlock
Three-position locking device for the draw-out socket Door interlock Door frame Auxiliary power module
Note: Extra costs are needed for the optional functions, optional accessories and the like for the breaker.
> >>
C-70
NA1
11
7 8
12
13
14
15 3
C-71
> >>
NA1
9
6
10
7 8 9
10 Connecting-rod type mechanical interlock 11 Shunt release 12 Closing electromagnet 13 Under-voltage release 14 Motor-driven energy-storage mechanism 15 Rotary handle 16 Fixed plate
2 6
16
> >>
C-72
NA1
NA1-1000
200A to 1000A
NA1-2000
630A to 2000A
Summary
5 basic frame sizes
For your various requirements, the Air Circuit Breaker NA1 includes 5 basic frame sizes as followed.
NA1-3200, 4000
2000A to 4000A
NA1-6300
4000A to 6300A
C-73
> >>
NA1
1. General
1.1 Application scope NA1 series air circuit breaker is suitable for the circuit of AC 50Hz/60Hz with rated service voltage 400V, 690V and rated service current up to 6300A. It is mainly used to distribute electric energy and protect circuits and electric equipment against over-load, under-voltage, short-circuit and single-phase earthing fault. With intelligentized and selective protection functions, the breaker can improve the reliability of power supply, and avoid unnecessary power failure. The breaker is applicable for power stations, factories, mines (for 690V) and modern high-buildings, especially for the distribution system of intelligentized building. 1.2 Standard: IEC/EN 60947-2. 2.6 Type designation NA1 - - / ---- Voltage of secondary circuit AC220V, AC380V, AC230V, AC400V DC220V, DC110V Wiring of main circuit: H:Horizontal wiring of main circuit V:Vertical wiring of main circuit Mode of installation: F:Fixed type D:Draweout type Mode of operation: M:Manual P: Power-driven No. of poles: 3:3-pole 4:4-pole Intelligent controller: M: Standard type 3M: Multifunctional type 3H: Communication type Rated current:
Frame size rated current Rated current 200A 400A 1000A 630A 800A 1000A 630A 800A 2000A 1000A 1250A 1600A 2000A 3200A 4000A 4000A 6300A 2000A 2500A 3200A 4000A 4000A 5000A 6300A
2. Operation conditions
2.1 Temperature condition: -5~40; the average value within 24h shall not exceed +35 (special situation excluded); 2.2 Altitude:2000m; 2.3 Pollution grade: Grade 3; 2.4 Air conditions: At mounting site, relative humidity not exceed 50% at the max temperature of +40, higher relative humidity is allowable under lower temperature, RH could be 90% at +20 , special measures should be taken to occurrence of dews; 2.5 Note: Without the intelligent controller, the breaker functions as a switch-disconnector.
Frame size rated current: 1000A, 2000A, 3200A,4000A, 6300A Design sequence number ACB Company code
> >>
C-74
NA1
3. Structure
+
Drawer seat Body Drawout type breaker/switch-disconnector
Fixed plate for the fixed type breaker Fixed type breaker/switch-disconnector
Enclosure
Under-voltage release
Locking device
Intelligent controller
C-75
> >>
NA1
4. Main technical parameter
Type NA1-1000
Rated ultimate short circuit breaking capacity Rated service short circuit breaking capacity Rated short-time withstand current Rated current In (A)
200 400
Icu=42kA Ics=30kA
400V 400V
25kA 20kA
690V 690V
Number of poles Rated voltage Ue (V) Rated insulation voltage Ui (V) Rated current of N-pole In (A)
Fixed disconnection time (ms)
Intelligent controller
Operation performance
Connection pattern
Motor operational standard configuration weight (kg)
Standard configuration: M type intelligent controller; Under-voltage release; Shunt release; Motor-driven energy-storage mechanism
Type
NA1-2000
Rated ultimate short circuit breaking capacity Rated service short circuit breaking capacity Rated short-time withstand current Rated current In (A) 630 800
Icu=80kA Ics=50kA
400V 400V
50kA 40kA
690V 690V
Number of poles Rated voltage Ue (V) Rated insulation voltage Ui (V) Rated current of N-pole In (A) Fixed disconnection time (ms) Intelligent controller Operation performance Connection pattern
Motor operational standard configuration weight (kg)
Standard type (M) Communication type (H) Electric life Mechanical life 5000 Non-maintenance 10,000 Maintenance 20,000
Horizontal, Vertical Drawout 3P/4P Fixed 3P/4P 67.5 / 79.8 42.4 / 52 69.6 / 83.65 44 / 54 78.6 / 90.5 45 / 56
> >>
C-76
NA1
Type NA1-3200, NA1-4000
Rated ultimate short circuit breaking capacity Rated service short circuit breaking capacity Rated short-time withstand current Rated current In (A) 2000
Icu=80kA Ics=65kA
400V 400V
65kA 65kA
690V 690V
Number of poles Rated voltage Ue (V) Rated insulation voltage Ui (V) Rated current of N-pole In (A) Fixed disconnection time (ms) Intelligent controller Operation performance Connection pattern
Motor operational standard configuration weight (kg)
Standard type (M) Communication type (H) Electric life Mechanical life 5000 Non-maintenance 10,000 Maintenance 20,000
Horizontal, Vertical Drawout 3P/4P Fixed 3P/4P 90.5 / 116 54.8 / 68 90.5 / 116 54.8 / 68 102.8 / 131 56.5 / 86 132 / 172 85 / -
Standard configuration: M type intelligent controller; Under-voltage release; Shunt release; Motor-driven energy-storage mechanism
Type
NA1-6300
Rated ultimate short circuit breaking capacity Rated service short circuit breaking capacity Rated short-time withstand current rated current In (A) 4000
Icu=120kA Ics=100kA
400V 400V
85kA 75kA
690V 690V
Number of poles Rated voltage Ue (V) Rated insulation voltage Ui (V) Rated current of N-pole In (A) Fixed disconnection time (ms) Intelligent controller Operation performance Connection pattern
Motor operational standard configuration weight (kg)
Standard type (M) Communication type (H) Electric life Mechanical life 2500 Non-maintenance 5000 Maintenance 10,000
Horizontal, Vertical Drawout 3P/4P Fixed 3P/4P 202 / 236 -/202 / 236 -/236 / -/-
C-77
> >>
NA1
5. Dimensions and connection
NA1-1000 Drawout-type
216 34
268 226
362
101.5
85
358
304
316
Installation panel
5
91.5
16 105 A 158 323 65 Connected position Disconnected position Installation hole on right side
L1 L N 12 200,400A 35 70 70 70
45
27
n13 15
12
NA1-1000
35 n10.5
L1 194 264
18
3P 4P
In(A)
28.5
630,800, 1000A
A(mm) 32 50 50
200, 400
158
2-11.58.5
L1(3P)
L1(4P)
NA1-1000 Fixed-type
101.5
259
85
312
270
Installation panel
2
46.5
216 70 70
15
n13
12
35
53
n10.5
NA1-1000
12
L1
A(mm) 32 50 50
H(mm) 6 8 10
3P 4P
4-913
L1
144
> >>
C-78
NA1
NA1-2000 Drawout-type
45(Disconnected position) a
448(4P) 353(3P)
37.5 N pole 28 60 813
112
258
439
95
95
95
92.5
92
42.5
37
70
10
97
23
67
95
95
95
92.5
268
360(4P)
265(3P)
378
302
302
11
155
47 20
N pole
115
17
14
55
172
28 60 95 95
40
21117
30
14
N pole
30
60
14
In A 630 2000
a mm 10 20
187.5
800~1600 15
45(Disconnected position)
C Direction
413 28
353(3P)
60
122.5
95.5
10
97
175
14 438.5 55
21.5
37
10
70
258
439
155
In A
302
a mm 10 15 20
268
11 360(4P) 265(3P)
630
378
302
800~1600
2000
21117 14
47 20
C Direction
55 115 175 33 344 187.5 172
N pole
95
95
95
92.5
C-79
> >>
NA1
NA1-2000 Drawout-type, horizontal, rear connection
448(4P)
45(Disconnected position)
C Direction
353(3P)
258
122.5
95.5
37
439
10
97
175 438.5
C
a mm 10 15 20
In A
21.5
630
155
800~1600
302
360(4P)
268
11 265(3P)
2000
378
302
21117 14
47 20
C Direction
60 N pole 28 813 14 92.5 10 55 95 95 95
55
175
115 33 344
172 187.5
NA1-2000 Fixed-type
Zero arcing covering ferreous material 18min 413(4P) 318(3P) 292 a 115 402
42 N pole 28 60 813
95
95
95
86
112
258
55
17
21
14
N pole
67
30
60
N pole
32
28
60
813
50
69.5
60
13
181
340(3P) 435(4P)
95
95
95
86
30
95
95
95
86
311.2
In A
N pole 115 40
a mm b mm 10 20 17 17
18.5
269
412 150
630 2000
300
800~1600 15
28.5
17
85
340(3P) 435(4P)
Installation panel
3213 95
28 60 95 95
342.2
> >>
C-80
11
11
NA1
NA1-3200 Drawout-type
N Pole 100 50 25 125 92.5 100 1613
45(Disconnected position)
a
528(4P) 413(3P)
125
a
258 439
125
112
92
42.5
37
70
1613
50
491 536
37.5
10
97
175
23
217.5
125
125
125
92.5
155
11 440(4P) 325(3P)
268
21117 14
47 20
378
362
302
14
75
25
115
N Pole 40
In A 2000~2500 3200
a mm 20 30
55
175
115
33
404 217.5
17
202
3213 115
45(Disconnected position)
C Direction
813
528(4P) 413(3P)
50
100
10
97
175 40 94 495
20
100
126
439
a mm 20 30
21.5
2000~2500 3200
440(4P)
11 325(3P)
378
362
N pole a
C Direction
21117 14
47 20
55
175
115
33
C-81
> >>
NA1
NA1-3200 Drawout-type, horizontal, rear connection
528(4P)
413(3P)
258 42.5 37 70
107.5
112
439
10
97
217.5 495
21.5
In A 2000~2500
155
a mm 20 30
3200
302 378
440(4P)
11 325(3P)
268
362
21117 14
47 20
C Direction
20 N pole 50 40 125
92.5
100
55
175
33
404 217.5
1613
115 125
94
115
202
Installation panel
NA1-3200 Fixed-type
N pole 72
40
15 115
96
86
1613
a 115
402
115
258
115
112
55
N pole
21
50
50
69.5
60
11
13
32
115
115
115
96
115
N pole 40
40
In A 2000~2500 3200
a mm 20 30
362 150
15
412
269
311
28.5
3213
Installation hole on
Installation panel
400(3P) 515(4P)
404
> >>
C-82
NA1
NA1-4000 Fixed-type (3P)
18min
493
15 15
120 40 134
10
352
30
130
402
Horizontal
258
112
55
130
50
515
13
150
69.5
11
11
21
175
40
412 269 362 150
28.5
311
17
50 2415 140
2
85 515
202 404
207.5
207.5
Vertical
30
258
112
92
42.5
10
97
21.5
37
70
439
11
268
155
20
302
440
20
378
362
1213 50 140
21117 14 55
47
175
115
103
33
197.5
197.5
77.5
C-83
> >>
40
40
NA1
NA1-4000 Drawout-type (4P)
45(Disconnected position)
C Direction
756
20
112
42.5 70
92
258
439
187.5 292
490 788
21.5
11 268 302
155
302
C Direction
378
40 N Pole 155 20 1613
678
21117
103
14 55
47
20
175
115 33 344
172
187.5
45(Disconnected position)
903(4P) 798(3P)
30
258
37
10
97
175
112
42.5
37
92
217.5
10
97
175 494
813(3P) 928(4P)
352
21.5
155
268
818(4P)
378
11 703(3P)
362
302
N Pole 100
70
439
20
14 55
115
47
21117
175
33
103
40
> >>
C-84
NA1
NA1-6300 (In=6300A) Drawout-type (3P)
45(Disconnected position)
903
30
92
112
10
97
175 494
21.5
11
268
155
70
180
302 378
439
260 20
362
818
21117 14 55
47
20
2415
202 404 217.5
103
40
175
115
33
C-85
> >>
NA1
6. Secondary circuit wiring
6.1 NA1-1000 Standard type, type (M)
Main circuit
Intelligent controller
Auxiliary contact
Emergency break
Motor-driven energy-storage
Auxiliary contact
TA FU
1 2 4 6 8 10 11 12 13 16 18 20 22 24 26 28 30 32 34 36 38 40 XT
Hl1: Failure indicator HL2: Close indicator HL3: Energy storage indicator SB1: Under-voltage button SB2: Shunt button SB3: Close button Q: Under-voltage release F: Shunt release X: Close electromagnet M: Energy storage motor DF1-F4: Auxiliary switch 1#, 2#: Auxiliary power input(DC24V) 3#,4#,5#: Fault trip contact output(4# common terminal, contact capacity AC230V,5A 6#,7#: To be connected with current transformer(selective)
Note:
Dashed is to be connected by users.
3 5 7 9 14 15 17 19 21 23 25 27 29 31
33 35
37
39 XT
FU
Intelligent controller
DF1 DF2 DF3
DC24V
Power module
8#,9#: Making indicator (capacity AC400V,1A) 10#: Over-current pre-alarm signal output (selective) # 11 : Short current trip signal output (selective) 12#: Earthing trip alarm output (selective) 13#: Self-checking alarm signal output (selective) # 14 : Common line of different contacts 15#: Earthing protection line 16#,17#: Normal contact of the controller (contact capacity AC400V 1A) 27#,28#: Under-voltage release 29#,30#: Shunt release # # 31 ,32 : Closing electromagnet # 33 ,34#,35#: Energy storage motor 18#~26#, 38#~40#: Auxiliary contact (auxiliary contact capacity: AC230V,5A)
> >>
C-86
NA1
Communication type, type (H)
Main circuit
L1 N PE FU
Intelligent controller
Emergenay break
Motor-driven break
Motor-driven make
Auxiliary switch
PE
HL3
12 13
14 15
16 17
18 19
12 13
14 15
16 17
TA
Hl1: Failure indicator HL2: Close indicator HL3: Energy storage indicator SB1: Under-voltage button SB2: Shunt button SB3: Close button Q: Under-voltage release F: Shunt release X: Close electromagnet M: Energy storage motor DF1-F4: Auxiliary switch 1#, 2#: Auxiliary power input(DC24V) # # # # 3 ,4 ,5 : Fault trip contact output(4 common terminal, contact capacity AC230V,5A 6#, 7#: To be connected with current transformer(N/O auxiliary contact, capacity AC400V, 1A,when no current transformer)
Note:
Dashed is to be connected by users.
C-87
3
Intelligent controller
1 2 4 6 8
21
23
25
27
29
31
33
35
37
39 XT
DF1
DF2
DF3
SA
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40 XT
DC24V
Power module
8#,9#: Making indicator(capacity AC400V,1A) 10#, 11#: communication output # # 12 , 13 : Signal alarm of load 1 output # 14 , 15#: Signal alarm of load 2 output 16#, 17#: Making signal output # # 18 , 19 : Closing signal output 20#: Communication shield ground line 21#~24#: Voltage signal input of phase N,A,B,C # # 25 , 26 : Auxiliary contact (capacity:AC230V,5A) 27#,28#: Under-voltage release 29#,30#: Shunt release # # 31 ,32 : Closing electromagnet # 33 ,34#,35#: Energy storage motor 36#~40#: Auxiliary contact (capacity:AC230V,5A)
> >>
NA1
3NO(normal open) 3NC (normal close) standard type (M)
Main circuit
Intelligent controller
Auxiliary contact
Motor-driven energy-storage
Auxiliary contact
14
15
17
19
21
23
25
27
29
31
33
35
37
39 XT
TA FU
1 2 4 6 8 10 11 12 13 16 18 20 22 24 26 28 30 32 34 36 38 40
DC24V
Hl1: Failure indicator HL2: Close indicator HL3: Energy storage indicator SB1: Under-voltage button SB2: Shunt button SB3: Close button Q: Under-voltage release F: Shunt release X: Close release M: Energy storage motor DF1-DF4: Auxiliary switch 1#, 2#: Auxiliary power input(DC24V) # # # # 3 ,4 ,5 : Fault trip contact output(4 common terminal,contact capacity AC230V,5A 6#, 7#: to be connected with current transformer(selective)
Note:
6NO(normal open) 6NC(normal close), without any additional function. Dashed is to be connected by users.
FU
Q
Intelligent controller
M
Power of control circuit
DF5
DF6
DF1
DF2
DF3 DF4
SA
XT
Power module
8#,9#: Making indicator (capacity AC400V,1A) 12#~26#: Auxiliary contact(auxiliary contact capacity: AC230V,5A) 27#,28#: Under-voltage release 29#,30#: Shunt release 31#,32#: Closing release 33#,34#:Energy storage indicator 34#,35#: Energy storage motor 38#~40#: Auxiliary contact(auxiliary contact capacity: AC230V,5A)
> >>
C-88
NA1
6.2 NA1-2000~6300 The secondary circuit wiring for NA1-2000~3600 with standard type (M) intelligent controller and instantaneous under-voltage release
Main circuit
Over-current release
Emergency break
Auxiliary contact
SB2
Failure
3 5 7 9 11 13 15 17 19 21 23 25 27
SB1 SB3
29
Energy storage
36 38 40 42 44 46 48 50
31 33 35
FU
Q F X M
AX
SA
Power
Processing unit
Intelligent Controller
FU
37 39 41 43 45 47 49 51
10
12 14 16 18 20 22 24
26 28
30
32
34
Open
Close
_ 110V ~ _ 220V Intelligent release power ("1" connect positive pole, and "2" connect negative pole for direct current) ~
~380V
37
39
41
43
45
47
37
39
41
43
45
47
49
SB1: Shunt button SB2: Under-voltage button SB3: Making button Q: Under-voltage release F: Shunt release X: Closing electromagnet M: Energy storage motor XT: Connection terminal SA: Position switch Note: If control voltage of Q, F, X is different from each other, they can be connected to different power. # # 1 ,2 : Auxiliary power input # # # 3 ,4 ,5 : Fault trip contact output(4# common terminal) # # # # 6 ,7 ,8 ,9 : Auxiliary contact, normal open, # # 10 ~24 : empty # # 25 ,26 : to be connected with current transformer(selective) # # 27 ,28 : Under-voltage release # # 29 ,30 : Shunt release # # 31 ,32 : Closing release # # 33 ,34 : Energy storage indicator # # 34 ,35 : Energy storage motor # # 36 ,51 : Auxiliary contact
Circuit explanation for signal output: a. Broken-line parts shall be provided by customers. # # b. Terminals 6 ,7 can output NC (normal close) contact if that is required by users. # c. Terminal 35 can be directly connected to power (automatic pre-storing energy), alternatively connect power after connecting NO button (manual-controlled pre-storing energy). d. Terminals 21#~24# is only for wiring with function meter display. (excluding the special wiring)
C-89
> >>
NA1
The secondary circuit wiring for NA1-2000~6300 with type (3M) intelligent controller and instantaneous under-voltage release
1 2
L1 N PE
Transformer connected
C
28 30 32 34 36 38 40 42 44 46
48 50
10
12
14
16
18
20
22
24
26
SA
AX
M
11
13
15
17
19
21
23
25
27
29
31
33
35 Energystorage
37
39
41
43
45
47
49
51
Fault
Open Close
Main circuit
Intelligent controller
Auxiliary switch
37 39 41
4 3 45 47
37 39 41
43 45 47
49
3 ,4 ,5 : Fault trip contact output(4 common terminal) # # # # 6 ,7 ,8 ,9 : Auxiliary contact(normal open) # # 10 ~11 : empty # # 12 ~19 : The programmable output terminal. The normal products without these terminals, but if the customer special ordered, the cost extra added.
SB1: Shunt button SB2: Under-voltage button SB3: Making button Q: Under-voltage release F: Shunt release X: Closing release M: Energy storage motor XT: connection terminal SA: Position switch 1#, 2#: Intelligent controller power input Note: When the power supply of the intelligent controller is AC power, the 1#~2# connects to the AC power directly. When the power supply is DC power, forbid connecting the 1#~2# to the DC power directly. Add a DC power supply module, then the DC power connect to the input terminal of the DC power supply module, and the 1#~2# connect to the output terminal of the DC power supply module, or else the intelligent controller will be damaged.
3M type acquiescence output: # # # # 12 ,13 : Signal alarm of load 1 output; 14 ,15 : Signal alarm of load2 output # # # # # # # 16 ,17 : Self-diagnose alarm; 18 ,19 : Fault trip; 20 : PE line; 21 ~24 : Display the voltage of the signal input. The normal products without these terminals, if the customer special ordered the function meter, the cost extra added. # 21 : N phase input terminal # # # 22 ,23 ,24 : A, B, C three phase power input terminal (note the sequence) # # 25 ,26 : Connect to the N phase current transformer or the input terminal of the current leakage transformer. The normal products without these terminals, if the customer special ordered, the cost extra added. # # # # # # # # 27 ,28 : Under-voltage release; 29 ,30 : Shunt release; 31 ,32 : Closing release; 33 ,34 : Energy storage indicator # # # # 34 ,35 : Energy storage motor; 36 ~51 : Auxiliary contact
Note:
a. Red colored part is to be connected by users b. When the power system is three phase three wire, directly connect the Un to U2. ( If the voltage exceeds 400V, special explanation when ordered)
> >>
C-90
NA1
The secondary circuit wiring for NA1-2000~6300 with type (3H) intelligent controller and instantaneous under-voltage release
L1 N PE
+ + 1 2 3 4 5 6 7 8 9 10 11
Modbus-RTV
SB1 SB3
Red
Green
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
SA
AX
M
11
13
15
17
19
21
23
25
27
29
31
33
35 Energy storage
37
39
41
43
45
47
49
Close
51
Fault
Open
Main circuit
Intelligent controller
Undervoltage release
Shunt release
Auxiliary switch
37 39 41
43 45 47
37 39 41
43 45 47
49
3 ,4 ,5 : Fault trip contact output(4 common terminal) # # # # 6 ,7 ,8 ,9 : Auxiliary contactnormal open # # 10 ~11 : communication output # # # # 12 ,13 : Signal alarm of load 1 output; 14 ,15 : Signal alarm of load2 output # # # # 16 ,17 :Breaking signal output; 18 ,19 :Making signal output # # 20 : PE line; 21 : N phase input terminal # # # 22 ,23 ,24 : A, B, C three phase power input terminal (note the sequence) # # 25 26 : Connect to the N phase current transformer or the input terminal of the current leakage transformer. The normal products without these terminals, if the customer special ordered, the cost extra added. ST~DP: DP protocol module. There is no need for the ST-DP protocol module, if the communication protocol is Modbus-RTV. But when the communication protocol is Profibus-DP, the ST-DP protocol module is necessary, but the cost extra added. ST power module IV: power converter (optional components) ST201: Magnify the signal capacity of the controller. ( optional components) If the customer special ordered, the cost extra added. # # # # 27 ,28 : Under-voltage release; 29 ,30 : Shunt release # # # # 31 ,32 : Closing release; 33 ,34 : Energy storage indicator # # # # 34 ,35 : Energy storage motor; 36 ~51 : Auxiliary contact
SB1: Shunt button; SB2: Under-voltage button SB3: Making button; Q: Under-voltage release F: Shunt release; X: Closing release M: Energy storage motor; XT: connection terminal SA: Position switch 1#, 2#: Intelligent controller power input Note: When the power supply of the intelligent controller is AC power, the 1#~2# connects to the AC power directly. When the power supply is DC power, forbid connecting the 1#~2# to the DC power directly. Add a DC power supply module, then the DC power connect to the input terminal of the DC power supply module, and the 1#~2# connect to the output terminal of the DC power supply module, or else the intelligent controller will be damaged.
Note:
a. Red colored part is to be connected by users b. When the power system is three phase three wire, directly connect the Un to U2. (If the voltage exceeds 400V, special explanation when ordered)
C-91
> >>
NA1
The secondary circuit wiring for NA1-2000~6300 with standard type (M) intelligent controller and time-delay under-voltage release
Main circuit
Over-current release
Emergency disconnection
Auxiliary switch
SB2
SB1 SB3
Energy storage
Failure 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
36
38
40
42 44
46 48 50
FU
AX
Processing unit
Power
Intelligent controller
FU 26 28 30 34 37 39 41 43 45 47
Open Close
1 2
4 6
10 12 14 16 18 20 22 24
32
49
51
_ 110V ~ _ 220V ~
~380V
Intelligent release power(1 connect positive pole, and 2 connect negative pole for direct current)
SB1: Shunt button SB2: Under-voltage button SB3: Making button Q: Under-voltage time-delay release F: Shunt release X: Closing electromagnet M: Energy storage motor XT: Connection terminal SA: Position switch Note: If control voltage of Q, F, X is different from each other, they can be connected to different power.
3 9 41
43 45 47
49
1 ,2 : Auxiliary power input # # # 3 ,4 ,5 : Fault trip contact output(4# common terminal) # # # # 6 ,7 ,8 ,9 : Auxiliary contactnormal open # # 10 ~24 : empty # # 25 ,26 : to be connected with current transformer(selective) # # 27 ,28 : Under-voltage release # # 29 ,30 : Shunt release # # 31 ,32 : Closing release # 33 ,34#: Energy storage indicator 34#,35#: Energy storage motor 36#,37#: Under-voltage time delay release 38#~51#: Auxiliary contact Circuit explanation for signal output: a. Broken-line parts shall be provided by customers. b. Terminals 6#,7# can output NC (normal close) contact if that is required by users. # c. Terminal 35 can be directly connected to power (automatic pre-storing energy), alternatively connect power after connecting NO button (manual-controlled pre-storing energy). d. The 21#~24# is only for wiring with function meter display. (Excluding the special wiring)
> >>
C-92
NA1
The secondary circuit wiring for NA1-2000~6300 with type (3M) intelligent controller and time-delay under-voltage release
L1 N PE 1 2
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
SA
AX
M
11
13
15
17
19
21
23
25
27
29
31
33
35 Energy storage
37
39
41
43
45
47
49
Close
51
Fault
Open
Main circuit
Intelligent controller
Emergency break
Shunt release
Energystorage motor
Auxiliary switch
3 9 41
43 45 47
49
SB1: Shunt button; SB2: Under-voltage button SB3: Making button; Q: Under-voltage release F: Shunt release; X: Closing release M: Energy storage motor; XT: Connection terminal SA: Position switch # # 1 , 2 : Intelligent controller power input Note: When the power supply of the intelligent controller # # is AC power, the 1 ~2 connects to the AC power directly. When the power supply is DC power, forbid connecting the # # 1 ~2 to the DC power directly. Add a DC power supply module, then the DC power connect to the input terminal # # of the DC power supply module, and the 1 ~2 connect to the output terminal of the DC power supply module, or else the intelligent controller will be damaged.
# # # #
3 ,4 ,5 : Fault trip contact output(4 common terminal); 6 ,7 ,8 ,9 : Auxiliary contactnormal open # # # # 10 ~11 : empty; 12 ~19 are the programmable output terminal. The normal products without these terminals, but if the customer special ordered, the cost extra added. 3M type acquiescence output: 12#,13#: Signal alarm of load 1 output; 14#,15#: Signal alarm of load2 output # # # # 16 ,17 : Self-diagnose alarm; 18 ,19 : Fault trip # # # 20 : PE line; 21 ~24 : Display the voltage of the signal input. The normal products without these terminals, if the customer special ordered the function meter, the cost extra added. # # # # 21 : N phase input terminal; 22 ,23 ,24 : A, B, C three phase power input terminal (note the sequence) # # 25 ,26 Connect to the N phase current transformer or the input terminal of the current leakage transformer. The normal products without these terminals, if the customer special ordered, the cost extra added. # # # # 27 ,28 : Under-voltage release; 29 ,30 : Shunt release # # # # 31 ,32 : Closing release; 33 ,34 : Energy storage indicator 34#,35#: Energy storage motor; 36#,37#: Under-voltage time delay release # # 38 ~51 : Auxiliary contact
Note:
a. Red colored part is to be connected by users b. When the power system is three phase three wire, directly connect the Un to U2. (If the voltage exceeds 400V, special explanation when ordered)
C-93
> >>
NA1
The secondary circuit wiring for NA1-2000~6300 with type (3H) intelligent controller and time-delay under-voltage release
L1 N PE 1 2
1 2 3 4 5
L N L N PE - + - +
STPower Supply Modular IV
- + 16 17
- + 18 19
12 13
14 15
+ 1 2 3 4 5 6 7 8 9 10 11
Modbus-RTV
Red
2 4 6 8 10
Green
12 14 16 18 20 22 24
C
40 42 44 46
48 50
26
28
30
32
34
36
38
SA
AX
M
11
13
15
17
19
21
23
25
27
29
31
33
35
Energy storage
37
39
41
43
45
47
49
Close
51
Fault
Open
Main circuit
Intelligent controller
Emergency break
Shunt release
Closing electromagnet
Auxiliary switch
39 41
43 4 5 4 7
49
3#,4#,5#: Fault trip contact output(4# common terminal) # # # # 6 ,7 ,8 ,9 : Auxiliary contactnormal open # # # # 10 ~11 : Communication output; 12 ,13 : Signal alarm of load 1 output # # 14 ,15 : Signal alarm of load 2 output; 16#,17#: Breaking signal output; 18#,19#: Closing signal output 20#: PE line; 21#: N phase input terminal 22#,23#,24#: A, B, C three phase power input terminal (note the sequence) 25#,26# Connect to the N phase current transformer or the input terminal of the current leakage transformer. The normal products without these terminals, if the customer special ordered, the cost extra added. ST~DP: DP protocol module. There is no need for the ST-DP protocol module, if the communication protocol is Modbus-RTV. But when the communication protocol is Profibus-DP, the ST-DP protocol module is necessary, but the cost extra added. ST power module IV: power converter (optional components) ST201: Magnify the signal capacity of the controller. ( optional components) If the customer special ordered, the cost extra added. # # # # 27 ,28 : Under-voltage release; 29 ,30 : Shunt release # # # # 31 ,32 : Closing release; 33 ,34 : Energy storage indicator # # # # 34 ,35 : Energy storage motor; 36 ,37 : Under-voltage time delay release # # 38 ~51 : Auxiliary contact
SB1: Shunt button; SB2: Under-voltage button SB3: Making button; Q: Under-voltage release F: Shunt release; X: Closing release M: Energy storage motor; XT: Connection terminal SA: Position switch # # 1 , 2 : Intelligent controller power input Note: When the power supply of the intelligent controller # # is AC power, the 1 ~2 connects to the AC power directly. When the power supply is DC power, forbid connecting the # # 1 ~2 to the DC power directly. Add a DC power supply module, then the DC power connect to the input terminal # # of the DC power supply module, and the 1 ~2 connect to the output terminal of the DC power supply module, or else the intelligent controller will be damaged.
Note:
a. Red colored part is to be connected by users b. When the power system is three phase three wire, directly connect the Un to U2. (If the voltage exceeds 400V, special explanation when ordered)
> >>
C-94
NA1
7. Installation
7.1 Installation 7.1.1 Unload the breaker from the soleplate of package. If it is drawout type, firstly pull out the handle under the drawer-base of breaker, and plug it into the hole on central part of plastic cover under the drawer-base crossbeam, anticlockwise turns the handle, the body will slowly slide along the outside of drawer-base. When the guide rod points to separated position and handle can't be rotated any longer, pull out the handle and firmly grasp the aluminum handle on drawer-base, pull out the breaker body and remove it form the base, then move the base from the sole plate and clean up the dirty things inside the drawer-base.
Possible positions
7.1.2 Check the insulation resistance with a 500V megger, resistance should not be less than 20M when ambient temperature is 20 5 and relative humidity is 50%~70%. Otherwise dry it.
7.1.3 Power supply NA1 devices can be supplied either from the top or from the bottom without reduction in performance, in order to facilitate connection when installed in a switchboard.
C-95
> >>
NA1
7.1.4 Put the breaker (fixed-type) or drawer-base (drawout-type) into the installation-bracket, and make it fixed, directly connect the cable wire of main circuit to the bus wire of fixed-type circuit breaker. Alternatively put breaker body onto the slideway of drawer-base. Plug the handle into installation hole, clockwise turns it until the under-part of drawer-base points at the connection position and click sound is heard. It indicates that breaker body has been connected to its place, then connect the cable of main circuit to drawer-base. Mounting the circuit-breaker It is important to distribute the weight of the device uniformily over a rigid mounting surface such as rails or a base plate. This mounting plane should be perfectly flat (tolerance on support flatness: 2 mm).This eliminates any risk of deformation which could interfere with correct operation of the circuit breaker. NA1 devices can also be mounted on a vertical plane using the special brackets. Mounting on rails
7.1.5 Partitions Sufficient openings must be provided in partitions to ensure good air circulation around the circuit breaker; Any partition between upstream and downstream connections of the device must be made of nonmagnetic material. For high-currents, of 2500 A and upwards, the metal supports or barriers in the immediate vicinity of a conductor must be made of non-magnetic material A;Metal barriers through which a conductor passes must not form a magnetic loop.
A
Busbars The mechanical connection must be exclude the possibility of formation of a magnetic loop around a conductor.
> >>
C-96
NA1
7.1.6 Busbar connections The busbars should be suitably adjusted to ensure the connection points are positioned on the terminals before the bolts are inserted B The connections are held by the supporter which is fixed to the framework of the switchboard, in this way the circuit breaker terminals do not have to support its weight C. (This support should be placed close to the terminals).
7.1.7 Main circuit adopts cable connection Users should not apply too strong mechanical strength on the terminals of Air Circuit Breaker. Extend the bus-bar of circuit breaker with connecting bus-bar, position the wiring piece of cable before inserting bolts; the cable should be fixed on the frame of distributing cabinet firmly.
18min
18min
C-97
> >>
NA1
7.1.8 Clamping Correct clamping of busbars depends on the tightening torques used for the nuts and bolts,etc. Over-tightening may have the same consequences as under-tightening. For connecting busbars to the circuit breaker, the tightening torques to be used are shown in the table below. These values are for use with copper busbars and steel nuts and bolts, class 8.8.
1 2 3 4
1 2 3 4 5
5
Examples
Connected position
Test position
Disconnected position
Drawout position
1.Both main circuit and control circuit are connected. 2.Normal application conditions
1.The main circuit is disconnected, and the control circuit is connected. 2.Test application conditions.
> >>
C-98
NA1
7.2 Wiring the secondary circuit according to electric principle diagram. Note: Bolts, nuts, gaskets shouldn't be left inside the drawer seat to avoid being blocked. 7.3 Operation Check the rated voltage of the following components whether conforms to the power voltage . Such as under voltage release, shunt release, closing electromagnet, motor-driven mechanism and intelligent controller. 7.4 Maintenance Check the technical parameters in time or add some lubricating oil, etc. This breaker structure is arranged vertically and modularized composition with each functioncell separated, which make the maintenance easy. It has compact structure, reliable operation and strong free maintenance capability. Please check the technical parameters on the nameplate in accordance with the requirements of order before installation.
Main body
Drawer seat
Handle
Slideway
Making the secondary circuit power, the motor-driven mechanism can store energy automatically until hearing the click and energy stored indicating on the panel. Otherwise press the storage handle for 6 times until hearing the click and the indicator display energy stored And the closing operation can be realized either by closing electromagnet or manual button.
Manual energy-storage
Shake with the manual energy-storage handle up and down about six times to "click".
NA1-1000
400 630 800 1000 630 800
NA1-2000 8 50 2 5 60 2 6 60 2 8 60 2 10 60 2 12 60 2 10 60 3 8 100 2
NA1-6300 10 7 10 8
1000 1250 1600 2000 2000 2500 2900 3200 4000/3P 4000/4P 4000 5000 6300
5 30 1
5 30 2
5 40 2
6 50 2
120 4
100 100
Note: the specifications in the table is obtained as the ambient temperature of air circuit breaker is 40, with open installation; this is in compliance with the specification of copper busbars adopted under the heating conditions regulated in IEC/EN60947-2.
9. Power loss
Inm(A) In(A)
Power loss (W) Drawer type Fixed type
NA1-1000 200 400 630 800 1000 630 40 33 101 123 110 177 85 107 94 70 476 34.4 800 110 50
1000 1250 1600 2000 2000 2500 3200 4000/3P 4000/4P 4000 5000 6300
C-99
> >>
NA1
10. A2S curve
I tA s10
2 2 6
741
341
200 190 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10
20
C
40 60 80 100 120 IskA
800 1000 1250 1600 2000 2000 2500 3200 4000 4000 5000 6300 800 1000 1250 1600 1900 2000 2400 3000 3800 4000 5000 6000 800 1000 1250 1500 1900 2000 2300 3000 3600 4000 5000 5600 800 1000 1200 1500 1800 2000 2200 2800 3400 4000 4800 5400 800 1000 1150 1300 1700 2000 2200 2800 3200 4000 4800 5200 800 1000 1150 1300 1650 2000 2200 2600 3200 4000 4800 5100
Note: The ACB is to calibrated at 40, special application please refer to the table above and the curve below.
5000 4800 4600
In=1000A
In=800A
In=630A
In=400A
In=200A
200 100 0 40 45 50 55 60 65 70
4400 4200 4000 3800 3600 3400 3200 3000 2800 2600 2400 2200 2000 1800 40 45
Rated current A
Rated current A
In=4000A
In=3200A
In=2500A In=2000A
50
55
60
65
70
Ambient temperature
NA1-3200, NA1-4000
2000 1900 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 40 45
In=2000A
7000 6800 6600 6400 6200 6000 5800 5600 5400 5200 5000 4800 4600 4400 4200 4000 3800 40 45
Rated current A
In=1600A
Rated current A
In=6300A
In=1250A
In=5000A
In=4000A
50
55
60
65
70
50
55
60
65
70
Ambient temperature
NA1-2000
Ambient temperature
NA1-6300
> >>
C-100
NA1
12. Coordination recommendations
Capacity of transformer (kVA) & parallelly connected number 1250 2250 3250 1315 2315 3315 1400 2400 3400 1500 2500 3500 1630 2630 3630 1800 2800 3800 11000 21000 31000 11250 21250 31250 11600 21600 31600 12000 22000 32000 12500 22500 13150 23150 Rated current of transformer In(A) 360 360 360 455 455 455 578 578 578 722 722 722 910 910 910 1154 1154 1154 1444 1444 1444 1805 1805 1805 2310 2310 2310 2887 2887 2887 3608 3608 4550 4550 Short circuit current of main circuit (kA) 9 9 9 11.4 11.4 11.4 14.4 14.4 14.4 18 18 18 22.7 22.7 22.7 19.3 19.3 19.3 24 24 24 30 30 30 36.5 36.5 36.5 48.2 48.2 48.2 60 60 75.8 75.8 Breaking capacity of air circuit breaker for main circuit (kA) 9 9 18.5 11.4 11.4 22.7 14.4 14.4 28.8 18 18 36.1 22.7 22.7 44.5 19.3 19.3 38.5 24 24 48.1 30 30 60.1 36.5 36.5 73 48.2 48.2 96.3 60 60 75.8 75.8
C-101
> >>
NA1
Type of air circuit breaker for main circuit NA1-1000-400 NA1-1000-400 NA1-1000-400 NA1-1000-630 NA1-1000-630 NA1-1000-630 NA1-1000-630 NA1-1000-630 NA1-1000-630 NA1-1000-800 NA1-1000-800 NA1-1000-800 NA1-1000-1000 NA1-1000-1000 NA1-2000-1000 NA1-2000-1250 NA1-2000-1250 NA1-2000-1250 NA1-2000-1600 NA1-2000-1600 NA1-2000-1600 NA1-2000-2000 NA1-2000-2000 NA1-2000-2000 NA1-3200-2500 NA1-3200-2500 NA1-3200-2500 NA1-3200-3200 NA1-3200-3200 NA1-3200-3200 NA1-6300-4000 NA1-6300-4000 NA1-6300-5000 NA1-6300-5000 4(10120) 7(10100) 4(10100) 2(10100) 3(1060) 2(1260) 2(1060) 2(850) 2(650) 2(540) 2(540) 2(530) Number and area of the busbar for main circuit (nWT) Breaking capacity of air circuit breaker for branch circuit (kA) 9 18.5 27.5 11.4 22.7 34.1 14.4 28.8 43.2 18 36.1 54.1 22.7 44.5 67.2 19.3 38.5 57.8 24 48.1 72.1 30 60.1 90.1 36.5 73 109.5 48.2 96.3 144.5 60 120 75.8 151.6 NA1, NM8 NA1, NM8 NA1, NM8 NA1, NM8 NA1, NM8 NA1, NM8 NA1, NM8 NA1, NM8 NA1, NM8 NA1, NM8
> >>
C-102
NA1
13. Selectivity protection
13.1 Selective protection between NM8 and NA1
Circuit breaker Rated current (A) Default setting ratings of short time-delay 8In (kA) Downstream Upstream Setting range (kA) Delayed tripping time (s) Returnable time Instantaneous Rated Frame size rated current current (A) setting ratings (kA) 16 20 25 32 40 50 63 80 100 125 100 160 200 250 0.16 0.19(motor) 0.2 0.24(motor) 0.25 0.30(motor) 0.32 0.38(motor) 0.40 0.48(motor) 0.50 0.60(motor) 0.63 0.75(motor) 0.80 0.96(motor) 1.0 1.20(motor) 1.25 1.5(motor) 1.0 1.2(motor) 1.6 1.92(motor) 2.0 2.4(motor) 2.5 3.0(motor) 0.4~6 0.4~6 0.4~6 0.4~6 0.4~6 0.414~6 0.4416~6 0.5224~6 0.552~6 0.6624~6 0.69~6 0.828~6 0.8694~6 1.035~6 1.104~6 1.325~6 1.38~6 1.656~6 1.725 ~6 2.07~6 1.38~6 1.656~6 2.208~6 2.65~6 2.76~6 3.312~6 3.45~6 4.14~6 0.63~9.45 0.63~9.45 0.63~9.45 0.63~9.45 0.63~9.45 0.63~9.45 0.63~9.45 0.63~9.45 0.63~9.45 0.6624~9.45 0.69~9.45 0.828~9.45 1.035~9.45 1.104~9.45 1.325~9.45 1.38~9.45 1.656~9.45 1.725~9.45 2.07~9.45 1.38~9.45 1.656~9.45 2.208~9.45 2.65~9.45 2.76~9.45 3.312~9.45 3.45~9.45 4.14~9.45 0.8~12 0.8~12 0.8~12 0.8~12 0.8~12 0.8~12 0.8~12 0.8~12 0.8~12 0.8~12 0.8~12 0.828~12 1.035~12 1.104~12 1.325~12 1.38~12 1.656~12 1.725~12 2.07~12 1.38~12 1.656~12 2.208~12 2.65~12 2.76~12 3.312~12 3.45~12 4.14~12 1~15 1~15 1~15 1~15 1~15 1~15 1~15 1~15 1~15 1~15 1~15 1~15 1~15 1.035~15 1.104~15 1.325~15 1.38~15 1.656~15 1.725~15 2.07~15 1.38~15 1.656~15 2.208~15 2.65~15 2.76~15 3.312~15 3.45~15 4.14~15 1.25~18.75 1.25~18.75 1.25~18.75 1.25~18.75 1.25~18.75 1.25~18.75 1.25~18.75 1.25~18.75 1.25~18.75 1.25~18.75 1.25~18.75 1.25~18.75 1.25~18.75 1.25~18.75 1.25~18.75 1.325~18.75 1.38~18.75 1.656~18.75 1.725~18.75 2.07~18.75 1.38~18.75 1.656~18.75 2.208~18.75 2.65~18.75 2.76~18.75 3.312~18.75 3.45~18.75 4.14~18.75 400 3.2 0.4~6 630 5.04 0.639.45 NA1-2000 800 6.4 0.8~12 1000 8 1~15 1250 10 1.25~18.75
NM8-125 NM8S-125
0.8694~9.45 0.8694~12
NM8-250 NM8S-250
C-103
> >>
NA1
NA1-3200 1600 2000 16 2~30 2000 16 2~30 2500 20 2.5~37.7 3200 25.6 3.2~48 3200 25.6
3.2~48
C
4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 1.725~60 2.07~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4.14~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 4~60 460 460 460 460 460 460 460 1.725~60 2.07~60 460 460 4~60 4~60 4~60 4~60 4~60 4.14~60 5~75 5~75 5~75 5~75 5~75 5~75 5~75 5~75 5~75 5~75 5~75 5~75 5~75 5~75 5~75 5~75 5~75 5~75 1.725~75 2.07~75 5~75 5~75 5~75 5~75 5~75 5~75 5~75 5~75 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 1.725~94.5 2.07~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5
1.6~24 1.6~24 1.6~24 1.6~24 1.6~24 1.6~24 1.6~24 1.6~24 1.6~24 1.6~24 1.6~24 1.6~24 1.6~24 1.6~24 1.6~24 1.6~24 1.6~24 1.656~24 1.725~24 2.07~24 1.6~24 1.656~24 2.208~24 2.65~24 2.76~24 3.312~24 3.45~24 4.14~24
2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 1.725~30 2.07~30 2~30 2~30 2.208~30 2.65~30 2.76~30 3.312~30 3.45~30 4.14~30
2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 2~30 1.725~30 2.07~30 2~30 2~30 2.208~30 2.65~30 2.76~30 3.312~30 3.45~30 4.14~30
2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.5~37.7 1.725~37.7 2.07~37.7 2.5~37.7 2.5~37.7 2.5~37.7 2.65~37.7 2.76~37.7 3.312~37.7 3.45~37.7 4.14~37.7
3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 1.725~48 2.07~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.312~48 3.45~48 4.14~48
3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 1.725~48 2.07~48 3.2~48 3.2~48 3.2~48 3.2~48 3.2~48 3.312~48 3.45~48 4.14~48
> >>
C-104
NA1
Circuit breaker Rated current (A) Default setting ratings of short time-delay 8In (kA) Downstream Upstream Setting range (kA) Delayed tripping time (s) Returnable time Instantaneous Rated Frame size rated current current (A) setting ratings (kA) 250 315 NM8-630 NM8S-630 350 400 500 NM8S-630 630 630 700 NM8-1250 NM8S-1250 800 1000 1250 2.5 3.0(motor) 3.15 3.78(motor) 3.5 4.2(motor) 4.0 4.8(motor) 5.0 6.0(motor) 6.3 7.56(motor) 6.3 7.56(motor) 7.0 8.4(motor) 8.0 9.6(motor) 10 12(motor) 12.5 15.0(motor) 3.45~6 4.14~6 4.347~6 5.216~6 4.83~6 5.796~6 5.52~6 3.45~9.45 4.14~9.45 4.347~9.45 5.216~9.45 4.83~9.45 5.796~9.45 5.52~9.45 6.624~9.45 6.9~9.45 8.28~9.45 8.694~9.45 8.694~9.45 3.45~12 4.14~12 4.347~12 5.216~12 4.83~12 5.796~12 5.52~12 6.624~12 6.9~12 8.28~12 8.694~12 10.44~12 8.694~12 10.44~12 9.66~12 11.59~12 11.04~12 3.45~15 4.14~15 4.347~15 5.216~15 4.83~15 5.796~15 5.52~15 6.624~15 6.9~15 8.28~15 8.694~15 10.44~15 8.694~15 10.44~15 9.66~15 11.59~15 11.04~15 13.25~15 13.8~15 3.45~18.75 4.14~18.75 4.347~18.75 5.216~18.75 4.83~18.75 5.796~18.75 5.52~18.75 6.624~18.75 6.9~18.75 8.28~18.75 8.694~18.75 10.44~18.75 8.694~18.75 10.44~18.75 9.66~18.75 11.59~18.75 11.04~18.75 13.25~18.75 13.8~18.75 16.56~18.75 17.25~18.75 400 3.2 0.4~6 630 5.04 0.639.45 800 6.4 0.8~12 NA1-2000 1000 8 1~15 0.1, 0.2, 0.3, 0.4 0.06, 0.14, 0.23, 0.35 1250 10 1.25~18.75
C-105
> >>
NA1
NA1-3200 1600 2000 16 2~30 2000 16 2~30 2500 20 2.5~37.7 3200 25.6 3.2~48 3200 25.6 3.2~48 NA1-4000 4000 32 4~60 4000 32 4~60 NA1-6300 5000 40 5~75 6300 50.4 6.3~94.5
C
3.45~24 4.14~24 4.347~24 5.216~24 4.83~24 5.796~24 5.52~24 6.624~24 6.9~24 8.28~24 8.694~24 10.44~24 8.694~24 10.44~24 9.66~24 11.59~24 11.04~24 13.25~24 13.8~24 16.56~24 17.25~24 20.7~24 3.45~30 4.14~30 4.347~30 5.216~30 4.83~30 5.796~30 5.52~30 6.624~30 6.9~30 8.28~30 8.694~30 10.44~30 8.694~30 10.44~30 9.66~30 11.59~30 11.04~30 13.25~30 13.8~30 16.56~30 17.25~30 20.7~30 3.45~30 4.14~30 4.347~30 5.216~30 4.83~30 5.796~30 5.52~30 6.624~30 6.9~30 8.28~30 8.694~30 10.44~30 8.694~30 10.44~30 9.66~30 11.59~30 11.04~30 13.25~30 13.8~30 16.56~30 17.25~30 20.7~30 3.45~37.7 4.14~37.7 4.347~37.7 5.216~37.7 4.83~37.7 5.796~37.7 5.52~37.7 6.624~37.7 6.9~37.7 8.28~37.7 8.694~37.7 10.44~37.7 8.694~37.7 10.44~37.7 9.66~37.7 11.59~37.7 11.04~37.7 13.25~37.7 13.8~37.7 16.56~37.7 17.25~37.7 20.7~37.7 3.45~48 4.14~48 4.347~48 5.216~48 4.83~48 5.796~48 5.52~48 6.624~48 6.9~48 8.28~48 8.694~48 10.44~48 8.694~48 10.44~48 9.66~48 11.59~48 11.04~48 13.25~48 13.8~48 16.56~48 17.25~48 20.7~48 3.45~48 4.14~48 4.347~48 5.216~48 4.83~48 5.796~48 5.52~48 6.624~48 6.9~48 8.28~48 8.694~48 10.44~48 8.694~48 10.44~48 9.66~48 11.59~48 11.04~48 13.25~48 13.8~48 16.56~48 17.25~48 20.7~48 4~60 4.14~60 4.347~60 5.216~60 4.83~60 5.796~60 5.52~60 6.624~60 6.9~60 8.28~60 8.694~60 10.44~60 8.694~60 10.44~60 9.66~60 11.59~60 11.04~60 13.25~60 13.8~60 16.56~60 17.25~60 20.7~60 4~60 4.14~60 4.347~60 5.216~60 4.83~60 5.796~60 5.52~60 6.624~60 6.9~60 8.28~60 8.694~60 10.44~60 8.694~60 10.44~60 9.66~60 11.59~60 11.04~60 13.25~60 13.8~60 16.56~60 17.25~60 20.7~60 5~75 5~75 5~75 5.216~75 5~75 5.796~75 5.52~75 6.624~75 6.9~75 8.28~75 8.694~75 10.44~75 8.694~75 10.44~75 9.66~75 11.59~75 11.04~75 13.25~75 13.8~75 16.56~75 17.25~75 20.7~75 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.3~94.5 6.624~94.5 6.9~94.5 8.28~94.5 8.694~94.5 10.44~94.5 8.694~94.5 10.44~94.5 9.66~94.5 11.59~94.5 11.04~94.5 13.25~94.5 13.8~94.5 16.56~94.5 17.25~94.5 20.7~94.5
> >>
C-106
NA1
13.2 Selective protection in NA1
Circuit breaker Rated current (A) Default setting ratings of short time-delay 8In (kA) Downstream Upstream Setting range (kA) Delayed tripping time (s) Returnable time Frame size rated current Default instantaneous Rated current (A) setting ratings 12In (kA) 400 630 800 4.8 7.56 9.6 12 15 19.2 24 24 30 38.4 38.4 48 48 60 75 6.348~9.45 6.348~12 9.998~12 6.348~15 9.998~15 12.696~15 6.348~18.75 9.998~18.75 12.696~18.75 15.87~18.75 400 3.2 630 5.04 NA1-2000 800 6.4 0.8~12 1000 8 1~15 1250 10 1.25~18.75
0.4~6 0.639.45
NA1-2000
NA1-3200
NA1-4000
NA1-6300
Note: It can satisfy the selective protection if only the short time-delay setting value of the superior breaker 1.32 times more than the subordinate breaker, when the instantaneous setting value is adjustive.
C-107
> >>
NA1
NA1-3200 1600 2000 16 2~30 2000 16 2~30 2500 20 2.5~37.7 3200 25.6 3.2~48 3200 25.6
3.2~48
C
6.348~60 9.998~60 12.696~60 15.87~60 19.837~60 25.392~60 31.74~60 31.74~60 39.675~60 50.784~60 50.784~60 6.348~60 9.998~60 12.696~60 15.87~60 19.837~60 25.392~60 31.74~60 31.74~60 39.675~60 50.784~60 50.784~60 6.348~75 9.998~75 12.696~75 15.87~75 19.837~75 25.392~75 31.74~75 31.74~75 39.675~75 50.784~75 50.784~75 63.48~75 63.48~75 6.348~94.5 9.998~94.5 12.696~94.5 15.87~94.5 19.837~94.5 25.392~94.5 31.74~94.5 31.74~94.5 39.675~94.5 50.784~94.5 50.784~94.5 63.48~94.5 63.48~94.5 79.35~94.5
> >>
C-108
NA1
14. Intelligent controller
14.1 The intelligent controller of NA1-1000 a. The standard M type intelligent controller (NA1-1000)
2 4 5 6
3 7 8
10
12 14 15 17 19
11 13 16 18 20
1: Reset key 2: Rated current 3: MCU indicator( normal operation indicator) 4: Current indicator 5-Earthing fault indicator 6: Short circuit instantaneous fault indicator 7: Short circuit short time-delay fault indicator 8: Overload fault indicator 9: Time setting table 10: Current setting table 11: Overload long time-delay time setting key 12: Overload long time-delay current setting key 13: Fault cheking key 14: Short circuit short time-delay time setting key 15: Short circuit short time-delay current setting key 16: Test key 17: Short circuit instantaneous current setting key 18: Clear LED key 19: Earthing current setting key 20: Earthing time setting key The function of keys show as followed: Fault checking key: After the breaker tripping, press this key to indicate the kind of fault. Test key key: used for checking the controller and the action of the breaker. Clear LED key: After the setting,testing and fault checking of the controller, make the circuit breaker at normal operation.
3 4 5 6 7
10 8 9 12 13 11 14 15 16
1: Reset key 2: LCD display window 3: Fault and alarm reset key 4: Curve LED indication 5: Fault/alarm LED 6: Normal LED 7: Communication indicator 8: Test key 9: Setting key 10: Message key 11: Protection key 12: Increasing key 13: Decreasing key 14: Choosing key 15: Exit key 16: Testing port
C-109
> >>
NA1
c. Basic functions
stands for definite setting stands for optional setting Standard (M type) Controller type Long time-delay protection Short time-delay protection Instantaneous protection Earthing fault protection Load current display Load current digital display (Ampere Meter) Test function Basic function Fault recall Self-diagnose function MCR making and breaking function Fault alarm Fault breaking indication Customer setting, testing Load monitor RS485 port MODBUS protocol Voltage measuring Frequency display Active power measuring Power factor measuring Electric energy measuring Over voltage protection Under voltage protection Optional auxiliary function Phase protection Current transformer earthing protection Exceed breaking function Thermal recall fuction Four output contacts Man-machine interface instruction Three cascades protection (3P+N model) Four cascades protection (3P+N model) stands for no funcion Communication (H type) Three cascades protection Four cascades protection
d. Operation instructions Standard intelligent controller setting According to the panel number 9 showed, dial the switch 11,14,20 to set the time you need. According to the panel number 10 showed, dial the switch 12,15,17,19 to set the current you need. Example 1: means that overload long time-delay current is 0.9In, overload long time-delay time is 60s. Example 2: means that short circuit short time-delay current is 4In, short circuit short time-delay time is 0.4s.
> >>
C-110
NA1
Example 1 Example 2
Ir
tr
Isd
tsd
Communication intelligent controller setting and operation. It provides 4 main menu and 1 default interface. Default interface Without other function action, it displays phases current column chart.
1. Testing menu
Harmonic wave H
Clock setting Measure metre setting Testing lock Communication setting I/O setting
Press or key to return default interface. On other non-fault interface, press to skip to testing menu. Without action for several minutes, it returns to the default interface.
Press or key to return default interface. On other non-fault interface, press to skip to system data setting menu. Without action for several minutes, it returns to the default interface.
Present alarm Operation times Contact wearing Product information Trip record
Press or key to return default interface. On other non-fault interface, press to skip to protection data setting menu. Without action for several minutes, it returns to the default interface.
Press or key to return default interface.. On other non-fault interface, press to skip to testing menu. Without action for several minutes, it returns to the default interface.
C-111
> >>
NA1
5. Submenu operation show: overload longtime-delay protection setting
Long time-delay Long time-delay Long time-delay
Ir=400A
(40.0%In)
Curve type
Ir=1000A
(100%In)
Curve type
Ir=1000A
(100%In)
Curve type
= SI
= SI
= SI
then
10000
5000
I R =(0.41)In
2000 1000
tl=(30240)s (M type)
500
200
100
50
20 10
t(a)
2 1
Isd=(3~10)IR(M type)
0.5
0.4s 0.3s
or(1.5~15)In(H type)
0.2s 0.1s
0.02 0.01 .2
> >>
C-112
NA1
Long time-delay overcurrent protection, inverse time characteristic.
Setting current (IR) Error Current 1.05IR
1.3IR
Time error
(0.4~1)In+OFF
10%
30 16.9
60 33.8 0.61~86
120 67.5
240 135
0.14~19.2
Instantaneous characteristic.
Type Setting current (Ii) Tripping Error
M H
(3~15)In+OFF (1~20)In+OFF
15% 15%
T(s)
min 100A
0.2
0.3
XIn
C-113
> >>
NA1
Wiring diagram of the earthing fault protection.
Transformer
Current transformer
Transformer
Current transformer
Intelligent controller
Intelligent controller
Transformer
Current transformer
Transformer
Current transformer
Intelligent controller
Intelligent controller
PE
10
In
In
> >>
C-114
NA1
14.2 The intelligent controller of NA1-2000, 3200, 4000, 6300 14.2.1 The standard M type intelligent controller (NA1-2000 3P 4P; NA1-3200 3P 4P; NA1 4000 3P) The M type intelligent controller is the core part of the NA1 Air Circuit Breaker to protect the electric circuit and the power supply against the dangers such as overload, short circuit and single-phase earthing fault. The controller adopts highly-integrated and highperformance digital signal processor that featuring power functions and reliable performance to perform real-time processing to the signal so as to achieve various protection function and numerous auxiliary functions. Appearance and panel illustration
Reset button
Selectivity protection
IL
IS
II
IG
C-115
> >>
NA1
a. Symbol designation table
Number Symbol Designation
1 2 3 4 5 6 7 8 9
Frame size rated current of breaker Rated current Action current of long time-delay, short time-delay and instantaneous Action current of earth fault or phase N Action time of long time-delay, short time-delay and grounding Phase A, B, C and N (or earth) Action current of load monitor 1 and load monitor 2 Time, current Unit Indicator: Ampere, kilo-Ampere, second
b.Operating power supply The operating power supply input to the intelligent controller: AC 400V/380V, 230V/220V, AC 110V, 50Hz; DC220V, 110V, 24V. c. Basic functions of intelligent controller Main protection function Query function Parameter setting function Test function Load monitor function (optional) Making current release (MCR) and High-Set Instantaneous Short Circuit (HSISC) function (optional) Signal alarm function (optional) d. Operation instructions Parameter setting operation Step 1: Setting right confirmation. The key must be switched to setting position for type H. This step is no necessary for type M. Step 2: Make sure the controller is under reset status. If the controller isn't under reset status, press reset key till the ammeter displays operation current. Note: When the controller is under malfunction alarm status, then the setup function is locked and the setup operation can't be conducted. Step 3: Press set key till the ammeter display window displays required action current or time setting. Step 4: Press + and - to set the items to be changed. Step 5: Press save key. At that time, the save indicator will flash once to indicate that the parameters are saved. If not desiring to save, then directly press reset key. Then the parameters won't be changed and will remain the original values.
Step 6: Repeat step 3 ~ step 5 in case requiring changing other parameters. If not, press reset key till the characteristic curve indicator is off. Note: In case of occurrence of malfunction under setup status, it will automatically exit the setup status and enter into malfunction status. During the adjustment of the parameters, the longer the time of pressing or holding the + or - key is, the faster the up or down speed is. Failure inquiry operation Query operation method Step 1: Make sure the controller is under reset status. Step 2: Press fault display key till the ammeter display window indicates the failure action value and the action time alternately. Press select to inquiry relevant parameters. Step 3: Press reset key to exit the inquiry status. Test operation method Step 1: Make sure the controller is under reset status. Step 2: Press set key till the indicator of the short time-delay characteristic curve current is on. Press +- to adjust the required current. Press trip key, then the breaker will trip. The ammeter display window will display the action current and action time in turn. Step 3: Press reset key to exit the test status.
> >>
C-116
NA1
e. Characteristic Over-current protection characteristic curve figure
10000 5000 Ir1=(0.41)In 2000 1000 500 200 100 50 20 10 t(a) 5 2 1
Ir2=(1.0~15)Ir1
Tr=(15~480)s
0.4s 0.3s
I 2t OFF
0.2s 0.1s
C-117
> >>
NA1
f. Earth fault protection The earth fault protection has definite time-delay characteristic with the failure delayed time no less than the definite time-delay time setting. Earth fault Protection Characteristic Curve
1000 500
100 50 20 10 t(s) 5 2 1 0.5 0.2 0.1 0.05 0.02 0.01 .05 .06 .08 .1 .2 .3 .4 .5 .6 .8 1 xIn 2 3 4 5 6 8 10 20 30
0.4s 0.3s 0.2s 0.1s 0.4s 0.3s 0.2s 0.1s
C
Ir4=(0.2~0.8)In
> >>
C-118
NA1
14.3 NA1 Multifunctional Intelligent Controller a. Menu Operation Explanation Display operation kneading board
2 3 4
2 3 4 5 6
16
16
1: LCD interface display 2: fault and warning Reset 3: fault/warning LED The LED will not flash when it works normally; the red LED will flash fast when tripping at fault; the red LED will on when warning occurs. 4: normal LED The green LED will always flash if only the ST40-3 is powered and works stably. 5: communication indicating lamp The communication condition is indicating as follows: Profibus: off when no communication; on when communication. Modbus: off when no communication; flash when communication. Device Net: Flash when no communication, on when communication.
6: curve LED There is the red LED indicating lamp hiding in the curve. The corresponding LED lamp will flash to indicate the fault type when tripping at fault. The LED is on to indicate the project set at the moment when protective parameter is set. 7: machinery reset button The button will spring when fault trips or test trips. When not press down, the circuit breaker are not allowed to shut off. When press down, fault indication will be reset at the same time.
C-119
> >>
NA1
10
11
12
13
14
15
8: Measure function key 1, switch to measure default theme menu (the key in the password input interface is left) 9: Set function key 2, switch to parameter set theme menu (the key in the password input interface is right) 10: protectionfunction key 3, switch to protection parameter set theme menu. 11: Informationfunction key 4, switch to history and maintenance theme menu. 12: Upup to move the menu content under the current used grade, or up to change the chose parameter. 13: Downdown to move the menu content under the current used grade, or down to change the chose parameter. 14: Escapeto escape from this grade and return to upper menu; or cancel the current parameter selected. 15: Selectenter into the next menu directed by the current item, or for the current parameter selected and store modifications. 16: Test portThe bottom of the front board has a 16 pin test port, which can insert a inserted portable power supply or inspection unit.
Selective protection t t
> >>
C-120
NA1
c. NA1 Multifunctional Intelligent Controller subject menu NA1 Multifunctional Intelligent controller has provided 4 subject menu and 1 default interface 1. Default interface 2. measure menu
452 A
150 100 50 0
3H
I U F
3H
energy power E P H
The controller displays the default interface when on electiicity. Under each subject menu, press or the corresponding subject key can return to default interface. If don't press any keys in 5 minutes and then the pane cursor will show the maximum phase automatically. In the non-activated fault interface, if don't press any key in 30 minutes and then will automatically return to the default interface.
harmonic
press to enter into measure main menu press or to return to default interface In other non-fault interface, press to jump to measure menu
3H
clock set
measurement meter set
3H
current protection load monitor voltage protection
3H
communication set I/O set
3H
other protection
Press or to return to default interface In other non-fault interface, press to jump to system parameter set menu
Press or to return to default interface In other non-fault interface, press to jump to protection parameter set menu
C-121
> >>
NA1
5. history and maintenancemenu
3H
current warning operating time contact wearout
3H
production information release record warning record
3H
Variable-record
Press or to return to default interface In other non-fault interface, press to jump to history and maintenance menu
C
6. Sub-menu operation example: overload long delay protection set
then
adjust
fixed value
2000 1000
500
200
Express inverse-time 1 (Ordinary use) Express inverse-time 2 (Motor protection) Express inverse-time Standard inverse-time
100 50
20
10 t(s) 5
1 0.5
0.2
0.1
0.05
0.02
0.01
0.3
0.8
2 Xin1
10
20
> >>
C-122
NA1
Function of intelligent controller
stands for definite setting stands for optional setting stands for no funcion Type Function configuration M Current display function Overload long time delay protection(inverse) Short circuit short time delay protection(inverse and definite) Short circuit instantaneous protection Single-phase earthing fault protection Current imbalance protection caused by phase failure Parameter setting function Test(simulate tripfunction Inquiry function Self-diagnose function Programing interface function Communication function Contact abrasion extent record Operating times record Clock function Alarm record Position (making, energy storage or breaking) change record The history current peak value record MCR(Making current release) and HSISC(High-setting instantaneous short circuit) Current leakage protection(inverse and definite) Neutral (N phase) protection Load monitor function (Modes 1 and Modes 2) Voltage measurement display function Frequency measurement display function Voltage imbalance measurement display function Power measurement display function Power factor measurement display function Electrical energy measurement display function Fault clock function History data record function Phase sequence checking Average value in a certain period of time measurement function (current and power) Humorous-wave measurement Over-voltage protection Under-voltage protection Voltage imbalance protection Over-frequency protection Under-frequency protection Phase sequence protection Inverse power potection Position lock function 3M 3H
C-123
> >>
NA1
e. Overload long time-delay protection
Power distribution or motor protection Ir1= Setting current Acting property Property curve Curve speed Precision (0.4~1.0)In + OFF (Exit position) I1.05Ir1 without actions in 2h I1.3Ir1 with actions while it's less than 1h Curve 1~curve 5, could be rectified, rectified as curve 3 for ex-factory IEC255 standard, 80 level points totally, could be rectified 10% (intrinsic 40ms)
Note: When N-phase is 50%, protective settings are treated as 50% for N-phase. If long delay setting is 2000A, long delay setting for phase A, B and C is 2000A, and 1000A for phase N. f. Instruction to short time-delay property
Ir2= Setting current Inverse-time delay (s) (Corresponding 2Ir1) Inverse-time property Short delay inverse-time thermal memory (15min) Acting property Ts= Precision (1.5~15) Ir1 + OFF (exit position) 0.9Ir2 without actions 1.1Ir2 delay action (0.1~0.4)s (0.1s level error) 10% (intrinsic 40ms) Curve is the same as overload long delay, but curve speed is 10 times faster Standard + OFF
Note: When controller is frame I (Inm=2000A), rectified value of short time-delay protection is 1.5 Ir1~15 Ir1; when controller is frame II (Inm=3200A, 4000A), rectified value of short time-delay protection is 1.5 Ir1~15 Ir1 and max is 40kA; When controller is frame III (Inm=6300A), rectified value of short time-delay protection is 1.5 Ir1~15 Ir1 and max is 50kA. g. Instruction to short circuit instantaneous property
Ir3= Setting current Acting property 1.01n~50kA/65kA/75kA+OFF (Exit position) 0.85Ir3 without actions 1.15Ir3 with actions
Note: When controller is frame I (Inm=2000A), rectified value of instantaneous protection is 1.0In~50kA+OFF; when controller is frameII (Inm=3200A), rectified value of instantaneous protection is 1.0In~65kA+OFF; When controller is frame III (Inm=6300A), rectified value of instantaneous protection is 1.01n~75kA+OFF. h. Earth fault or residual current protective property: t=TGKGIf /I
Earth fault protection If= Setting current Acting property Earth fault protection TG = Inverse-time (s) (Corresponding 2Ir1) Inverse-time cutting coefficient KG Precision If= Setting current Acting property Property curve Delay (s) TG = Precision (0.1~1.0)s + OFF (Level difference 0.1s, OFF means it only alarms without tripping.) (1.5~6)s+OFF (Level difference 0.5, OFF means earth fault is definite-time) 10% (intrinsic 40ms) (0.1~1.0)Io + OFF (Level different 0.01A, OFF means exit position) 0.8If without actions 1.0 If delayed action Curve 1~curve 5, could be rectified, rectified as curve 3 for ex-factory (1.5~6)s + OFF (Level difference 0.5s, OFF means is definite-time) 15% (0.2~0.8)In + OFF (with 160A as the minimum and 1200A as the maximum. OFF means it only alarms without tripping) 0.8If without actions 1.0 If delayed action
> >>
C-124
NA1
Wiring diagram of earth fault protection 3PT type
CT
4PT type
CT L1 L2 L3 N PE
(3P+N) T method
CT L1 L2 L3
L1 L2 L3 PEN
intelligent controller
N PE
L1 L2 L3 N
intelligent
ZT100
intelligent controller
intelligent controller
controller
PE or PEN
10000
5000 2000 1000 500 200 100 50 tr2=60s t1=(15~480)S Ir1=(0.4~1)In Ic1=(0.2~1)In Ic2=(0.2~1)In
t(a)
5 2 1 0.5
t(a)
5 2 1 0.5 tr1=1/2tL
xIn
xIn
C-125
> >>
NA1
Technical parameter:
Load monitor type 1 IC1= Rectified current Acting property Property curve Curve speed Ic2= Rectified current Maximal inversetime delay (s) Acting property Property curve Curve speed (0.2~1.0)In + OFF (OFF means exit position) 1.05Ic1 without action 1.21c1 delay relay action The same as overload long delay Could be set separately (Setting content is the same as that of overload long delay) (0.2~1.0)In + OFF (OFF means exit position) 1.05Ic2 without action 1.21c2 delayed relay The same as overload long delay Could be set separately (Setting content is the same as that of overload long delay)
Inverse-time (s)
Load monitor type 2 Ic1= Rectified current Acting property Property curve Inverse-time (s) Rectified current Fixed delay (s) Precision Thermal memory (30min, could be eliminated while power-off) Curve speed Ic2= Acting property (0.2~1.0)In + OFF (OFF means exit position) 1.05Ic1 without action 1.21c1 delay relay action The same as overload long delay Could be set separately (Setting content is the same as that of overload long delay) (0.2~1.0)In + OFF (OFF means exit position) 0.9Ic2 without action Fixed as 60s 10% (Intrinsic 40ms) Standard + OFF
k. Communication networking Make key-lock at communication position, connect to # # secondary terminals 10 and 11 through cable to achiveve the communication function. Profibus-DP protocal networking
Rt
Rt RS232 RS485
Converter
ST-DP
RS485
ST-DP
ST-DP
NA1
Monitor host
NA1
NA1
Monitor host
> >>
C-126
NA1
15. Accessories
15.1 Under-voltage release Without power supply, under-voltage release can't close. It is classified into instantaneous and time-delay type. Delay time 0, 1s, 2s, 3s, 4s, 5s, 6s, 7s are fixed for NA1-1000; 1s, 3s, 5s are fixed for NA1-2000, 3200, 4000, 6300. Within 1/2 time-delay range, circuit breaker does not trip when power voltage recovers and exceeds 85%Ue. Characteristic
Type Rated control power voltage Us(V) Action voltage(V) Reliable making voltage(V) Reliable non-making voltage(V) Power loss(W)
NA1-2000, 3200, 4000, 6300 AC400, 230, 127 (0.35-0.7)Us (0.85-1.1)Us 0.35Us DC220, 110
20VA
48VA
Optional configure: Auto suction type under-voltage release, and this device can substitute normal one, it can prvent mechanism form misoperation. Make sure there is power supply on the under-voltage release, before making the circuit breaker. 15.2 Shunt release Shunt release can realize the remote control to break the circuit breaker. Characteristic
Type Rated control power voltage Us(V) Work voltage Power loss Breaking time 56VA
NA1-2000, 3200, 4000, 6300 AC400, 230, 127 300VA (30~50)ms DC220, 110 134W 75W
(5010)ms
Forbid making the power for long time to avoid the shunt release being damaged. 15.3 Closing electromagnet After the motor finishing the energy storage, closing release can instantly close the circuit breaker. Characteristic
Type Rated control power voltage Us(V) Work voltage (V) Power loss (W) Closing time 56VA
NA1-2000, 3200, 4000, 6300 AC400, 230, 127 300VA 70ms DC220, 110 134W 75W
(5010)ms
Forbid making the power for long time to avoid the closing release being damaged.
C-127
> >>
NA1
15.4 Motor-driven energy-storage mechanism With the function of motor-driven energy storing and auto restoring energy after closing the circuit breaker, the mechanism can ensure closing the circuit breaker instantly after breaking the circuit breaker. Manual energy-store is available. Characteristic
Type Rated control power voltage Us(V) Work voltage (V) Power loss (W) Energy-storage time Operation frequency 75VA <4s
NA1-2000, 3200, 4000, 6300 AC400, 230, 127 85/110/150W <5s No more than 3 times per minute DC220, 110 192W
15.5 Auxiliary contact NO Standard model: 4NO(normal open)/4NC(normal close) and 6NC(normal close). Characteristic
Type
NA1-1000 AC230 6 300VA AC400 6 100VA DC220 0.5 60W AC230 6 300VA
15.6 Doorcase Installed on the door of the distribution cubicle, for sealing the distribution cubicle and making the protection class to IP40( fixed type and drawout type).
15.7 Phases barrier Installed between the busbars to increase the creepage distance.
15.8 Operation pushbutton lock Used for locking the break pushbutton and the close pushbutton. ( Padlock is prepared by users)
15.9 Transparent shield (NA1-2000) Installed on the doorcase of the cubicle's small door, make the protection class to IP54. It is suitable for the fixed, drawout type circuit breaker and the load switch.
> >>
C-128
NA1
15.10 Off position locking mechanism When the circuit breaker is disconnected, padlock can be used to lock it after pulling out the lock lever, then the circuit breaker can't be Test or connected position.( Padlock is prepared by users) 15.11 Key lock Lock the circuit breaker on the OFF position, then the circuit breaker can't be closed. Locks and keys will be provided by us. Separate lock and key is matched with one set of the circuit breaker. Three same locks and two same keys are matched with three circuit breaker. Note: Before pulling out the key, the break pushbutton should be pressed first, rotate the key anticlockwise, then pull it out.
NA1Install the locking system
1. Components of the locking system:
washer
key
into
4. Push the red button ON, and take the key out, then install the cover.
15.12 Cable mechanical interlock It can realize the interlock of two horizontal or vertical-installed, three poles or four poles , drawout type or fixed type circuit breaker. a. If need bend the cable, make sure the radian is more than 120. b. Check and make sure enough lubricating oil of the cable. c. The maximal distance between two interlock circuit breaker is 2m.
2m(max)
Circuit diagram
1QF
2QF
1QF 0 0 1
2QF 0 1 0
Notes: a. when the steel cable needs to be bent, enough transition arc should be reserved to guarantee flexible movement of steel cable; b. check the steel cable and make sure there is enough lubricant in the steel cable to guarantee flexible movement of steel cable.
C-129
> >>
NA1
15.13 Connecting-rod type mechanical interlock Three vertical-installed three-poles or four-poles, drawout-type or fixed type circuit breakers realize the interlock between one breaker with another two different-state breakers.
Circuit diagram
Manner 1: three power supplies are provided for one circuit breaker only
1QF
2QF
1QF 0 0 1
2QF 0 1 0
15.14 Drawer base misplug-proof device (NA1-1000) Only the matched circuit breaker body could inserted to the drawer base. When not matched, it can't be inserted.
Bracket 2
Nameplate
Match
Mis-match
Mis-match
> >>
C-130
NA1
16. Regular malfunction and solutions
Fault description Reasons analysis Maintenance method 1. 2. 3. 4. 1. 2. 3. 4. 5. 1. 2. 3. 4. Check the breaking current value and operation time of intelligent release. Analyze the load and electric network, exclude the overload if it happens. Match the actual operating current with long time-delay current setting value. Press the reset button to reclose the breaker Check the breaking current value and operation time of intelligent release. Exclude the short circuit fault if it happens Check the setting value of intelligent release Check the normal state of breaker Press the reset button to reclose the breaker Check the breaking current value and acting time of intelligent release. Exclude the earthing fault if that happens. Match the fault current setting value with the actual protection. Press the reset button to reclose the breaker.
Short circuit tripping (IsorIiindicator flashing) Tripping of circuit breaker Earthing fault tripping (IG indicator flashing)
Under-voltage release fault: 1. Rated working voltage is less than 70%Ue 2. Fault of control unit Mechanical interlock acting Intelligent release don't reset (panel is raised) The breaker can't be closed Secondary circuit of drawerouttype breaker isn't connected
1.Check the power is on or not 2.Check the power voltage of under-voltage release, it shouldn't be less than 85%Ue. 3.Replace the control unit of under-voltage release Check the working state of two circuit breakers fixed with mechanical interlock Press the reset button to reclose the breaker Make the breaker to "making" position ("click" sound will be heard) Check the secondary circuit: 1. Power voltage of motor shouldn't less than 85%Ue. 2. Check the storage mechanism, replace it if necessary. Check the working state of two circuit breakers fixed with mechanical interlock
Mechanical interlock acting leads to locking of breaker The breaker can't be closed Closing electromagnet: 1.Rated control voltage is less than 85%Us; 2.Closing electromagnet is damaged Tripping immediately: 1. Short circuit current is closed 2.Delay tripping because of transient current is high when closing; 3. Overload current is closed The breaker can't be opened manually 1. There is fault with mechanical operating mechanism The breaker can't be opened by motor remotely 1. There is fault with mechanical operating mechanism 2. Power voltage of shunt release is less than 70%Us; 3. Shunt release is damaged
1. Power voltage of closing electromagnet shouldn't less than 85%Us. 2. Replace the electromagnet.
1. 2. 3. 4. 5. 6.
Check the breaking current value and operation time of intelligent release; Exclude the short circuit fault if it happens; Exclude overload fault Check the normal state of breaker Modify the current setting value of intelligent release Press the reset button to reclose the breaker
1. Check the mechanism, if there is fault happened. 2. Check the Power voltage of shunt release is less than 70%Us or not 3. Replace shunt release
C-131
> >>
NA1
Fault description Reasons analysis Manual storage can't be realized Motor storage can't be realized 1.Power voltage of motor energy-stored device is less than 85%Us; 2.There is mechanical fault with energy-storage device 1. There is padlock at the "opening" position 2. Slideway or breaker body isn't pulled into its position 1.Handle isn't pulled out 2.Breaker is not totally at the opening" position Maintenance method Mechanical fault with the energy-storage device
1. Power voltage of motor energy-stored device shouldn't less than 85%Us 2. Mechanical fault with the energy-storage device
Handle of drawerouttype circuit breaker can't be drawn in or out Drawerout-type breaker can't be drawn out at the "opening" position
1.Take away the padlock 2.Pull the slideway or breaker body into its position
1.Pull out the handle 2.Keep the circuit breaker totally at opening position
1. Something drop into the drawer base, and lock the mechanism or mechanism fault happens. 2. Breaker body not match with the frame-size rated current of drawer base 1. Release isn't connected with power 2.There is fault with release Closing electromagnet: 1. Rated control voltage is less than 85%Us; 2. Electromagnet is damaged Fault happened with intelligent release
1. Check and clean the drawer base, or contact with manufacturer 2. Match the body with relevant drawer base
1.Check the power is connected or not 2.Cut off the power, then connect again. Otherwise contact with manufacturer 1. Check the electromagnet power voltage shouldn't be less than 85%Us. 2. Replace the closing electromagnet. Cut off the power, then connect again. Otherwise contact with manufacturer
> >>
C-132
NA1
NA1-1000 Orde sheet
Customer: Quantity:
Model Rated current In ( A ) Installation mode Number of poles NA1-1000 200 4 00 63 0 8 00 10 00 Drawerout type Three poles Fixed type Four poles
Tel:
Date:
Conventional setting before delivery: IR=1In, 30s, Isd=8In, Tsd 0.4s; Ii=12In; Ig=OFF tg=0.4s Long time-delay protection IR Short circuit short timedelay protection Isd Short circuit instantaneous protection Ii Earthing protection Ig Current setting: Time setting: Current setting: Time setting: Current setting: Current setting: Time setting: In (0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1, OFF) s (30, 60, 120, 240) IR (3, 4, 5, 6, 7, 8, 10,OFF) s (0.2, 0.4) In (3, 4, 6, 8, 10, 12, 15, OFF) In (0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, OFF Min100A) s (0.2, 0.4, 0.6, 0.8)
Standard M type
Protection data setting: LED display; Test function; Fault recall; Self-diagnose function; MCR and HSISC function; Fault breaking indication Intelligent controller Optional function Exceed skipping function Overload alarm Self-diagnose alarm Earthing fault alarm Fault breaking alarm
Conventional setting before delivery: IR=1In, 17.2s,; Is=6IR, Isd=8IR; Tsd 0.4s; Ii=12In; Ig=OFF tg=0.4s Long time-delay protection IR Short circuit short timedelay protection Isd Instantaneous protection Ii Earthing protection Ig Current setting:(0.4~1)In Time setting(1.5In): 0.61, 0.98, 1.47, 2.46, 3.68, 4.91, 6.14, 8.29, 11.1, 17.2, 24.6, 36.8, 49.1, 61.4, 73.7, 86s Current setting: (1.5~15)IR + OFF Time setting: (0.1~0.4)s Current setting: (1.0~20)In+OFF Current setting: (0.2~1.0) In Time setting: (0.1~1)s
Communication H type
LCD display; Code switch and toggle switch; Fault recall; Self-diagnose function; LED indication; Clock Peak current recall;Test function: Earthing current measuring; Thermal recall fuction; Earthing fault alarm; Phase protection; unbalanced current protection; MCR making and breaking function; Fault recall; Optional function Other Modbus communication Display of power Profibus-DP communication Display of voltage Display of frequency
Over voltage/under voltage protection Phases protection AC230V DC220V DC110V DC24V
delay
AC400V AC230V Shunt release: AC400V AC230V DC220V DC110V Electrical accessories Closing electromagnet: AC400V AC230V DC220V DC110V Motor for breaker: AC400V AC230V DC220V DC110V Auxiliary contact: 2NO(normal open)and 2NC(normal close) 3NO(ornmal open)and 3NC(normal close) Busbar Special requireme nts Horizontal Connection Vertical Connection Phases barrier Steel cable interlocking Off position locking device
Note: 1) Please mark or fill figure in the relative if no mark, we will provide according to conventional.
NA1-1000
C-133
> >>
NA1
NA1-2000~6300 Orde sheet
Customer: Quantity:
Model Rated current (In)A Installation mode Number of poles M-typ e sta ndard typ e (default configuration) NA1-2000 630 8001000 1250 1600 2000 Drawerout type Three poles Protection function NA1-3200 2000 2500 3200 NA1-4000 4000 NA1-6300 40005000 6300(only 3 poles)
Tel:
Date:
Fixed type (note: =In 4000A fixed type is not available) Four poles Others functions Optional function Display of voltage Display of frequency Display of power factor Display of power Function of monitoring load ! Not items to be selected necessarily, cost of the increased will be calculated additionally
1. Ir1 protection for overload long time-delay, Ir2 inverse-time protection + definite time-delay protection for short-circuit short time-delay, Ir3 instantaneous protection for short-circuit, Ir4 4-section protection for single-phrase earthing. 2. Ir1 protection for overload long time-delay, Ir2 definite time-delay protection for short-circuit short time-delay, Ir3 instantaneous protection for short-circuit, Ir4 4-section protection for single-phrase earthing.
1. Ir1 protection for overload long time-delay, Ir2 definite time-delay protection for short-circuit short-delay, Ir3 instantaneous protection for short-circuit, 4-section protection for single-phrase earthing. 2. Ir1 protection for overload long time-delay, Ir2 inverse-time protection + definite time-delay protection for short-circuit short time-delay, Ir3 instantaneous protection for short-circuit, 4-section protection for single-phrase earthing.
Intelligent controller
1. Function of current meter 2. Function of self-diagnosis 3. Function of setting 4. Function of test 5. Function of display
Explanation: Available set range of protection function and conventional setting before delivery
Available set range of Ir1 long-delay current:0.4~1In Conventional setting before delivery: overload long time-delay: 1.0In Available set range of operating time with overload 1.5In: 15, 30, 60......480s Conventional setting before delivery: overload 1.5In, operating 15s ! Conventional setting before delivery: short time-delay current 8Ir1 Available set range of current of Ir2 short-delay; Operating time of short-delay: 0.1~0.4s ! Conventional setting before delivery: operating time of short time-delay: 0.4s 0.1~0.4s Available set range of Ir3 instantaneous current : 1.0 In~50kA/75kA/100kA ! Conventional setting before delivery: 12In Available set scope of Ir4 earthing protection current: 0.2~0.8 In; Available set scope of operating time of earthing protection: 0.1~0.4s ! Conventional setting before ex-factory: 0.5 In;OFF
Electrical accessories
Power supply of controller Under-voltage release (default configuration) Shunt release (default configuration) Motor (default configuration) Interlocking device (cost will be calculated additionally)
AC380V, AC220V, DC220V, DC110V AC380V, AC220V, DC220V, customize Instantaneous Delay V
AC380V, AC220V, DC220V, DC110V Connecting-rod interlocking (only provided for drawer-type) Steel cable interlocking :( for both types of drawer-type and fixed-type) Button lock Key lock: ( for both types of drawer-type and fixed-type) Door interlock (open or closed position) Door interlockstatus of ON/OFF
(Optional) (Optional)
Special requirements
Function of earthing protection with external mutual-inductor (Mutual-inductor is prepared by the user)
Connection of main circuit Explanation of vertical connection (prepared with vertical bus-bar): conventional supply is horizontal connection Revolving bus-bar (Drawerout type In3200) (cost of the increased will be burden by the user) Remark: Current of frame size, rated current, and auxiliary control voltage must be indicated when ordering Note: 1) Please mark or fill figure in the relativeif no mark, we will provide according to conventional factory settings. 2) For ordering products with optional function or special requirements, please contact with us.
NA1-6300
NA1-4000
NA1-3200
NA1-2000
> >>
C-134
NA1
Configurations explanation
1. NA1-2000~6300 fundamental configurations a. Motor-driven: Under-voltage instantaneous release; Shunt release; Closing electromagnet; Motor driven operating mechanism; 4 suits of transform contact; M-type Intelligent Controller; Horizontal wiring of main circuit; Doorcase; Element of main circiut; Operating instructions of Air Circuit Breaker; Packing box; Drawer seat (Drawout type) b. Manual: Under-voltage instantaneous release; 4 suits of transform contact; M-type Intelligent Controller; Horizontal wiring of main circuit; Doorcase; Element of main circuit; Operating instructions of Air Circuit Breaker; Packing box; Drawer seat(Drawout type) 2. NA1-1000 fundamental configurations a. Motor-driven: Under-voltage instantaneous release; Shunt release; Closing electromagnet; Motor driven operating mechanism; 4 normal open and 4 normal close auxiliary contacts; M-type Intelligent Controller; Closing and breaking push button lock; Horizontal wiring of main circuit; Doorcase; Element of main circuit; Operating instructions of Air Circuit Breaker; Packing box; Drawer seat(Drawout type) b. Manual: Under-voltage instantaneous release; 4 normal open and 4 normal close auxiliary contacts; M-type Intelligent Controller; Horizontal wiring of main circuit; Closing and breaking push button lock; Doorcase; Element of main circuit; Operating instructions of Air Circuit Breaker; Packing box; Drawer seat(Drawout type)
C-135
> >>
NA1
3. Additional selective configurations(need extra cost) NA1-2000~6300 selective configurations explanation: Under-voltage time release(1s, 3s, 5s). Connecting-rod type mechanical interlock (Drawerout type). Cable mechanical interlock; Operation pushbutton lock; Key lock; Door interlock; Outer transformer with earthing protect function; Vertical bus bar; Rotating bus bar(In3200); Indication mechanism; Counter; Shield; 5 suits of transform contact. 4. Additional selective configurations(need extra cost) NA1-1000 selective configurations explanation: Breaking button locking device; Vertical bus bar; Mechanical interlock; Transparent cover; Multifunctional intelligent controller; Note: Please indicate the voltage when orderd If there is additional function and special requirement, please contact with the manufacturer.
> >>
C-136