Guide To Forms of Seperation
Guide To Forms of Seperation
Guide To Forms of Seperation
Section Preface Introduction Useful definitions What are forms of separation Fundamental objectives of separation Legal obligations Basics of separation Main considerations Detailed selection Decision tree Other considerations Illustrations Page 2 3 3 5 5 6 6 7 9 12 13 15
Useful Definitions
The Standard includes definitions relating to Assemblies. Those particularly relevant to the forms of separation of Assemblies include the following. Assembly Power switchgear and controlgear assembly (PSC-ASSEMBLY) Low-voltage switchgear and controlgear ASSEMBLY used to distribute and control energy for all types of loads, intended for industrial, commercial and similar applications where operation by ordinary persons is not intended. This includes floor standing or wall mounting distribution switchboards, panel boards, and motor control centres using electromechanical and/or electronic components. It does however specifically exclude individual devices and self-contained components which control a single circuit i.e. wall mounted starters and fuse switches. Functional Unit Part of an ASSEMBLY comprising all the electrical and mechanical elements including switching devices that contribute to the fulfilment of the same function. NOTE Conductors which are connected to a functional unit but which are external to its compartment or enclosed protected space (e.g. auxiliary cables connected to a common compartment) are not considered to form part of the functional unit Comprises all parts necessary to form a complete incoming or outgoing circuit. It includes the load current carrying device(s) and associated equipment, cable terminals, and control devices within the assembly, that are necessary to form the complete circuit. It excludes the connections from the unit to the busbars (busbar connections) and any insulation or shrouding with which they may be provided. It may consist of more than one compartment or enclosed protected space. Section Constructional unit of an ASSEMBLY between two successive vertical delineations. Usually considered to be a single full height column containing one or more functional units. One or more columns are required to complete an Assembly. Sub-Section Constructional unit of an ASSEMBLY between two successive horizontal or vertical delineations within a section. The area or space within a column identified and bounded by two adjacent and horizontal constructional members e.g. cross members or shelves. Compartment Section or sub-section enclosed except for openings necessary for interconnection, control or Ventilation Enclosure Housing affording the type and degree of protection suitable for the intended application. Provides protection for equipment against certain external influences from any accessible direction and against direct contact to a degree of protection of at least IP2X. Partition Part of the enclosure of a compartment separating it from other compartments. A component used to form the top, bottom, sides, front or back of a compartment or enclosure and which can be manufactured
from metal or an appropriate synthetic material. A devices integral housing may also satisfy this requirement. Barrier Part providing protection against direct contact from any usual direction of access. Used to achieve a form of separation, it must meet the requirement of at least IP2X. It can also take the form of insulating material in direct contact with the live part, e.g., heat shrink sleeving on a busbar. Alternatively it can be rigid insulation e.g. terminal shields or an earthed metal screen appropriately positioned relative to the live part(s). Duty Holder The term used within the Electricity At Work Regulations to refer to the person appointed to be responsible for the electrical equipment, systems and conductors and any work or activities being carried out on or near the electrical equipment. The Duty Holder must be competent and may be the employer, an employee, or a self-employed person.
These are much less precise requirements than normally expected in a standard. The forms of separation given are only typical and the means by which separation is achieved is subject to agreement between the user and the manufacturer. More fundamentally, no indication is given as to the objectives of separating an assembly. The benefits a particular form of separation may bring are not defined, conversely, nor are the disadvantages if an inappropriate selection is made.
Verification of separation is by application of the appropriate IP test to BS EN 60529 (IPXXB and/or IP2X).
Legal Obligations
As most National Standards, including BS EN 61439-1, are derived from International Standards, they reflect good practice but they do not fully encompass the requirements of local legislation. Indeed, the standards may not be legally binding. In the United Kingdom legal obligations take precedence over standards. For low-voltage assemblies the Low Voltage Directive (LVD) and the Electricity at Work Act are relevant and in particular, Regulation 14 of the latter must be respected.
Forms Of Separation
The Law
Regulation 14
No person shall be engaged in any work activity on or near any live conductor (other than one suitably covered with insulating material so as to prevent danger) that danger may arise unless:(a) it is unreasonable in all circumstances for it to be dead; and (b) it is unreasonable in all circumstances for him to be at work on or near it while it is live; and (c) suitable precautions (including where necessary the provision of suitable protective equipment) are taken to prevent injury
Clearly this regulation is pertinent and onerous when contemplating working within a partially energised assembly. There is no allowance for tolerable risk. If an assembly can reasonably be isolated prior to any covers being removed, it must be isolated. Where it is impractical to totally isolate an assembly prior to carrying out work within an assembly, the degree of separation, and the way in which the separation is achieved within the assembly should be considered in a risk assessment to be undertaken by the Duty Holder (see definitions). This risk assessment will consider all relevant factors including: (i) Work to be carried out, (ii) Mechanical protection afforded by any insulation and separation, (iii) Possibility of initiating a flashover, (iv) Likelihood of an electric shock.
Basics of Separation
Specifying the most appropriate form of separation for an assembly is not an easy matter. In specifying a form of separation the following should be considered: The consequences of isolating the assembly or part of, Nature of task to be performed, Competence of person undertaking work whilst the remainder of the assembly is energised.
Users and specifiers of assemblies are encouraged to consider in detail the application and then to follow the process outlined in the main considerations section, in order to determine the most appropriate form of separation required.
Application Needs
Isolation available for all internal operations (except changing fuse links)
Adjust setting and carry out limited maintenance in functional units, as applicable whilst adjacent circuits are live.
Connect and disconnect cables. Adjust setting and carry out limited maintenance in functional units, as applicable whilst adjacent circuits are live.
FORM 1 OR 2
FORM 3
FORM 4
Forms Of Separation
Having established the fundamental form for separation needed for an application, specific details must be considered. The IEC and EN versions of 61439-2 divide Forms 2, 3 and 4 into two sub-categories. However, within the requirements defined in the standards there are three fundamental ways of providing separation: Insulation of live parts, Partitions or barriers (metallic or non-metallic), Integral housing of a device.
Each has different attributes; clearly much depends on the agreement between user and manufacturer. In order to aid the agreement between user and manufacturer, BS EN 61439-2 includes a National Annex which further details the sub-categories by type of construction such as describing the location of terminals for external conductors and in some instances, the location of cable glands relative to the associated cable terminals. In making the appropriate choice the user needs to consider: The tasks to be carried out with the assembly partially energised adjusting relay setting, terminating large power cables, replacing components, etc. What tools may be used. Is there a risk of tools slipping and damaging insulation. Possibility of mechanical impact causing damage to the integrity of the separation. Is there a danger of small components falling from one compartment to another causing a hazard. Can temporary barriers be effectively used to supplement the protection provided by separation whilst work is being carried out. The additional safety that can be provided by the use of Personal Protective Equipment. The anticipated level of skill of those carrying out any work within the assembly.
Form 2b
Type 1
Busbar separation is achieved by insulated covering, e.g. sleeving, wrapping or coatings. Busbar separation is by metallic or non-metallic rigid barriers or partitions.
Type 2
With Form 1 all components including busbars and cable termination can, and usually are, in the same compartment. In order to safely work within the assembly it must be isolated upstream. Form 2 has the busbars separated from the functional units and, depending on whether 2a or 2b is selected the cable terminals may be separated from the busbars. However, as functional units are not separated from each other, Form 2 has little practical advantage over Form 1. In reality a Form 2 assembly without any additional barriers or screens must be isolated prior to the interior of the assembly being accessed.
Form 3b
Type 1
Busbar separation is achieved by insulated covering, e.g. sleeving, wrapping or coatings. Busbar separation is by metallic or non-metallic rigid barriers or partitions.
Type 2
Form 3 may permit work to be carried out within the functional unit, for example; routine maintenance, fault finding, replacement of fuse links. In selecting the constructional type the specifier must, bearing in mind there is no requirement for the terminals of one circuit to be separated from adjacent circuits, determine if there is benefit to be gained from separating the busbars from cable terminals. If there is advantage in having the busbars separated, the means of separation, sleeving or similar or rigid barriers must be determined based on the likely mechanical needs of the separation.
10
Type 2
Type 3
Terminals for external conductors not in the same compartment as the associated functional unit, but in individual, separate, enclosed protected spaces or compartments.
Form 4b
Type 4
Type 5
Type 6
Type 7
Form 4 provides many variants which offer different opportunities in use. Selecting the most appropriate needs a very detailed understanding of the application and a logical thought process to arrive at the most suitable solution. The following flow chart may assist in this exercise.
11
Forms Of Separation
Form 4
NO
Is there a need for clear demarcation between the functional unit and the associated
YES
YES Type 1
Light physical work only to be undertaken in the functional unit and cabling areas, e.g. adjustment of settings, fault finding, replacement of fuse links. The termination of power cables without isolation of the assembly or the use of supplementary protection is not required.
YES
Type 4
NO
Work may need to be carried out within the functional unit, e.g. routine maintenance, fault finding, replacement of fuse links. The termination of power cables without isolation of the assembly or the use of supplementary protection is not required.
YES
NO
Type 5
NO
Work may need to be carried out within the functional unit, e.g. routine maintenance, fault finding, replacement of fuse links. Cables may need to be terminated adjacent to live cable cores insulation on the cable core is considered to provide adequate mechanical protection.
YES Type 2
YES
Type 6
NO
Work may need to be carried out within the functional unit, e.g. routine maintenance, fault finding, replacement of fuse links. Heavy cables may need to be terminated adjacent to live cables added mechanical protection of cable armour up to cable box/area considered necessary. Supplementary protection is not required.
NO
YES
Type 7
12
13
Forms Of Separation
BS 7671 (UK wiring regulations) prescribes that except for a main switch intended for operation by ordinary persons, in a TN-S or TN-C-S system the neutral conductor need not be isolated or switched where it can be regarded as being reliably connected to earth by a suitably low impedance. The neutral conductor of a circuit may remain connected when the line conductor(s) of that circuit are isolated. This could be a hazard because a voltage difference between a neutral and earth can be present. Prior to undertaking work on the circuit it must be ascertained if the capacity to deliver a harmful electric shock exists. In a TN-S or TN-C-S system, a harmful touch voltage due to load current in the neutral is unlikely, where the circuit conductors have been sized to comply with the voltage drop constraints in Table 12A of BS 7671. Nevertheless, a competent person must complete a risk assessment and appropriate test(s) to confirm that, the exposed neutral connection within the assembly is not a hazardous live part. In particular, The (UK) Electricity at Work Regulations 1989 including any amendments must be complied with. 7. Safe Working with adjacent equipment energised Switchboard manufacturers cannot give all embracing assurances for safe working, according to the form of separation with parts of the assembly energised. Specifying a particular form of separation will not guarantee this for any given form number. Effectively this means that where live working is being contemplated a risk assessment and judgement must be made for every situation by the Duty Holder. 8. Cost Higher forms of separation, generally lead to larger and structurally more complex assemblies and therefore higher costs. For the most cost effective solution the lowest level of separation that meets the needs of the application should be specified.
14
15
Forms Of Separation
16
Forms Of Separation
17
Forms Of Separation
18
Forms Of Separation
19
Forms Of Separation
20
Forms Of Separation
21
Forms Of Separation
22
FormsOf Separation
23
Forms Of Separation
24
Forms Of Separation
25
Forms Of Separation
26
Forms Of Separation
27
Forms Of Separation
28
Forms Of Separation
29
Forms Of Separation
The information within this document is taken from the BEAMA Guide To Forms Of Seperation and as such should be used for reference only.
30