Anderson Separator: Fuel Gas Skid General Arrangment - 250 Psig
Anderson Separator: Fuel Gas Skid General Arrangment - 250 Psig
Anderson Separator: Fuel Gas Skid General Arrangment - 250 Psig
Service Main Inlet Main Inlet Main Outlet Hot Gas Inlet Hot Gas Outlet Drain Instrument Air
Client Tie-in Schedule Material Schedule Flange Rating Remarks Line Type SA-106-B 80 300# Carbon Steel 30A2 SA-106-B 80 300# Carbon Steel 30A2 SA-312-304/3104L 80 300# Stainless Steel 30M0 SA-106-B 80 300# Carbon Steel 30A2 SA-106-B 80 300# Carbon Steel 30A2 SA-106-B 80 150# Carbon Steel 15A2 SA-106-B 80 150# Carbon Steel NA
96.000
SSPC-SP10 SSPC-SP10
Paint Requirements:
Internal Surfaces: External Surfaces: Primer: IAW PDVSA Standards - Primer @ 2-3 Mils DFT IAW PDVSA Standards -Paint @ 2-3 Mils DFT None
FI-2113103
Top Coat:
General Notes
1. All Dimensions Shown with Inches Unless Noted Otherwise. 2. Bolt Holes to Straddle Vessel Centerlines Unless Noted Otherwise.
FLOW 54.228
3. All Welds to be Visually Inspected 4. Unless otherwise Noted Tolerances Are Per Clark-Reliance Standard Specifications. 5. Inlet and Outlet to be Permanently Identified. 6. Vessels - Design and Fabrication IAW ASME Section VIII Division 1 - 2004 Edition - 2006 Addenda
E B
7. Piping - Design and Fabrication IAW ASME B31.1. 8. Structural - Design and Fabricatin IAW AWS D1.1 9. System - Design IAW SWPC Specification 10.Use a 4 Point Lifting Arrangement when Lifting the Assembled Skid.
9.000 0 0
Electric Heater EH-2113102/202/302/402/502/602 Code of Construction ASME section VIII Div. I - 2004 Edition Description 165 kW Circulation Heater 480 V, 3 Phase - 50 Hz Design Pressure 550 PSIG Design Temperature +20 F / 300 F Operating Flow Rate 4 mmscfd Corrosion Allowance 0.0625" Materials of Construction Carbon Steel Size 10" NPS X 94" OAL Heat Exchanger E-2113102/202/302/402/502/602 Code of Construction ASME section VIII Div. I and TEMA -C Description Shell and Tube - 08-096 Type E Design Pressure Shell 550 PSIG / Tube 655 PSIG Design Temperature Shell / Tube +20 F / 300 F Operating Flow Rate 4 mmscfd Corrosion Allowance 0.0625" Materials of Construction Carbon Steel Size 8" NPS X 96" OAL Coalescer - FI-2113103/FI-2113104 Code of Construction ASME section VIII Div. I - 2004 Edition 2006 Addenda Description Coalescing Design Pressure 550 PSIG Design Temperature 300 F Operating Flow Rates 4 mmscfd @ 325 PSIG & 146 Deg. F Corrosion Allowance 0.0625" Materials of Construction Carbon Steel Size 12" NPS x 82 Seam to Seam Filters 2710E2 (qty 1) Removal Efficiency 100% Solids & Liquids - 5 micron or Greater
24.000
65.688
264.000
268.000
FLOW
FLOW
A B 54.375
Package Tagging - X-21131152/252/352/452/552/652 Coalescer Electric Heater Heat Exchanger FI-2113103/2113104 EH-2113102 E-2113102 FI-2113203/2113204 EH-2113202 E-2113202 FI-2113303/2113304 EH-2113302 E-2113302 FI-2113403/2113404 EH-2113402 E-2113402 FI-2113503/2113504 EH-2113502 E-2113502 FI-2113603/2113604 EH-2113602 E-2113602
D E 26.375
ANDERSON SEPARATOR
16.375 F
Drawing Schedule Description Drawing Number Piping & Instrument Diagram 51L6438-250-PNID General Arrangement Drawing51L6438-250-GA Foundation Loading Diagram 51L6438-250-SBFL Electrical Wiring Diagram 51L6438-250-EWD
G 14.375
16633 FOLTZ PARKWAY STRONGSVILLE, OHIO 44149 PHONE: 440-572-1500 FAX: 440-238-8828
0
Customer: Project Name: P.O. No.: Service: Tag No.:
Document Tag
Jantesa Corparation Gas Anaco Project - Santa Rosa Venezuela 7662-03-M-995-PO-800-E Fuel Gas Conditioning Skid X2113152
THIS DRAWING AND ALL INFORMATION ON IT IS THE PROPERTY OF THE CLARK-RELIANCE CORPORATION. IT IS CONFIDENTIAL AND IS GIVEN TO YOU FOR A LIMITED PURPOSE AND MUST BE RETURNED ON REQUEST. NEITHER THIS DRAWING NOR ANY PART OF IT NOR ANY INFORMATION CONCERNING IT MAY BE COPIED, EXHIBITED OR FURNISHED TO OTHERS NOR MAY PHOTOGRAPHS BE TAKEN OF ANY ARTICLE FABRICATED OR ASSEMBLED FROM THIS DRAWING WITHOUT CONSENT OF THE CLARK-RELIANCE CORPORATION.
SHEET 1 OF
51L6438-250-GA
Mark A B C D E F G
Service Main Inlet Main Inlet Main Outlet Hot Gas Inlet Hot Gas Outlet Drain Instrument Air
Client Tie-in Schedule Material Schedule Flange Rating Remarks Line Type SA-106-B 80 300# Carbon Steel 30A2 SA-106-B 80 300# Carbon Steel 30A2 SA-312-304/3104L 80 300# Stainless Steel 30M0 SA-106-B 80 300# Carbon Steel 30A2 SA-106-B 80 300# Carbon Steel 30A2 SA-106-B 80 150# Carbon Steel 15A2 SA-106-B 80 150# Carbon Steel NA
Package Tagging - X-21131152/252/352/452/552/652 Coalescer Electric Heater Heat Exchanger FI-2113103/2113104 EH-2113102 E-2113102 FI-2113203/2113204 EH-2113202 E-2113202 FI-2113303/2113304 EH-2113302 E-2113302 FI-2113403/2113404 EH-2113402 E-2113402 FI-2113503/2113504 EH-2113502 E-2113502 FI-2113603/2113604 EH-2113602 E-2113602
Client Tie-in - B Main Gas Inlet 3" 300# RF CS Buttefly Valve Manual Operation Client Tie-in - A Main Gas Inlet 3" 300# RF CS Buttefly Valve Manual Operation
3" 300# Butterfly Valve With Actuator/Limit Switches and Solenoid Valve
Thermal Relief Valve 1" 300# X 1" 150# FI-2113103 12" NPS Fuel Gas Filter/Separator E-2113102 Shell and Tube Heat Exchanger API Basco 1435-08-096-005
FI-2113104 12" NPS Fuel Gas Filter/Separator Vent 1" 300# RF Ball Valve
3" 300# Level Control Valve Client Tie-in - G Instrument Air 1" 150# RF
Ground Pad
Skid Base W8 X 35 Wide Flange with 1/2" Thick Deckplate Junction Box
ANDERSON SEPARATOR
16633 FOLTZ PARKWAY STRONGSVILLE, OHIO 44149 PHONE: 440-572-1500 FAX: 440-238-8828
Document Tag
Jantesa Corparation Gas Anaco Project - Santa Rosa Venezuela 7662-03-M-995-PO-800-E Fuel Gas Conditioning Skid X2113152
PART NO.: GKOE40273BA1A CHECKED: ND DRAWN: CMN SCALE: NTS DATE: 10/2/07 REV. 0 REVISION: 0 PER CDC-07-xxx DRAWING NUMBER: 2
SHEET 2 OF
51L6438-250-GA