Contador Hanyoung GE4
Contador Hanyoung GE4
Contador Hanyoung GE4
Electric Sensor, Rotary Encoder, Optical Fiber Sensor, Pressure Sensor - ANALOG : Timer, Temperature Controller HEAD OFFICE 1381-3, Juan-Dong, Nam-Gu Incheon, Korea TEL: (82-32)876-4697 FAX : (82-32)876-4696
Specification
Model Appearance(mm) Power voltage a.c d.c GE4-P 48(W) 48(H) 84(D)mm 10 10 100 V-240 V d.c / a.c (50-60 Hz) 24 V - 60 V d.c / a.c (50-60 Hz) Max. 13.5 V a.c Max. 9 V A Preset P4 (P4 Digits) PV : 11 mm, SV : 8 mm Totalizer 6 Digits GE7-T
INSTRUCTION MANUAL
We appreciate you for purchasing HanYoung NUX Co.,Ltd product. Before using the product you have purchased, check to make sure that it is exactly what you ordered. Then, please use it following the instructions below.
Consumption a.c power d.c Type Display digit FND height Memory protection
Safety information
Before you use, read safety precautions carefully, and use this product properly. The precautions described in this manual contains important contents related with safety; therefore, please follow the instructions accordingly. The precautions are composed of DANGER, WARNING and CAUTION.
20. The warranty period for this product including parts is one year if this product is properly used. 21. When the power is on, the preparation period of contact output is required. In case of use for signals of external interlock circuit, use with a delay relay.
10 years (Nonvolatile memory) CP1, CP2, RESET, BATCH RESET (Preset type) [H]level 4-30 V d.c, [L]level 0-2 V d.c, Pull-up / Pull-down resistance connetion by NPN/PNP set (4.7
Coefficient Input 1(CP1) / Inhibit Input (INHIBIT) Terminal Counter during its use is used as coefficient input or inhibit input. Timer during its use puts a hold on the processing time. Coefficient Input 2(CP2) / Start (START) Terminal l Counter during its use is used as coefficient input or inhibit input. l Timer during its use can be used for Signal On Start or Signal One Start. (Refer to Output Action Mode) (SIGNAL ON START: Timer operates only with the continuous input.) (SIGNAL ONE START: Timer operates only with the supply of Input 1 Pulse.) BAT RESET l This is used as batch reset during the use of counter/timer. RESET l This initializes the coefficient value and current time during the use of counter/timer. OUT2 (OUT): This is used as the counter/timer comparative output. BAT.O: Batch Counter Output (Level 1 Setup Type) (BAT.O): Select between Level 1 Setup Output and Batch Counter Output (Level 2 Setup Type)
External output power ONE SHOT output Control output contact 0.01-99.99 s(OUT1, OUT2) 1 step 1c (OUT) 2 step 1a (OUT1), Ic (OUT2) 3 step NO contact: 250V a.c. 3A resistance load, NC contact: 250V a.c. 2A resistance load 1 step NPN 2 points 2 step 3 step Open collector 30V d.c. 100mA Max. comparative cycle : Every 2ms, Repeat set error: Max. 5ms
DANGER
Do not touch or contact the input/output terminals because they may cause electric shock.
(Batch Counter)
WARNING
1. If there is a possibility of an accident caused by errors or malfunctions of this product, install external protection circuit to prevent the accident. 2. This product does not contain an electric switch or fuse, so the user needs to install a separate electric switch or fuse externally. (Fuse rating : 250 V 0.5 A) 3. To prevent defection or malfunction of this product, supply proper power voltage in accordance with the rating. 4. To prevent electric shock or devise malfunction of this product, do not supply the power until the wiring is completed. 5. Since this product is not designed with explosion-protective structure, do not use it at any place with flammable or explosive gas. 6. Do not decompose, modify, revise or repair this product. This may cause malfunction, electric shock or fire. 7. Reassemble this product while the power is off. Otherwise, it may cause malfunction or electric shock. 8. It you use the product with methods other than specified by the manufacturer, there may be bodily injuries or property damages. 9. Due to the danger of electric shock, use this product installed onto a panel while an electric current is applied.
PRESET BATCH TOTAL (Indicator) 4 : 9999 (4 digit) 6 : 999999 (6 digit) 1 stage 2 stage 100 V-240 V a.c 24 V-60V d.c
Twin timer
Non-contact
Timer operating
Setting time : 100ms from POWER ON. Dielectrical strength 2000 V a.c 50 - 60 Hz for 1 minute Withstand noise Squard wave noise by noise simulator(l ms) +/-2 (Power supply input terminal) Vibration
Malfunction 10-55Hz Double amplitude width 0.5mm Durability
10-55Hz Double amplitude width 0.75mm 300 Min. 0.1millions (250 V a.c 2 A Resistance load) IP65 (Front part) (Without icing) , 35 ~ 85% R.H. (Without freezing and icing) Max.133 g CE Max.102 g -10 ~ 55
Power Supply
SOURCE
Shock
ms ms
Relay Life
Protection structure
CAUTION
1. The contents of this manual may be changed without prior notification. 2. Before using the product you have purchased, check to make sure that it is exactly what you ordered. 3. Check to make sure that there is no damage or abnormality of the product during delivery. 4. Do not use this product at any place with corrosive(especially noxious gas or ammonia) or flammable gas. 5. Do not use this product at any place with direct vibration or impact. 6. Do not use this product at any place with liquid, oil, medical substances, dust, salt or iron contents. (Pollution level 1 or 2) 7. Do not polish this product with substances such as alcohol or benzene. 8. Do not use this product at any place with excessive induction trouble, static electricity or magnetic noise. 9. Do not use this product at any place with possible thermal accumulation due to direct sunlight or heat radiation. 10. Install this product at place under 2,000m in altitude. 11. When the product gets wet, the inspection is essential because there is danger of an electric leakage or fire. 12. If there is excessive noise from the power supply, using insulating transformer and noise filter is recommended. The noise filter must be attached to a panel grounded, and the wire between the filter output side and power supply terminal must be as short as possible. 13. If gauge cables are twisted closely, the effect on noise may occur. 14. Do not connect anything to the unused terminals. 15. After checking polarity of terminal, connect wires at the correct position. 16. When this product is connected to a panel, use a circuit breaker or switch approved with IEC847-1 or IEC947-3. 17. Install the circuit breaker or switch at near place for convenient use. 18. For the continuous and safe use of this product, the periodical maintenance is recommended. 19. Some parts of this product have limited life span, and others are changed by their usage.
The first 100 ms after power input and 200 ms after power opening is the period designated for the ascent and descent of internal power and external output power. Therefore, in order to prevent malfunction from the incomplete output action of the external sensor, do not operate during the unstable period. Supply signal only after 100ms following the power input. Supply power only after 200 ms following the power shutdown.
Connection Diagram
GE4-P1(P41/P61)
[Unit]
GE4-P2(P42/P62)
Coefficient Indication Section (RED FND) Indicates coefficient (counter), progression time value (timer), batch coefficient, and setup items Setup Indication Section (GREEN FND) Displays setup value (counter), setup time (timer), batch setup value, instant output setup (batch set at 0 at the timer) and setup details SET1, SET2 (SET), BAT Indicates the status of coefficient section and setup section (BAT lamp corresponds to batch status.) TIM (Timer) This flashes when the timer progresses and remains lighted when the device stops from inhibit input or reset. (It is indicated in Change Mode of the device during TIM/TTWIN setup.) CNT (Counter) This is indicated during 1CNT/2CNT setup in Change Mode of the device. OUT1, OUT2(OUT), BAT.O (Output Action Indication) BAT.O lights up when the batch setup value is set. (OUT1 Output) BAT.O lights up and outputs when the device operates with the instant output where the batch setup value is 0 (timer). CP1, CP2, RST. Verification of Input Status (Exclusively for TOTAL) LOCK:Key Lock (KEY LOCK) Action IndicationThis lights up during Lock Setup. This key is for function setup Mode Entry and Mode change. It can also be used for ending after saving when changing the setup value Setup value change Entry and Location shift UP Key RESET KEY Batch and Operation Mode switchover key TOTAL Model does not have Setup Indication Section, SET1, SET2 and BAT Lamp. OUT1, OUT2, BAT.O change their use as CP1, CP2, RST Input Status Check Lamp. Level 1 Setup Model does not have SET1 and OUT1 Lamp, and SET2 is displayed as SET and OUT2 is displayed as OUT.
48
5.3
84.7 64.3
15
48
44.8
NPN Input
60
GE4-P1(P41/P61)
45 +0.6 0
60
45
+0.6 0
PNP Input GE4-T6 : TOTAL does not possess transistor and relay output.
As for Level 1 Counter (Out), it is the same as 2ND Output (OUT2) Action.
Select One Shot Output between 0.01ms~99.99ms One Shot Time Delay Self-Maintenance Output Self-Maintenance Output One Shot Output of OUT2 Output
Up - A Inhibit input
Input Mode
Level 1 Output Level 2 Output
Output Mode
Output Time
Up - B Inhibit input
s
Out1 Output time
s s
Batch Output Port Selection
Coefficient value indication continues on during START and OUT2 yields One Shot Output. Self-Maintenance Output of OUT1 is turned off when OUT2 is turned off. (Repetitive Action)
Level 1 Output Level 2 Output
Coefficient value indication is maintained during One Shot Time, and then resets. (Repetitive Action)
Up - AB Individual input
Prescale
n n-2 n-4
Reset Time
Coefficient value indication continues on. OUT2 yields One Shot Output. Self-Maintenance Output of OUT1 is turned off after One Shot Time of OUT2.
Level 1 Output
n-5 n-7 n-8
Power Cutoff
Level 2 Output
Coefficient value returns to the initial status, and coefficient value indication is maintained during One Shot Time. The processed coefficient value is indicated after One Shot Time. (Repetitive Action)
Key Lock
# Refer to Output operation Mode (Counter) 1 level setup type : display as OUT One short delay time (D setup is self-maintenance OUT2 Output output)) One short time setup Output Time No display for level 1 product Batch Set a BATCH output port ( or :Relay, :Transistor)
UP /Down - C Phase difference input UP/Down - F Phase difference input
BATCH Output Counting speed Deciaml point setup PRESCALE RESET TIME Memory Input Logic Key Lock
No display Output mode, OUT2 output time, OUT1 output time, and BATCH output setup items for TOTAL product. No display OUT1 output time and BATCH output setup for level 1 product.
/
Convert Operation Mode to Function Mode -> Press MD key for 2 seconds
: 1 level setup counter : 2 levels setup counter CP1,CP2 Dual inputs UP mode operatio : CP1,CP2 Dual inputs down mode operation # Refer to Input operation Mode (Counter) is set when contact is used with maxmum input speed Minimum signal width of external reset signal input : Coefficient value is saved when power failure : Coefficient value is initialized when power failure Convertible by dip switch : Key Lock remove : No use for all keys ( : No use for , , : No use for exception) keys
UP
Coefficient value increases and OUT2 yields One Shot Output. The device is reset after the One Shot Output. (Repetitive Action)
Level 1 Output Level 2 Output
Coefficient value is maintained and OUT2 yields One Shot Output. OUT1 and OUT2 are independent from one another. # If OUT1 is the same as SET1 setup value, it leads to One Shot Output or Self-Maintenance Output. (In case of Level 1 Setup Type, OUT is the same as OUT2.) # Reset refers to OUT1 and OUT 2 being turned off and coefficient value being initialized.
SET
-99999
During Down Mode, Set Value is first to decrease. 6 digits: When -999999(-999), it flashes and is no longer counted. During Up Mode, it increases to the maximum indication value, initializes to 0 and then increases again.
Input Method H L
PNP Setup Voltage Input 5-30 V d.c 0-2 V d.c O.C 5-30 V d.c OPEN Voltage Input 0-2V d.c 5-30 V d.c
For receiving Open Collector Input, Input Logic (PNP/NPN) Switchover Switch is embedded internally to Pull up / Pull down the resistance of 4.7 . (NPN Setup during shipment)
NPN
PNP
Input Logic Setup Status can be verified in Function Setup Mode. Internal Impedance is 4.7 , and switches over to Pull Up or Pull Down from NPN/PNP Selection. (Refer to Input Connection)
To prevent chattering during the use of Contact Input Counter, setup the coefficient speed at 1 or 30 cps in Function Setup Mode.
Timer Setup Operation Mode Press the Operation for two seconds. Device Change
9999 h h : hour
t
Runs when START (CP2) is On. Output is On during the set time, and the indicated value is initialized and output is Off when the set time elapses.
Runs when START (CP2) isOn from the initial setup value Maintains indicated value and controls output when exceeds the set time (One Shot Output for OUTT Setup)
Output Connection
Example of Non-Contact Output
Connect surge observer (diode, varistor) on the both ends of the load when using inductive load (relay etc.), and must use with GND since the internal circuit and non-contact output are isolated from one another. Calculate power load and load to prevent the non-contact output from exceeding the maximum of 30V 100mA.
Scale Change
0
Time range
Operation Mode
Output Time
Input Time
Surge Observer Relay Output Resistance : 220 Condenser : 0.1 Voltage : 630 V a.c
Avoid the flow of excessive current since it is AC250V NO 3A (load resistance) NC 2A (load resistance), and the connection must correspond to standard connection method.
t
Off
Runs when CP2 (START) isOnfrom the initial setup value, and resets when Maintains indicated value and controls output when exceeds the set time (One Shot Output for OUTT Setup)
[HOLD] Setup (when output time [OUTT] is set at 0{HOLD}) Setup Set Time in Run Mode Maintains the indication of initial value when Power is On Runs when becomes START (CP2). On/Off Repetitious Action of control output after reaching the Set Time. Initializes and stops when Reset is On ONE SHOT TIME Setup (when output time [OUTT] is set at more than 1) Setup Set2 Time in Run Mode. Maintains the indication of initial value when Power is On Runs when Power is On One Shot Output after reaching the Set Time. Initializes and stops when Reset is On
TTIM(TWIN TIMER)Setup Power ON RUN ON delay Power ON RUN OFF delay Signal One RUN ON delay Signal One RUN OFF delay
Key Lock
Input logic
/
: Timer : Twin Timer 10 (Decimal) / 60 (Sexagesimal) system 0.1sec~999999(9999)h UP/DOWN selectable Twin timer is not available with level 1 output model. Refer to output operation mode chart , , keys key exception) keys No use
Signal Addition
Signal Addition
CP1/INHIBIT function stops the time. [S.---] is activated when CP2 (START) is ON [S ---] is activated when CP2 is maintained ON, and resets when Off. [P ---] activates with Power On Setup as in order to compensate for interruption of electric power during Power Off (Indicates the Memorized Value when electric power is inputted again.)
When START (CP2) is On, output is also On and the time indicates the initial value. Time activates the initial value to run when START (CP2) is Off. The initial value is initialized and output is Off when the set time elapses.
SET
* Level 1 Setup Type Output is OUT. * INHIBIT (CP1) temporarily stops the time.
0 ON OFF
Even in the batch display state, counter/timer action operates normally. Batch coefficient increases at the output of OUT2 (OUT). Batch output is outputted as (BAT.O). (BAT.O lamp is lighted)
Press Keys.
SET display
BATCH display
Runs after initializing the process value upon the authorization of Run Reset Signal when Power is On Set Time is first to be reduced during Down Mode Setup.
Press Keys.
GE7-P62
Signal RUN
SET1 display
Press Keys. Press Keys.
SET2 display
Runs when START (CP2) is On, and resets when START (CP2) is Off Set Time is first to be reduced during Down Mode Setup.
BATCH display