0% found this document useful (0 votes)
186 views4 pages

Energytek Flame Switch Catalog

flame switch that can be compatible with Honeywell UV flame detector and various kinds of flame rod.

Uploaded by

hsihua
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
186 views4 pages

Energytek Flame Switch Catalog

flame switch that can be compatible with Honeywell UV flame detector and various kinds of flame rod.

Uploaded by

hsihua
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Energytek Corporation

Flame/UV detector Switch Instruction Sheet

Wire the switch


1. Wiring and overload protection should conform to local

electrical regulations

2. Verify that the wiring is correct before power on.

TYPICAL WIRING DIAGRAMS


FS-01

Flame/UV Detector Switch are essentially switches which, when used

with the appropriate sensors, can signal the presence or absence of a

flame or ultraviolet (UV) light and flame rod.

SPECIFICATIONS
ELECTRICAL RATING:115/230Vac (± 10 %),50/60 Hz.

CONTACT: 3 isolated DPDT contacts. Rating: 5A.

AMBIENT TEMPERATURE LIMITS:-10 to + 60 °C FRONT PANEL


MAXIMUM RELATIVE HUMIDITY:90% RH at + 40 ° C.

DEGREE OF PROTECTION:IP40

FLAME FAILURE RESPONSE TIME: Less than one second

CLASSIFICATION: CE LVD:SM2K09016, EMC:SE2K09028

INSTALLATION
IMPORTANT
1. Disconnect the power supply before beginning the CHECKOUT AFTER INSTALLATION
installation. Check the points on this list before starting the
2. Whenever possible, use the burner/boiler manufacturer’s system
instructions. If these are not provided, follow the instructions • That system overload protection is correct.
below. • That wiring connections are correct and that all terminal
ONLY FOR FS-01: you have an internal fuse to protect screws are tight.

your flame detector. • That the flame detector is correctly installed and that
Mounting the correct flame detector is being used.

1. The switch may be installed in any plane, but the • That the burner is completely purged and ready to fire
vertical is recommended. with the fuel lines purged of air.

2. Ensure that sufficient space is available to access the • That the combustion chamber and flues are clear of
switch for servicing or removal. fuel. That power is on at the system main switch.
Note that the following have an influence on flame detector * Indicates a marginal installation, a defect in the circuit or

performance. a detective component.

(1) Position, size and burning characteristics of the flame. ** Do not permit signal to exceed 5μA as it could shorten

(2) Ambient temperature at the detector (except flame rod). photocell life.

See detector instruction sheet.

(3) Refractory - When refractory temperature exceeds

1370° C12500° F, some ultra-violet radiation may occur.

Lower refractory temperatures may affect photocells;

see relevant data sheets.

(4) Temperatures of sensor

Flame rods: ensure suitable rod.

Other sensors: see relevant data sheets.


Energytek® Corporation
Honeywell®紫外線火焰偵測及火焰感應棒偵測開關使用說明

接線
1. 接線及過載保護須符合當地法規

2. 啟動前請再一次的確認接線是否正確

接線圖
FS-01

本偵測開關基本上是利用連接至本開關之合適的火焰棒或紫外線偵測

器,來檢知火焰或紫外線存在於否,以作動內部之繼電器,以達到控制

之目的。

規格
電源:115/230Vac (± 10 %),50/60 Hz

接點:3組獨立DPDT接點。電流:5A 前方面板
操作環境溫度:-10 至 + 60 ℃

操作環境最大溼度:90% RH at + 40℃

防護等級:IP40

火焰失效反應時間:小於一秒

認證字號:CE LVD:SM2K09016、EMC:SE2K09028

安裝
注意 安裝後確認
1. 安裝前請先移除電源。 啟動前請先確認下列之重點
2. 盡可能參照燃燒機或鍋爐廠商之操作手冊。如廠商無提供 •確認系統之過載保護是否裝置正確

操作手冊,請參照以下說明。 •確認接線是否正確,其接點固定螺絲是否鎖緊

僅限於FS-01:本檢知開關內部電路設有保險絲,以保護您的檢 •確認是否連接合適之火焰檢知器及其接線是否正確

知器 •確認燃燒機及燃料管路是否清氣完成以備啟動

•確認燃燒室及煙道是否淨空、主電源是否啟動

安裝
1. 本開關可裝置於控制箱之任何部位,安裝時請以垂直方式安裝。 注意:下列狀況可能會有影響火焰檢知器之性能

2. 安裝時確保留有足夠的空間以備日後維修或拆除之用。 (1) 火焰之位置、尺寸及其外觀特性

(2) 火焰開關之環境操作溫度(火焰棒除外)
(3) 斷熱材料-當斷熱材料的溫度超過1370℃(12500℉)時,斷熱材料

可能會產生紫外線。 * 表示最低限度之安裝,在電路上可能有缺陷請偵錯

(4) 檢知器溫度: **訊號電流請勿超過5μ安培,超過可能會降低光電元件之壽命

火焰棒或紫外線檢知器:確認是否使用合適之火焰棒或紫外線檢

知器。

其他檢知器:請參照相關資料

如低於最小操作限
度或不穩定*時請
火焰檢知器 建議使用電流
依下列說明執行檢

各種火焰棒
Honeywell®
C7004B
C7005A/B 充分的接地、
C7007A 2 - 5μA 火焰棒於火焰之適
C7008A 當位置
C7009A
C7011A
Q179A/B/C/D
紫外線檢知器
Honeywell® 適當的看見火焰、
C7012A/C/G 清潔視窗玻璃、
3 – 7.5μA
C7027A 不穩定的火焰信號
C7035A 代表看到局部火焰
C7044A