Oil in Service
Oil in Service
Oil in Service
Dr B Pahlavanpour, Nynas UK
2012-11-03
2012-11-03
Transformer Failure
Before 1930 Lack of transformer oil maintenance many kinds of oil in use Lack of specification for manufacture of oil Lack of standard for determining oil quality Lack of understanding of what transpires inside a transformer as it ages
2012-11-03
Nynas- 2012
2012-11-03
2012-11-03
Maintenance standard
IEC60422 Mineral insulating oils in electrical equipment Supervision and maintenance guidance.
IEEE C57, 106 IEEE Guide for acceptance and maintenance of insulating oil in equipment.
2012-11-03
2012-11-03
Aim
Prevent forced outage Eliminate unnecessary maintenance Provide the appropriate amount of maintenance at right time Prevent premature ageing
2012-11-03
10
2012-11-03
IEC60422 recommendation
Three group of tests are recommended:
Routine tests (Group 1) Complementary tests (Group 2) Special Investigative tests (Group 3)
11
2012-11-03
12
2012-11-03
13
2012-11-03
14
2012-11-03
15
2012-11-03
Group 2 tests
16
2012-11-03
Group 3 tests
Oxidation stability Flash point Compatibility Pour point Density Viscosity Polychlorinated biphenyls (PCBs) Corrosive sulphur 3 3 3 3 3 3 3 3 IEC 61125 ISO 2719 IEC 61125 ISO 3016 ISO3675 ISO 3104 IEC 61619
IEC 62535 ASTM D1275B DIN 51353
3 3
17
Oil sampling
It is essential that every effort be made to ensure that samples are representative of the insulating oil in equipment Sampling should be performed by an experienced person, who has received adequate training, in accordance with IEC 60475. Where available, manufacturers instructions should be followed.
18
2012-11-03
19
2012-11-03
20
2012-11-03
Categories of equipment
In order to take account of different user requirements, equipment has been placed in various categories as O, A, B, C, D, E, F, G O, 400 KV and above A, 170 to 400 KV B, 72.5 to 170 KV C, transformers <72.5 KV. OCB, switchgear D, Instrument transformers >170 KV E, Instrument transformers <170 KV F, Diverter tanks of on-load tap-changers G, Circuit breakers <72.5 KKV
21
2012-11-03
Recommended limits for mineral insulating oils after filling in new electrical equipment prior to energization
22 Subjectmatter, Name, Division 2012-11-03
23
2012-11-03
interpretation of results
should be performed by experienced personnel Characteristic values for the type and family of oil and equipment, developed by statistical methods Evaluation of trends and the rate of variation of the values for a given oil property Normal, or typical values, for fair or poor for the appropriate type and family of equipment
24
2012-11-03
Equipment category A
1 to 3
B
1 to 4
C
2 to 6
D
1 to 2
E
2 to 6
F
2 to 6
G
2 to 6
6 month or less, depending on the rate of decrease and the absolute value.
25
2012-11-03
26
2009
Oil tests
Field tests Only limited number of tests can be performed Obtain a prompt estimation of oil condition Establish the classification of service-aged oils Eliminate any changes to the oil samples properties due to transportation to a laboratory and/or storage of oil samples Laboratory tests More accurate A complete examination scheme of recommended tests can be performed
27
2012-11-03
28
2012-11-03
Good
Oil in normal condition; continue normal sampling No corrective action is require
29
2012-11-03
Fair
Oil deterioration detectable; more frequent sampling recommended
30
2012-11-03
10
Poor
Oil deterioration abnormal schedule effective actions
31
2012-11-03
Corrective action
Two types of contamination / deterioration of the oil can be considered physical chemical Each one requires a different remedial action
32
2012-11-03
Important point:
Where a test result is outside the limits recommended value should be compared with previous results and fresh sample obtained for confirmation before any other action is taken. If rapid deterioration or acceleration in the rate of deterioration is observed more frequent tests should be instituted promptly and/or appropriate remedial action should be taken. It may be desirable to consult the manufacturer of the equipment
33
2012-11-03
11
All equipment
Dark and/or As dictated by Clear and turbid other tests. without visible contamination
Dark colour is a symptom of chemical contamination or ageing. Turbidity is a symptom of high water content.
34
2012-11-03
O, A, D B, E C F
50 to 60 40 to 50 30 to 40
<30 kV for OLTC in star-point application <40 kV for OLTC in delta or line-end application <30 Good: Continue normal sampling. Fair: More frequent sampling.. Poor: Recondition the oil
35
2012-11-03
36
2012-11-03
12
saturation water content in unused oil (log Ws = 7.0895 - 1567/T) typical saturation water content in oxidised oil with acidity of 0.3 mg KOH/g
150
100
50
37
2012-11-03
f 2,24e0,04 t s
2,00 Correction factor
1,00
38
2009
39
2009
13
% Saturation = (mg/kg of water / Ws) x 100 Condition of cellulosic insulation Dry insulation Moderately wet, low numbers indicate fairly dry to moderate levels of water in the insulation. Values toward the upper limit indicate moderately wet insulation Wet insulation Extremely wet insulation Source : IEEE C57.106:2002 (B6)
21 30 % > 30 %
40
2009
Effect of temperature
water ppm
35
Loaded
water ppm 20
oil temp
60
30 25 20 15 10 5 0 1 2 3 4 5 6
Time
50 40 30 20 10 0
10
11
12
41
2009
Acidity (mgKOH/goil)
O, A, D B, E C F, G <0,10 <0,10 <0,15 0,10 to 0,15 0,10 to 0,20 0,15 to 0,30 Not a routine test. >0,15 >0,20 >0,30
Good: Continue normal sampling Fair: More frequent sampling. Check the presence of sediment and sludge. An inhibited oil that reached fair values has possibly lost its oxidation protection. Poor: Starting from a value of 0,15, Reclaim the oil or change the oil
42 Subjectmatter, Name, Division 2012-11-03
Temperature (C)
14
Good: Continue normal sampling. Fair: More frequent sampling. Check other parameters. Poor: Reclaim oil, change the oil
43
2012-11-03
Resistivity (Gm)
At 20 C O, A B, C D E O, A B, C D E >200 >60 >800 >60 >10 >3 >50 >3 20 to 200 4 to 60 250 to 800 7 to 60 At 90 C 3 to 10 0,2 to 3 10 to 50 0,4 to 3 <3 <0,2 <10 <0,4 <20 <4 <250 <7
Good: Continue normal sampling Fair: More frequent sampling. Check other parameters. Poor: Reclaim the oil or change the oil
44 Subjectmatter, Name, Division 2012-11-03
45
2012-11-03
15
Inhibitor content
Good >60 % of original value Fair 40 % to 60 % of original value Poor <40 % of original value
Good: No action require if not indicated by other properties Fair: (where acidity <0,08 mgKOH/g and IFT >28 mN/m). Consider re-inhibition to original base line level based on local experience Poor: Continue to use and monitor as uninhibited oil, reclaim or change the oil
46
2012-11-03
Good: less frequent monitoring acceptable Fair: maintain regular monitoring Poor: remove the source of corrosivity by changing the oil or by removing corrosive compounds by mean of suitable oil treatments or passivat the oil
47
2012-11-03
48
2012-11-03
16
>28 >25
22 to 28 20 to 25
<22 <20
Good: Continue normal sampling. Fair: More frequent sampling. Poor: Check the presence of sediment and sludge.
49
2012-11-03
Corrosive sulphur
Category
Recommended Action
O, A, B, C, D, E, F
Corrosiv For corrosive oil: e - conduct risk assessment - reduce the corrosivity of the oil by adding a copper passivator (e.g. triazole derivates) or - remove the source of corrosivity by changing the oil or by removing corrosive compounds by mean of suitable oil treatments.
50
2012-11-03
O, A, B, C, D, E, F
Informative test
If the breakdown voltage and water content are near or outside the limit for the appropriate equipment category and the particle number is higher than the limits for any of the size ranges, filter the oil.
51
2012-11-03
17
Flash point
All Categories
52
2012-11-03
53
2009
Chemical
-Reclaiming -- or change the oil Restore original additive concentration according to recommendations
54
2012-11-03
18
Reconditioning
Reconditioning is a process that eliminates or reduces physical contamination by means of physical processes (filtration, drying, degassing etc.) Reconditioning reduces the particle and water content of the oil The process may also remove some dissolved gases and other components such as Furanic compounds it is recommended that the oil should not be vacuum treated at temperatures over 85 C. If it is desirable to reduce particles or free water, cold treatment at atmospheric pressure may be appropriate.
55
2012-11-03
Conditions for processing inhibited and/or passivator containing mineral insulating oils Temperature (C) 40 50 60 70 80 85 Minimum Pressure (Pa) 8 15 30 80 200 280
56
2012-11-03
40
50
65
100
150
200
250
300
350
57
2012-11-03
19
On-line methods
Advantages: Possible for transform ers that cannot withstand vacuum Transformer remains in service
58
Off-line methods
Advantages: Efficiency Speed Disadvantages: Transformer has to be taken out of service for the duration of the process Cost
2012-11-03
Disadvantages:
Reconditioning equipment
Filter Filtering equipment usually forces oil under pressure through absorbing material such as paper or other filter media. Centrifuge use for rough bulk cleaning where large amounts of contaminated oil are to be handled. Vacuum dehydrator It is an efficient means of reducing the gas and water content of a mineral insulating oil to very low values
59
2012-11-03
60
2012-11-03
20
Oil Reclamation
This is a process that eliminates or reduces soluble and insoluble polar contaminants from the oil by chemical and physical processing. The resulting product should be evaluated on critical parameters Reclamation of oils of moderate to high acidity will usually result in oils with a lower oxidation resistance than the original new oil IEC developed new standards for reclaimed oil IEC62701
61
2012-11-03
62
2012-11-03
63
2012-11-03
21
Passivation
Metal passivator is added as a stock solution, dissolved in insulating oil The stock solution can be added via an oil processing unit or other suitable equipment. This treatment is recommended for unused and in-service insulating oil
64
2012-11-03
Renewal of additives
Oil reclamation remove oxidation inhibitors Additives shall be replaced in the reclaimed oil after the reclaiming process and before the equipment is re-energized The most widely used additives are 2,6-di-tert-butyl-paracresol (DBPC) and 2,6-di-tert-butyl-phenol (DBP). Metal passivators will also be reduced or removed due to their polar nature.
65
2012-11-03
66
2012-11-03
22
Dehalogenation process
Several process are available
Dehalogenation processes using sodium and lithium derivatives Dehalogenation processes using polyethylene glycol and potassium hydroxide (KPEG) Dehalogenation in continuous mode by closed circuit process
67
2012-11-03
23