DSE710 & DSE720 AUTO START & AUTO MAINS FAILURE CONTROL MODULES
SPECIFICATION
DC SUPPLY 8V to 35V continuous CRANKING DROPOUTS Able to survive 0V for 50mS, providing supply was at least 10V before dropout and supply recovers to 5V. This is achieved without the need for internal batteries. MAXIMUM OPERATING CURRENT 180mA at 12V. 190mA at 24V MAXIMUM STANDBY CURRENT 145mA at 12V. 150mA at 24V GENERATOR INPUT RANGE 35V(L-N) to 333V AC (L-N) absolute maximum 50Hz - 60Hz (min 15V AC) AUXILIARY OUTPUTS Solid state 2.4A DC at supply voltage FUEL/START OUTPUTS Solid state 3.4A DC at supply voltage GENERATOR C.T. 5A secondary 0.5VA MAINS (UTILITY) SENSING INPUT RANGE (DSE720 only) 35V(L-N) to 333V AC (L-N) 50Hz - 60Hz (min 15V AC) DSE710 & DSE720 DIMENSIONS 209mm x 146mm x 30.3mm 8.2 x 5.7 x 1.2 DSE710 & DSE720 PANEL CUTOUT: 182mm x 137mm 7.2 x 5.4
DSE710
DSE720
The DSE710 is an Automatic Start Control Module that offers an advanced range of engine monitoring and protection features. The module has been designed to monitor generator frequency, generator volts, generator current, engine oil pressure, engine coolant temperature, engine running hours and battery volts. The module also displays the engine speed. When the module detects a fault condition it automatically shuts down the engine and indicates the exact fault on the modules LCD display or relevant LED indicator. The module can be configured using the front panel or via the DSE810 interface and a PC. The module can also be controlled from a PC that is located up to 100 meters away. The DSE720 is an Automatic Mains Failure Control Module and incorporates all the features of the DSE710 plus the ability to automatically monitor the mains supply and switch over to the generator when the mains power fails.
FEATURES PC configurable Digital and analogue inputs Digital outputs Automatic mains (utility) supply monitoring Automatic shutdown when fault conditions are detected Manual start Engine pre-heat Engine monitoring and protection features Protected Solid State (PSS) outputs Front panel mounting Front panel programming Tamper proof engine hours counter Remote start LED indicators Configurable timers Configurable outputs Configurable inputs Back-lit character LCD display BENEFITS Transfer between mains (utility) and generator power On-site module configuration and remote configuration (Max 100 Meters) using PC software User-friendly set-up and button layout Multiple engine parameters are monitored simultaneously License free PC software
OPERATION The module is operated using the front STOP/RESET, MANUAL, AUTO, TEST and START push buttons. An additional push button next to the LCD display is used to scroll through the modules metering displays. CONFIGURATION The modules can be configured using the front panel or remotely using the DSE810 interface and a PC. As well as configuration the DSE810 interface has the ability to provide real time diagnostic facilities.
DEEP SEA ELECTRONICS PLC Highfield House Hunmanby Industrial Estate Hunmanby, North Yorkshire YO14 0PH England
Registered in England & Wales No.01319649
DEEP SEA ELECTRONICS PLC THAILAND TPI Tower, Lobby 3 Floor 27, 26-56 Chan New Road Tungmahamek, Sathom Bangkok 10120, Thailand DEEP SEA ELECTRONICS INC USA 3230 Williams Avenue Rockford IL 61101-2668 USA
TELEPHONE +66 (0) 2678 3028 FACSIMILE +66 (0) 2670 6228 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL [email protected] WEBSITE www.deepseaplc.com EMAIL [email protected] WEBSITE www.deepseausa.com INSTRUMENTATION AND ALARMS The DSE710 and DSE720 both provide comprehensive metering and alarm facilities. The table below outlines the modules capabilities.
DSE720 ONLY
P1 L1 S1 S2
P2 L1
DSE710/DSE720
Generator Frequency Engine Speed Generator Volts (L1-N, L2-N, L3-N) Generator Volts (L1-L2, L2-L3, L3-L1) Generator Current (L1, L2, L3) Engine Oil Pressure Engine Coolant Temperature Hours Run Counter Battery Volts Mains Volts (DSE720 only) (L1-N, L2-N, L3-N) Mains Volts (DSE720 only) (L1-L2, L2-L3, L3-L1)
L2
L2
FROM GENERATOR
L3
L3
FROM MAINS
N N
2 AMP F USES
E LECTRICAL I NTERLO CK
2 A MP FUSE S
G
NO RMAL LY O PEN NORMALL Y CLOSED
18
L1
19
L2
20
L3
21
CO M
26
L1
27
N
9
C LO SE G EN
8
CL OSE MA INS
22
L1
23
L2
24
L3
25
N
MA INS
CO O LA NT TEMP
IN PUT 1
10
11
12
13
15
16
IN PUT 2
CRA NK
BA TTERY
14
REMO TE STA RT
O IL PRES SURE
CH RG A LT
O UTPUT 1
O UTPUT 2
EM STOP
F UEL
+ VE
- VE
17
2 A MP F USE
2 A MP FU SE
BA TTERY
FU EL SO L ENOI D
CRA NK SO LE NOI D
BATTE RY NE GATI VE MUS T B E GRO UNDED SCREW TERMI NALS TI GHTENING TORQ UE = 0.8Nm (7 lb-in) * NOTE . ALL THE OUTPUTS ARE S OLI D STA TE AND ARE POS ITIVE SWITCHING