BrainChild C91
BrainChild C91
UM0C911A
BRAINCHILD
Warning Symbol
The Symbol calls attention to an operating procedure, practice, or the like, which, if not correctly performed or adhered to, could result in personal injury or damage to or destruction of part or all of the product and system. Do not proceed beyond a warning symbol until the indicated conditions are fully understood and met.
UM0C911A
Contents
Page No Chapter 1 Overview 1-1 General -------------------------5 1-2 Ordering Code ---------------8 1-3 Programming Port ------------9 1-4 Keys and Displays ---------10 1-5 Menu Overview -------------12 1-6 Parameter Descriptions ---13 Chapter 2 Installation 2-1 Unpaking ----------------------20 2-2 Mounting ----------------------20 2-3 Wiring precautions ----------22 2-4 Power Wiring -----------------25 2-5 Sensor Installation ---------Guidlines----------------------25 2-6 Sensor Input Wiring --------26 2-7 Control Output Wiring -----26 2-8 Alarm Wiring -----------------30 2-9 Data Communication ------31 Chapter 3 Programming 3-1 Lockout -----------------------33 3-2 Signal Input ------------------33 3-3 Control Outputs --------------34 3-4 Alarm ---------------------------39 3-5 Configure Display ----------40 3-6 Ramp --------------------------41 3-7 Dwell Timer ------------------42 3-8 PV Shift -----------------------43 3-9 Digital Filter -------------------44 3-10 Failure Transfer -------------45 3-11 Auto-tuning ------------------46 3-12 Manual tuning --------------47 3-13 Manual Control -------------48 3-14 Data communication -----50 Chapter 6 Specifications ----60 Chapter 7 Communications Modbus Communications---66 7-1 Functions Supported -------66 7-2 Exception Responses -----68 7-3 Parameter Table -------------69 7-4 Data Conversion ------------73 7-5 Communication Examples-73 Appendix A-1 Error Codes ------------------76 A-2 Warranty ----------------------77 Page No Chapter 4 Applications 4-1 Heat Only Control with -Dwell Timer ------------------51 4-2 Cool Only Control -----------52 4-3 Heat-Cool Control -----------53 Chapter 5 Calibration --------55
UM0C911A
Page No
Figure 1.1 Fuzzy Control Advantage ----------------------------------------------------------------6 Figure 1.2 Programming Port Overview ------------------------------------------------------------9 Figure 1.3 Front Panel Description -----------------------------------------------------------------11 Figure 1.4 Display of Initial Stage -------------------------------------------------------------------11 Figure 2.1 Mounting Dimensions -------------------------------------------------------------------21 Figure 2.2 Lead Termination for C91 and C92--------------------------------------------------23 Figure 2.3 Lead Termination for C21---------------------------------------------------------------23 Figure 2.4 Rear Terminal Connection for C21--------------------------------------------------23 Figure 2.5 Rear Terminal Connection for C91----- --------------------------------------------24 Figure 2.6 Rear Terminal Connection for C92----- --------------------------------------------24 Figure 2.7 Power Supply Connections ------------------------------------------------------------25 Figure 2.8 Sensor Input Wiring ----------------------------------------------------------------------26 Figure 2.9 Output 1 Relay or Triac (SSR) to Drive Load ---------------------------------------26 Figure 2.10 Output 1 Relay or Triac (SSR) to Drive Contactor -------------------------------27 Figure 2.11 Output 1 Pulsed Voltage to Drive SSR ---------------------------------------------27 Figure 2.12 Output 1 Linear Current ---------------------------------------------------------------28 Figure 2.13 Output 1 Linear Voltage ---------------------------------------------------------------28 Figure 2.14 Output 2 Relay or Triac (SSR) to Drive Load -------------------------------------28 Figure 2.15 Output 2 Relay or Triac (SSR) to Drive Contactor -------------------------------29 Figure 2.16 Output 2 Pulsed Voltage to Drive SSR ---------------------------------------------29 Figure 2.17 Output 2 Linear Current ---------------------------------------------------------------29 Figure 2.18 Output 2 Linear Voltage --------------------------------------------------------------30 Figure 2.19 Alarm Output to Drive Load ----------------------------------------------------------30 Figure 2.20 Alarm Output to Drive Contactor ----------------------------------------------------30 Figure 2.21 RS-485 Wiring ---------------------------------------------------------------------------31 Figure 2.22 RS-232 Wiring ---------------------------------------------------------------------------32 Figure 2.23 Configuration of RS-232 Cable ------------------------------------------------------32 Figure 3.1 Conversion Curve for Linear Type Process Value ---------------------------------34 Figure 3.2 Heat Only ON-OFF Control ------------------------------------------------------------35 Figure 3.3 Output 2 Deviation High Alarm --------------------------------------------------------38 Figure 3.4 Output 2 Process Low Alarm ----------------------------------------------------------38 Figure 3.5 RAMP Function ---------------------------------------------------------------------------41 Figure 3.6 Dwell Timer Function --------------------------------------------------------------------42 Figure 3.7 PV Shift Application ----------------------------------------------------------------------43 Figure 3.8 Filter Characteristics ---------------------------------------------------------------------44 Figure 3.9 Effects of PID Adjustment -------------------------------------------------------------49 Figure 4.1 Heat Control Example -------------------------------------------------------------------51 Figure 4.2 Cooling Control Example ---------------------------------------------------------------52 Figure 4.3 Heat-Cool Control Example ------------------------------------------------------------53 Figure 5.1 RTD Calibration ---------------------------------------------------------------------------57 Figure 5.2 Cold Junction Calibration Setup ------------------------------------------------------58 Table 1.1 Display Form of Characters -------------------------------------------------------------11 Table 3.1 Heat-Cool Control Setup Value ---------------------------------------------------------34 Table 3.2 PID Adjustment Guide --------------------------------------------------------------------48 Table A.1 Error Codes and Corrective Actions --------------------------------------------------66
UM0C911A
Chapter 1 Overview
1-1 General
The Fuzzy Logic plus PID microprocessor-based controller series, incorporate a bright, easy to read 4-digit LED display, indicating process value or set point value. The Fuzzy Logic technology enables a process to reach a predetermined set point in the shortest time, with the minimum of overshoot during power-up or external load disturbance. C21 is a 1/32 DIN size panel mount controller. C91 is a 1/16 DIN size panel mount controller. C92 is DIN rail mount controller. These units are powered by 11-26 or 90-264 VDC/VAC supply, incorporating a 2 amp. control relay output as standard. The second output can be used as cooling control, an alarm or dwell timer. Both outputs can select triac, 5V logic output, linear current or linear voltage to drive external device. There are six types of alarm plus a dwell timer can be configured for the second output.The units are fully programmable for PT100 and thermocouple types J,K, T, E, B, R, S, N, L with no need to modify the unit. The input signal is digitized by using a 18-bit A to D converter. Its fast sampling rate allows the unit to control fast processes. Digital communications RS-485 or RS-232 ( for C21, C91) are available as an additional option. These options allow the units to be integrated with supervisory control system and software. A programming port is available for automatic configuration, calibration and testing without the need to access the keys on front panel. By using proprietary Fuzzy modified PID technology, the control loop will minimize the overshoot and undershoot in a shortest time. The following diagram is a comparison of results with and without Fuzzy technology.
UM0C911A
Figure 1.1 Fuzzy Control Advantage Warm Up High Accuracy The series are manufactured with custom designed ASIC(Application Specific Integrated Circuit ) technology which contains a 18-bit A to D converter for high resolution measurement ( true 0.1 BF resolution for thermocouple and PT100 ) and a 15-bit D to A converter for linear current or voltage control output. The ASIC technology provides improved operating performance, low cost, enhanced reliability and higher density. Fast Sampling Rate The sampling rate of the input A to D converter reaches 5 times/second. The fast sampling rate allows this series to control fast processes. Fuzzy Control The function of Fuzzy control is to adjust PID parameters from time to time in order to make manipulation output value more flexible and adaptive to various processes. The results is to enable a process to reach a predetermined set point in the shortest time, with the minimum of overshoot and undershoot during power-up or external load disturbance. Digital Communication The units are equipped with RS-485 or RS-232 interface card to provide digital communication. By using the twisted pair wires there are at most 247 units can be connected together via RS-485 interface to a host computer.
6 UM0C911A
Load Disturbance
Time
Programming Port A programming port is used to connect the unit to a hand-held programmer or a PC for quick configuration, also can be connected to an ATE system for automatic testing & calibration. Auto-tune The auto-tune function allows the user to simplify initial setup for a new system. A clever algorithm is provided to obtain an optimal set of control parameters for the process, and it can be applied either as the process is warming up ( cold start ) or as the process has been in steady state ( warm start ). Lockout Protection According to actual security requirement, one of four lockout levels can be selected to prevent the unit from being changed abnormally. Bumpless Transfer Bumpless transfer allows the controller to continue to control by using its previous value as the sensor breaks. Hence, the process can be well controlled temporarily as if the sensor is normal. Soft-start Ramp The ramping function is performed during power up as well as any time the set point is changed. It can be ramping up or ramping down. The process value will reach the set point with a predetermined constant rate. Digital Filter A first order low pass filter with a programmable time constant is used to improve the stability of process value. This is particularly useful in certain application where the process value is too unstable to be read.
UM0C911A
Accessories
OM94-6 = Isolated 1A / 240VAC Triac Output Module ( SSR ) OM96-3 = Isolated 4 - 20 mA / 0 - 20 mA Analog Output Module OM96-4 = Isolated 1 - 5V / 0 - 5V Analog Output Module OM96-5 =Isolated 0 -10V Analog Output Module CM94-1 = Isolated RS-485 Interface Module for C21, C92. CM94-2 = Isolated RS-232 Interface Module for C21, C92 CM96-1 = Isolated RS-485 Interface Module for C91 DC94-1 = Isolated 20V/25mA DC Output Power Supply DC94-2 = Isolated 12V/40mA DC Output Power Supply DC94-3 = Isolated 5V/80mA DC Output Power Supply CC94-1 = RS-232 Interface Cable ( 2M )
Signal Input
1: Standard Input Thermocouple: J, K, T, E, B, R, S, N, L RTD: PT100 DIN, PT100 JIS 9: Special Order
Output 1
0: None 1: Relay rated 2A/240VAC 2: Pulsed voltage to drive SSR, 5V/30mA 3: Isolated 4 - 20mA / 0 - 20mA 4: Isolated 1 - 5V / 0 - 5V 5: Isolated 0 - 10V 6: Triac output 1A / 240VAC,SSR 9: Special order
Output 2
0: None 1: Form A relay 2A/240VAC 2: Pulsed voltage to drive SSR, 5V / 30mA 3: Isolated 4 - 20mA / 0 - 20mA 4: Isolated 1 - 5V / 0 - 5V 5: Isolated 0 - 10V 6: Triac output, 1A / 240VAC, SSR 7: Isolated 20V/25mA transducer power supply 8: Isolated 12V/40mA transducer power supply 9: Isolated 5V/80mA transducer power supply A: RS-485 interface (for C91) B: Special order
Related Products
SNA10A = Smart Network Adaptor for third party software, which converts 255 channels of RS-485 or RS-422 to RS-232 Network. SNA10B = Smart Network Adaptor for BC-Net software, which converts 255 channels of RS-485 or RS-422 to RS-232 network.
Communications
0: None 1: RS-485 interface (for C21, C92) 2: RS-232 interface (for C21, C92) 9: Special order
Display Color
0: Red color 1: Green color
UM0C911A
Access Hole
Rear Terminal
6 4 2
5 31
C21
Programming Port
C9 NT RO LLE R
CO
C92
Figure 1.2 Programming Port Overview A special connector can be used to touch the programming port which is connected to a PC for automatic configuration, also can be connected to an ATE system for automatic calibration and testing. The programming port is used for off-line automatic setup and testing procedures only. Don't attempt to make any connection to these pins when the unit is used for a normal control purpose.
UM0C911A
ENTER KEY : Press for 3 seconds or longer . Press for 3 seconds to: 1. Ener setup menu. The display shows . 2. Enter manual control mode during manual control mode or is selected. 3. Enter auto-tuning mode during auto-tuning mode AT(for C91, C92) or (for C21) is selected. 4. Perform calibration to a selected parameter during the calibration procedure. Press for 4.2 seconds to select calibration mode.
10
UM0C911A
C21
PV
AT
R
C91
Auto-tuning Indicator Manual Mode Indicator 4 Buttons for ease of control setup and set point adjustment.
3 Silicone Rubber Buttons for ease of control setup and set point adjustment.
Figure 1.3
A B C c D
E F G H h
I J K L M
N O P Q R
S T U V W
X Y Z ? =
: Confused Character
OP1 OP2 C F
Display program code of the product for 2.5 seconds. The left diagram shows program no. 34 for C91 with version 16. The program no. for C21 is 33, and for C92 is 35.
PV
AT
R
C91
1- 5 Menu Overview
User menu *1
PV SP1 SP2 MAN MAN AT
PV
SP1 SP2 H C PV INPT UNIT DP PB TI TD CYC1 ADDR
C91 C92
Value
Value
User Menu *1
(DISP=PV)
PV SP1 SP2
(DISP=SP1)
or or
SP1 PV
Value Value
H C
C21
A-T
Value
LOCK INPT UNIT DP INLO INHI SP1L SP1H SHIF FILT DISP PB TI TD OUT1 O1TY O1FT O1HY CYC1 OFST RAMP RR OUT2 O2TY O2FT O2HY CYC2 CPB DB ALMD COMM ADDR BAUD DATA PARI STOP SEL1 SEL2 SEL3 SEL4 SEL5 SEL6 SEL7 SEL8
Value
ADLO ADHI RTDL RTDH CJLO CJHI
Value
Value
Press for 3 seconds to perform calibration. Apply these modes will break the control loop and change some of the previous setting data. Make sure that if the system is allowable to apply these modes. *1: The flow chart shows a complete listing of all parameters. For actual application the number of available parameters depends on setup conditions, and should be less than that shown in the flow chart. *2: Release , press again for 2 seconds or longer (but not longer than 3 seconds), then Value release to enter the calibration menu.
Value
12
UM0C911A
SP1 SP2
Set point for output 1 Set point for output 2 when output 2 performs alarm function or dwell timer
10.0 BC (18.0BF)
: No parameter is locked : Setup data are locked : Setup data and User data except Set point are locked : All data are locked
: J type thermocouple : K type thermocouple : T type thermocouple : E type thermocouple : B type thermocouple : R type thermocouple : S type thermocouple : N type thermocouple : L type thermocouple : PT 100 ohms DIN
curve : PT 100 ohms JIS curve : 4 - 20 mA linear current input : 0 - 20 mA linear current input : 0 - 60 mV linear millivolt input : 0 - 1V linear voltage input : 0 - 5V linear voltage input : 1 - 5V linear voltage input : 0 - 10V linear voltage input 1 (0)
INPT
9 10 11 12 13 14 15 16 17
UM0C911A
13
Parameter Notation
Parameter Description
0
UNIT
1 2
0 1 2 3
INLO INHI SP1L SP1H
: No decimal point : 1 decimal digit 1 : 2 decimal digits : 3 decimal digits High: 45486
-17.8 LC ( 0 LF )
DP
Input low sale value Input high scale value Low limit of set point value High limit of set point value PV shift (offset) value
High: 45536
-17.8 LC (0 LF)
SHIF
0.0
: 0 second time
constant constant
FILT
5 6 7 8 9
14
UM0C911A
Parameter Notation
Parameter Description
Range
Default Value
0
DISP
PB
TI TD
0 : Display set point 1 value normally 10.0 LC High: 500.0 LC (900.0 LF) (18.0 LF) High: 1000 sec High: 360.0 sec : Reverse (heating )
control action control action
100 25.0
OUT1
Output 1 function
1
: Direct (cooling)
0 1 2 3
O1TY Output 1 signal type 4 5 6 7 8
: Relay output : Solid state relay drive output : Solid state relay output : 4-20 mA current module
: 0 - 20 mA current
module
: 0 - 1V voltage
module module module
O1FT
Select BPLS ( bumpless transfer ) or 0.0 ~ 100.0 % to continue output 1 control function as the unit fails, or select OFF (0) or ON (1) for ON-OFF control.
O1HY CYC1
OFST
Low: 0.1 High: 50.0 BC(90.0BF) Low: 0.1 High: 90.0 sec.
Low: 0 High: 100.0 %
UM0C911A
15
Range
Default Value
: No Ramp Function : Use unit/minute as Ramp Rate : Use unit/hour as Ramp Rate
High: 500.0 LC (900.0 LF)
0.0
: Output 2 No Function : Dwell timer action : Deviation High Alarm : Deviation Low Alarm : Deviation band out of band Alarm : Deviation band in band Alarm : Process High Alarm : Process Low Alarm : Cooling PID Function 2
O2TY
4 5 6 7 8
: 0 - 20 mA current : : : :
module 0 - 1V voltage module 0 - 5V voltage module 1 - 5V voltage module 0 - 10V voltage module
O2FT
Select BPLS ( bumpless transfer ) or 0.0 ~ 100.0 % to continue output 2 control function as the unit fails, or select ON (0) or OFF (1) for alarm and dwell timer function.
16
UM0C911A
Range
Default Value
Output 2 hysteresis value when output 2 performs alarm function Output 2 cycle time Cooling proportional band value Heating-cooling dead band (negative value= overlap)
High: 50.0 LC (90.0 LF) High: 90.0 sec. High: 300 % High: 36.0 %
: Normal alarm
action
: Latching alarm
ALMD
2 3
COMM
0 1
: No communication : Modbus RTU mode protocol High: 255 : 2.4 Kbits/s baud rate : 4.8 Kbits/s baud rate : 9.6 Kbits/s baud rate : 14.4 Kbits/s baud rate : 19.2 Kbits/s baud rate : 28.8 Kbits/s baud rate 1
ADDR
Low: 1 0 1 2
BAUD
3 4 5
6 UM0C911A
Range
Default Value
DATA
: 7 data bits : 8 data bits : Even parity : Odd parity : No parity bit : One stop bit : Two stop bits
: No parameter selected : LOCK is put ahead : INPT is put ahead : UNIT is put ahead : DP is put ahead : SHIF is put ahead : PB is put ahead : TI is put ahead : TD is put ahead : O1HY is put ahead : CYC1 is put ahead : OFST is put ahead : RR is put ahead : O2HY is put ahead : CYC2 is put ahead : CPB is put ahead : DB is put ahead : ADDR is put ahead
PARI
1 2
STOP
0 1 0 1 2 3 4 5 6 7
SEL1
18
UM0C911A
Range
Default Value
Select 2'nd parameter for user menu Select 3'rd parameter for user menu Select 4'th parameter for user menu Select 5'th parameter for user menu Select 6'th parameter for user menu Select 7'th parameter for user menu Select 8'th parameter for user menu
Same as SEL1 Same as SEL1 Same as SEL1 Same as SEL1 Same as SEL1 Same as SEL1 Same as SEL1
3 4 6 7 8 10 17
UM0C911A
19
Chapter 2 Installation
Dangerous voltages capable of causing death are sometimes present in this instrument. Before installation or beginning any troubleshooting procedures the power to all equipment must be switched off and isolated. Units suspected of being faulty must be disconnected and removed to a properly equipped workshop for testing and repair. Component replacement and internal adjustments must be made by a qualified maintenance person only. To minimize the possibility of fire or shock hazards, do not expose this instrument to rain or excessive moisture. Do not use this instrument in areas under hazardous conditions such as excessive shock, vibration, dirt, moisture, corrosive gases or oil. The ambient temperature of the areas should not exceed the maximum rating specified in Chapter 6.
2-1 Unpacking
Upon receipt of the shipment remove the unit from the carton and inspect the unit for shipping damage. If any damage due to transit , report and claim with the carrier. Write down the model number, serial number, and date code for future reference when corresponding with our service center. The serial number (S/N) and date code (D/C) are labeled on the box and the housing of control.
2-2 Mounting
Make panel cutout to dimension shown in Figure 2.1. Take the mounting clamp away and insert the controller into panel cutout. Install the mounting clamp back.
20
UM0C911A
C21
SCREW Panel 98.0mm 10.0mm
12.5mm
45 mm
45 mm
C91
Panel
86 mm 94 mm
44.8mm
CONTROLLER
126.9mm
C92
OP1 OP2
LC
LF
17.6
91.8mm
35.4
PV
SP1 SP2
MAN
AT
17.8
BRAINCHILD
C92
UM0C911A 21
2 - 3 Wiring Precautions
* Before wiring, verify the label for correct model number and options. Switch off the power while checking. * Care must be taken to ensure that maximum voltage rating specified on the label are not exceeded. * It is recommended that power of these units to be protected by fuses or circuit breakers rated at the minimum value possible. * All units should be installed inside a suitably grounded metal enclosure to prevent live parts being accessible from human hands and metal tools. * All wiring must conform to appropriate standards of good practice and local codes and regulations. Wiring must be suitable for voltage, current, and temperature rating of the system. * Beware not to over-tighten the terminal screws. * Unused control terminals should not be used as jumper points as they may be internally connected, causing damage to the unit. * Verify that the ratings of the output devices and the inputs as specified in Chapter 6 are not exceeded.
22
UM0C911A
OP2
_
4
OP1
_
6 7
+
2
N 3
1
L
2A/240 VAC
2A/240 VAC
TX1 TXD 12 TX2 RXD 13
COM 11
14
_
B V I
+
RTD
RS-485 RS-232
CAT. I I
UM0C911A
23
1 2 3 4 5
2A 240 VAC
240 VAC
9
NO
10
C + OP1
11 12 13 14 15
INPUT
POWER IN RA N L
IN
IN+
16 17 18 19 20
+ TC
V
B
+ V + mA B RTD A
CAT. I I
24
UM0C911A
2 - 4 Power Wiring
The controller is supplied to operate at 11-26 VAC / VDC or 90-264 VAC. Check that the installation voltage corresponds with the power rating indicated on the product label before connecting power to the controller.
1 2
6 7
20 19
Fuse
This equipment is designed for installation in an enclosure which provides adequate protection against electric shock. The enclosure must be connected to earth ground. Local requirements regarding electrical installation should be rigidly observed. Consideration should be given to prevent from unauthorized person access to the power terminals.
Proper sensor type is also a very important factor to obtain precise measurements. The sensor must have the correct temperature range to meet the process requirements. In special processes the sensor might need to have different requirements such as leak-proof, antivibration, antiseptic, etc. Standard sensor limits of error are A4 degrees F (A 2 degrees C ) or 0.75% of sensed temperature (half that for special ) plus drift caused by improper protection or an over-temperature occurrence. This error is far greater than controller error and cannot be corrected on the sensor except by proper selection and replacement.
A RTD
8 9 10
3 4 5
18 17 16
B B
_
TC
C21
C91
C92
5 6
10 9
15 14
_V _
V mA RTD
LOAD
26
UM0C911A
5 6
10 9
15 14
Contactor
No Fuse Breaker
SSR
Load
5 6
10 9
15 14
+
_
UM0C911A
27
5 6
10 9
15 14
0 - 20mA, 4 - 20mA
Load _
5 6
10 9
15 14
Load _
3 4
2 1
7 6
LOAD
28
UM0C911A
3 4
2 1
7 6
Contactor
No Fuse Breaker
SSR
Load
3 4
2 1
7 6
3 4
2 1
7 6
0 - 20mA, 4 - 20mA
Load _
3 4
2 1
7 6
Load _
3 4
2 1
7 6
LOAD
3 4
2 1
7 6
Three Phase Heater Power Three Phase Contactor Delta Heater Load No Fuse Breaker
30
UM0C911A
12 13
2 1
10 9
Twisted-Pair Wire
PC
12 13
2 1
10 9
TX1
TX2
12 13
2 1
10 9
UM0C911A
31
RS-232
C21 C92
TXD RXD COM
12 10 13 9 11 8
PC
If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable must be modified according to the following circuit diagram.
C21 C92
TXD RXD COM
12 10 13 9 11 8
RD TD GND
2 3 4 5
6 7 8 9
32
UM0C911A
Chapter 3 Programming
Press for 3 seconds and release to enter setup menu. Press to select the desired parameter. The display indicates the parameter symbol. Press or to view or adjust the value of the selected parameter.
3-1 Lockout
There are four security levels can be selected by using LOCK parameter. If NONE is selected for LOCK, then no parameter is locked. If SET is selected for LOCK, then all setup data are locked. If USER is selected for LOCK, then all setup data as well as user data (refer to section 1-5) except set point are locked to prevent from being changed. If ALL is selected for LOCK, then all parameters are locked to prevent from being changed.
process value INHI PV INLO SL S SH input signal Figure 3.1 Conversion Curve for Linear Type Process Value
S SL SH SL Example : A 4-20 mA current loop pressure transducer with range 2 0 - 15 kg/cm is connected to input, then perform the following setup :
INPT = 4 - 20 INLO = 0.00 INHI = 15.00 DP = 2-DP Of course, you may select other value for DP to alter the resolution.
OUT2
O1HY
O2HY
CPB
DB
34
Heat Only ON-OFF Control : Select REVR for OUT1, Set PB to 0, O1HY is used to adjust dead band for ON-OFF control, The output 1 hysteresis ( O1HY ) is enabled in case of PB = 0 . The heat only on-off control function is shown in the following diagram : PV SP1 Dead band = O1HY SP1 O1HY Time
OUT1 Action
ON OFF Time
then increase OFST 25 %, and vice versa. After adjusting OFST value, the process value will be varied and eventually, coincide with set point. Using the P control ( TI set to 0 ), the auto-tuning is disabled. Refer to section 3-12 " manual tuning " for the adjustment of PB and TD. Manual reset ( adjust OFST ) is not practical because the load may change from time to time and often need to adjust OFST repeatedly. The PID control can avoid this situation. Heat only PID control : Selecting REVR for OUT1, PB and TI should not be zero. Operate auto-tuning for the new process, or set PB, TI and TD with historical values. See section 3-11 for auto-tuning operation. If the control result is still unsatisfactory, then use manual tuning to improve the control . See section 3-12 for manual tuning. The unit contains a very clever PID and Fuzzy algorithm to achieve a very small overshoot and very quick response to the process if it is properly tuned. Cool only control:ON-OFF control, P ( PD ) control and PID control can be used for cool control. Set OUT1 to DIRT ( direct action ). The other functions for cool only ON-OFF control, cool only P ( PD ) control and cool only PID control are same as descriptions for heat only control except that the output variable ( and action ) for the cool control is inverse to the heat control. NOTE : The ON-OFF control may result excessive overshoot and undershoot problems in the process. The P ( or PD ) control will result in a deviation process value from the set point. It is recommended to use PID control for the Heat-Cool control to produce a stable and zero offset process value. Other Setup Required : O1TY, CYC1, O2TY, CYC2, O1FT, O2FT O1TY & O2TY are set in accordance with the types of OUT1 & OUT2 installed. CYC1 & CYC2 are selected according to the output 1 type ( O1TY ) & output 2 type ( O2TY ). Generally, selects 0.5 ~ 2 sec. for CYC1, if SSRD or SSR is used for O1TY; 10 ~ 20 sec. if relay is used for O1TY, and CYC1 is ignored if linear output is used. Similar condition is applied for CYC2 selection.
36
UM0C911A
You can use the auto-tuning program for the new process or directly set the appropriate values for PB, TI & TD according to the historical records for the repeated systems. If the control behavior is still inadequate, then use manual tuning to improve the control. See section 3-12 for manual tuning. CPB Programming : The cooling proportional band is measured by % of PB with range 50~300. Initially set 100% for CPB and examine the cooling effect. If cooling action should be enhanced then decrease CPB, if cooling action is too strong then increase CPB. The value of CPB is related to PB and its value remains unchanged throughout the auto-tuning procedures. Adjustment of CPB is related to the cooling media used. For air is used as cooling media, adjust CPB at 100(%).For oil is used as cooling media, adjust CPB at 125(%). For water is used as cooling media, adjust CPB at 250(%). DB Programming: Adjustment of DB is dependent on the system requirements. If more positive value of DB ( greater dead band ) is used, an unwanted cooling action can be avoided but an excessive overshoot over the set point will occur. If more negative value of DB ( greater overlap ) is used, an excessive overshoot over the set point can be minimized but an unwanted cooling action will occur. It is adjustable in the range -36.0% to 36.0 % of PB. A negative DB value shows an overlap area over which both outputs are active. A positive DB value shows a dead band area over which neither output is active. Output 2 ON-OFF Control ( Alarm function ): The output 2 can also be configured as alarm function. There are 6 kinds of alarm functions can be selected for output 2, these are: DE.HI (deviation high alarm ), DE.LO (deviation low alarm ), DB.HI (deviation band out of band alarm ), DB.LO (deviation band in band alarm), PV.HI (process high alarm ) and PV.LO ( process low alarm ). Refer to Figure 3.3 and Figure 3.4 for the description of deviation alarm and process alarm with normal alarm mode ( NORM is set for ALMD ).
UM0C911A
37
OUT2=DE.HI
Time
Time
Time
Time
3-4 Alarm
The output 2 can be selected as alarm output. There are 6 types of alarm functions and one dwell timer can be selected, and four kinds of alarm modes ( ALMD ) are available for each alarm function. A process alarm sets two absolute trigger levels. When the process is higher than SP2, a process high alarm ( PV.HI ) occurs, and the alarm is off as the process is lower than SP2-O2HY. When the process is lower than SP2, a process low alarm ( PV.LO ) occurs and the alarm is off as the process is higher than SP2+O2HY. A process alarm is independent of set point. A deviation alarm alerts the user when the process deviates too far from set point. When the process is higher than SV+SP2, a deviation high alarm (DE.HI) occurs and the alarm is off as the process is lower than SV+SP2-O2HY. When the process is lower than SV+SP2, a deviation low alarm (DE.LO) occurs and the alarm is off as the process is higher than SV+SP2+O2HY. Trigger level of deviation alarm is moving with set point. A deviation band alarm presets two trigger levels relative to set point. The two trigger levels are SV+SP2 and SV - SP2 for alarm. When the process is higher than ( SV+SP2 ) or lower than ( SV - SP2 ), a deviation band high alarm ( DB.HI ) occurs. When the process is within the trigger levels, a deviation band low alarm (DB.LO) occurs. In the above descriptions SV denotes the current set point value for control which is different from SP1 as the ramp function is performed. There are four types of alarm modes available for each alarm function, these are: Normal alarm, Latching alarm, Holding alarm and Latching/ Holding alarm. They are described as follows: Normal Alarm : ALMD = NORM When a normal alarm is selected, the alarm output is de-energized in the non-alarm condition and energized in an alarm condition. Latching Alarm : ALMD = LTCH If a latching alarm is selected, once the alarm output is energized, it will remain unchanged even if the alarm condition is cleared. The latching alarm is reset when the RESET key is pressed, once the alarm condition is removed. 39 UM0C911A
Holding Alarm : ALMD = HOLD A holding alarm prevents an alarm from power up. The alarm is enabled only when the process reaches the set point value. Afterwards , the alarm performs same function as normal alarm. Latching / Holding Alarm : ALMD = LT.HO A latching / holding alarm performs both holding and latching function. The latching alarm is reset when the RESET key is pressed, once the alarm condition is removed. Alarm Failure Transfer is activated as the unit enters failure mode. Alarm will go on if ON is set for O2FT and go off if OFF is set for O2FT. The unit will enter failure mode when sensor break occurs or if the A-D converter of the unit fails.
Examples:
If LOCK is set with NONE, OUT2 is set with DEHI, DISP is set with PV, set SEL1=SHIF, SEL2=ADDR. SEL3=PB, SEL4~SEL8=NONE, then the display scrolling for C21 becomes:
PV
If LOCK is set with NONE, OUT1 is set with REVR,nonzero value is set for PB and TI, OUT2 is set with COOL, DISP is set with SP1, set SEL1=INPT, SEL2=PB, SEL3=TI, SEL4~SEL8=NONE, then the display scrolling for C21 becomes:
SP1
40
UM0C911A
Example for C91/C92: Set OUT2=PVLO, LOCK=NONE, SEL1=INPT, SEL2=UNIT, SEL3=DP , SEL4~SEL8=NONE, then the display scrolling for C91 and C92 becomes
PV SP1 SP2 MAN AT
PV
SP1
SP2
PV
3 - 6 Ramp
The ramping function is performed during power up as well as any time the set point is changed. Choose MINR or HRR for RAMP , the unit will perform the ramping function. The ramp rate is programmed by adjusting RR. The ramping function is disabled as soon as the failure mode, the manual control mode, the auto-tuning mode or the calibration mode occurs. Example without Dwell Timer Select MINR for RAMP , selects LC for UNIT, selects 1-DP for DP , Set RR= 10.0. SV is set to 200 LC initially, and changed to 100 LC after 30 minutes since power up. The starting temperature is 30 LC. After power up the process is running like the curve shown below:
PV 200 C 100 C 30 C 0 17 30 40
Note: When the ramp function is used, the display will show the current ramping value. However it will revert to show the set point value as soon as the up or down key is touched for adjustment. The ramping value is initiated to process value either as power up or RR and /or set point are changed. Setting RR to zero means no ramp function at all.
UM0C911A 41
PV SP
ALM
Time SP3
power off or touch RESET key
3 - 8 PV Shift
In certain applications it is desirable to shift the controller display value from its actual value. This can be easily accomplished by using the PV shift function. The SHIF function will alter PV only. Here is an example. A process is equipped with a heater, a sensor and a subject to be warmed up. Due to the design and position of the components in the system, the sensor could not be placed any closer to the part. Thermal gradient ( different temperature ) is common and necessary to an extent in any thermal system for heat to be transferred from one point to another. If the difference between the sensor and the subject is 35 LC, and the desired temperature at the subject to be heated is 200 LC, the controlling value or the temperature at the sensor should be 235 LC. You should input -35 LC as to subtract 35 LC from the actual process display. This in turn will cause the controller to energize the load and bring the process display up to the set point value.
Subject Heat Transfer 165 C 200 C Sensor
C
Heater
Heater
Heater
3- 9 Digital Filter
In certain application the process value is too unstable to be read. To improve this a programmable low pass filter incorporated in the controller can be used. This is a first order filter with time constant specified by FILT parameter . The default value of FILT is 0.5 sec. before shipping. Adjust FILT to change the time constant from 0 to 60 seconds. 0 second represents no filter is applied to the input signal. The filter is characterized by the following diagram.
PV
FILT=0 1 sec FILT=1
FILT=30
1 sec
Time
Figure 3.8 Filter Characteristics
Note The Filter is available only for PV, and is performed for the displayed value only. The controller is designed to use unfiltered signal for control even if Filter is applied. A lagged ( filtered ) signal, if used for control, may produce an unstable process.
44
UM0C911A
UM0C911A
45
3 -11 Auto-tuning
The auto-tuning process is performed at set point. The process will oscillate around the set point during tuning process. Set a set point to a lower value if overshooting beyond the normal process value is likely to cause damage. The auto-tuning is applied in cases of :
* Initial setup for a new process * The set point is changed substantially from the previous autotuning value
NOTE :
The ramping function, if used, will be disabled once auto-tuning is proceeding. The auto-tuning mode is disabled as soon as either failure mode or manual control mode occurs.
46 UM0C911A
Procedures:
The auto-tuning can be applied either as the process is warming up ( Cold Start ) or as the process has been in steady state ( Warm Start ). After the auto-tuning procedures are completed, the AT indicator will cease to flash and the unit revert to PID control by using its new PID values. The PID values obtained are stored in the nonvolatile memory. Auto-Tuning Error If auto-tuning fails an ATER message will appear on the display in cases of : If PB exceeds 9000 ( 9000 PU, 900.0 LF or 500.0 LC ). or if TI exceeds 1000 seconds. or if set point is changed during auto-tuning procedure. Solutions to 1. Try auto-tuning once again. 2. Don't change set point value during auto-tuning procedure. 3. Don't set zero value for PB and TI. 4. Use manual tuning instead of auto-tuning. ( See section 3-12 ). 5. Touch RESET key to reset message.
3 - 12 Manual Tuning
In certain applications ( very few ) using auto-tuning to tune a process may be inadequate for the control requirement, then you can try manual tuning. If the control performance by using auto- tuning is still unsatisfactory, the following rules can be applied for further adjustment of PID values :
UM0C911A
47
Table 3.2 PID Adjustment Guide Figure 3.9 shows the effects of PID adjustment on process response.
PB too low
P action
PB too high
Time
TI too high PV
I action
Time
PV
Set point
TD too high
D action
Time
3 - 14 Data Communication
The controllers support RTU mode of Modbus protocol for the data communication. Other protocols are not available for the series.
Two types of interface are available for Data Communication. These are RS485 and RS-232 interface. Since RS-485 uses a differential architecture to drive and sense signal instead of a single ended architecture which is used for RS-232, RS-485 is less sensitive to the noise and suitable for a longer distance communication. RS-485 can communicate without error over 1 km distance while RS-232 is not recommended for a distance over 20 meters. Using a PC for data communication is the most economic way. The signal is transmitted and received through the PC communication Port ( generally RS-232 ). Since a standard PC can't support RS-485 port, a network adaptor ( such as SNA10A , SNA10B ) has to be used to convert RS-485 to RS-232 for a PC if RS-485 is required for the data communication. But there is no need to be sad. Many RS-485 units ( up to 247 units ) can be connected to one RS-232 port, therefore a PC with 4 comm ports can communicate with 988 units. It is quite economic. Setup Enters the setup menu. Select RTU for COMM . Set individual address as for those units which are connected to the same port. Set the Baud Rate ( BAUD ), Data Bit ( DATA ), Parity Bit ( PARI ) and Stop Bit ( STOP ) such that these values are accordant with PC setup conditions. If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable should be modified for proper operation of RS-232 communication according to Section 2-9.
50
UM0C911A
Chapter 4 Applications
4 - 1 Heat Only Control with Dwell Timer
An oven is designed to dry the products at 150 BC for 30 minutes and then stay unpowered for another batch. A C91 equipped with dwell timer is used for this purpose. The system diagram is shown as follows : Set SP1=150.0 SP2 =30.0
4
OP1 OP2 C F
Oven
C
PV SP1 SP2 MAN AT
T/C
Heater
R
C91
10 9 Mains Supply ON
OUT1
Timer ( ALM )
OFF
To achieve this function set the following parameters in the setup menu. INPT=K_TC OUT1=REVR O1FT=BPLS UNIT= L C O1TY=RELY OUT2=TIMR DP=1_DP CYC1=18.0 O2FT=ON
RTD
Mains Supply
4 3
9 10
C F
OP1 OP2
PV
AT
R
C91
52
UM0C911A
4 - 3 Heat-Cool Control
An injection mold required to be controlled at 120 LC to ensure a consistent quality for the parts. An oil pipe is buried in the mold. Since plastics is injected at higher temperature ( e.g. 250 LC ), the circulation oil needs to be cooled as its temperature rises. Here is an example:
Plastics
10 5 4 3
INPT
PV
AT
R
C91
UM0C911A
53
The PID Heat-Cool is used for the above example. To achieve this set the following parameters in the Setup Menu: INPT=PT.DN UNIT= LC DP= 1-DP OUT1=REVR O1TY=RELY CYC1=18.0 (sec.) O1FT=BPLS OUT2=COOL O2TY=4-20 O2FT=BPLS
Adjust SV at 120.0 LC , CPB at 125 ( % ) and DB at -4.0 (%). Apply Auto-tuning at 120 LC for a new system to get an optimal PID values. See Section 3-11.
Adjustment of CPB is related to the cooling media used. If water is used as cooling media instead of oil, the CPB is set at 250 (%). If air is used as cooling media instead of oil, the CPB is set at 100 (%). Adjustment of DB is dependent on the system requirements. More positive value of DB will prevent unwanted cooling action, but will increase the temperature overshoot, while more negative value of DB will achieve less temperature overshoot, but will increase unwanted cooling action.
54
UM0C911A
Chapter 5 Calibration
Do not proceed through this section unless there is a definite need to re-calibrate the controller. Otherwise, all previous calibration data will be lost. Do not attempt recalibration unless you have appropriate calibration equipment. If calibration data is lost, you will need to return the controller to your supplier who may charge you a service fee to re-calibrate the controller.
Entering calibration mode will break the control loop. Make sure that if the system is allowable to apply calibration mode.
Equipments needed before calibration: (1) A high accuracy calibrator ( Fluke 5520A Calibrator recommended ) with following functions: 0 - 100 mV millivolt source with A0.005 % accuracy 0 - 10 V voltage source with A0.005 % accuracy 0 - 20 mA current source with A0.005 % accuracy 0 - 300 ohm resistant source with A0.005 % accuracy (2) A test chamber providing 25 BC - 50 BC temperature range (3) A switching network ( SWU16K, optional for automatic calibration ) (4) A calibration fixture equipped with programming units ( optional for automatic calibration ) (5) A PC installed with calibration software BC-Net and Smart Network Adaptor SNA10B ( optional for automatic calibration ) The calibration procedures described in the following section are a step by step manual procedures.
Since it needs 30 minutes to warm up an unit before calibration, calibrating the unit one by one is quite inefficient. An automatic calibration system for small quantity as well as for unlimited quantity is available upon request.
UM0C911A
55
* Perform step 2
Step 2. Short the thermocouple inpt terminals , then press scroll key for at least 3 seconds. The display will blink a moment and a new value is obtained. Otherwise, if the display didn't blink or if the obtained value is equal to -199.9 or 199.9, then the calibration fails. Step 3. Press scroll key until the display shows . Send a 60 mV signal to the thermocouple input terminals in correct polarity . Press scroll key for at least 3 seconds . The display will blink a moment and a new value is obtained . Otherwise , if the display didn't blink or if the obtained value is equal to -199.9 or 199.9, then the calibration fails.
56
UM0C911A
Step 4. Press scroll key until the display shows . Send a 100 ohms signal to the RTD input terminals according to the connection shown below: C21 8 9 10 C91 3 4 5 C92 18 17 16
100 ohms
Step 5. Press scroll key and the display will show . Change the ohm's value to 300 ohms .Press scroll key for at least 3 seconds. The display will blink a moment and two values are obtained for RTDH and RTDL ( step 4 ). Otherwise, if the display didn't blink or if any value obtained for RTDH and RTDL is equal to -199.9 or 199.9 , then the calibration fails. * Perform step 6 to calibrate offset of cold junction compensation , if required. Step 6. Setup the equipments according to the following diagram for calibrating the cold junction compensation. Note that a K type thermocouple must be used.
UM0C911A
57
C21
9 10
C91
4 5
C92
17 16
The 5520A calibrator is configured as K type thermocouple output with internal compensation. Send a 0.00 LC signal to the unit under calibration.
The unit under calibration is powered in a still-air room with temperature 25A3 BC. Stay at least 20 minutes for warming up. Perform step 1 stated above, then press scroll key until the display shows . Press up/down key to obtain 40.00. Press scroll key for at least 3 seconds. The display will blink a moment and a new value is obtained . Otherwise , if the display didn't blink or if the obtained value is equal to -5.00 or 40.00, then the calibration fails. step 7 to calibrate gain of cold junction compensation * Perform if required. Step 7. Setup the equipments same as step 6. The unit under calibration is powered in a still-air room with temperature 50 A3 BC. Stay at least 20 minutes for warming up . The calibrator source is set at 0.00 BC with internal compensation mode.
58
UM0C911A
Perform step 1 stated above , then press scroll key until the display shows . Press scroll key for at least 3 seconds. The display will blink a moment and a new value is obtained. Otherwise , if the display didn't blink or if the obtained value is equal to -199.9 or 199.9, then the calibration fails. This setup is performed in a high temperature chamber, hence it is recommended to use a computer to perform the procedures.
Input modification and recalibration procedures for a linear * voltage or a linear current input: 1. Remove R60(3.3K) and install two 1/4 W resistors RA and RB on the control board with the recommended values specified in the following table. The low temperature coefficient resistors should be used for RA and RB. Input Function T/C, RTD, 0~60mV 0~1V 0 ~ 5V, 1 ~ 5V 0 ~ 10 V 0~20mA, 4~20mA RA X 61.9K 324K 649K 39W RB X 3.92K 3.92K 3.92K 3.01W R60 3.3K X X X X
2. Perform Step 1 and Step 2 to calibrate the linear input zero. 3. Perform Step 3 but send a span signal to the input terminals instead of 60mV. The span signal is 1V for 0~1V input, 5V for 0~5V or 1~5V input, 10V for 0~10V input and 20mA for 0~20mA or 4~20mA input.
Final step
Chapter 6 Specifications
Power
90 264 VAC, 47 63 Hz, 10VA, 5W maximum 11 26 VAC / VDC, 10VA, 5W maximum
Input
Resolution : 18 bits Sampling Rate : 5 times / second Maximum Rating : -2 VDC minimum, 12 VDC maximum ( 1 minute for mA input ) Temperature Effect : A1.5uV/ BC for all inputs except mA input A3.0uV/ BC for mA input Sensor Lead Resistance Effect : T/C: 0.2uV/ohm 3-wire RTD: 2.6 LC/ohm of resistance difference of two leads 2-wire RTD: 2.6 LC/ohm of resistance sum of two leads Burn-out Current : 200 nA Common Mode Rejection Ratio ( CMRR ): 120dB Normal Mode Rejection Ratio ( NMRR ): 55dB
60
UM0C911A
Characteristics:
Type J K T E B Range
Accuracy @ 25 C
A2 LC A2 LC A2 LC A2 LC A2 LC ( 200 C 1800 C ) A2 LC A2 LC A2 LC A2 LC A0.4 LC A0.4 LC A0.05 % A0.05 % A0.05 %
Input Impedance
0 C 1800 C ( 32 BF 3272 BF ) 0 C 1767.8 C ( 32 BF 3214 BF ) 0 C 1767.8 C ( 32 BF 3214 BF ) -250 C 1300 C ( -418 F 2372 F ) -200 C 900 C ( -328 F 1652 F ) -210 C 700 C ( -346 F 1292 F ) -200 C 600 C ( -328 F 1112 F ) -8mV 70mV -3mA 27mA -1.3V 11.5V
UM0C911A
61
Output 1 / Output 2
Relay Rating : 2A/240 VAC, life cycles 200,000 for resistive load Pulsed Voltage : Source Voltage 5V, current limiting resistance 66 . Linear Output Characteristics
62
UM0C911A
DC Voltage Supply Characteristics ( Installed at Output 2 ) Type Tolerance Max. Output Current 20 V 12 V 5V A0.5 V A0.3 V A0.15 V 25 mA 40 mA 80 mA Ripple Voltage 0.2 Vp-p 0.1 Vp-p Isolation Barrier 500 VAC 500 VAC
Output 2 Functions : Dwell timer, Deviation High / Low Alarm, Deviation Band High / Low Alarm, PV High / Low Alarm, PID cooling control Alarm Mode : Normal, Latching, Hold, Latching / Hold. Dwell Timer : 0.1 - 4553.6 minutes
Data Communication
Interface : RS-232 ( 1 unit ), RS-485 ( up to 247 units ) Protocol : Modbus Protocol RTU mode Address : 1 - 247 Baud Rate : 2.4 ~ 38.4 Kbits/sec Data Bits : 7 or 8 bits Parity Bit : None, Even or Odd Stop Bit : 1 or 2 bits Communication Buffer : 160 bytes
UM0C911A
63
User Interface
Single 4-digit LED Display Keypad : 4 keys for C91 and C92, 3 keys for C21 Programming Port : For automatic setup, calibration and testing Communication Port : Connection to PC for supervisory control
Control Mode
Output 1 : Reverse ( heating ) or direct ( cooling ) action Output 2 : PID cooling control, cooling P band 50~300% of PB, dead band -36.0 ~ 36.0 % of PB ON-OFF : 0.1 - 90.0 ( LF ) hysteresis control ( P band = 0 ) P or PD : 0 - 100.0 % offset adjustment PID : Fuzzy logic modified Proportional band 0.1 ~ 900.0 LF. Integral time 0 - 1000 seconds Derivative time 0 - 360.0 seconds Cycle Time : 0.1 - 90.0 seconds Manual Control : Heat (MV1) and Cool (MV2) Auto-tuning : Cold start and warm start Failure Mode : Auto-transfer to manual mode while sensor break or A-D converter damage Ramping Control : 0 - 900.0 LF/minute or 0 - 900.0 LF/hour ramp rate
Digital Filter
Function : First order Time Constant : 0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds programmable
64
UM0C911A
Approval Standards
Safety : UL61010C-1 CSA C22.2 No. 24-93 EN61010-1 ( IEC1010-1 ) Protective Class : IP65 front panel for C21 IP30 front panel for C91, all indoor use. IP20 for terminals and housing with protective cover. EMC: EN61326
UM0C911A
65
CRC16 Hi CRC16 Lo Function 06: Preset single Register Query ( from master ) Slave address (0-255) Function code (6) Register address Hi (0) Register address Lo (0-79) Data Hi Data Lo CRC16 Hi CRC16 Lo Response ( from slave )
66
UM0C911A
Function 16: Preset Multiple Registers Query ( from master ) Slave address (0-255) Function code (16) Starting address of register Hi (0) Starting address of register Lo (0-79) No. of words Hi (0) No. of words Lo (1-79) Byte count (2-158) Data 1 Hi Data 1 Lo Data 2 Hi Data 2 Lo Response ( from slave )
CRC16 Hi CRC16 Lo
CRC16 Hi CRC16 Lo
UM0C911A
67
Function code is not supported by the controller Illegal data address Register address out of range Illegal data value Data value out of range or attempt to write a read-only or protected data
68
UM0C911A
-1999.9 4553.6
-1999.9 4553.6
UM0C911A
69
Parameter Output 2 cycle time Cooling P band Heating-cooling dead band Alarm function Reserved Alarm opertion mode Alarm hysteresis Alarm failure transfer Communication function Address Baud rate Data bit count Parity bit Stop bit count Selection 1 Selection 2 Selection 3 Selection 4 Selection 5 Selection 6 Selection 7 Selection 8 mV calibration low coefficient mV calibration high coefficient RTD calibration low coefficient RTD calibration high coefficient
Scale High 6553.5 65535 65535 65535 65535 *5 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535
Notes R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
-1999.9 4553.6
Cold junction calibration low coefficient -199.99 455.36 Cold junction calibration high coefficient -1999.9 4553.6 Reserved Reserved Working hours of the controller 0 0 0 65535 65535 65535
70
UM0C911A
Parameter Bumpless transfer of OP1 Bumpless transfer of OP2 Cold junction signal low Process value Current set point value OP1 control output value
Notes R R R R
R Read only, unless in 655.35 manual control 655.35 Read only, unless in manual control R R R R R/W R/W R/W R/W R R R R
67
MV2
0.00
68 69 70 71 72 73 74 75 76 77 78 79
Remaining time of dwell timer Error code *1 Operation mode & alarm status *2 Program code *3 Command code Job code Job code Job code Reserved Reserved Reserved Reserved
-1999.9 4553.6 0 0 0.00 0 0 0 0 0 0 0 0 65535 65535 655.35 65535 65535 65535 65535 65535 65535 65535 65535
*1: The error code is show in the first column of Table A.1. *2: Definition for the value of MODE register H'000X = Normal mode H'0X00 = Alarm status is off H'010X = Calibration mode H'0x01 = Alarm status is on H'020X = Auto-tuning mode H'030X = Manual control mode The alarm status is shown in H'040X = Failure mode MV2 instead of MODE for models C21, C91 and C92.
UM0C911A 71
*3: The PROG Code is defined in the following table: Model No. BTC-9100 BTC-8100 BTC-4100 BTC-7100 C21 C91 C92 6.XX PROG Code 11.XX 12.XX 13.XX 33.XX 34.XX 35.XX Where XX denotes the software version number. For example: PROG=34.18 means that the controller is C91 with software version 18. *4: The scale high/low values are defined in the following table for SP1, INLO, INHI, SP1L, SP1H, SHIF, PV and SV: Conditions Scale low Scale high Non-linear input -1999.9 4553.6 Linear input Linear input Linear input Linear input DP = 0 DP = 1 DP = 2 DP = 3 -19999 45536 -1999.9 4553.6 -199.99 455.36 -19.999 45.536
*5: The scale high/low values are defined in the following table for PB, O1HY, RR, O2HY and ALHY: Non-linear Linear input Linear input Linear input Linear input Conditions input DP = 0 DP = 1 DP = 2 DP = 3 Scale low Scale high 0.0 6553.5 0 65535 0.0 6553.5 0.00 655.35 0.000 65.535
*6: The scale high/low values are defined in the following table for SP3: Conditions Scale low Scale high ALFN=1 Non-linear Linear input Linear input Linear input Linear input (TIMR) input DP = 0 DP = 1 DP = 2 DP = 3 -1999.9 -1999.9 -19999 4553.6 4553.6 45536 -1999.9 -199.99 -19.999 4553.6 455.36 45.536
*7: The scale high/low values are defined in the following table for SP2: For C21, C91and C92 OUT2=1 Non-linear Linear input Linear input Linear input Linear input Conditions (TIMR) input DP = 0 DP = 1 DP = 2 DP = 3 Scale low Scale high
72
For BTC-9100, BTC-8100, BTC-7100 and BTC-4100 Conditions Scale low Scale high Non-linear input -1999.9 4553.6 Linear input Linear input Linear input Linear input DP = 0 DP = 1 DP = 2 DP = 3 -19999 45536 -1999.9 4553.6 -199.99 455.36 -19.999 45.536
UM0C911A
73
01
10
00
00
00
34
68
4F 19 4E 83
4E
83
Addr. Func. Starting Addr. No. of words Bytes SP1=25.0 SP2=10.0 SP3=10.0 00 00 LOCK=0 00 01 INPT=1 00 00 UNIT=0 00 01 4D 6D 51 C4 DP=1 INLO=-17.8 INHI=93.3 00 64 PB=10.0 00 01 O1HY=0.1 00
4D 6D 63 21 4E 1F 00 02 00 00 SP1L=-17.8 SP1H=537.8 SHIF=0.0 FILT=2 DISP=0 00 64 TI=100 00 FA 00 00 00 00 TD=25.0 OUT1=0 O1TY=0 4E 1F O1FT=0
00 00 00 02 00 RR=0.0 OUT2=2
00 00 4E 1F 00 01 00 B4 00 64 4E 1F O2TY=0 O2FT=0 O2HY=0.1 CYC2=18.0 CPB=100 DB=0 00 02 ALFN=2 00 00 00 00 ALMD=0 00 01 ALHY=0.1 00 00 PARI=0 00 07 SEL5=7 00 00 ALFT=0 00 00 STOP=0 00 08 SEL6=8 01 00 COMM=1 02 00 SEL1=2 0A 00 SEL7=10
74
UM0C911A
Example 2: Read PV, SV, MV1, MV2, TIMER, EROR and MODE Send the following message to the controller via the COMM port or programming port: 03 Addr. Func. 00 H'40 00 07 Hi Lo
Starting Addr.
No. of words
CRC16
Example 3: Perform Reset Function (same effect as pressing R key) Query 06 Addr. Func. 00 H'48 H'68 H'25 Hi Lo
Register Addr.
Data Hi/Lo
CRC16
Example 4: Enter Auto-tuning Mode Query 06 Addr. Func. 00 H'48 H'68 H'28 Hi Lo
Register Addr.
Data Hi/Lo
CRC16
Example 5: Enter Manual Control Mode Query 06 Addr. Func. 00 H'48 H'68 H'27 Hi Lo
Register Addr.
Data Hi/Lo
CRC16
Starting Addr.
No. of words
CRC16
UM0C911A
75
10 11 14
Communication error: bad function Correct the communication code software to meet the protocol requirements. Don't issue an over-range Communication error: register register address to the slave. address out of range Communication error: attempt to write a read-only data or a protected data Communication error: write a value which is out of range to a register Don't write a read-only data or a protected data to the slave. Don't write an over-range data to the slave register. 1.The PID values obtained after auto-tuning procedure are out of range. Retry auto-tuning. Fail to perform auto-tuning function 2.Don't change set point value during auto-tuning procedure. 3.Use manual tuning instead of auto-tuning. 4. Don't set a zero value for PB. 5. Don't set a zero value for TI. 6. Touch RESET key
15
26
29 30
EEPROM can't be written correctly Return to factory for repair. Cold junction compensation for thermocouple malfunction Input sensor break, or input current below 1 mA if 4-20 mA is selected, or input voltage below 0.25V if 1 - 5V is selected A to D converter or related component(s) malfunction Return to factory for repair.
39
40
76
UM0C911A
WARRANTY
Brainchild Electronic Co. is pleased to offer suggestions on the use of its various products. However, Brainchild makes no warranties or representations of any sort regarding the fitness for use, or the application of its products by the Purchaser. The selection, application or use of Brainchild products is the Purchaser's responsibility. No claims will be allowed for any damages or losses, whether direct, indirect, incidental, special or consequential. Specifications are subject to change without notice. In addition, Brainchild reserves the right to make changes-without notification to Purchaser-to materials or processing that do not affect compliance with any applicable specification. Brainchild products are warranted to be free from defects in material and workmanship for two years after delivery to the first purchaser for use. An extended period is available with extra cost upon request. Brainchild's sole responsibility under this warranty, at Brainchild's option, is limited to replacement or repair, free of charge, or refund of purchase price within the warranty period specified. This warranty does not apply to damage resulting from transportation, alteration, misuse or abuse.
RETURNS
No products return can be accepted without a completed Return Material Authorization ( RMA ) form.
UM0C911A
77
BRAINCHILD Electronic Co., Ltd. 6F., No.209, Chung Yang Rd., Nan Kang Dist., Taipei, Taiwan, R.O.C. Tel: 886-2-27861299 Fax: 886-2-27861395 web site: http://www.brainchild.com.tw