Omron K3MA-L Datasheet
Omron K3MA-L Datasheet
Omron K3MA-L Datasheet
K3MA-L
CSM_K3MA-L_DS_E_6_1
Highly Visible LCD Display with 2-color (Red and Green) LEDs
Wide input range - select from two types of platinum-resistance thermometers and ten types of thermocouples. Front-panel key operation for easy setting. Average processing function suppresses flicker. Temperature input shift and temperature unit selection functions. Easy confirmation of max/min display. Short 80-mm depth (measured from edge of face plate). Finger protective cover (standard equipment) protects against electric shock. Water- and dust-proof NEMA4X (IP66 equivalent) front panel. Recognized to conform to U.S. and Canadian requirements under the Component Recognition Program of UL. CE marking.
Refer to Safety Precautions for All Digital Panel Meters.
Ordering Information
List of Models
Input type Platinum-resistance thermometer or thermocouple Supply voltage 100 to 240 VAC 24 VAC/VDC None 1 relay contact output (SPDT) None 1 relay contact output (SPDT) Output Model K3MA-L 100-240VAC K3MA-L-C 100-240VAC K3MA-L 24VAC/VDC K3MA-L-C 24VAC/VDC
Rubber Packing
Model K32-P1
Hard Cover
K32-49HC
K3MA-L
Specifications
Ratings
K3MA-L 100-240VAC, K3MA-L-C 100-240VAC Supply voltage Operating voltage range Power consumption (under maximum load) Insulation resistance Dielectric strength Noise immunity 100 to 240 VAC 85% to 110% of the rated supply voltage 6 VA max. 4.5 VA max. (24 VAC) 4.5 W max. (24 VDC) K3MA-L 24VAC/VDC, K3MA-L-C 24VAC/VDC 24 VAC (50/60 Hz), 24 VDC
20 M min. (at 500 VDC) between external terminal and case. Insulation provided between inputs, outputs, and power supply. 2,000 VAC for 1 min between external terminal and case. Insulation provided between inputs, outputs, and power supply. 1,500 V on power supply terminals in normal or com- 480 V on power supply terminals in normal mode. mon mode. 1,500 V in common mode. 1 s, or 100 ns for square-wave noise with 1 ns. 1 s, or 100 ns for square-wave noise with 1 ns. Vibration: 10 to 55 Hz, Acceleration: 50 m/s2 5 min each in X, Y, and Z directions for 10 sweeps. 150 m/s2 (100 m/s2 for relay contact outputs) 3 times each on 3 axes, 6 directions. Operating: 10C to 55C (with no condensation or icing) Storage: 25C to 65C (with no condensation or icing) Operating: 25% to 85% (with no condensation) UL61010-1, conforms to EN61010-1 (Pollution degree 2/overvoltage category II) Conforms to VDE0106/P100 (finger protection) (EMI) Emission Enclosure: Emission AC Mains: (EMS) Immunity ESD: EN61326+A1 Industry CISPR 11 Group 1 class A CISPR 11 Group 1 class A EN61326+A1 Industry EN61000-4-2: 4 kV contact discharge 8 kV air discharge Immunity RF-interference: EN61000-4-3: 10 V/m (amplitude-modulated, 80 MHz to 1 GHz) Electrical Fast Transient Noise: EN61000-4-4: 2 kV (power line) Immunity Burst Noise: 1 kV line to line (I/O signal line) Immunity Surge: EN61000-4-5: 1 kV (power line) 2 kV line to ground (power line) Immunity Conducted Disturbance: EN61000-4-6: 3 V (0.15 to 80 MHz) Immunity Voltage Dip/Interrupting: EN61000-4-11: 0.5 cycle, 0, 180, 100% (rated voltage) Approx. 200 g
Vibration resistance Shock resistance Ambient temperature Ambient humidity Approved safety standards EMC
Weight
K3MA-L
Characteristics
Indication accuracy (at 235C) (See note.) Thermocouple: (0.5% of indication value or 1C, whichever greater) 1 digit max. Platinum-resistance thermometer: (0.5% of indication value or 1C, whichever greater) 1 digit max. Thermocouple: K, J, T, E, L, U, N, R, S, B Platinum-resistance thermometer: JPt100, Pt100 Double integral method 500 ms Sampling period (sampling times multiplied by number of averaging times if average processing is selected.) 4 digits (1999 to 9999) 7-segment digital display, Character height: 14.2 mm is displayed automatically with a negative input signal. Leading zeros are not displayed. Input shift equivalent to the setting value supported for all points within the sensor measurement range. Max hold (maximum value), Min hold (minimum value) Programmable with front-panel key inputs (0001 to 9999). Display color change (green (red), green, red (green), red) Average processing (simple average OFF/2/4/8 operations) Setting change lockout Parameter initialization Relay contact (SPDT) 1 s max. Front panel: NEMA4X for indoor use (equivalent to IP66) Rear case: IEC standard IP20 Terminals: IEC standard IP00 + finger protection (VDE0106/100) Non-volatile memory (EEPROM) (possible to rewrite 100,000 times)
Input Measurement method Sampling period Display refresh period Max. displayed digits Display Polarity display Zero display Input shift Hold function Hysteresis setting Other functions
Memory protection
Note: The indication accuracy of the K thermocouple at a temperature of 200 to 1300C is 2C 1 digit maximum. The indication accuracy of the T and N thermocouples at a temperature of 100C or less is 2C 1 digit maximum. The indication accuracy of the U and L thermocouples at any temperature is 2C 1 digit maximum. The indication accuracy of the B thermocouple at a temperature of 400C or less is unrestricted. The indication accuracy of the R and S thermocouples at a temperature of 200C or less is 3C 1 digit maximum.
Measuring Ranges
Platinum-resistance Thermometer
Input Range Parameter C F 200 to 850 300 to 1500 0 Pt100 199.9 to 500.0 199.9 to 900.0 1 0.0 to 100.0 0.0 to 210.0 2 199.9 to 500.0 199.9 to 900.0 3 JPt100 0.0 to 100.0 0.0 to 210.0 4
Thermocouple
Input Range C F Parameter 200 to 1300 300 to 2300 5 K 20.0 to 500.0 0.0 to 900.0 6 100 to 850 100 to 1500 7 J 20.0 to 400.0 0.0 to 750 8 200 to 400 300 to 700 9 T 199.9 to 400.0 199.9 to 700.0 10 E 0 to 600 0 to 1100 11 L 100 to 850 100 to 1500 12 200 to 400 300 to 700 13 U 199.9 to 400.0 199.9 to 700.0 14 N 200 to 1300 300 to 2300 15 R 0 to 1700 0 to 3000 16 S 0 to 1700 0 to 3000 17 B 100 to 1800 300 to 3200 18
Input/Output Ratings
Relay Contact Output
Item Rated load (UL ratings) Rated carry current Max. contact voltage Max. contact current Max. switching capacity Min. permissible load (P level, reference value) Mechanical life Electrical life (at an ambient temperature of 20C) Resistive load (cos = 1) 5 A at 250 VAC, 5 A at 30 VDC 5 A max. (at COM terminal) 400 VAC, 150 VDC 5 A (at COM terminal) 2,000 VA, 192 W 10 mA at 5 VDC 20,000,000 times min. (at a switching frequency of 1,200 time/min) 100,000 times min. (at a rated load switching frequency of 10 time/min) 375 VA, 30 W Inductive load (cos = 0.4, L/R = 7 ms) 1.5 A at 250 VAC, 1.5 A at 30 VDC
K3MA-L
Connections
Terminal Arrangement
Power supply Output terminals 100- to 240-VAC type or 24-VAC/VDC type (No polarity for 24-VDC connection.)
A1 A2
E1 E2 E3 E4 E5 E6 E4
A B B
Input terminals
E5 E6
Terminal No.
A1 - A2 E4 - E6 - E5 E1 , E2 - E3
Description Connects the operation power supply. Connects the thermocouple or platinum-resistance thermometer input. Outputs the relay outputs.
Block Diagram
Input Input Microcomputer EEPROM Key
5V
12 V
K3MA-L
Operation
Main Functions
Input Types and Ranges
Parameter in-t 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 N R S B E L U T J Thermocouple K JPt100 Setting Input type Platinum-resistance thermometer Pt100 Meaning 200 to 850C 199.9 to 500.0C 0.0 to 100.0C 199.9 to 500.0C 0.0 to 100.0C 200 to 1300C 20.0 to 500.0C 100 to 850C 20.0 to 400.0C 200 to 400C 199.9 to 400.0C 0 to 600C 100 to 850C 200 to 400C 199.9 to 400.0C 200 to 1300C 0 to 1700C 0 to 1700C 100 to 1800C 300 to 1500F 1999 to 900.0F 0.0 to 210.0F 199.9 to 900.0F 0.0 to 210.0F 300 to 2300F 0.0 to 900.0F 100 to 1500F 0.0 to 750.0F 300 to 700F 199.9 to 700.0F 0 to 1100F 100 to 1500F 300 to 700F 199.9 to 700.0F 300 to 2300F 0 to 3000F 0 to 3000F 300 to 3200F
Lower limit (Low Acting): The output is turned ON when the measurement value is less than its set value. Upper and lower limits (Outside Band Acting): An upper limit (H set value) and lower limit (L set value) can be set independently. The output is turned ON when the measurement value is greater than the upper-limit set value or less than the lower-limit set value. Parameter out 1.t hi lo hi-lo Setting Meaning Upper limit: Alarm operates at upper limit. Lower limit: Alarm operates at lower limit. Upper and lower limits: Alarm operates at upper and lower limits.
Hysteresis
Hysteresis
Hysteresis
Hysteresis
K3MA-L
Temperature Input Shift
Input shift equivalent to the setting value supported for all points within the sensor measurement range. Parameter ins -1999 to 9999
Red
Setting
258.9
Temperature OUT1 value Before shift After shift Temperature input shift value Input Green
192.0
Parameter Initialization
This function returns all of the parameters to their initial values. Parameter init off on Setting --Initializes all parameters. Meaning
Move-to-Protect-Level Time
The time required to shift to the protect level can be set as desired.
MAX/MIN Display
The maximum and minimum measurement (display) values from the time the power is turned ON until the current time can be stored and displayed. This is useful, for example, when measuring the maximum value.
Current value
Use this to reset the K3MA-L after returning it to its factory-set condition.
Average Processing
Average processing stabilizes displayed values to minimize flicker by averaging the fluctuating input signals. Average processing can be performed for the measurement values in either of four steps (OFF, 2 times, 4 times, or 8 times).
MAX/MIN LEVEL MODE SHIFT UP
MAX/MIN
MAX value
Max
MAX/MIN
MAX/MIN LEVEL MODE SHIFT UP
MIN value
Min
This is useful for ignoring rapid fluctuations, e.g., eliminating spike noise.
MAX/MIN LEVEL MODE SHIFT UP
MAX/MIN
Set value
Hysteresis
Measurement value
ON Output OFF
K3MA-L
Nomenclature
2. Operation indicators
Max Min
1. Main indicator
3. Level indicator
SV
MAX/MIN
LEVEL
MODE
SHIFT
UP
Functions
Used to display the MAX and MIN values when a measurement value is being displayed. Used to change the level. Used to allow the main indicator to indicate parameters sequentially. Used to enable a set value to be changed. When changing a set value, this key is used to move along the digits. Used to change a set value. Used to set or clear a forced-zero function when a measurement value is being displayed. Level Protect Operation Adjustment Initial setting Advanced-function setting
p
Not lit
a s f
K3MA-L
Dimensions
101.2 91 Finger protective cover (provided)
Panel cut-out
120 min.
96
MAX/MIN
LEVEL
MODE
SHIFT
Application Examples
Monitoring the temperature of an industrial furnace Sending a temperature alarm for molding equipment
PID control E5EN
K3MA-L Industrial furnace Molding Alarmequipment output Alarm output K3MA-L Alarm output
Monitoring the temperature of an industrial furnace/sintering furnace. Monitoring/alarm function for disinfecting equipment.
Monitoring (failsafe checking) abnormal temperatures in molding equipment. Monitoring the liquid temperature for cleaning devices.
85
97 7.6 mm
75 min.
0 92+0.5
12 1.3 80
45 0
+0.5
44.8 48
UP
Mounting Recommended Panel Thickness 1 to 8 mm. Mount the product horizontally. The K3MA-L uses M3 terminals. A terminal cover is provided.
Monitoring temperature rises in electric power generating facilities. Inspecting temperatures in machines and devices.
K3MA-L
Installation
1. Insert the K3MA-L into the panel cut-out hole. 2. For a waterproof installation, insert the rubber gasket onto the body of the K3MA-L.
Wiring
Use the following M3 crimp terminals.
5.8 mm max.
5.8 mm max.
3. Fit the adaptor into the grooves on the left and right sides of the rear case, then push it until it contacts the panel to secure the K3MA-L.
Note: For scales and gauges, use the unit labels that are specified by the relevant laws or regulations.
10 30
Wiring Precautions
Use crimp terminals. Tighten the terminal screws to a torque of approximately 0.5 Nm. To avoid the influence of noise, route signal lines and power lines separately.
K3MA-L
Operating Procedures
Operations in Run Mode
Checking the Maximum and Minimum Values
The maximum and minimum values can be displayed by pressing the MAX/MIN Key while the measurement is being displayed.
Measurement value
MAX/MIN Key
MAX value
MAX/MIN Key
MIN value
MAX/MIN Key
The maximum and minimum values can be reset by pressing the MAX/MIN Key for 1 s min. when the maximum or minimum value is displayed.
Checking and Setting Comparative Set Values (for Models with the Comparative Output Function)
Each time the Mode Key is pressed when the measurement value, maximum value, or minimum value is displayed, the comparative values will be displayed in the following order: OUT1 value (or OUT1 upper-limit value, OUT1 lower-limit value).
After shift
OUT1 value
Input
Mode Key
The value set for the temperature input shift is applied to the entire measurement range of the temperature sensor.
10
K3MA-L
Levels
Level refers to a grouping of parameters. The following table lists the operations that are possible in each of the levels, and the diagram tells how to move between levels. There are some parameters that are not displayed for certain models. Level name Protect Operation Adjustment Initial setting Advanced-function setting Setting lockouts. Displaying current values, and setting OUT 1 value. Setting communications writing control. Function Continue Continue Continue Measurement
Making initial settings of input type, output operating action, and other Stopped parameters. Setting average processing, display color settings, and other advanced function parameters. Stopped
Power ON
Operation level + Time set by user (See note.) Protect level + 1 s min.
1 s min. 1 s min.
- 123.4
Continue to press the key for 2 s min. Initial setting level
1 s min.
Password "0169"
Note: The move-to-protect-level time can be set in the advanced-function setting level.
11
K3MA-L
Parameters
Note: 1. Some parameters are not displayed for certain models. 2. The K3MA-L will stop measurement if the level is changed to the initial setting level or the advanced-function setting level. 3. If the input range is changed, some parameters are set to default values. Therefore, set the input range first. 4. Settings displayed in reversed colors are defaults.
Power ON Press Level Key for less than 1 s. Adjustment level Press Level Key for less than 1 s. Current value
Temperature input shift For models with the comparative output function MODE
Operation level
OUT1 value
MODE
MODE
OUT1 lower-limit value
MODE
12
K3MA-L
To change a setting, press the Shift Key make the change with the Up Key .
Input type
MODE
Average processing
/ /
Unit: times
MODE
Models with the comparative output function
OUT1 hysteresis
OUT1 Hysteresis
MODE
Display color change
Green (red) Green Red (green) Red
MODE
Password: 0169
MODE
Display auto-return time
Unit: s
MODE
Move-toprotectlevel time
MODE
Unit: s
13
K3MA-L
Press Level Key + Mode Key for more than 1 s.
Operation Level
Press Level Key + for more than preset time. Mode Key
Protect level
Operation/adjustment lockouts
MODE
/ / / / /
Operation/Adjustment Lockouts
Restricts key operations for operation level and adjustment level. Parame- Setting ter oapt 0 1 2 Operation level Process value display Allowed Allowed Allowed Set value display Allowed Allowed Prohibited Moving to adjustment level Allowed Prohibited Prohibited
Initial Settings
Power ON
Initial setting is 0. This cannot be displayed on models not equipped with the comparative output function.
If desired, shift to the adjustment level to set the temperature input shift value.
If required, shift to the advanced-function setting level to set the number of measurements for averaging, hysteresis values, auto-zero time, display color change, display auto-return time, or move-to-protect-level time.
icpt
0 1 2
Measurement starts.
14
K3MA-L
Setting Example
Initial Settings
The settings for the following example are shown here. Here, the temperature inside the furnace is to be displayed in centigrade (C). Temperature sensor: E52-PR Thermocouple, Measurement range: 0 to 1,400C. 1. Set the K3MA-L input type to the thermocouple R input range. Parameter: in-t (input type), Setting value: 16 2. Select centigrade (C) as the temperature unit. Parameter: d-u (temperature unit), Setting value: c If you are using a comparative output model, make the setting as desired.
Max Min
SV
MAX/MIN
LEVEL
MODE
SHIFT
UP
K3MA-L-C 100-240VAC
Troubleshooting
When an error occurs, error details will be displayed on the main indicator. Confirm the error from the main indicator and take the appropriate countermeasures. Level display Not lit e111 Main indicator Error contents RAM memory error Countermeasures Repair is necessary. Consult your OMRON sales representative. When this error is displayed, press the Level Key for 3 seconds, and the settings will be restored to the factory settings. If the error cannot be recovered, repair is necessary. Consult your OMRON sales representative. Confirm that the temperature sensor is correctly connected, and that there are no broken signal lines to the temperature sensor. Input value is out of the specified range (control range). Set the value within the range immediately. If the condition does not return to normal, repair is necessary. Consult your OMRON sales representative.
e111
Not lit
Flashes s.err
Input error
Not lit
Flashes 9999
The measurement value after tem- The temperature input correction perature input correction exceeds value may be inappropriate. 9999. Use the adjustment level to review the temperature input correction value. The measurement value after tem- The temperature input correction perature input correction is lower value may be inappropriate. than 1999. Use the adjustment level to review the temperature input correction value.
Not lit
Flashes -1999
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice.
15
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products: Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog. Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRONs test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.