F940wgot TWD Installation M
F940wgot TWD Installation M
F940wgot TWD Installation M
Installation Manual
JY992D93901D
This manual contains text, diagrams and explanations which will guide the reader in the correct installation, safe use and operation of the F940WGOT-TWD-E and should be read and understood before attempting to install or use the unit. Further information can be found in the associated manuals list below. Specifications are subject to change without notice
Guidelines for the Safety of the User and Protection of the F940WGOT Series.
This manual has been written to be used by trained and competent personnel. The definition of such a person or persons is as follows: a) Any engineer using the product associated with this manual, should be of a competent nature, trained and qualified to the local and national standards. These engineers should be fully aware of all aspects of safety with regards to automated equipment. b) Any commissioning or service engineer must be of a competent nature, trained and qualified to the local and national standards. c) All operators of the completed equipment should be trained to use that product in a safe and co-ordinated manner in compliance to established safety practices. Note: The term completed equipment refers to a third party constructed device which contains or uses the product associated with this manual.
2) Indicates that the identified danger could POSSIBLY cause physical and property damage. Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment. All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples. Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability for your specific application.
Associated Manuals
Manual Name F940WGOT Series ! (F940GOT-TWD) Installation Manual GOT-F900 " OPERATION MANUAL (describes GT Designer2) " GOT-F900 Series Operation Manual Manual Number JY997D93901 Description Describes the specifications, wiring, and installation of F940WGOT Series graphic operation terminal. (hardware) Describes the operation and use of the GOTF900 Series graphic operation terminals and GT Designer2. Describes the operation and use of the GOTF900 Series graphic operation terminals, GT Designer and FX-PCS-DU/WIN-E. Describes wiring and installation of the GOTF900 Series graphic operation terminals. Describes the operation of GT Designer2 (SW*D5C-GTD2-E) and data transfer to the GOT-900 Series. Describes the specifications and setting of object functions in GT Designer2 (SW*D5C-GTD2-E). Describes the operation of GT Designer (SW*D5C-GOTR-PACKE) and data transfer to the GOT-900 Series. (Refer to the help file) Describes the operation of FX-PCS-DU/WIN-E screen creation software.
JY997D09101 (separate volume) JY992D94701 (separate volume) JY992D94801 (separate volume) (PDF files on CDROM included with product) (PDF files on CDROM included with product) Included with the screen creation software JY992D68301 (included with the screen creation software)
GOT-F900 Series " Hardware Manual (connection diagram) ! GT Designer2 Version1 Operating Manual GT Designer2 Version1 Reference Manual GT Designer Operating Manual
Description This manual contains explanations for installation and operating procedures of the F9GT-40FMB data transfer adapter.
" Indispensable manual ! Either manual is necessary. # Refer if necessary, please. Refer to the Programming manual () or relevant hardware manuals for details concerning the applicable PLC.
1. Introduction
The F940WGOT series (hereafter called GOT) is to be mounted on the face of a control panel or operations panel, and c o nn e ct e d t o t he pr o gra m m in g p or t ( CP U po r t ) o r t h e communication port (communication port) of a PLC. Various devices can be monitored and PLC data changed through the GOT screens. Several display screens are built-in to the GOT, and additional personalized screens can be created by the user. 1) The GOT can connect to MELSEC FX, A, QnA and Q PLCs as well as a host of third party manufactured units. Further information can be found in GOT-F900 Series Hardware Manual.
P L C
P r o g r a m m in g p o rt
G O T
2) PLC user programs can be downloaded, uploaded and monitored using programming software GXDeveloper or FX-PCS/WIN-E on a personal computer via the GOT. Further information can be found in GOT-F900 Series Operation Manual. 3) Display screens are created using the following software: Software Name GT Designer2 SW#D5C-GTD2-E (# indicates version) GT Designer SW#D5C-GOTR-PACKE (# indicates version) FX-PCS-DU/WIN-E Version GOT-F900 and GOT-A900 Series (for Windows) screen creation software.
GOT-F900 and GOT-A900 Series (for Windows) screen creation software. SW5-F edition of SW5D5C-GOTR-PACKE (version 5.05F) or later GOT-F900 Series (for Windows) screen creation software. SW0PC-FXDU/WIN-E version 2.50 or later
FX-50DU-CAB0
Communication cable (GOT CPU port in FX0, FX0S, FX1S, FX0N, FX1N, FX2N or FX2NC series PLC) FX-50DU-CAB0/EN The connector on the GOT side is wired straight through. Cable length is 3m (9' 10"). Communication cable (GOT CPU port in FX0, FX0S, FX1S, FX0N, FX1N, FX2N or FX2NC series PLC) FX-50DU-CAB0-**M The connector on the GOT side is wired straight through. ** M is cable length. 1M: 1m (3' 3"), 10M: 10m (32' 9"), 20M: 20m (65' 7"), 30M: 30m (98' 5") FX-40DU-CAB Communication cable (GOT CPU port in FX, FX2C, A or QnA series PLC) The connector on the GOT side is wired straight through. Cable length is 3m (9' 10"). Communication cable (GOT CPU port in FX, FX2C, A or QnA series PLC) The connector on the GOT side is wired straight through. ** M is cable length. 10M: 10m (32' 9"), 20M: 20m (65' 7"), 30M: 30m (98' 5") Communication cable (GOT CPU port in Q series PLC) The connector on the GOT side wired straight through. Cable length is 3m (9' 10"). Data exchange cable (GOT Personal computer <9-pin D-sub>) Battery for Alarm history, sampling and current time data retention. Transparent protection sheet for F940WGOT (5 pieces) Data transfer adapter (Flash memory built in)
FX-40DU-CAB-**M
Caution
During abnormal communication (including cable breakages) ages when monitor within the GOT, communication between the GOT and programmable controller CPU is interrupted. It is impossible to operate switches or devices in the PLC through the GOT. Communication and normal operation resumes when the GOT system is correctly configured. DO NOT configure emergency stop or safety features to operate through the GOT, and be sure that there is no adverse consequences in the event of a GOT - PLC communications malfunction.
Note;
Do not lay signal cables near high voltage power cables or allow them to share the same trunking duct, otherwise, effects of noise or surge induction are likely to take please. Keep a safe distance of more than 100 mm from these wires. Operate touch switches on the display screen by hand. DO NOT use excessive force, or attempt operate them with hard or pointed objects. The tip of a screw driver, pen or similar object for example may break the screen.
1 2 3 (4 .8 4 ") 7 0 .6 (2 .7 8 ")
5 (0 .2 0 ") 2 1 5 (8 .4 6 ")
1 0 (0 .3 9 ")
d )
1 0 (0 .3 9 ") c )
7 0 .6 (2 .7 8 )
2 3 (0 .9 1 ")
5 0 (1 .9 6 ")
g ) f ) 3 4 .5 (1 .3 5 ")
2 4 V D C
3 4 .5 (1 .3 5 ") 5 ( 0 .2 0 " ) o r le s s
1 4 3 (5 .6 3 ")
1 3 3 (5 .2 4 ")
Description RS-422 port for connecting PLC (including1:N connection) or communication (computer link) unit <9-pin D-sub> RS-232C port for connecting PLC (including1:N connection), printer or bar-code reader <9-pin D-sub> RS-232C port for connecting personal computer, printer or bar-code reader <9-pin D-sub> e) PM-20BL battery g) Communication cable
d) Mounting bracket and tightening bolt f) DC power supply terminal (M3) h) Packing seal
2. Specifications
2.1 General Specifications
Item Operating Temperature Storage Temperature Humidity Vibration Resistance - intermittent vibration Vibration Resistance - Continuous vibration Shock Resistance Noise Immunity Insulation Resistance Ground Protection Specifications Horizontal mounting: 0 ~ 50 C (32 ~ 122 F) Vertical and flat mounting: 0 ~ 40 C (32 ~ 104 F) -20 ~ 60 C (-4 ~ 140 F) 35 ~ 85% Relative Humidity, No condensation Conforms to IEC 1131-2; 10 ~ 57 Hz: 0.075 mm Half Amplitude 57 ~ 150 Hz: 9.8 m/s2 Acceleration Sweep Count for X, Y, Z: 10 times (80 min. in each direction) Conforms to IEC 1131-2; 10 ~ 57 Hz: 0.035 mm Half Amplitude 57 ~ 150 Hz: 4.9 m/s2 Acceleration Sweep Count for X, Y, Z: 10 times (80 min in each direction) Conforms to IEC 1131-2: 147m/s2 Acceleration, 3 times in each direction X, Y, and Z 1000 Vp-p, 1micro second, 30 ~ 100 Hz, tested by noise simulator 5 M > at 500 V DC, tested between power terminals and ground Grounding resistance 100 or less. (Class D) IP 65F
Dielectric Withstand Voltage 500 V AC > 1 min, tested between power terminals and ground
1 3 3 (5 .2 4 ")
b )
h )
3. Installation
Note;
Do not mount the GOT in an environment that contains dust, soot corrosive or conducive dust, corrosive or flammable gas, or expose the unit to high temperatures, dew condensation, rain wind or impact and vibration. If the GOT is used in such a place, electrical shock, fire, malfunction, damages or deterioration may be caused. Never drop cutting chips or electric wire chips into the ventilation window of the GOT when drilling screw holes or performing wiring. Such chips may cause fire, failure or malfunction. Turn off the power before securely connecting any cables. Poor connection may cause malfunction.
The GOT is designed to be mounted in a panel. Install it using the following procedure:
1 2 4 ( 4 .8 8 " ) + 1 (+ 0 .0 4 ")
1) Preparing the panel surface. On the panel surface, cut a rectangular mounting slot of the dimensions shown on the right. At this time, space of 10 mm is required at each of the top and the bottom of the slot, inside the panel for metal fixtures as shown in 4) Dimensions required inside the panel for installation.
U n it: m m ( in c h e s )
S lo t to b e c u t o n p a n e l
2 0 6 ( 8 .1 1 " ) + 1 (+ 0 .0 4 ")
0
Note
Make sure that the thickness of the panel surface is no more than 5 mm (0.20").
2) Inserting the GOT into the panel surface Attach the packing seal to the GOT, and insert the GOT from the front face of the panel surface. a) Packing seal b) GOT c) Mounting slot
a )
b )
c )
3) Fixing the GOT Put hooks of the mounting brackets (supplied) in to the mounting holes of the GOT. Tighten mounting bolts (also supplied) until the GOT is securely fixed. Fix mounting bolts in all four positions, above and below the GOT. a) Clamping bolt b) Mounting bracket
a ) b )
Note:
Make sure to tighten the clamping bolts with a torque of 0.3 ~ 0.5 N$m.
4) Dimensions required inside the panel for installation. When installing the GOT, make sure that the inner dimensions shown on the right are available. a) PLC connection cable b) Packing seal
1 4 3 (5 .6 3 ")
2 2 5 (8 .8 6 ")
7 0 .6 (2 .7 8 ")
a ) 5 ( 0 .2 0 " ) o r le s s b )
Note:
Wire the power supply using electric wires of 0.75 mm2 or more so that voltage drop will not occur. Use M3 size crimp style terminals. Securely tighten crimp-style terminals with a torque of 0.5 ~ 0.8 N$m so that errors can be avoided. Insure correct termination of the DC power source, incorrect connection may result in unit failure serious damage to the GOT. Attach a 2 A fuse to the 24V DC power supply. Perform Class D (100 or less) grounding with an electric wire of at least 1.25 mm2. Never perform common grounding of the GOT and a strong power system.
Note
Use an external power supply to provide 24V DC. (The service power supply of the programmable controller cannot be used.) Even if instantaneous power interruption of less than 1 ms occurs, the GOT continues to operate. When power interruption for a considerable period of time or voltage drop occurs, the GOT stops its operation. However, when the power supply is recovered, the GOT automatically restar ts its operation. (The screen displayed just after recovery is determined by the working environment originally set.)
Grounding resistance 100 or less (class D) 24V DC external power supply
Fuse (2A)
24V DC
PLC
GOT
6. Maintenance
Cautions:
Correctly connect the battery for memory backup. Never charge, disassemble, heat, burn or short-circuit the battery. If the battery is handled in such a way, or fire may be caused. Always power OFF and remove the GOT from the panel before starting replacement of the battery. If this is not the case, electrical shock may be sustained. Never disassemble or modify the GOT. Disassembly or modification may cause failure, malfunction or fire. For repair, please, contact a service representative.
Note:
Turn off the power, before connecting/disconnecting cables. Connecting/disconnecting cables while the power is turned on will cause failure or malfunction. When repairing the backlight and liquid crystal screen, please, contact a service representative.
Note:
For approximately one month after the control device (system information) for battery voltage drop turns ON, the battery will back up the alarm history, sampling and the current time. When the control device turns ON, replace the battery (PM-20BL) as soon as possible. The screen data is stored in the flash memory, therefore, data will remain even after severe battery voltage loss. 6.1.1 Replacement Procedure 1) Turn off the power to the GOT and remove the battery holder cover. 2) Remove the existing battery from the battery holder, and disconnect. 3) Within 30 seconds, connect a new battery. 4) Insert the new battery into the battery holder, and attach the cover.
P M -2 0 B L
HEAD OFFICE : MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100-8310 HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
Description This manual contains explanations for installation and operating procedures of the F9GT-40FMB data transfer adapter.
Note;
Do not lay signal cables near high voltage power cables or allow them to share the same trunking duct, otherwise, effects of noise or surge induction are likely to take please. Keep a safe distance of more than 100 mm from these wires. Operate touch switches on the display screen by hand. DO NOT use excessive force, or attempt operate them with hard or pointed objects. The tip of a screw driver, pen or similar object for example may break the screen.
Installation Manual
JY992D93901D
This manual contains text, diagrams and explanations which will guide the reader in the correct installation, safe use and operation of the F940WGOT-TWD-E and should be read and understood before attempting to install or use the unit. Further information can be found in the associated manuals list below. Specifications are subject to change without notice
" Indispensable manual ! Either manual is necessary. # Refer if necessary, please. Refer to the Programming manual () or relevant hardware manuals for details concerning the applicable PLC.
1. Introduction
The F940WGOT series (hereafter called GOT) is to be mounted on the face of a control panel or operations panel, and c o nn e ct e d t o t he pr o gra m m in g p or t ( CP U po r t ) o r t h e communication port (communication port) of a PLC. Various devices can be monitored and PLC data changed through the GOT screens. Several display screens are built-in to the GOT, and additional personalized screens can be created by the user. 1) The GOT can connect to MELSEC FX, A, QnA and Q PLCs as well as a host of third party manufactured units. Further information can be found in GOT-F900 Series Hardware Manual.
P L C
1 2 3 (4 .8 4 ") 7 0 .6 (2 .7 8 ")
P r o g r a m m in g p o rt
This manual has been written to be used by trained and competent personnel. The definition of such a person or persons is as follows: a) Any engineer using the product associated with this manual, should be of a competent nature, trained and qualified to the local and national standards. These engineers should be fully aware of all aspects of safety with regards to automated equipment. b) Any commissioning or service engineer must be of a competent nature, trained and qualified to the local and national standards. c) All operators of the completed equipment should be trained to use that product in a safe and co-ordinated manner in compliance to established safety practices. Note: The term completed equipment refers to a third party constructed device which contains or uses the product associated with this manual.
G O T
2 1 5 (8 .4 6 ")
5 (0 .2 0 ")
2 3 (0 .9 1 ")
3) Display screens are created using the following software: Software Name GT Designer2 SW#D5C-GTD2-E (# indicates version) GT Designer SW#D5C-GOTR-PACKE (# indicates version) FX-PCS-DU/WIN-E Version GOT-F900 and GOT-A900 Series (for Windows) screen creation software.
5 0 (1 .9 6 ")
2) PLC user programs can be downloaded, uploaded and monitored using programming software GXDeveloper or FX-PCS/WIN-E on a personal computer via the GOT. Further information can be found in GOT-F900 Series Operation Manual.
1 0 (0 .3 9 ")
d )
1 0 (0 .3 9 ") c )
7 0 .6 (2 .7 8 )
g ) f )
2 4 V D C
GOT-F900 and GOT-A900 Series (for Windows) screen creation software. SW5-F edition of SW5D5C-GOTR-PACKE (version 5.05F) or later GOT-F900 Series (for Windows) screen creation software. SW0PC-FXDU/WIN-E version 2.50 or later
3 4 .5 (1 .3 5 ")
3 4 .5 (1 .3 5 ") 5 ( 0 .2 0 " ) o r le s s
1 4 3 (5 .6 3 ")
1 3 3 (5 .2 4 ")
2) Indicates that the identified danger could POSSIBLY cause physical and property damage. Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment. All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples. Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability for your specific application.
Description RS-422 port for connecting PLC (including1:N connection) or communication (computer link) unit <9-pin D-sub> RS-232C port for connecting PLC (including1:N connection), printer or bar-code reader <9-pin D-sub> RS-232C port for connecting personal computer, printer or bar-code reader <9-pin D-sub> e) PM-20BL battery g) Communication cable
FX-50DU-CAB0
Associated Manuals
Manual Name F940WGOT Series ! (F940GOT-TWD) Installation Manual GOT-F900 " OPERATION MANUAL (describes GT Designer2) " GOT-F900 Series Operation Manual Manual Number JY997D93901 Description Describes the specifications, wiring, and installation of F940WGOT Series graphic operation terminal. (hardware) Describes the operation and use of the GOTF900 Series graphic operation terminals and GT Designer2. Describes the operation and use of the GOTF900 Series graphic operation terminals, GT Designer and FX-PCS-DU/WIN-E. Describes wiring and installation of the GOTF900 Series graphic operation terminals. Describes the operation of GT Designer2 (SW*D5C-GTD2-E) and data transfer to the GOT-900 Series. Describes the specifications and setting of object functions in GT Designer2 (SW*D5C-GTD2-E). Describes the operation of GT Designer (SW*D5C-GOTR-PACKE) and data transfer to the GOT-900 Series. (Refer to the help file) Describes the operation of FX-PCS-DU/WIN-E screen creation software.
Communication cable (GOT CPU port in FX0, FX0S, FX1S, FX0N, FX1N, FX2N or FX2NC series PLC) FX-50DU-CAB0/EN The connector on the GOT side is wired straight through. Cable length is 3m (9' 10"). Communication cable (GOT CPU port in FX0, FX0S, FX1S, FX0N, FX1N, FX2N or FX2NC series PLC) FX-50DU-CAB0-**M The connector on the GOT side is wired straight through. ** M is cable length. 1M: 1m (3' 3"), 10M: 10m (32' 9"), 20M: 20m (65' 7"), 30M: 30m (98' 5") FX-40DU-CAB Communication cable (GOT CPU port in FX, FX2C, A or QnA series PLC) The connector on the GOT side is wired straight through. Cable length is 3m (9' 10"). Communication cable (GOT CPU port in FX, FX2C, A or QnA series PLC) The connector on the GOT side is wired straight through. ** M is cable length. 10M: 10m (32' 9"), 20M: 20m (65' 7"), 30M: 30m (98' 5") Communication cable (GOT CPU port in Q series PLC) The connector on the GOT side wired straight through. Cable length is 3m (9' 10"). Data exchange cable (GOT Personal computer <9-pin D-sub>) Battery for Alarm history, sampling and current time data retention. Transparent protection sheet for F940WGOT (5 pieces) Data transfer adapter (Flash memory built in)
d) Mounting bracket and tightening bolt f) DC power supply terminal (M3) h) Packing seal
2. Specifications
2.1 General Specifications
Item Operating Temperature Storage Temperature Humidity Vibration Resistance - intermittent vibration Vibration Resistance - Continuous vibration Shock Resistance Specifications Horizontal mounting: 0 ~ 50 C (32 ~ 122 F) Vertical and flat mounting: 0 ~ 40 C (32 ~ 104 F) -20 ~ 60 C (-4 ~ 140 F) 35 ~ 85% Relative Humidity, No condensation Conforms to IEC 1131-2; 10 ~ 57 Hz: 0.075 mm Half Amplitude 57 ~ 150 Hz: 9.8 m/s2 Acceleration Sweep Count for X, Y, Z: 10 times (80 min. in each direction) Conforms to IEC 1131-2; 10 ~ 57 Hz: 0.035 mm Half Amplitude 57 ~ 150 Hz: 4.9 m/s2 Acceleration Sweep Count for X, Y, Z: 10 times (80 min in each direction) Conforms to IEC 1131-2: 147m/s2 Acceleration, 3 times in each direction X, Y, and Z 1000 Vp-p, 1micro second, 30 ~ 100 Hz, tested by noise simulator 5 M > at 500 V DC, tested between power terminals and ground Grounding resistance 100 or less. (Class D) IP 65F
JY997D09101 (separate volume) JY992D94701 (separate volume) JY992D94801 (separate volume) (PDF files on CDROM included with product) (PDF files on CDROM included with product) Included with the screen creation software JY992D68301 (included with the screen creation software)
GOT-F900 Series " Hardware Manual (connection diagram) ! GT Designer2 Version1 Operating Manual GT Designer2 Version1 Reference Manual GT Designer Operating Manual
FX-40DU-CAB-**M
Caution
During abnormal communication (including cable breakages) ages when monitor within the GOT, communication between the GOT and programmable controller CPU is interrupted. It is impossible to operate switches or devices in the PLC through the GOT. Communication and normal operation resumes when the GOT system is correctly configured. DO NOT configure emergency stop or safety features to operate through the GOT, and be sure that there is no adverse consequences in the event of a GOT - PLC communications malfunction. Noise Immunity Insulation Resistance Ground Protection
Dielectric Withstand Voltage 500 V AC > 1 min, tested between power terminals and ground
1 3 3 (5 .2 4 ")
Guidelines for the Safety of the User and Protection of the F940WGOT Series.
b )
h )
2) Inserting the GOT into the panel surface Attach the packing seal to the GOT, and insert the GOT from the front face of the panel surface. a) Packing seal b) GOT c) Mounting slot
a )
b )
6. Maintenance
c )
Cautions:
Correctly connect the battery for memory backup. Never charge, disassemble, heat, burn or short-circuit the battery. If the battery is handled in such a way, or fire may be caused. Always power OFF and remove the GOT from the panel before starting replacement of the battery. If this is not the case, electrical shock may be sustained. Never disassemble or modify the GOT. Disassembly or modification may cause failure, malfunction or fire. For repair, please, contact a service representative.
3) Fixing the GOT Put hooks of the mounting brackets (supplied) in to the mounting holes of the GOT. Tighten mounting bolts (also supplied) until the GOT is securely fixed. Fix mounting bolts in all four positions, above and below the GOT. a) Clamping bolt b) Mounting bracket
a ) b )
Note:
Turn off the power, before connecting/disconnecting cables. Connecting/disconnecting cables while the power is turned on will cause failure or malfunction. When repairing the backlight and liquid crystal screen, please, contact a service representative.
Note:
Make sure to tighten the clamping bolts with a torque of 0.3 ~ 0.5 N$m.
When the battery voltage drops, a control device (system information) set by the screen design software turns ON. The control device interlocks with an auxiliary relay in the PLC. It is recommended to provide a lamp while utilizing the output of the PLC so that voltage drop can be monitored outside the GOT. For details of control devices, refer to the GOT-F900 Series Operation Manual.
Note:
For approximately one month after the control device (system information) for battery voltage drop turns ON, the battery will back up the alarm history, sampling and the current time. When the control device turns ON, replace the battery (PM-20BL) as soon as possible. The screen data is stored in the flash memory, therefore, data will remain even after severe battery voltage loss.
5 ( 0 .2 0 " ) o r le s s b )
a )
6.1.1 Replacement Procedure 1) Turn off the power to the GOT and remove the battery holder cover. 2) Remove the existing battery from the battery holder, and disconnect. 3) Within 30 seconds, connect a new battery. 4) Insert the new battery into the battery holder, and attach the cover.
P M -2 0 B L
3. Installation
Note;
Do not mount the GOT in an environment that contains dust, soot corrosive or conducive dust, corrosive or flammable gas, or expose the unit to high temperatures, dew condensation, rain wind or impact and vibration. If the GOT is used in such a place, electrical shock, fire, malfunction, damages or deterioration may be caused. Never drop cutting chips or electric wire chips into the ventilation window of the GOT when drilling screw holes or performing wiring. Such chips may cause fire, failure or malfunction. Turn off the power before securely connecting any cables. Poor connection may cause malfunction.
Note:
Wire the power supply using electric wires of 0.75 mm2 or more so that voltage drop will not occur. Use M3 size crimp style terminals. Securely tighten crimp-style terminals with a torque of 0.5 ~ 0.8 N$m so that errors can be avoided. Insure correct termination of the DC power source, incorrect connection may result in unit failure serious damage to the GOT. Attach a 2 A fuse to the 24V DC power supply. Perform Class D (100 or less) grounding with an electric wire of at least 1.25 mm2. Never perform common grounding of the GOT and a strong power system.
The GOT is designed to be mounted in a panel. Install it using the following procedure:
1 2 4 ( 4 .8 8 " ) + 1 (+ 0 .0 4 ")
Note
Use an external power supply to provide 24V DC. (The service power supply of the programmable controller cannot be used.) Even if instantaneous power interruption of less than 1 ms occurs, the GOT continues to operate. When power interruption for a considerable period of time or voltage drop occurs, the GOT stops its operation. However, when the power supply is recovered, the GOT automatically restar ts its operation. (The screen displayed just after recovery is determined by the working environment originally set.)
Grounding resistance 100 or less (class D) 24V DC external power supply
1) Preparing the panel surface. On the panel surface, cut a rectangular mounting slot of the dimensions shown on the right. At this time, space of 10 mm is required at each of the top and the bottom of the slot, inside the panel for metal fixtures as shown in 4) Dimensions required inside the panel for installation.
U n it: m m ( in c h e s )
S lo t to b e c u t o n p a n e l
2 0 6 ( 8 .1 1 " ) + 1 (+ 0 .0 4 ")
0
Note
Make sure that the thickness of the panel surface is no more than 5 mm (0.20").
24V DC
PLC
GOT
HEAD OFFICE : MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100-8310 HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN