APPA-Module 7-Protection & Coordination
APPA-Module 7-Protection & Coordination
|
% 6
5000
= Z
KVA
kV kV 16 . 4 / 86 . 22
R
FAULT Line of End
FUSE
R
A x IPhase 1000 400 5 . 2 = =
Note: Cooper W & RX type Recloser Ratings:
Coil Size Min Trip Rating Interrupting Rating
560 A 1120 A 10,000 A
3800A Fault G -
4500A Fault - 3
=
=
|
|
A Fault G 175
1500A Fault - 3
=
=
|
|
400A(Peak) I =
Source Fuse-Recloser Coordination
Ground Trip Setting Steps:
1. Estimate Normal Load unbalance: 10% of Peak-Load
Example: Iunbalance= 10% of Peak Load
Iunbalance-Normal= 0.1 x 400=40A
2. Estimate the load unbalance created by the largest
single-phase device:
Example: Assume the largest single phase Load is 90A
Fuse. Iunbalance-Load=90A
3. Calculate Unbalanced downline Ground Current:
4. Select Minimum Ground Trip:
A IGround 130 40 90 = + =
Load unbalance Normal unbalance Ground I I I + =
) A 175 ( ) A 140 ( ) A 130 ( Fault Min Setting Ground Unbalanced G I I I < <
A 140 = Trip Min Ig
Source Side Fuse-Recloser Coordination
Recloser-Fuse (Load Side) Coordination
Determine an appropriate Fuse size @ Point B
Which fuse coordinates the best (100K or 140K?)
Answer 140K; Why?
C A
RX
2 2
Recloser
% 6
5000
= Z
KVA
kV kV 16 . 4 / 86 . 22
R
A Fault Min
A
FAULT
600
1900 G
=
= u
FUSE
R
Amp 400
Amp 90
B
Power System Review
Recloser-Fuse (Load Side) Coordination
A K
A K
2380 140
1112 100
Limit on Coordinati Fuse
A Fault G 175
1500A Fault - 3
=
=
|
|
E 1 & 1
C 2 & A 2
Recloser
2 A g
RX
|
% 6
5000
= Z
KVA
kV kV 16 . 4 / 86 . 22
R
FAULT Line of End
FUSE
R
3800A Fault G -
4500A Fault - 3
=
=
|
|
A Fault G 175
1500A Fault - 3
=
=
|
|
400A(Peak) I =
B
Relays
Mechanical
&
Digital
Protection System Elements
Protective relays
Circuit breakers
Current and voltage transducers
Communications channels
DC supply system
Control cables
Three-Phase Diagram of the Protection Team
CTs
VTs
Relay
CB
Control
Protected
Equipment
SI
52
TC
DC Station
Battery
SI
Relay
Contact
Relay
Circuit
Breaker
52a
+
Red
Lamp
Most Common Protective Relays
Protection Principles for Transmission &
Distribution Lines:
Overcurrent (50, 51, 50N, 51N)
Directional Overcurrent (67, 67N)
Distance (21, 21N)
Differential (87)
Circuit Breaker Selection
Relay (The Brain)
CT Ratio
PT or VT Ratio
Interrupting Cycle
Voltage Class
K rating=(VMAX/Vmin)
BIL rating
Power System Review
Load
Ib
Relay-Circuit Breaker Operation
Load
Phase relays
Ground relay
CTs
Circuit
Breaker
In
A
B
C
Ia
Ib
Ic
Ia
Ib
Ic
c b a n I I I I + + =
LOAD
Power System Review
Induction-Type Relays
Power System Review
Relay Classification
Overcurrent
Overvoltage
Undervoltage
Differential
Directional
Under Frequency
Distance
Power System Review
Relays for Phase Faults
Time overcurrent 51
Instantaneous & time overcurrent 50/51
Directional Time Overcurrent 67
Instantaneous & directional time over
current
50/67
Directional Instantaneous Overcurrent 67
Step Time Overcurrent 51
Directional Instantaneous and directional 67
Zone Distance 21
Power System Review
Relays for Ground Faults
Time Overcurrent 51N
Instantaneous & Time Overcurrent 50N/51N
Product Overcurrent 67N
Instantaneous and Product Overcurrent 67N/50N
Directional time overcurrent 67N
Instantaneous and directional time overcurrent 67N
Directional Instantaneous Overcurrent 67N
Three-zone distance system 21N
Power System Review
Transformer Protection
Open-Phase Condition
CTs=600/5
In
A
B
C
Ia
Ib
Ic
In
Ia
Ic
c a n I I I + + = 0
Open
400 a 0 a 400 a
Z =
+ =
+ =
+ = + + =
+ Z = = Z =
=
60 333 . 3
886 . 2 666 . 1
886 . 2 667 . 1 333 . 3
120 333 . 3 , 0 , 0 333 . 3
120
n
n
n
a
Ratio
I
j In
j I
Ic Ia Ic Ib Ia I
Ic Ib I
CT
Ground Relay Could Pickup
Z = 60 333 . 3 n I
+ Z 120 3 . 3
Z0 3 . 3
0
Single-Phase to Ground
Fault
CTs=600/5
In
A
B
C
Ib
Ia
Ic
Z = 0 7 . 46 n I
Short
6,000a
400 a
400 a
Z =
=
+ + =
+ Z = Z = Z =
=
0 666 . 46
667 . 1 667 . 1 50
120 333 . 3 120 333 . 3 , 0 50
120
n
n
n
a
Ratio
I
I
Ic Ib Ia I
Ic Ib I
CT
SC I
Z = 0 50 a I
+ Z 120 3 . 3
Z 120 3 . 3
In
SC I
Ground & Phase Relays both Pickup
Line-to-Line to Ground Fault
CTs=600/5
In
A
B
C
Ib
Ia
Ic
Z = 60 7 . 46 n I
Short
6,000a
400 a
Z =
=
+ =
+ + =
+ Z = Z = Z =
=
60 67 . 46
415 . 40 333 . 23
886 . 2 667 . 1 301 . 43 25 50
120 333 . 3 120 50 , 0 50
120
n
n
n
a
Ratio
I
j In
j j I
Ic Ib Ia I
Ic Ib I
CT
SC I
Z = 0 50 a I
+ Z 120 3 . 3
In
a I
Ground & Phase Relays both Pickup
SC I
Z 120 50
b I
C I
Three-Phase to Ground
Fault
CTs=600/5
In
A
B
C
Ib
Ia
Ic
0 = n I
Short
0
120 100 120 100 , 0 100
120
=
+ + =
+ Z = Z = Z =
=
n
n
a
Ratio
I
Ic Ib Ia I
Ic Ib I
CT
SC I
Z = 0 100 a I
2
100a Ib =
a Ic 100 =
000 , 12 = c I 000 , 12 = b I 000 , 12 = a I
000 , 12 = a I
SC I
SC I
000 , 12 = a I 000 , 12 = a I
Only Phase Relays Pickup
Ib
Ia
Ic
Relay Settings
Time Overcurrent pickup
& time setting must be
capable of handling:
Peak Load
Cold-Load Pickup
Motor starting
Instantaneous Setting
must be capable of
handling:
XFMR Inrush
Capacitor Inrush
Asymmetrical Faults
Safety factor=1.2xSymm Fault
Two Settings:
1. Time Overcurrent
2. Instantaneous
Power System Review
Relay Settings
Phase Time Over Current (TOC) Setting
Phase pick up:
Method 1: 2xImax < I Pick up < I Min (phase-phase Fault current)
Note: Ensure I Min-Fault 2 x I Peak- Load
I Min=Iphase-to-Phase=0.866 x I Three-Phase fault
Method 2: 25% Margin ; IPickup= Ifull-load/0.80
Ground Time Over Current (TOC) Setting
Ground Pick up:
Method 1: 2xI Normal ground Current < I Pick up< I Min Ground Fault Current
Where; Normal Ground Current Range: 10% to 20% of Load Current
Method 2: Ipickup=(0.40 to 0.75)x Ipeak-Load
Power System Review
Instantaneous Relays Pickup
Settings
Instantaneous Pickup
Range:
Typical Instantaneous Phase & Ground
Pick up= 2x Time Over Current relay pick ups
Pickup Phase eous ins Pickup Phase I x I I x < < 10 2 tan tan
Power System Review
How to determine Pickup &
Time Dial?
Step 1: Calculate Short Circuit Current @ each Bus
( usually Phase-Phase Fault)
Step 2: Identify CT Ratio & Breaker Interrupting Cycles at
each Bus
Step 3: Calculate Relay Minimum Pickup for each Device
Step 3: Starts with the last relay and apply Time Margin of
0.3 to 0.4 sec (ANSI/IEEE Std-242 )between Relays:
o CBs operating time (5 cycles): 0.08 sec
o Relay Over travel time: 0.1 sec
o Safety factor (CT saturation, Errors): 0.22 sec
Total 0.4 Seconds
Power System Review
0.4 Sec
Relay-Relay Setting
Power System Review
TCC Coordination Time
Margins
Relay-Fuse TCC Curve Separation Rule:
Mechanical Relay requires minimum time margin of 0.3 sec
time interval
Digital Relay requires minimum time margin of 0.2 sec time
interval
Relay-Relay (Mechanical) TCC Curve Separation Rule:
According to ANSI/IEEE Std-242:1986, the rime interval
between two relays in series must be 0.3 to 0.4 seconds.
This time interval components are:
Circuit Breaker Operating Time(5cycle): 0.08 sec
Relay Overtravel Time: 0.1 sec
Safety factor for CT Saturation & errors: 0.22 sec
Power System Review
Relay-Relay (Digital)TCC Curve Separation:
Time margin between series Relays must be minimum of
0.25 sec. This time separation consists of the following:
5 Cycle Breaker (0.08 sec)
Relay Accuracy (0.04 sec)
Safety factor & CT Ration (0.13 sec)
Relay-Recloser
Time Margin between Mechanical Relay & Hydraulic
Recloser must be minimum of 0.28-0.30 sec
Time Margin between Mechanical Relay & Electronic
Recloser must be minimum of 0.25 sec
TCC Coordination
Time Margins
Power System Review
Relay-Recloser-Fuse
Coordination
In the following CKT coordinate Breaker B1, Cooper
Form-4C Recloser, ABB PCD2000 Reclsoer, and 100K
Tap Fuse.
1 B R 3 R
1 L 2 L 3 L
400A Load =
4C Form
Cooper
3
2 1
MVA 25
kV kV 86 . 22 / 115
PCD2000
ABB
A 1000
A 4000 3
2 @
=
= u
Fault Min
Bus FAULT
K 100
A Fault Min
A
Bus FAULT
443
3000 3
1 @
=
= u
A 2000 N
A 6000 3
3 @
=
= u
Bus FAULT
2 B
300A Load = 200A Load =
231A Load =
BUS
kV 115
Power System Review
Relay-Recloser-Fuse Coordination
Relay settings:
Phase setting: PU=2.4 x 400=960A
Ground setting: PU= 960/2=480 A
Cooper Recloser Form 4C settings:
Phase setting: PU=2x300=600A
Ground setting: 160A<PU=600/3=200A<443A
ABB Recloser Model PCD2000 settings:
Phase setting: PU=2x200=400A
Ground setting: 140A<(PU=150 A)<443
Power System Review
Relay-Recloser-Fuse Coordination
Over Voltage Protection
Insulation Voltage Class
Basic Impulse Level (BIL)
Nameplate Rating
Surge arrestors.
Power System Review
Overvoltage Protection
Sources of Overvoltage:
Ferroresonance
Low Order Hormonics
Voltage Regulation (XFMR LTC Malfunction)
Transients caused by:
Lightning surge
Switching operations
Line-to-Ground faults
Capacitor Bank Switching
Protection methods:
Surge Arresters(ANSI C62.1-1981)
Static Wires
Useful IEEE/ANSI Standards
Graph of Curves can be found in ANSI/IEEE Standard
C37.91-1985, Guide for Protective Relay Applications
to Power Transformers,
ANSI/IEEE C57.109-1993, Guide for Transformer
Through-Fault Current Duration.
IEEE/ANSI Standards 141&242
IEEE Std 242 Buff Book
IEEE Std 141 Red Book
IEEE Std 399 Brown Book
IEEE C37.90 Relays
IEEE C37.91 Transformer Protection
IEEE C37.102 Guide for AC Generator Protection
References
1. J.D. Golver, M.S. Sarma, Power System Analysis and design,
4
th
ed., (Thomson Crop, 2008).
2. M.S. Sarma, Electric Machines, 2
nd
ed., (West Publishing Company,
1985).
3. A.E. Fitzgerald, C. Kingsley, and S. Umans, Electric
Machinery, 4
th
ed. (New York: McGraw-Hill, 1983).
4. P.M. Anderson, Analysis of Faulted Power systems(Ames, IA: Iowa
Satate university Press, 1973).
5.W.D. Stevenson, Jr., Elements of Power System Analysis, 4
th
ed. (New York: McGraw-Hill, 1982).
Solution
Answer: 37.5 KVA
Break Time !!!!!