Cable Diff. 11,22KV Specification 4-4-2006
Cable Diff. 11,22KV Specification 4-4-2006
Cable Diff. 11,22KV Specification 4-4-2006
Technical Specifications: 1- Numerical fiber optical diff. Protection matched in length and specification of the ordered fiber optical cable (attached). 2- Low C.T. burden . 3- Provide selectivity and high speed operation (less than 40 ms). 4- Independent measuring elements and simultaneous tripping of relays at each line end. 5- Suitable means for securing the relay settings. 6- Necessary amount of programmable LEDs for each phase fault, trip, and back up protection as well as the monitoring. 7- Inrush and steady state charging current compensation. 8- Built in back up over current protection. 9- Built in fault recording with time 1.5 sec at least in one page. 10- The relay shall compensate for unequal primary current transformation ratio to ensure correct operation of diff. Protection. 11- Upon detection of fiber optic failure , an alarm should be given and the diff. Protection shall be switched automatically out of service. 12- The amount of differential and restraining current shall possibly be displayed and measured during loading. 13- Facility of reversing polarity of measurement without disturbing the current circuit wiring. 14- Shall be stable during harmonics and C.T. saturation.
3/1
15- An over current check feature shall be included. 16- Since this protection operates as a unit protection , the bidder shall responsible to supply the same relay and all required accessories at the remote end of the cable. 17- Original software , plug connection to PC, test plug, test switch and otter accessories to be handed over. 18- Reference list for the offered protection inside and outside A.R.E. to be handed over with the offer. 19- All accessories for connection with fiber optical cables such as terminal connectors etc. Shall be provided.
Technical Data:
Current Circuit: Rated current Thermal withstand capability Current Setting: I diff Reset Ratio 0.2 .. 1In steps 0.1 In 0.95 1and/or 5 A (one relay for both) for 1.0 sec 40 In Continuos 4.0 In
Technical Data:
Rated frequency Power supply Voltage Disturbance Recorder: Number of Storage Faults Duration For Each Storage Fault Initiated by Pick up or trip Output contact: Number of contact 50 Hz 110: 250 Vd.c 20% 4 1.5 Sec
3/2
Current Carrying Capacity (1Sec) Continuous Rating Making capacity Breaking capacity Rated voltage Binary Inputs: Number of B/I Binary Inputs Voltage Operation System Interface: Dielectric Tests: According to IEC Insulation test voltage Test Voltage Environment condition: Ambient temp. Transport and storage temp. Humidity
10 A 5 A 900 W/VA 25 VA 250 VDC 6.0 B/I at least 110- 250 vdc 20% RS232/485
10 to + 50 C 40 to + 60 C 90%
3/3