Terminating Unarmored Variable Frequency Drive (VFD) Cables Foil-Braid or Copper-Tape Shield Constructions
Belden VFD Cables are designed for quick and easy termination.
This Belden VFD Cable Termination Guide takes a step-by-step approach to the connection/ termination of unarmored VFD cables with either foil-braid or copper-tape shield constructions. The instructions cover the termination of the cables in external and self-contained enclosures, at the motor junction box or using an alternative method. VFD Cable Installation Location Considerations It is advisable to maintain as much separation as possible between noise-susceptible cables and VFD cables a minimum of one foot for shielded instrumentation cables and three feet for unshielded instrumentation cables. If the two types of cable must lie close to each other, it is best to minimize the amount of parallel runs between them, limiting these stretches to 10 feet or less to reduce the likelihood of radiated noise pickup. Also, if the two types of cables must cross, it is preferable to cross them perpendicularly at a single point.
As you use this step-by-step VFD Cable Termination Guide, please note the references to the drive or motor manufacturers recommendations. You should be familiar with the manufacturers termination guidelines as well. If you have specific questions on the instructions given within this guide, please contact Belden Technical Support at 1.800.BELDEN.1 (1.800.235.3361).
Beldens Variable Frequency Drive (VFD) Cable Offering See VFD Cable Matrix (page 3) for additional information.
Original Design
One Full-sized Insulated Ground (same AWG as Circuit Conductors) Three Stranded TC Circuit Conductors with XLPE Insulation
Overall Duofoil Shield + 85% TC Braid plus full size TC Drain Wire
Overall Duofoil Shield + 85% TC Braid plus full size TC Drain Wire
Ratings
1000V Flexible 600V 2000V UnderMotor UL 1277 UL 1277 ground Supply Type TC Type TC (burial) Rating
Shielding
PVC Jacket
ER Rating
MSHA
ULWTTC
Original
16-2
Yes
1Full-sized Insulated
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Original Symmetrical
1-4/0
Yes
1 - Full-sized Dual Spiral Segmented Overlapping Into Copper Tape 3 - Bare CU (100% Symmetrical Coverage) 1Full-sized Insulated 1Full-sized Insulated Overall 100% Duofoil + 85% TC Braid Overall 100% Duofoil + 85% TC Braid
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Original with Brake/ Signal Pair Original for 2kV Applications Original Symmetrical for 2kV Applications Original with Haloarrest Low Smoke Zero Halogen Jacket Original Symmetrical with Haloarrest Low Smoke Halogen Jacket Original Interlocked Armor Original Symmetrical Interlocked Armor
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
14-2
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
1-4/0
Yes
1 - Full-sized Dual Spiral Segmented Overlapping Into Copper Tape 3 - Bare CU (100% Symmetrical Coverage) 1Full-sized Insulated Overall 100% Duofoil + 85% TC Braid
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
16-2
Yes
Yes
Yes
LSZH
Yes
Yes
Yes
Yes
Yes
Yes
1-4/0
Yes
1 - Full-sized Dual Spiral Segmented Overlapping Into Copper Tape 3 - Bare CU (100% Symmetrical Coverage) 1Full-sized Insulated Overall 100% Duofoil + 85% TC Braid
Yes
LSZH
Yes
Yes
Yes
Yes
Yes
Yes
16-2
Yes
Yes
Yes
Yes
Meets MC
Yes
Yes
Yes
Yes
Yes
1-4/0
Yes
1 - Full-sized Dual Spiral Segmented Overlapping Into Copper Tape 3 - Bare CU (100% Symmetrical Coverage) Dual Spiral Overlapping 3 - Bare CU Copper Tape Symmetrical (100% Coverage)
Yes
Yes
Meets MC
Yes
Yes
Yes
Yes
Yes
Basics Symmetrical
16-4/0
No
Yes
Yes
Yes
Yes
Yes
VFD Cable Termination Instructions Foil-Braid Constructions External and Self-Contained Drive Enclosures
General Termination Instructions
To properly and effectively terminate a VFD cable system, first ensure the following: Ideally, the shield and jacket should be
intact all the way back to the drive so they do not introduce any jumping off points for the common mode currents carried on the common mode current containment system. In this case, no special tools, materials or termination kits are required.
Intermediate termination of the cable elements on terminal blocks should be avoided as the terminations may significantly reduce the ability of the shielding system to conduct and contain harmful high frequency currents.
How to Terminate an External Enclosure (For Self-Contained Drive Enclosure Instructions - Nema 1,4,4x - skip to Step 2).
STEP 1
STEP 2
STEP 3
A. Ingress the enclosure using an isolating cable gland with a suitable protection rating for the enclosure and the environment. Allow a sufficient length of cable to easily reach the drive without unnecessary cable strain. Do not remove the outer cable jacket. B. Secure the cable with suitable cable ties, or through cable duct as appropriate. C. If the drive is open style, route the jacketed cable assembly back to the drive vicinity.
A. If the drive is in an internal enclosure, ingress the drive through a suitable insulating cable gland. Measure and mark the cable to determine the jacket strip location and cutoff length. B. If possible, remove the measured cable and place the end for preparation on a suitable work surface.
A. Neatly remove the outer cable jacket, exposing sufficient conductor to reach the drive terminals, while still leaving some excess conductor length for trimming (after neatly routing to the drive terminals). B. It is desirable to combine the shielding drains and braid for termination intact at the ground terminal of the drive.
STEP 4
STEP 5
STEP 6
A. Push the remaining braid forward, and use a tool to open the braid.
STEP 7
STEP 8
STEP 9
A. Push the primary conductors and ground through an opening in the braid, separating the intact braid system from the conductors.
STEP 10
STEP 11
STEP 12
A. Apply 3-5 inches of heat shrink tubing over the entire cable assembly, centered at the jacket strip point. Shrink this piece completely. B. Secure the cable jacket to the drive (or enclosure) if it is not secured by a cable gland.
A. Route and trim the conductors to the power terminals, leaving sufficient material for phase reversal, if necessary.
A. Terminate the motor leads per the drive manufacturers recommendations. B. Trim the ground wire to sufficient length to reach the drive ground terminal.
STEP 13
STEP 1
STEP 2
A. Ingress the motor junction box through an isolating cable gland with a suitable protection rating for the enclosure. Do not remove the outer cable jacket. Measure and mark the cable for length. When possible, it is desirable to remove the cable from the motor junction box for ease of preparation. B. Neatly remove the outer cable jacket, exposing sufficient conductor to reach the motor leads and ground lug, while still leaving some excess conductor length for trimming (after neatly routing to the motor terminals). C. Follow the cable preparation instruction above as specified for the drive end connection. D. Secure the cable jacket to the motor by tightening the isolating cable gland.
A. Route and trim the conductors to the motor terminals, leaving sufficient material for phase reversal, if necessary. Use the termination system recommended by the motor manufacturer. B. Terminate the motor leads per the motor manufacturers recommendations, or trained practices of a qualified electrician. C. Trim the ground wire to sufficient length to reach the motor ground terminal. D. Heat shrink the drain wire covering and trim to length for connection to the drive ground terminal. Strip to expose conductor as necessary. E. Terminate the ground and drain using a standard lug, or on the provided connection point.
VFD Cable Termination Instructions Foil-Braid Constructions Alternate Method: Conductive Cable Gland
How to Terminate in a Conductive Cable Gland
Note: It may be more desirable to terminate the braid in a conductive cable gland at the motor connection. If so, suitable conductive cable glands are available through your Belden Distributor. It should be noted, however, that
this will be no more effective for common mode current containment than terminating the braid intact, and will involve a more expensive connector. This connection may provide additional mechanical security, depending on
the connector selection, and could reduce EMI in very close proximity to the motor junction box.
STEP 1
STEP 2
STEP 3
A. Ingress the motor junction conduit box through the conductive cable gland.
A. Trim the foil at least back to the prepared edge of the braid. B. Secure the cable to the gland per gland manufacturers recommendations, and pass the cable into the motor junction box.
STEP 4
STEP 5
STEP 6
A. Secure the cable jacket to the motor by tightening the cable gland lock nut. B. Route and trim the conductors to the motor terminals, leaving sufficient material for phase reversal if necessary. Use the connection system as recommended by the motor manufacturer. C. Trim the ground wire to sufficient length to reach the motor ground terminal. D. Heat shrink the drain wire(s) covering and trim to length for connection to the drive ground terminal. Strip to expose conductor as necessary.
A. Terminate the ground and drain using a standard lug, or on the provided connection point.
A. Terminate the motor leads per the motor manufacturers recommendations, or trained practices of a qualified electrician.
VFD Cable Termination Instructions Copper Tape Shield Constructions External and Self-Contained Drive Enclosures
How to Terminate a Drive Mounted in an External Enclosure (For Self-Contained Drive Enclosure Instructions - Nema 1,4,4x - skip to Step 4).
STEP 1
STEP 2
STEP 3
A. Ingress the enclosure with an isolating cable gland with a suitable protection rating for the enclosure and the environment. Allow a sufficient length of cable to easily reach the drive without unnecessary cable strain. Do not remove the outer cable jacket. B. Secure the cable with suitable cable ties, or through cable duct as appropriate. C. If the drive is open style, route the jacketed cable assembly back to the drive vicinity.
A. If the drive is in an internal enclosure, ingress the drive through a suitable insulating cable gland. B. Neatly remove the outer cable jacket, exposing sufficient conductor to reach the drive terminals, while still leaving some excess conductor length for trimming (after neatly routing to the drive terminals).
A. Remove the exposed copper tape shield. B. De-cable the exposed conductors and grounds.
STEP 4
STEP 5
STEP 6
A. Apply 3-6 inches of heat shrink tubing over the entire cable assembly, centered at the jacket strip point. Shrink this piece completely. B. Secure the cable jacket to the drive (or enclosure) if it is not secured by a cable gland.
STEP 7
STEP 8
A. Route and trim the conductors to the power terminals, leaving sufficient material for phase reversal, if necessary. B. Terminate the motor leads per the drive manufacturers recommendations. Use lugs and ferrules as appropriate. No special pieces are required.
A. Trim the ground wire(s) to sufficient length to reach the drive ground terminal. B. Terminate the ground per the drive manufacturers recommendations. Note that there is no shield termination for copper tape shielded constructions.
VFD Cable Termination Instructions Copper Tape Shield Constructions Motor Junction Box
How to Terminate at the Motor Junction Box
STEP 1
STEP 2
STEP 3
A. Ingress the motor junction box through an isolating cable gland with a suitable protection rating for the enclosure. Do not remove the outer cable jacket. B. Measure and mark the cable for jacket removal inside the motor junction box. C. Neatly remove the outer cable jacket, exposing sufficient conductor to reach the motor leads and ground lug, while still leaving some excess conductor length for trimming after neatly routing to the motor terminals.
A. Trim back the copper tape shield, and any fillers in the cable. B. De-cable the exposed conductors and grounds.
A. Combine the ground wires by twisting them together. Apply heat shrink tubing to the combined grounds. B. Secure the cable jacket to the motor by tightening the isolating cable gland. C. Route and trim the conductors to the motor terminals, leaving sufficient material for phase reversal, if necessary. Use the connection system as recommended by the motor manufacturer. D. Terminate the motor leads per the motor manufacturers recommendations, or trained practices of a qualified electrician. E. Trim the ground wire to sufficient length to reach the motor ground terminal. F. Terminate the ground using a standard lug, or on the provided connection point.
Can I run multiple motor cables in a conduit or cable tray without capacitive losses?
Belden VFD Cables will eliminate the potentially significant current losses associated with cable charging of nearby conductors.
VFD Cables overcome the challenges found in the toughest of environments.
Additional Information If you need information on the type of VFD cable that is appropriate for your specific installation, or if you have questions related to the instructions given within this guide, please contact Belden Technical Support at 1.800.BELDEN.1 (1.800.235.3361). Additional information is also available on Beldens website at www.belden.com. Here, you can view VFD Cable Procurement Documentation, or you can download Beldens VFD Cable Size Selection Guide (Based on Motor HP), VFD Cable Product Bulletin #316, and a Capabilities Overview for 2000V VFD cables.
Are Belden VFD Cables suitable for applications with moderate flexing?
Belden Original Foil Braid VFD Cables are tested to over 1 million flexes with a bending radius of not more than 10 times the cable diameter.
11
www.belden.com
GLOBALLOCATIONS
UNITED STATES
Division Headquarters Americas
CANADA
National Business Center
2200 U.S. Highway 27 South Richmond, IN 47374 Inside Sales: 800-235-3361 Fax: 765-983-5294 [email protected] web: www.belden.com
Contact for Belden Brand Phone: 765-983-5200
6100 Hollywood Boulevard Suite 110 Hollywood, Florida 33024 Fax: 954-987-8022 [email protected]
Phone: 954-987-5044
Phone: 514-822-2345
Fax: 514-822-7979
2200 U.S. Highway 27 South Richmond, IN 47374 Phone: 765-983-5200 Fax: 765-983-5294 [email protected] web: www.belden.com