Post Insulator

K-Line Insulators has introduced a new silicone line post insulator for 69 kV overhead lines that features a one-piece, injection molded silicone rubber that is chemically bonded to an epoxy fiberglass rod. This insulator provides reliable performance, especially in contaminated environments, as its hydrophobic silicone material inherently resists water filming and limits leakage currents. The 69 kV line post insulator is available in horizontal, vertical, tie-top, or K-clamp configurations, with the K-clamp offering advantages like integrated conductor attachment without a separate clamp.

Uploaded by

Bilal Ahmad
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
179 views2 pages

Post Insulator

K-Line Insulators has introduced a new silicone line post insulator for 69 kV overhead lines that features a one-piece, injection molded silicone rubber that is chemically bonded to an epoxy fiberglass rod. This insulator provides reliable performance, especially in contaminated environments, as its hydrophobic silicone material inherently resists water filming and limits leakage currents. The 69 kV line post insulator is available in horizontal, vertical, tie-top, or K-clamp configurations, with the K-clamp offering advantages like integrated conductor attachment without a separate clamp.

Uploaded by

Bilal Ahmad
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

New Silicone Line Post Insulator For 69 kV Overhead Lines

K-Line Insulators has introduced a new silicone line post insulator that is applicable for 69 kV overhead lines. This insulator is designed for installations with high electrical requirements. This insulator features the highly reliable proprietary K-Line silicone rubber that is one piece, injection molded and chemically bonded to a high quality epoxy fiberglass rod. This insulator will greatly improve the electrical performance of the System, especially in contaminated environments. Insulator contamination is a common problem on overhead lines. The fundamental element for interruptions with contaminated insulators is moisture. Wet atmospheric conditions result in water filming on surfaces and causing leakage currents to develop. On wood structures, leakage currents can cause pole top fires and eventual failures. On steel structures, leakage currents can develop into faults. K-Lines proprietary silicone material offers the ultimate solution in post insulator applications. Because of its hydrophobicity, this material inherently resists water filming thereby limiting leakage currents. These silicone insulators reduce leakage currents, even when contaminated and require less frequent if any washing. The savings in maintenance costs are added benefits of using K-Line silicone insulators. The 69 kV line post insulator has been designed to meet the requirements of CEA LWIWG-02, ANSI C29.18, and IEC 61952. The 69 kV line post insulator is available in four different configurations: horizontal, vertical, tie-top, or K-clamp. The K-clamp design offers the best and most cost effective solution in most cases.

69 kV K-Clamp Line Post


The K-clamp insulator has an integral clamp for attaching the conductor directly to the line post insulator without the use of a separate conductor clamp. The K-clamp insulator can be mounted either in the vertical or horizontal position and offers several advantages over the conventional line post insulators. The K-clamp has a smooth clamping zone that accommodates a conductor diameter range of 0.30 inch (7.6 mm) to 1.34 inch (34 mm). The single galvanized steel clamp bolt that secures the keeper can be operated with hot line tools from either side of the clamp. It also extends beyond the clamp body to allow for the attachment of stringing devices. The K-clamp insulator can provide substantial labour cost savings in stringing, sagging and conductor clamping. There are other savings that can be achieved in shipping, stocking and maintenance.

Configuration & Hardware Accessories


The 69 kV line post is available in three other configurations: vertical, horizontal, or tie-top (ANSI F-Neck). Also, the horizontal line post can be supplied with a gain base (See below). For the clamp-top trunnions conductor clamps are also available.

Vertical

Tie-Top

Horizontal with Gain Base

Technical Data
SPECIFICATION UNIT CATALOGUE NUMBER* KL69S
Voltage Class CEA Class ANSI Class Dry Arcing Distance Leakage Distance Critical Impulse Flashover (Positive) Low-Frequency Flashover Dry Wet kV mm (in) mm (in) kV kV 69 LP69M 51-16 & 51-26 551 (21.7) 1511 (59.5) 360 235 190** Radio Influence Voltage (RIV) at 1 MHz Specified Tensile Load (STL) Specified Cantilever Load (SCL) Max. Design Cantilever Load (MDCL) Approx. Weight Standard Packaging Test Max kV V kN (lb) kN (lb) kN (lb) kg (lb) -

SPECIFICATION

UNIT

CATALOGUE NUMBER* KL69S


45 6 22 (5000) 11 (2475) 5.5 (1240) 8.0 (17.5) 2

* Ordering Information To Line Post Catalogue Number, add suffix KP1 for K-clamp, HP1 for horizontal, VP1 for vertical, or TFP1 for tie-top. The standard base thread is -9 UNC. Different base threads are available upon request. ** The value shown is as per CEA and the ANSI value is 165 kV.