J. Steven Brown(a), Piotr A. Domanski(b)(C), and Eric W. Lemmon(d) (aJDepartment of Mechanical Engineering, Catholic University of America, Washington, DC 20064 USA (b)Building and Fire Research Laboratory, NIST, Gaithersburg, MD 20899 USA (d)Physical and Chemical Properties Division, NIST, Boulder, CO 80305 USA (C)Corresponding author: National Institute of Standards and Technology, Gaithersburg, MD 20899 USA [email protected]; fax: 1-301-975-8973
ABSTRACT
This paper presents Version 4.0 of CYCLE_D, a vapor compression cycle design program. The model can simulate a basic subcritical or transcritical refrigeration cycle, both with or without a liquidline/suction-line heat exchanger. In addition, the model can simulate a subcritical two-stage economizer cycle, a subcritical three-stage economizer cycle, and a subcritical two-stage compression cycle with intercooling. The model is a user-friendly tool for screening the performance of single-component refrigerants and refrigerant mixtures.
1. INTRODUCTION
The CYCLE_D Version 4.0 package simulates vapor compression refrigeration cycles that use singlecomponent refrigerants or mixtures of refrigerants. The model can simulate a basic subcritical or transcritical refrigeration cycle, both with or without a liquid-line/suction-line heat exchanger. In addition, the model can simulate a subcritical two-stage economizer cycle, a subcritical three-stage economizer cycle, and a subcritical two-stage compression cycle with intercooling. CYCLE_D operates in a user-friendly environment on a standard PC that facilitates evaluating the performance of selected working fluids at different operating conditions. Calculations are based on refrigerant properties as represented in REFPROP (Lemmon et aI., 2007). Note: most of the contents of this paper are extracted from the CYCLE_D Version 4.0 Users' Guide (Brown et a!., 2009), which the reader may consult for more detailed information.
2. MODELLING APPROACH
The basic subcritical or transcritical system simulated by CYCLE_D consists of a compressor, a discharge line, a condenser for the subcritical cycle (a gas cooler for the trans critical cycle), an expansion device, an evaporator, and a compressor suction line. The other subcritical cycles may contain a second compressor, and one or two economizers or an intercooler. The basic subcritical and transcritical cycles can also include a liquid-line/suction-line heat exchanger (LLSL-HX). The user of the program has to specify the refrigerant and provide input data for the above listed hardware components, except for the expansion device, which is modeled as being isenthalpic. The user can also specify the auxiliary powers for the indoor fan, outdoor fan, and control unit of the system.
3rd
IIR Conference on Thermophysical Properties and Transfer Processes of Refrigerants, Boulder, CO, 2009
2.3 Compressor
For a basic subcritical cycle, CYCLE _ D provides two options for representation of the compressor: the "Compressor Efficiency" option and the "Compressor Map" option. For other subcritical cycles and for the transcritical cycle, only the "Compressor Efficiency" option is available. The "Compressor Efficiency" option requires input values of the compression process isentropic efficiency, the compressor volumetric efficiency, the electric-motor efficiency, and a target system Cooling Capacity, which is the evaporator capacity adjusted for the heat added by the indoor coil fan. If the value of the electric motor efficiency is less than unity, the entire heat rejected by the electric motor is assumed to heat the suction vapor before the compressor suction port. If the cycle includes two compressors, their inputs have to be independently specified. The "Compressor Map" option uses compressor-map correlations, which are typically derived from compressor calorimeter tests. Three types of correlations are allowed. The "Compressor Map" option also requires a value for either the system Cooling Capacity or Capacity Multiplier. If Capacity Multiplier is specified, its value is used in the simulation as a multiplication factor for the compressor capacity (calculated by compressor-map correlations) and for indoor and outdoor fan powers (entered by the user). Power input to the system control unit is unaffected. If the system Cooling Capacity is specified, the simulations are performed for a system with a compressor of identical efficiency characteristics but with
3rd
Paper No. 204 adjusted displacement, so the system could provide the specified capacity. Power input to the indoor and outdoor fans and system control unit are unaffected by the specified capacity value. Compressor-map equations correlate compressor performance at a certain suction superheat and condenser subcooling. To allow simulations at user-specified superheat and subcooling, the following steps and assumptions are taken by the model: The isentropic efficiency of the compressor is calculated using the compressor-map correlations at user-specified saturation temperatures (or pressures) and at the superheat and subcooling levels used during the calorimeter tests. It is assumed that the isentropic efficiency is not affected by the level of superheat, and the calculated efficiency value is used in the cycle calculations . When calculating refrigerant mass flow rate, it is assumed that the compressor volumetric efficiency and speed (revolutions per minute, RPM) are not affected by the suction vapor superheat. Consequently, the refrigerant mass flow rate at the user-specified superheat equals the value of mass flow rate at the superheat maintained during the calorimeter tests, adjusted for the different specific volume of the suction vapor caused by a different superheat.
IIR Conference on Thermophysical Properties and Transfer Processes of Refrigerants, Boulder, CO, 2009
3
2.6 Simulation Results Simulation results are generated in two categories: (1) for the thermodynamic cycle and (2) for the compressor and system. The cycle category presents the results obtained per unit mass of refrigerant. These results reflect refrigerant parameters only and are not affected by the auxiliary power to the indoor fan, outdoor fan, and controls. The compressor and system results are calculated for the system Cooling Capacity or Capacity Multiplier as specified by the user. CYCLE_D calculates line sizing information using the thermodynamic parameters identified throughout the cycle and the refrigerant mass flow rate needed to obtain the target system capacity. 2.7 Uncertainties in Simulation Results Uncertainties in the simulation results are directly related to the uncertainties of thermodynamic properties calculated by the NIST REFPROP 8.0 (Lemmon et aI., 2007) property routines incorporated into the CYCLE_D package. CYCLE_D uses the REFPROP default property models. The user should be aware that the uncertainties in these models vary considerably depending on the refrigerant, property, and thermodynamic state. It is thus impossible to give a simple, global statement regarding uncertainties. Even for the most-studied fluids with equations of state based on accurate, wide-ranging data, uncertainties are complicated functions of temperature and pressure. For details, refer to the original literature sources listed in Lemmon et al. (2007).
3. USING CYCLE D
CYCLE _ D consists of several menus and tabs, which allow the user to specifY the cycle of interest.
3rd
tab.
1 Ge,GO
3rd
IIR Conference on Thermophysical Properties and Transfer Processes of Refrigerants, Boulder, CO, 2009
5
4. SOME EXAMPLES
In this section, some brief examples, without presenting detailed results or analyses, are provided to demonstrate some of the capabilities of CYCLE_D. In the first example, operating conditions for typical unitary air conditioners (Calm and Domanski, 2004) are used to simulate the performance potentials of thirty nine single-component refrigerants (of the total 48); these 39 are the ones that have sufficiently high critical temperatures to ensure subcritical cycles. The condensing temperature is 46.1 DC,the evaporation temperature is 10C, and the compressor isentropic efficiency is 70 %. First, the simulations were conducted for evaporator superheat and condenser subcooling values of zero. Second, the simulations were conducted for evaporator superheat and condenser subcooling values of 5C. Third, the simulations were conducted for evaporator superheat and condenser subcooling values of zero, but now using an LLSL-HX. The results are plotted in Figure 7. Note: (1) each abscissa location represents a different refrigerant; (2) the results have been sorted in order of increasing volumetric cooling capacity (VCC) for the baseline case (first case); (3) the data points are connected by lines simply to aid the reader, and do not have physical significance. It is interesting to note that all of the cycles with subcooling and superheat values of 5 C have better coefficient of performance (COP) and VCC values than the baseline cases; whereas, some of LLSL-HX cycles have better and some have worse COP and VCC values than the baseline cases, implying that the LLSL-HX helps some refrigerants and penalizes others.
A second example is to consider transcritical cycles for five of the remaining nine single-compound refrigerants; these five refrigerants are ones where the high-side temperature and the evaporation temperature are such that the cycles are transcritical. The evaporation temperature is 10C, the compressor isentropic efficiency is 70 %, and the evaporator superheat is 0 DC. The cycle uses the optimum high-side gas cooling pressure with the gas cooler refrigerant outlet temperature specified as 35 DC,and a LLSL-HX with an effectiveness value of75 %. The simulation results are presented in Table 1. Table 1. Transcritical cycle simulations for 5 fluids. Refrigerant (kJ
m-3)
11136 6359 3.441 3.556 9800 3.844 3.057 6785 8102 4750 4734 5391 8484 VCC 15875 3.625 COP Optimum Gas Cooler Pressure (kPa)
A third example is the transcritical CO2 cycle. The evaporation temperature is 10C, the compressor isentropic efficiency is 70 %, and the evaporator superheat is 0 DC. The cycle uses the optimum high-side pressure and a LLSL-HX with an effectiveness value of 75 %. The gas cooler refrigerant outlet temperature is varied from 32C to 48 C and the results are plotted in Figures 8 and 9. Figure 8 shows the COP and VCC values and Figure 9 shows the optimum gas cooler refrigerant pressure, both as functions ofthe gas cooler refrigerant exit temperature. A fourth and final example is for the two-stage economizer cycle for R-410A. The evaporation temperature is 10C, the condensation temperature is 46.1 DC,the compressor isentropic efficiency is 70 %, and the evaporator superheat and condenser subcooling values are zero. The intermediate pressure is varied from 1100 kPa to 2700 kPa, and the results are plotted in Figure 10.
3rd
IIR Conference on Thermophysical Properties and Transfer Processes of Refrigerants, Boulder, CO, 2009 6
2 31
- vcc
E 0 >
-cOP
eo
~14
~
~
~12
...:-
,....,--, pJ
6 2 ... 4
-1
VCC - LLSL-HX
c?
Figure 7. COP
V
v f'
:l;;~ .....
& VCC
for subcritical
10
~ . 39 single-component
:~
16
>
E ~ U
I'"
VCC , 0 refrigerants.
J:
~ 2
1 I 32
34
36
38
40
TgC,exit
42
(DC)
44
46
I 10 48
Figure 8. COP & VCC for a CO2 transcritical cycle as a function of gas cooler exit tem perature.
E '7 8000 -, 7500 :OS 8500 9000
:OS
ro
Q& ~is
0...
0 0
7000
4,5 >
- VCC
-cOP
6500
7000 32 34 36 38 40
Tgc,exit
42
44
46
48
4.0 I I 6000 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
Pintermedlate
(C)
(kPa)
CO2 transcritical
Figure 9. Optimum gas cooler pressure for a cycle as a function of gas cooler exit temperature.
Figure 10. COP & VCC for a two-stage economizer cycle as a function of intermediate pressure.
5. CONCLUSIONS
This paper Compression cycles that subcritical exchanger. three-stage presents Version 4.0 of the NIST Standard Reference Database 49 - CYCLE_D: NIST Vapor Cycle Design Program. CYCLE_D Version 4.0 simulates vapor compression refrigeration use single-component refrigerants or refrigerant mixtures. The model can simulate a basic or transcritical refrigeration cycle, both with or without a Iiquid-line/suction-line heat In addition, the model can simulate a subcritical two-stage economizer cycle, a subcritical economizer cycle, and a subcritical two-stage compression cycle with intercooling.
3rd
ACKNOWLEDGEMENTS
Version 1.0 ofCYCLE_D, authored by J. Chi, D.A. Didion, and P.A. Domanski, was developed in 1992 under partial funding from the Trane Company and the Electric Power Research Institute, with G. Lange and T. Statt, respectively, managing the project. The authors acknowledge helpful suggestions from P. Glamm. J. Wnek made modifications and improvements of the graphical user interface in Version 2.0, and J. Schnotale and P.A. Domanski implemented thermodynamic charts and line sizing calculations in Version 3.0. For Version 4.0, J.S. Brown extended simulation options to include transcritical cycles, cycles with two-stage compression with intercooling, and two and three-stage economizer cycles; and E.W. Lemmon provided new thermodynamic charts. The authors acknowledge K. Tchen's assistance in upgrading the graphical user interface, and J. Calm, D. Yashar, B. Dougherty, and D. Bivens for their testing and comments.
NOMENCLATURE
COP LLSL-HX T VCC Subscripts gc,exit gc,optimum intermediate Coefficient of Performance liquid-line/suction-line heat exchange temperature (K or 0c) Volumetric Cooling Capacity (kJ m-3)
h P s P
enthalpy (kJ kg-I) pressure (kPa) entropy (kJ kg-1 K"l) density (kg m-3)
gas cooler exit gas cooler optimum value two-stage economizer cycle intermediate value
REFERENCES
Brown, J.S., Domanski, P.A., Lemmon, E.W., 2009. CYCLE_D: NIST Vapor Compression Cycle Design Program, NIST Standard Reference Database 49, Version 4.0, National Institute of Standards and Technology, Gaithersburg, MD. Calm, J.M. and Domanski, P.A., 2004. R-22 replacement status. ASHRAE J. 46 (8), 29-39. Lemmon, E.W., Huber M.L., and McLinden, M.O., 2007. NIST Reference Fluid Thermodynamic Transport Properties-REFPROP. NIST Standard Reference Database 23, Version http://www.nist.gov/srd/nist23.htm.NationaIInstituteofStandardsandTechnology.Gaithersburg.MD. and 8.0,