Acti 9 & Compact NSX/NS: Short Form Selection Chart - 2011

This document contains cascading and discrimination tables for Schneider Electric's Compact NSX and NS circuit breakers. The tables show: 1) The enhanced breaking capacity in kA provided to downstream devices through cascading when paired with upstream devices. 2) The enhanced discrimination/selectivity limit in kA provided through cascading between two devices. 3) Which combinations of circuit breakers provide total discrimination up to the reinforced breaking capacity of the downstream device. The tables apply only to cases with combined discrimination and cascading between two circuit breakers rated at 380/415V. They indicate the enhanced protection provided by cascading upstream and downstream devices.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
468 views1 page

Acti 9 & Compact NSX/NS: Short Form Selection Chart - 2011

This document contains cascading and discrimination tables for Schneider Electric's Compact NSX and NS circuit breakers. The tables show: 1) The enhanced breaking capacity in kA provided to downstream devices through cascading when paired with upstream devices. 2) The enhanced discrimination/selectivity limit in kA provided through cascading between two devices. 3) Which combinations of circuit breakers provide total discrimination up to the reinforced breaking capacity of the downstream device. The tables apply only to cases with combined discrimination and cascading between two circuit breakers rated at 380/415V. They indicate the enhanced protection provided by cascading upstream and downstream devices.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Cascading and enhanced discrimination chart for

Compact NSX160 - NSX630 & Compact NS800 - NS1600

Acti 9 & Compact NSX/NS


Short Form Selection Chart - 2011

Enhanced discrimination tables: 380/415V


For each combination of two circuit breakers, the

Cascading: 380 / 415V


Upstream Breaking
Capacity
Trip Unit
Downstream
Rating (A)
iC60a 6kA
1-25
iC60a 6kA
32-40
iC60a 6kA
50-63
iC60N 10kA
1-40
iC60N 10kA
50-63
iC60H 15kA
1-40
iC60H 15kA
50-63
iC60L 25kA
1-25
iC60L 20kA
32-40
iC60L 15kA
50-63
C120N 10kA
80-100
C120H 15kA
80-100

tables indicate the:

C120N
10kA

C120H
15kA

10
10
10

15
15
15
15
15

NSX100F
36kA

NSX160F
36kA

15
10
10
25
25
36
36
36
36
36
25
25

NSX250F
36kA
TM-D

15
10
10
25
25
36
30
36
36
30
25
25

NSX100H
70kA

NSX160H
70kA

20
15
15
30
30
40
36
40
40
36
25
25

15
10
10
25
25
30
25
30
30
25
25
25

NSX250H
70kA

15 / 25

20
15
15
30
25
30
25
36
36
30
25
25

20
15
15
30
30
40
30
40
40
36
25
25

Downstream device breaking


capacity enhanced by cascading
in kA.

Selectivity / discrimination limit


enhanced by cascading (in kA)

A box containing two equal values (shaded area) indicates


that discrimination is provided up to the reinforced
breaking capacity of the downstream device (total
discrimination). These tables apply only to cases with
combined discrimination and cascading between two
devices.

Cascading with enhanced discrimination: 380 / 415V


Upstream Breaking
Capacity

Downstream
iC60a 6kA

iC60N

10kA

iC60H

15kA

iC60L

25kA

iC60L 20kA
iC60L 15kA
C120N 10kA

C120H 15kA
NSX100F 36kA
TM-D Trip Unit
NSX160F 36kA
NSX250F 36kA

Trip Unit
Rating (A)
<16
20-25
32-40
50-63
<16
20-25
32-40
50-63
<16
20-25
32-40
50-63
<16
20-25
32-40
50-63
80
100
125
80
100
<25
40-100
All TM-D/MA
All TM-D/MA

NSX 160F
36kA

80-100

125-160
15/15
15/15
10/10
10/10
25/25
25/25
25/25
25/25
36/36
36/36
36/36
30/30
36/36
36/36
36/36
30/30

NSX 250F
36kA

200
15/15
15/15
10/10
10/10
25/25
25/25
25/25
25/25
30/30
30/30
30/30
25/25
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25

NSX160H
70kA

TM-D
250
80-100
15/15
15/15
10/10
10/10
25/25
25/25
25/25
25/25
30/30
30/30
30/30
25/25
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25

125-160
20/20
20/20
15/15
15/15
30/30
30/30
30/30
30/30
40/40
40/40
40/40
30/30
40/40
40/40
40/40
36/36

NSX250H
70kA

200
20/20
20/20
15/15
15/15
30/30
30/30
30/30
25/25
30/30
30/30
30/30
25/25
36/36
36/36
36/36
30/30
25/25
25/25
25/25
25/25
25/25
70/70
36/70

250
20/20
20/20
15/15
15/15
30/30
30/30
30/30
25/25
30/30
30/30
30/30
25/25
36/36
36/36
36/36
30/30
25/25
25/25
25/25
25/25
25/25
70/70
36/70

NSX400N NSX630N NSX400H NSX630H


50kA
50kA
70kA
70kA

400

50/50
50/50
50/50

Micrologic 2.3
630
400

50/50
50/50
50/50
50/50

70/70
70/70
70/70

NS800N
50kA

NS800H
70kA

630

800

800

70/70
70/70
70/70
70/70

50/50
50/50
50/50
50/50

70/70
70/70
70/70
70/70

NS1000N
50kA

NS1600N
50kA

NS1600H
70kA

Micrologic 2.0 or Micrologic 5.0


1000
1000
1250
1250

NS1000H
70kA

1600

1600

50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50

70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70

NS1250N
50kA

50/50
50/50
50/50
50/50

NS1250H
70kA

70/70
70/70
70/70
70/70