Hazardous voltages and high speed moving parts. Will cause death, serious injury or property damage. Always de-energize and ground the equipment before maintenance. Read and understand this instruction manual before using equipment. Maintenance should be performed only by qualified personnel. The use of unauthorized parts in the repair of the equipment or tampering by unqualified personnel will result in dangerous conditions which will cause death, severe injury or equipment damage. Follow all safety instructions contained herein.
Important The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the user of responsibility to use sound practices in application, installation, operation and maintenance of the equipment purchased. Siemens reserves the right to make changes in the specifications shown herein or to make improvements at any time without notice or obligations. Should a conflict arise between the general information contained in this publication and the contents of drawings or supplementary material or both, the latter shall take precedence. Qualified person For the purpose of this manual a qualified person is one who is familiar with the installation, construction or operation of the equipment and the hazards involved. In addition, this person has the following qualifications: I s trained and authorized to de-energize, clear, ground and tag circuits and equipment in accordance with established safety procedures.
I s trained in the proper care and use of protective equipment, such as: rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety practices. Is trained in rendering first aid. Further, a qualified person shall also be familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials and insulated tools and test equipment. Such persons are permitted to work within limited approach of exposed live parts operating at 50 volts or more, and shall, at a minimum, be additionally trained in all of the following: T he skills and techniques necessary to distinguish exposed energized parts from other parts of electric equipment. T he skills and techniques necessary to determine the nominal voltage of exposed live parts. T he approach distances specified in NFPA 70E and the corresponding voltages to which the qualified person will be exposed. T he decision-making process necessary to determine the degree and extent of the hazard and the personal protective equipment and job planning necessary to perform the task safely.
Table of contents
Introduction
4 -5
Note: These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise that are not covered sufficiently for the purchasers purposes, the matter should be referred to the local sales office. The contents of this instruction manual shall not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens Energy, Inc. The warranty contained in the contract between the parties is the sole warranty of Siemens Energy, Inc. Any statements contained herein do not create new warranties or modify the existing warranty.
6 -8
9 - 10
Vacuum interrupter/operator
11 - 28
Maintenance
29 - 43
Overhaul
44 - 48
49 - 52
Appendix
53 - 58
Introduction
Hazardous voltage and high-speed moving parts. Will cause death, serious injury and property damage. Always de-energize and ground the equipment before maintenance. Maintenance should be performed only by qualified personnel. The use of unauthorized parts in the repair of the equipment or by tampering by unqualified personnel will result in dangerous conditions that will cause death, severe injury or equipment damage. Follow all safety instructions contained herein.
Introduction The type 3AH vacuum circuit breaker module is designed to meet all applicable ANSI, NEMA and IEEE standards. Successful application and operation of this equipment depends as much upon proper installation and maintenance by the user as it does upon the proper design and fabrication by Siemens. The purpose of this instruction manual is to assist the user in developing safe and efficient procedures for the installation, maintenance and use of the equipment. Contact the nearest Siemens representative if any additional information is desired.
Signal words The signal words "danger," "warning" and "caution" used in this instruction manual indicate the degree of hazard that may be encountered by the user. These words are defined as: Danger - Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Warning - Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Caution - Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. Caution (without safety alert symbol) Indicates a potentially hazardous situation which, if not avoided, may result in property damage.
Introduction
Hazardous Procedures In addition to other procedures described in this instruction manual as dangerous, user personnel must adhere to the following: 1. A lways work only on a de-energized circuit breaker. The circuit breaker should be isolated, grounded and have all control power removed before performing any tests, maintenance or repair. 2. A lways perform maintenance on the circuit breaker after the springcharged mechanisms are discharged (except for test of the charging mechanisms). Check to be certain that the indicator flags read OPEN and DISCHARGED. 3. A lways let an interlock device or safety mechanism perform its function without forcing or defeating the device. Field service operation and warranty issues Siemens can provide competent, welltrained field service representatives to provide technical guidance and advisory assistance for the installation, overhaul, repair and maintenance of Siemens equipment, processes and systems. Contact regional service centers, sales offices or the factory for details, or telephone Siemens field service at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S. For medium-voltage customer service issues, contact Siemens at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S.
Heavy weight. Improper lifting or hoisting can result in death, serious injury or property damage. Obtain the services of a qualified rigger prior to hoisting the circuit breaker to assure adequate safety margins in the hoisting equipment and procedures to avoid damage.
Introduction This portion of the instruction manual covers the receiving, handling and storage instructions for a type 3AH vacuum circuit breaker module. This section of the instruction manual is intended to help the user identify, inspect and protect the circuit breaker prior to its installation. Receiving procedure Make a physical inspection of the shipping container before removing or unpacking the circuit breaker. Check for shipment damage or indications of rough handling by the carrier. Check each item against the manifest to identify any shortages. Accessories (as applicable) such as the manual charging crank, racking crank or split-plug jumper are shipped separately.
Shipping damage claims Important: The manner in which visible shipping damage is identified by consignee prior to signing the delivery receipt can determine the outcome of any damage claim to be filed. Notification to carrier within 15 days for concealed damage is essential if loss resulting from unsettled claims is to be eliminated or minimized. 1. W hen the shipment arrives, note whether the equipment is properly protected from the elements. Note the trailer number the equipment arrived on. Note also any blocking of equipment. During unloading, check the actual equipment delivered to verify it agrees with the delivery receipt. 2. M ake immediate inspection for visible damage upon arrival and prior to disturbing or removing packaging or wrapping material. This should be done prior to unloading when possible. When total inspection cannot be made on vehicle prior to unloading, close inspection during unloading must be performed and visible damage noted on the delivery receipt. Take pictures if possible.
Hazardous voltage and high-speed moving parts. Will cause death, serious injury and property damage. Read instruction manuals, observe safety instructions and use qualified personnel.
10
Rating plate
CLOSE pushbutton Opening for manual spring-charging CHARGED/DISCHARGED indicator CLOSED/OPEN indicator Operations counter OPEN pushbutton
Figure 1: Front panel controls of circuit breaker and manual charging of closing spring
Pole head Upper connection pad Upper post insulator Mechanism housing Vacuum interrupter Strut Pole plate
When the two contacts separate, an arc is initiated that continues conduction up to the following current zero. At current zero, the arc extinguishes and any conductive metal vapor that has been created by and supported the arc condenses on the contacts and on the surrounding arc shield. Contact materials and configuration are optimized to achieve arc motion and to minimize switching disturbances. Primary connections (refer to Figure 2) Figure 2 illustrates the pad provision to accept the primary connections. Each circuit breaker has three upper and three lower primary disconnect pad provisions, to allow connection to the switchgear. For stationary circuit breaker applications, bus conductors connect directly to these pads. Bolting hardware is M12 x 1.75 grade 8. Torque M12 bolts to 52 ft-lb (70 Nm). Phase barriers (if applicable) Plates of glass-polyester insulating material are attached to the circuit breaker and provide suitable electrical insulation between the vacuum interrupter and primary conductors and the cubicle. Stored-energy operating mechanism The stored-energy operating mechanism of the circuit breaker is an integrated arrangement of springs, coils and mechanical devices designed to provide a number of critical functions. The energy necessary to close and open the contacts of the vacuum interrupters is stored in powerful opening and closing springs. The closing springs are normally charged automatically, but there are provisions for manual charging. The operating mechanism that controls charging, closing and tripping functions is fully trip-free. "Trip-free" requires that the tripping function prevail over the closing function as specified in ANSI/IEEE C37.04-1999, clause 6.9.
13
Strut Vacuum interrupter Moving contact Centering piece Terminal clamp Flexible connector Eye bolt Pole bottom Lever Jack shaft
4. O perate all these functions automatically through an electrical charging motor, cutout switches, an anti-pump relay, a close coil, an open coil and an auxiliary switch. 5. Provide indication of the circuit breaker status (OPEN/CLOSED), spring condition (CHARGED/DISCHARGED) and number of operations. Construction The essential parts of the operating mechanism are shown in Figures 6 and 7. The control and sequence of operation of the mechanism is described in Figure 8. Motor-operating mechanism (refer to Figure 6) The spring-charging motor (50.4) is bolted to the charging mechanism (50.2) gear box installed in the operator housing. Neither the charging mechanism nor the motor require any maintenance. Mode of operation The operating mechanism is of the stored-energy trip-free type. For example, the charging of the closing spring is not automatically followed by the contacts changing position, and tripping function prevails over the closing function. When the stored-energy mechanism has been charged, the mechanism is ready for a closing operation at any time. The mechanical energy for carrying out an "Open-Close-Open" sequence for auto-reclosing duty is stored in the closing and opening springs. Charging The details of the closing spring charging mechanism are shown in Figure 6. The charging shaft is supported in the charging mechanism (50.2), but is not coupled mechanically with the charging mechanism. Fitted to it are the crank (62.2) at one end, and the cam (62.3), together with lever (62.5), at the other.
Angled lever
When a opening command is given, the energy stored in the opening and contact pressure springs (49.0) is released by pawl (64.2) (refer to Figure 7). The opening sequence is similar to the closing sequence. The residual force of the opening spring maintains the moving contacts in the open position. Operating mechanism The operating mechanism is comprised of the mechanical and electrical components required to: 1. Charge the closing spring with sufficient potential energy to close the circuit breaker and to store opening energy in the opening and contact pressure springs. 2. Mechanisms to release closing and opening actions. 3. Means of transmitting force and motion to each of the three vacuum interrupters.
14
55.2
50.2
50.5
62.1 62.2 62.5.2 68.0 53.0 55.1 62.0 50.4.1 53.1 54.1
59.0
60.0 50.2 - Charging mechanism gear box 50.3 - Charging flange 50.3.1 - Driver (not visible) 50.4 - Spring-charging motor 88 50.4.1 - Limit switches 50.5 - Manual spring-charging port 53.0 - Close pushbutton 53.1 - Close coil 52SRC 54.0 - Open pushbutton 54.1 - Trip coil 52T 55.0 - Closing spring-charge indicator 55.1 - Linkage 55.2 - Control lever
61.8
63.5
63.0 63.1 62.8.3 - Trip-free coupling lever* 63.0 - Jack shaft 63.1 - Lever - phase C 63.5 - Lever - phase B 63.7 - Lever - phase A 64.0 - Opening spring 68.0 - Auxiliary switch 68.1 - Auxiliary switch link
58.0 - CLOSE/OPEN indicator 59.0 - Operations counter 60.0 - Operator housing 61.8 - Shock absorber 62.0 - Closing spring 62.1 - Charging shaft 62.2 - Crank 62.3 - Cam disc 62.5 - Lever 62.5.1 - Pawl roller (not visible) 62.5.2 - Close latch pawl 62.6 - Driver lever 62.8 - Straight coupling rod* 62.8.1 - Spring return latch (not shown)*
15
Closing (refer to Figures 6-11) If the circuit breaker is to be closed manually, the closing spring is released by pressing the Close button (53.0). In the case of remote electrical control, the close coil 52SRC (53.1) unlatches the closing spring (62.0). As the closing spring discharges, the charging shaft (62.1) is turned by crank (62.2). The cam disc (62.3) at the other end of the charging shaft actuates the drive lever (62.6), with the result that jack shaft (63.0) is turned by lever (63.5) via the coupling rod (62.8). At the same time, the levers (63.1), (63.5) and (63.7) fixed on the jack shaft operate the three insulating couplers (48.0) (refer to Figure 5) for the circuit breaker poles. Lever (63.7) changes the OPEN/CLOSE indicator (58.0) over to OPEN. Lever (63.5) charges the opening spring (64.0) during closing, and the circuit breaker is latched in the closed position by lever (64.3) with pawl roller (64.3.1) and by pawl (64.2). Lever (63.1) actuates the auxiliary switch (68.0) through the linkage (68.1). The crank (62.2) on the charging shaft (62.1) moves the linkage (55.1) by acting on the control lever (55.2). The closing spring charged indication is thus canceled, and the limit switches (50.4) switch in the control supply to cause the closing spring to recharge immediately.
64.3.1 64.3
54.0 - Open pushbutton 62.8 - Trip-free coupling rod* 62.8.1 - Spring-return latch* 62.8.2 - Trip-free coupling link (draw bar)* 64.2 - Trip-latch pawl (not visible) 64.3 - Lever 64.3.1 - Pawl roller
*For type SDV6 and some fixedmounted circuit breakers, trip-free coupling rod (62.8) is replaced with a straight coupling rod, and other parts associated with drawout interlocking are eliminated.
Figure 7: Stored-energy operating mechanism (circuit breaker shown in CLOSED position) (Drawout trip-free linkage shown)
When the charging mechanism is actuated by hand with a hand crank (refer to Figures 13 and 14) or by a motor (50.4), the flange (50.3) turns until the driver (50.3.1) locates itself in the cutaway part of the cam disc (62.3), thus causing the charging shaft to follow. The crank (62.2) charges the closing spring (62.0). When the closing spring has been fully charged, the crank actuates the linkage (55.1) via the control lever (55.2) for the closing spring CHARGED indicator (55.0), and actuates the limit switches (50.4.1) for interrupting the motor supply. At the same time, the lever (62.5) at the other end of the charging shaft is securely locked by the close latch pawl (62.5.2). When the closing spring is being charged, the cam disc (62.3) follows along, and it is brought into position for closing when the closing spring is fully charged.
16
17
62.5.1
62.6
48.0 - Insulating coupler 50.3 - Charging flange 50.3.1 - Driver 53.0 - Close pushbutton 53.1 - Close coil 52SRC 54.0 - Open pushbutton 54.1 - Trip coil 52T 62.1 - Charging shaft 62.2 - Crank 62.2.2 - Closing-spring mounting 62.3 - Cam disc 62.5 - Lever 62.5.1 - Pawl roller 62.5.2 - Close latch-pawl 62.6 - Drive lever 62.8 - Trip-free coupling rod* 62.8.1 - Spring-return latch* 62.8.2 - Trip-free coupling link (draw bar)* 62.8.3 - Trip-free coupling lever* 62.8.5 - Push rod and cam assembly* 62.8.6 - Interlock lever push rod* 62.8.7 - Interlock lever actuator* 62.8.8 - Trip-free actuator* 63.0 - Jack shaft 63.1 - Lever - phase C 63.5 - Lever - phase B 63.7 - Lever - phase A 64.0 - Opening spring 64.2 - Trip-latch pawl 64.2.1 - Trip-latch pin 64.2.2 - Latching pawl-release lever 64.3 - Lever 64.3.1 - Jack-shaft pawl 64.5 - Opening-spring shaft
18
48.0 - Insulating coupler 50.3 - Charging flange 50.3.1 - Driver 53.0 - Close pushbutton 53.1 - Close coil 52SRC 54.0 - Open pushbutton 54.1 - Trip coil 52T 62.1 - Charging shaft 62.2 - Crank 62.2.2 - Closing-spring mounting 62.3 - Cam disc 62.5 - Lever 62.5.1 - Pawl roller 62.5.2 - Close-latch pawl 62.6 - Drive lever 62.8 - Trip-free coupling rod* 62.8.1 - Spring return-latch* 62.8.2 - Trip-free coupling link (draw bar)* 62.8.3 - Trip-free coupling lever* 62.8.5 - Push rod and cam assembly* 62.8.6 - Interlock lever push rod* 62.8.7 - Interlock lever actuator* 62.8.8 - Trip-free actuator* 63.0 - Jack shaft 63.1 - Lever - phase C 63.5 - Lever - phase B 63.7 - Lever - phase A 64.0 - Opening spring 64.2 - Trip-latch pawl 64.2.1 - Trip-latch pin 64.2.2 - Latching pawl-release lever 64.3 - Lever 64.3.1 - Jack-shaft pawl 64.5 - Opening-spring shaft * F or a type SDV6 outdoor circuit breaker and some fixed-mounted circuit breakers, tripfree coupling rod (62.8) and other parts associated with drawout interlocking are eliminated. ** Items moved from position shown in Figure 11 on trip operation. Underlined items moved from position shown in Figure 8 on closed spring-discharge operation.
50.3 62.5.1
62.5 62.2.2
64.5*
54.1*
19
62.5.2 - Close latch-pawl 62.8.1 - Spring-return latch* 62.8.2 - Trip-free coupling link (draw bar)* 62.8.3 - Trip-free coupling lever* 62.8.5 - Push rod and cam assembly* 62.8.6 - Interlock lever push rod* 62.8.7 - Interlock lever actuator* 62.8.8 - Trip-free actuator* 63.1 - Lever - phase C 63.5 - Lever - phase B 63.7 - Lever - phase A 64.0 - Opening spring 64.2.1 - Trip-latch pin 64.2.2 - Latching pawl-release lever 64.3 - Lever 64.3.1 - Jack-shaft pawl 64.5 - Opening spring-shaft
53.1
62.8
20
62.5.2 - Close latch pawl 62.8.1 - Spring return latch* 62.8.2 - Trip-free coupling link (draw bar)* 62.8.3 - Trip-free coupling lever* 62.8.5 - Push rod and cam assembly* 62.8.6 - Interlock lever push rod* 62.8.7 - Interlock lever actuator* 62.8.8 - Trip-free actuator* 63.1 - Lever - phase C 63.5 - Lever - phase B 63.7 - Lever - phase A 64.0 - Opening spring 64.2.1 - Trip-latch pin 64.2.2 - Latching pawl release lever 64.3 - Lever 64.3.1 - Jack shaft pawl 64.5 - Opening spring shaft
62.3
62.2.2
21
Manually charging the closing spring (refer to Figures 13 and 14) Insert the hand crank (50.0) with the over running coupling pushed forward (50.6) through the opening (50.1) onto hand crank coupling (50.5) and turn it clockwise (about 48 revolutions) until the closing-spring indicator (55.0) shows CHARGED. The hand crank is coupled with the charging mechanism via an over-running coupling; thus the operator is not exposed to any risk should the control supply be restored during manual charging. Manual closing (refer to Figure 6) Press the close button (53.0). The CLOSE/ OPEN indicator (58.0) will then display CLOSED and the closing spring condition indicator (55.0) will now read DISCHARGED. Manual opening (refer to Figure 6) The opening spring (64.0) is charged during closing. To open the circuit breaker, press the Open pushbutton (54.0) and OPEN will be displayed by indicator (58.0).
22
Closing
Anti-pumping feature (52Y) assures a continuously applied closing command does not cause the circuit breaker to reclose automatically after it has tripped out on a fault. Continuous closing command. Close coil (52SRC) unlatches closing spring and circuit breaker closes. Motor cutoff switches LS21, LS22 and LS3 are closed because the closing spring is discharged. Before the springcharge motor has recharged the closing spring and opened LS3, antipump relay (52Y) picks up and seals in. The anti-pump relay (52Y) opens two contacts in series with the close coil (52SRC). The close coil (52SRC) is now blocked and cannot be activated until springs are fullycharged and close command is removed. Footnote: 1 Optional items.
LS9 closes close circuit only when closing spring is fully charged.
circuit circuit breaker breaker No action! Open 52b open. closed. in series with close Closing coil (52SRC) blocks command closing springwhen release. closing spring not charged. No action! Antipump relay (52Y) picks up through the closed LS3 contact and opens. 52a contacts in series with the trip coil (52T) close to enable a trip opertion. Circuit breaker auxiliary contacts 52a and 52b change state.
Close coil actuated through closed 52b contacts and two normally closed contacts of the antipump relay (52Y).
LS21 and LS22 close to energize motor. LS3 closes and LS4 opens to cancel closing spring signal.
Rapid auto-reclosing. The closing spring is automatically recharged as described above. Therefore, when the circuit breaker is closed both of its springs are charged. The closing spring charges the opening spring during closing. As a result, the circuit breaker is capable of an O-0.3s-CO-3 min-CO operating cycle. The dashed line shows the operating sequence initiated by the closing command.
Tripping
Trip command. Undervoltage device (27) is activated by opening a NC contact in series with 27 or by loss or reduction of tripping voltage.1 Undervoltage device (27) is activated by closing NO contact, shorting the 27 coil. The NO contact is only effective with the circuit breaker closed. Resistor required.1
Trip coil (52T) can only be activated when series connected 52a contact is closed.
Secondary shuntrelease (dual-trip) function activated by remote trip command contact NO.1 Secondary release unlatches the opening spring.1
23
The schematic shown in Figure 15 is intended to aid in understanding the mechanism operation discussed in this instruction manual. It shows a drawout circuit breaker as an example. Refer to the schematic diagram furnished with your circuit breaker for specific information. Close coil (52SRC)
55.0
54.0
50.0 - Hand crank 50.1 - Manual spring-charging port 53.0 - Manual CLOSE button 54.0 - Manual OPEN (TRIP) button 55.0 - CHARGED/DISCHARGED indicator
Figure 13: Use of manual spring-operation crank
The close coil (3AY1510) is a standard component of the circuit breaker that is used to unlatch the stored energy of the closing spring and thus close the circuit breaker electrically. It is available for either ac or dc operation. After completion of a closing operation, the close coil is deenergized internally. If operated with ac voltage, a rectifier is installed in the circuit breaker. Trip coil (52T) The trip coil (3AY1510) is a standard component of the circuit breaker. The electrically supplied tripping signal is passed on to the trip-latching mechanism by means of a direct action solenoid armature and the circuit breaker is thus opened. It is available for either ac or dc operation. After completion of an opening operation, the trip coil is de-energized internally. If operated with ac voltage, a rectifier is installed in the circuit breaker.
50.5
50.6
50.0
50.0 - Hand crank 50.5 - Manual spring-charging port 50.6 - Over-running coupling
(+) 01 C SD16 W 21 22 SD3 Motor 13 DC supply 14 LS41 21 22 22 21 TB 1 2 3 4 5 6 LS22 88 SD13 LS21 G 41 42 22 21 31 32 A1 52SRC MI1 22 A2 MI2 13 21 14 A2 LS9 52b 21 52Y 22 52Y A1 52Y SD14 A2 34 33 SD2 14 LS3 13 SD4 52Y 31 32 24 52b 23 A1 52T 52a SD1 R 01 T
52a
SD15
(-)
SD11
SD9
SD7
SD5
54 53 SD12
64 52a 63
52a
91 92 SD10
52b
74 73 SD8
84 52a 83
52a
- Spring-charging motor - Auxiliary switch is open when circuit breaker is open - Auxiliary switch is closed when circuit breaker is closed
LS
- Spring-charged switch
Standard: Fuses in close circuit. Slugs in trip circuit (fuses optional). Shown with springs discharged, triplatch reset, circuit breaker open, connect or withdrawn position.
MI1, MI2 - Mechanical interlock 01/C 01/T R W - Control switch (CLOSE) - Control switch (TRIP) Red indicating light - (CLOSED) -W hite indicating light (spring-charged)
52SRC - Spring-release coil (CLOSE) 52T 52Y G - Shunt trip coil Closing relay (anti-pump) - - Green indicating light (TRIP)
25
Indirect releases - secondary shunt release (dual trip) (52T1) or undervoltage (27.0)
33.0 31.0
7.0 1.0
The indirect release provides for the conversion of modest control signals into powerful mechanical-energy impulses. It is primarily used to open medium-voltage circuit breakers while functioning as a secondary shunt-release (dual trip) or undervoltage device. These releases are mechanical energystorage devices. Their internal springs are charged as a consequence of the circuit breaker mechanism operation. This energy is released upon application or removal (as appropriate) of applicable control voltages (refer to Figures 16, 17 and 18). The secondary shunt-release and undervoltage release mounts to the immediate right of the trip coil (54.1). Secondary shunt-release (52T1) (refer to Figure 16) A secondary shunt-release (extra-trip coil) (3AX1101) is used for electrical opening of the circuit breaker by protective relays or manual control devices when more than one trip coil is required. The second trip coil is generally connected to a separate auxiliary supply (dc or ac) from the control supply used for the normal trip coil. Undervoltage release (27.0) (refer to Figures 17 and 18) The undervoltage release (3AX1103) is used for continuous monitoring of the tripping supply voltage. If this supply voltage falls excessively, the undervoltage release will provide for automatic tripping of the circuit breaker. The undervoltage device may be used for manual or relay tripping by employing a contact in series with undervoltage device holding coil. Relay tripping may also be achieved by employing a normally open contact in parallel with the holding coil. If this scheme is used, a resistor must be provided to limit current when the normally open contact is closed. Secondary shunt and undervoltage releases are available for all standard ANSI/ IEEE control voltages.
1.0 - Magnet core 3.0 - Housing 5.0 - Mounting holes 7.0 - Magnet coil 9.0 - Magnet armature 11.0 - Tension spring 13.0 - Adjusting screw (factory-set) for 11.0
15.0 - Tripping pin 21.0 - Locking pin 23.0 - Striker pin 25.0 - Latch 27.0 - Spring 31.0 - Striker-pin spring 33.0 - Terminal block
23.0
25.0
21.0 21.0 - Locking pin 23.0 - Striker pin 25.0 - Latch 27.0 - Spring
27.0
23.0 29.0
A B
23.0 29.0
A B
Cancel the lock for the undervoltage release by shifting the locking screw (29.0) from A to B. 23.0 - Striker pin 29.0 - Screw
01 T
SD5 24 23 A1 52T A2 34 33
52a Capacitor (+) (-) 1 Resistor 2 (+) Rectifier (-) Capacitor trip
52a
28
Maintenance
Failure to maintain the equipment can result in death, serious injury, property damage or product failure, and can prevent successful functioning of connected apparatus. The instructions contained herein should be carefully reviewed, understood and followed. The maintenance tasks in Table 1 must be performed regularly.
Introduction and maintenance intervals Periodic inspections and maintenance are essential to safe and reliable operation of the circuit breaker. When circuit breakers are operated under "usual service conditions," maintenance and lubrication are recommended at tenyear intervals (five-year intervals for the type SDV6 outdoor distribution circuit breaker) or at the number of operations indicated in Table 2. "Usual" and "unusual" service conditions for medium-voltage metal-clad switchgear (includes circuit breaker module) are defined in ANSI/IEEE C37.20.2, sections 4 and 8.1, ANSI/IEEE C37.04, section 4 and ANSI/IEEE C37.010, section 4. Generally, "usual service conditions" are defined as an environment where the equipment is not exposed to excessive dust, acid fumes, damaging chemicals, salt air, rapid or frequent changes in temperature, vibration, high humidity and extreme temperatures. The definition of "usual service conditions" is subject to a variety of interpretations. Because of this, you are best served by adjusting maintenance and lubrication intervals based on your experience with the equipment in the actual service environment. Regardless of the length of the maintenance and lubrication interval, Siemens recommends that circuit breakers should be inspected and exercised annually.
For the safety of maintenance personnel as well as others who might be exposed to hazards associated with maintenance activities, the safety related work practices of NFPA 70E (especially chapters 1 and 2) should always be followed when working on electrical equipment. Maintenance personnel should be trained in the safety practices, procedures and requirements that pertain to their respective job assignments. This instruction manual should be reviewed and retained in a location readily accessible for reference during maintenance of this equipment. The user must establish a periodic maintenance program to ensure troublefree and safe operation. The frequency of inspection, periodic cleaning and a preventive maintenance schedule will depend upon the operation conditions. NFPA publication 70B, "Electrical equipment maintenance" may be used as a guide to establish such a program. Note: A preventive maintenance program is not intended to cover reconditioning or major repair, but should be designed to reveal, if possible, the need for such actions in time to prevent malfunctions during operation.
29
Maintenance
Hazardous voltage and high-speed moving parts. Will cause death, serious injury and property damage. De-energize before working on this equipment. Read instruction manuals, observe safety instructions and use qualified personnel.
Recommended hand tools Metric hardware is used on these circuit breakers. The following list of hand tools describes those normally used in disassembly and reassembly procedures: O pen-end wrenches: 7, 8, 10, 13, 17, 19 and 24 mm O pen-end wrench: 55 mm used to exchange shock absorber (Quantity: two pieces are required for the task) Sockets: 7, 8, 10, 13 and 17 mm S ocket: 36 mm (used for replacing post insulators) Deep sockets: 19 and 24 mm Hex keys: 5, 6, 8 and 10 mm T orque wrench: 0-150 Nm (0-100 ft-lbs) S crewdrivers: 0.032 x 1/4 in wide and 0.055 x 7/16 in wide Pliers Light hammer Dental mirror Flashlight Drift pins: 1/8, 3/16 and 1/4 in R etaining ring plier (external type, tip diameter 0.038 in).
Recommended maintenance and lubrication Periodic maintenance and lubrication should include all the tasks shown in Table 1. Recommended procedures for each of the listed tasks are provided in this section of the instruction manual. The list of tasks in Table 1 does not represent an exhaustive survey of maintenance steps necessary to ensure safe operation of the equipment. Particular applications may require further procedures. Should further information be desired or should particular problems arise that are not covered sufficiently for the User's purposes, the matter should be referred to the local Siemens sales office. Checks of the primary power path The primary power path consists of the three vacuum interrupters, the three upper and the three lower primary disconnects (drawout only) or bus connections (stationary only). These components are checked for cleanliness and condition. The vacuum interrupters are also checked for vacuum integrity. Some test engineers prefer to perform the contact-erosion check during the manual spring-charging check of the operator, since charging of the springs is necessary to place the contacts in the CLOSED position.
30
Maintenance
The use of unauthorized parts in the repair of the equipment, or tampering by unqualified personnel can result in hazardous conditions, that can result in death, serious injury or property damage. Follow all safety instructions contained herein.
Also, the vacuum-integrity check is usually performed in conjunction with the highpotential tests. These instructions assume these tests (contact-erosion/manual spring-charging check and vacuum-integrity/high-potential tests) will be combined as described. Cleanliness check Figure 2 is a side view of the circuit breaker with the insulating barriers removed (if furnished) to show the vacuum interrupter, and the upper and lower connection pads. All of these components must be clean and free of dirt or any foreign objects. Use a dry lint-free cloth. For stubborn dirt, use a clean cloth dipped in isopropyl alcohol (except for the vacuum interrupters). For stubborn dirt on a vacuum interrupter use a cloth and warm water and a small amount of mild liquid-household detergent as a cleaning agent. Dry thoroughly using a dry lint-free cloth. Inspection of flexible connectors Inspect the flexible connectors that connect the bottom movable contacts of the vacuum interrupters to the lower connection pad for tightness and absence of mechanical damage, burning or pitting.
31
Maintenance
Circuit Number of breaker type years/closing operations (whichever comes first)
SDV6 5-years/ 10,000 operations
Checks of the stored-energy operator mechanism The stored-energy operator checks are divided into mechanical and electrical checks for simplicity and better organization. This first series of checks determine if the basic mechanism is clean, lubricated and operates smoothly without control power. The contact-erosion check of the vacuum interrupter is also performed during these tasks. Maintenance and lubrication Table 2 gives the recommended maintenance intervals for circuit breakers. These intervals assume that the circuit breaker is operated under "usual service conditions" as discussed in ANSI/IEEE C37.20.2, section 4 (for drawout circuit breakers) or ANSI/IEEE C37.04, section 4 and elaborated in ANSI/IEEE C37.010, section 4 (for outdoor distribution circuit breakers). The maintenance and lubrication interval is the lesser of the number of closing operations or the time interval since last maintenance. The vacuum interrupter operator mechanism is shown in Figure 20, with the front cover removed to show construction details. Both the opening spring and the closing spring are shown. The movable end of the closing spring is connected to a crank arm. The movable end of the opening spring is connected to the jack shaft by a pull rod. Clean the entire stored-energy operator mechanism with a dry, lint-free cloth. Check all components for evidence of excessive wear. Place special attention upon the closing spring-crank and the insulating couplers and linkages. Lubricate all non-electrical moving or sliding surfaces with a light coat of synthetic grease or oil. Lubricants composed of ester oils and lithium thickeners will be generally compatible.
F or all lubrication (except electrical moving or sliding surfaces), use one of the following: lber Isoflex Topas L32 K (part 3AX11333H) Klber Isoflex Topas L32N (spray) (part 15-172-879-201).
Source: K lber Isoflex Topas L32 or L32N: Klber Lubrication North America L.P. www.klueber.com. Fastener check Inspect all fasteners for tightness. Both locknuts and retaining rings are used. Replace any fasteners that appear to have been frequently removed and replaced. Manual spring-charging and contacterosion checks Perform the manual spring-charging check contained in the section describing the installation check and initial functional tests (refer to pages 9-10). The key steps of this procedure are repeated here: 1. I nsert the hand-charging crank into the manual-charge socket at the front of the operator control panel. Turn the crank clockwise (about 48 revolutions) to charge the closing spring. Continue cranking until the CHARGED flag appears in the window of the spring indicator. 2. P ress the Close (black) pushbutton. The contact-position indicator on the operator control-panel should indicate that the circuit breaker contacts are Closed.
All others
32
Maintenance
Figure 20: Operator mechanism lubrication
33
Maintenance
High-speed moving parts. Can result in serious injury. Tripping spring is charged. If trip latch is moved, the storedenergy springs will discharge rapidly. Stay clear of circuit breaker components that are subject to sudden, high-speed movement.
Figure 21: Contact-erosion check mark dot circled in orange (shown with circuit breaker OPEN)
3. P erform the contact-erosion check. Contact erosion occurs when high fault-currents are interrupted. Determination of acceptable contact condition is checked by the visibility of the white contact-erosion mark shown in Figure 21. The white contact-erosion mark is located on the movable stem of the vacuum interrupter, near the plastic guide-bushing. The contacterosion check procedure is: a) Be sure the circuit breaker primary contacts are Closed. b) O bserve the white contact-erosion mark (refer to Figure 21) of each pole. When any part of the white contact-erosion mark is visible, contact wear is within acceptable limits. 4. P ress the red Open pushbutton after completing the contact-erosion check. Visually verify the Discharged condition of the closing spring and that the circuit breaker contacts are Open. 5. P ress the black Close pushbutton. Nothing should happen. The manualspring check should demonstrate smooth operation of the operating mechanism.
Electrical control checks The electrical controls of the circuit breaker should be checked during inspections to verify absence of any mechanical damage, and proper operation of the automatic spring-charging and Close and Trip circuits. Unless otherwise noted, all of these tests are performed without any control power applied to the circuit breaker. Check of the wiring and terminals 1. P hysically check all of the circuit breaker wiring for evidence of abrasion, cuts, burning or mechanical damage. 2. C heck all terminals to be certain they are solidly attached to their respective device.
34
Maintenance
Hazardous voltage and high-speed moving parts. Will cause death, serious injury and property damage. Do not bypass interlocks or otherwise make interlocks inoperative. Interlocks must be in operation at all times. Read instruction manuals, observe safety instructions and use qualified personnel.
Automatic spring-charging check (control power required) Repeat the automatic spring-charging check described in the section describing the installation check and initial functional tests (refer to pages 9-10). Primary tasks of this check are: 1. T he circuit breaker must be energized with control power for this check. 2. Energize the control-power source. 3. W hen control power is connected to the circuit breaker, the closing spring should automatically charge. Visually verify that the closing spring is charged. Note: A temporary source of control power and test leads may be required if the control-power source has not been connected to the switchgear or circuit breaker. When control power is connected to the circuit breaker, the closing spring should automatically charge. Electrical close and trip check (control power required) A check of the circuit breaker control circuits shall be performed. This check is made with the circuit breaker energized by control power either from the switchgear or an external control-power source.
1. O nce the circuit breaker springs are charged, move the switchgearmounted Close/Trip switch to the Close position. Verify by both the sound of the circuit breaker closing and by the main contact status indicator that the circuit breaker contacts are closed. 2. A s soon as the circuit breaker has closed, the automatic spring-charging process is repeated. 3. A fter a satisfactory close operation is verified, move the switchgear-mounted Close/Trip switch to the Trip position. Verify by both the sound of the circuit breaker opening and by the main contact status indicator that the circuit breaker contacts are open. 4. A fter a satisfactory open operation is verified, hold the circuit breaker manual Trip button and apply and maintain an electrical close signal. The circuit breaker should close, immediately trip, the close spring should charge, and the circuit breaker should not attempt to close again. Completion of these checks demonstrates satisfactory operation of auxiliary switches, internal relays and open and close coils.
35
Maintenance
Table 3: Typical vacuum interrupter contact life expectancy
Graph
29 kA @ 4.76 kV; 36 kA @ 3.85 kV 41 kA @ 4.76 kV; 49 kA @ 4.0 kV 33 kA @ 8.25 kV; 41 kA @ 6.6 kV 18 kA @ 15.0 kV; 23 kA @ 11.5 kV 28 kA @ 15.0 kV; 36 kA @ 11.5 kV 37 kA @ 15.0 kV; 48 kA @ 11.5 kV 21 kA @ 38.0 kV; 35 kA @ 23.0 kV
A E B B A B E B D
Interrupting class kA
Graph
4.76 4.76 4.76 4.76 8.25 15.0 15.0 15.0 15.0 15.0 15.0 15.5 15.5 15.5 15.5 27.6 27.6 38.0 38.0 38.0 38.0
VS-17006 VS-17040 VS-15052 VS-17040 VS-15052 VS-17085 VS-15052 VS-17040 VS-17006 VS-17006 VS-17006 VS-17040 VS-15052 VS-17040 VS-15052 VS-17085 VS-25008 VS-25008 VS-15052 VS-15052 VS-25008 VS-25008 VS-30030 VS-30030 VS-30041 VS-30041
A E B E B F B E A A A E B E B F C C B B C C D D D D
36
Footnote: 1. Maximum symmetrical interrupting current rating of circuit breaker (refer to Tables 11 and 12).
Maintenance
Figure 22: Typical vacuum interrupter contact life curves
Load graph "A" vacuum interrupter type VS-17006 Load graph "C" vacuum interrupter type VS-25008 Load graph "E" vacuum interrupter type VS-17040
200 100 50
20 C 10 1 2 5 10 20 25 31.540 50 100 A E
Breaking current (symmetrical value) Note: Right-hand vertical segment of curve is located at the maximum symmetrical interrupting current rating of the circuit breaker, as indicated in Table 3.
37
Appendix
Figure 22: Typical vacuum interrupter contact life curves (continued)
Load graph "B" vacuum interrupter type VS-15052 Load graph "D" vacuum interrupter types VS-30030 and VS-30041 Load graph "F" vacuum interrupter type VS-17085
200 100 50
20 D 10 1 2 5 10 20 40 50 63 100 B F
Breaking current (symmetrical value) Note: Right-hand vertical segment of curve is located at the maximum symmetrical interrupting current rating of the circuit breaker, as indicated in Table 3.
38
Maintenance
Checks of the spring-charging motor (88.0) No additional checks of the springcharging motor are necessary. If it is necessary to remove or replace the springcharging motor, torque motor-mounting hardware to 7.3-8 ft-lb (10-11 Nm). Anti-pump relay If it is necessary to remove the connections to the anti-pump relay, use care to avoid damaging the relay. Replace the relay if the relay terminals are damaged or loose in the relay body. Vacuum interrupters The life expectancy of vacuum interrupters is a function of the numbers of interruptions and magnitude of current interrupted (refer to Table 3 and Figure 22). The vacuum interrupters must be replaced before the number of mechanical operations (listed in Table 2) are reached, or when the contacts have been eroded beyond allowed limits. Vacuum interrupter replacement procedures are detailed in the following maintenance instructions. The vacuum interrupter contact life curves (refer to Figure 22) are offered as a guide to expected life. Vacuum-integrity check (using mechanical test) (refer to Figure 23) Before putting the circuit breaker into service, or if a vacuum interrupter is suspected of leaking as a result of mechanical damage, check the vacuum integrity either mechanically as described in this section, or alternatively, electrically using a high-potential test set as described in the next section. Open and isolate the circuit breaker and detach the insulating coupler (48.0) from lever (48.6) (refer to Figure 23). The atmospheric pressure will force the moving contact of a hermetically sealed vacuum interrupter into the "Closed" position, causing lever (48.6) to move into the position shown in Figure 23. A vacuum interrupter may be assumed to be intact if it shows the following characteristics: 1. A n appreciable closing force has to be overcome when lever (48.6) is moved to the "Open" position by hand (refer to Figure 23); 2. W hen the lever is released, it must automatically return to the "Closed" position with an audible sound as the contacts touch. After checking the vacuum, reconnect the lever (48.6) to the insulating coupler (48.0) (refer to Figure 23).
High-potential tests employ hazardous voltages. Will cause death and serious injury. Follow safe procedures, exclude unnecessary personnel and use safety barriers. Keep away from the circuit breaker during application of test voltages. Disconnect the split plug jumper from between the circuit breaker and switchgear before conducting high-potential tests.
39
Maintenance
Vacuum interrupters may emit X-ray radiation. Can result in serious injury. Keep personnel more than six feet away from a circuit breaker under test.
High-potential tests The next series of tests (vacuum-integrity test and insulation tests) involve use of high-voltage test equipment. The circuit breaker under test should be inside a suitable test barrier equipped with warning lights. Vacuum-integrity check (using dielectric test) A high-potential test is used to verify the vacuum integrity of the circuit breaker. The test is conducted on the circuit breaker with its primary contacts in the Open position. Vacuum integrity test procedure 1. O bserve safety precautions listed in the danger and warning advisories. Construct the proper barrier and warning light system. 2. G round the frame of the circuit breaker, and ground each pole not under test. 3. A pply test voltage (refer to Table 4) across each pole for one minute (circuit breaker Open). 4. I f the pole sustains the test voltage for that period, its vacuum integrity has been verified.
Note: Do not use dc high-potential testers incorporating half-wave rectification. These devices produce high peak voltages. High peak voltages will produce X-ray radiation. DC testers producing excessive peak voltages also show erroneous readings of leakage current when testing vacuum circuit breakers. High-potential test voltages The voltages for high-potential tests are shown in Table 4. Note: This test includes not only the vacuum interrupter, but also the other insulation components in parallel with the vacuum interrupter. These include the post insulators and the insulating coupler, as well as the insulating (tension) struts between the upper and lower vacuum interrupter supports. If these insulation components are contaminated or defective, the test voltage will not be sustained. If so, clean replace the affected components, and retest.
40
Maintenance
Equipment maximum voltage rating kV
4.76 8.25 15.0 15.5 27.6 38
Table 4: High-potential test voltages
As-found insulation and contact resistance tests As-found tests verify the integrity of the circuit breaker insulation system. Megger* or insulation resistance tests and contactresistance tests conducted on equipment prior to installation provide a basis of future comparison to detect changes in the protection afforded by the insulation system. A permanent record of periodic as-found tests enables the maintenance organization to determine when corrective actions are required by watching for significant deterioration in insulation resistance, or increases in contact resistance. * Megger is a registered trademark of Megger Group, Ltd.
Insulation and contact-resistance test equipment In addition to the high-potential test equipment capable of test voltages as listed in Table 4, the following equipment is also required: A C high-potential tester with test voltage of 1,500 volts, 60 Hz T est equipment for contact-resistance tests.
41
Maintenance
48.0 - Insulating coupler 48.6 - Lever
6. D isconnect the leads to the springcharging motor. 7. F or drawout applications, connect all points of the secondary disconnect with a shorting wire. For stationary applications, disconnect secondary circuits for the operating mechanism by disconnecting the multiple pin-plug at the upper right corner of the operator, and connect all pins on the operator side with a shorting wire. Connect the shorting wire to the highpotential lead of the high-voltage tester, and ground the circuit breaker housing. Starting with zero voltage, gradually increase the test voltage to 1,500 volts rms, 60 Hz. Maintain test voltage for one minute. 8. I f no disruptive discharge occurs, the secondary control insulation level is satisfactory.
48.6
48.0
48.6 48.0
Figure 23: Circuit breaker pole assembly/vacuum-check mechanical/contact-resistance test
9. D isconnect the shorting wire, reattach the multiple pin-plug (if applicable) and reattach the leads to the springcharging motor. 10. P erform contact-resistance tests of the primary contacts. The resistance should be read between the lower and upper connection pads (refer to Figure 23).Contact resistance should not exceed the values listed in Table 5.
Insulation and contact-resistance test procedure 1. O bserve safety precaution listed in the danger and warning advisories for the vacuum integrity check tests (refer to pages 38-39). 2. C lose the circuit breaker. Ground the frame of the circuit breaker, and ground each pole not under test. Use manual charging, closing and tripping procedures. 3. A pply the proper ac or dc (refer to Table 4) high-potential test voltage between a primary conductor of the pole and ground for one minute. 4. I f no disruptive discharge occurs, the insulation system is satisfactory. 5. A fter test, ground both ends and the middle of each vacuum interrupter to dissipate any static charge.
42
Maintenance
Inspection and cleaning of circuit breaker insulation 1. P erform the spring-discharge check (refer to page 9) on the circuit breaker after all control power is removed. The spring-discharge check consists of: a) P ressing the red Open pushbutton b) P ressing the black Close pushbutton c) P ressing again the red Open pushbutton. ll of these controls are on the circuit A breaker front panel (refer to Figure 1). Visually verify the Discharged condition of the springs. 2. R emove any inter-phase and outerphase barriers if furnished (applicable for certain types only). 3. C lean barriers and post insulators using clean cloth dipped in isopropyl alcohol. 4. R eplace all barriers. Check all visible fasteners again for condition and tightness. Note: Do not use any cleaning compounds containing chlorinated hydrocarbons, such as: trichlorethylene, perchlorethylene or carbon tetrachloride. These compounds will damage the phenylene ether copolymer material used in the barriers and other insulation on the circuit breaker. Functional tests Refer to the installation checklist in the installation checks and initial functional tests section of this instruction manual (refer to pages 9-10). Functional tests consist of performing at least three manual spring-charging checks and three automatic spring-charging checks. After these tests are complete, and the springs are fully discharged, all fasteners and connections are checked again for tightness and condition. Current rating A Contact resistance Micro-Ohms
1,200
35
2,000
30
3,000
30
43
Overhaul
Circuit breaker type Closing operations Introduction The following procedures along with the troubleshooting charts in this instruction manual (refer to pages 47-51), provide maintenance personnel with a guide to identifying and correcting possible malfunctions of the circuit breaker. Circuit breaker overhaul Table 6 gives the recommended overhaul schedule type 3AH operating mechanisms. These intervals assume that the circuit breaker is operated under "usual service conditions" as discussed in ANSI/IEEE C37.20.2 section 4 (for drawout circuit breakers) or ANSI/IEEE C37.04 section 4 and elaborated in C37.010 section 4 (for outdoor distribution circuit breakers). If the circuit breaker is operated frequently, the overhaul interval in Table 6 may coincide with the maintenance interval in Table 2. Replacement at overhaul The following components are replaced during an overhaul of the circuit breaker, when required: V acuum interrupters as determined by vacuum integrity test, contact erosion or according to overhaul schedule (refer to Table 6) Close coil, 52SRC Trip coil, 52T T rip-free drive bar mechanism (if applicable). When these parts are changed, locking devices must also be removed and replaced. These include lock washers, retaining rings, retaining clips, spring pins, cotter pins, etc. 1. R eplace vacuum interrupter; instructions follow. 2. Close coil (52SRC) and trip coil (52T). a) R emove two "push on" terminal connections b) Remove two M4 hex-head screws and remove solenoid. c) Install replacement coils with new M4 x 10 hex-head screws (Siemens part # 00-000-443-820) and new lock washers for M4 (Siemens part # 00-000-288-316). d) The coil-mounting screws must be installed using thread locking adhesive (Loctite #222, Siemens part 15-133-281-007) and primer (Loctite primer T (#7471), Siemens part 15-133-281-005). e) Connect wires to coils with new wire terminals (Siemens part # 15-171600-002). 3. L ubricate operating mechanism according to maintenance and lubrication information (refer to page 32). 4. W hen work is finished, operate circuit breaker and close and open several times, and check that all screw connections are tight. Replacement of vacuum interrupters Replacement vacuum interrupters are furnished as a complete assembly. They have been completely tested and dielectrically and mechanically conditioned. It is recommended that one vacuum interrupter be removed and replaced completely rather than removing two or more vacuum interrupters at a time. The following procedure in check list format describes the procedure for removing and replacing a vacuum interrupter. Components may be identified by reference to Figures 24 and 25.
10,000
All others
10,000
44
Overhaul
Instructions herein apply for replacement of all vacuum interrupters except type VS17085 vacuum interrupters, and interrupters on 3,000 A circuit breakers having the flexible connector (refer to 29.1 in Figure 24) electron-beam welded to the moving terminal (refer to 36.1 in Figure 24) of the vacuum interrupter. These interrupters must be replaced by factorytrained personnel. Contact Siemens medium-voltage customer service at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S. 1. Removing the vacuum interrupter 1.4 R emove coupling pin from the eye bolt (36.3). 1.5 F ree struts (28.0) from the pole head (20.0). Loosen the strut hardware on the pole bottom (40.0) and swing the struts forward and downward. 1.6 L oosen screws fastening the centering ring (28.1). 1.7 R emove bolt (31.2), lock washer and large washer at the stationary contact of the vacuum interrupter (18 mm or 24 mm socket with extension). 1.8 U sing a 24 mm socket with an extension, loosen and remove hexcap screw fastening the pole head to the post insulator. Completely remove the pole head and set aside. 1.9 G rasp the vacuum interrupter (30.0) and withdraw vertically. Assistance may be required to work the terminal clamp off the movable stem of the vacuum interrupter. DO NOT USE UNDUE FORCE OR TWISTING MOTION. If the terminal clamp (29.2) cannot be easily removed, STOP!, check to be certain hardware is loose, and that the terminal clamp (29.2) is not binding. 2. Installing a vacuum interrupter
Note: Special care needs to be exercised in removal or installation of hardware around the bottom, or movable contact end, of the vacuum interrupter. The movable contact uses a metal bellows to maintain the vacuum seal while still permitting up and down motion of the contact. The bellows is rugged and reliable, and is designed to withstand years of vertical movement. However, care should be exercised to avoid subjecting the bellows to excessive torque during removal and replacement. Twisting the bellows through careless bolt removal or tightening may damage the vacuum interrupter, resulting in loss of vacuum integrity. 1.1 B efore starting work, the circuit breaker should be isolated from all primary and control-power sources and all stored energy discharged by opening, closing and opening the circuit breaker by hand. Discharge any static charge by grounding both ends and the middle of each vacuum interrupter. Carefully remove outerphase and inter-phase barriers. 1.2 L oosen the lateral bolt(s) on terminal clamp (29.2). Employ the illustrated procedure to loosen clamp hardware (refer to Figure 25). 1.3 W ithdraw pin (48.5) from insulating coupler (48.0) and levers (48.6).
Note: Replacement vacuum interrupter (30.0) will be received from the factory with an eye bolt (36.3) in place, adjusted and torqued to specific requirements. DO NOT ALTER THE ADAPTER (EYE-BOLT) SETTING. 2.1 I nspect all silver-plated connection surfaces for cleanliness. Clean only with a cloth and solvent. Do not abrade, as this will damage the silver plating. 2.2 I nsert vacuum interrupter (30.0) into the lower pole-support (40.0). Slip terminal clamp (29.2) into position on the movable stem. 2.3 A lign vacuum interrupter and fasten "finger tight" using heavy flat washer, lock washer and bolt (31.2).
45
Overhaul
Figure 24: Vacuum interrupter replacement illustration
20.0 - Upper pole-support (pole-head) 28.0 - Strut 28.1 - Centering ring 20.0 31.2 29.1 - Flexible connector 29.2 - Terminal clamp 29.3 - Spacer (or shoulder) 30.0 - Vacuum interrupter 31.2 - Upper terminal-bolt 36.1 - Moving terminal 36.3 - Eye bolt (or adapter) 40.0 - Lower pole-support (pole-bottom) 48.0 - Insulating coupler 28.0 48.5 - Pin 48.6 - Angled lever 48.9 - Drive link 30.0
36.1
28.1 29.3 29.2 29.1 36.3 40.0 48.6 48.5 48.0 48.9 48.9
46
Overhaul
2.4 F asten the pole head to the post insulator (16.1) "finger tight" using hex-head bolt, lock washer and flat washer. 2.5 A ttach struts (28.0) to the upper polesupport (20.0), replace hardware (M10), but do not tighten at this time. 2.6 C ouple levers (48.6) and drive link (48.9) to the eye bolt (36.3), using the pin supplied. Apply retaining clips. Appropriate pin is modestly chamfered, not to be confused with pin for the insulating coupler. 2.7 R aise the terminal clamp (29.2) against the step or the spacer (if applicable) of the moving contact (36.1) of the vacuum interrupter (30.0) so that the radius of the movable contact faces the connecting surface of the flexible connector (29.1). Employ technique illustrated to fasten terminal clamp (refer to Figure 25). Note opposing wrenches. Tighten the bolt(s) of the terminal clamp to a torque of 40 Nm (30 ft-lb), taking care to see that the terminal of the vacuum interrupter is not subjected to excessive bending movement. Note: Excessive bending movement exerted while fastening the terminal clamp will damage the vacuum interrupter. 2.8 A lign pole head (20.0) correctly and tighten bolt fastening it to the post insulator. Torque M16 bolt to 130 Nm (96 ft-lb). Fasten securely all bolts associated with struts (28.0).
Position of torque wrench to avoid undue stressing of moving contact (36.1)
Vacuum interrupter
Figure 25: Illustration showing required technique for fastening terminal-clamp hardware
2.9 T ighten vacuum interrupter fastening bolt (31.2) on the pole head (20.0) holding the vacuum interrupter firmly by its upper insulator and operate levers (48.6), by hand, to see whether the movable contact moves freely. If any binding or lack of freedom is noted, loosen bolt (31.2) and adjust the vacuum interrupter in pole head by turning and moving it slightly. Torque M12 bolt to 60 Nm (44 ft-lb) and M16 bolt to 130 Nm (96 ft-lb). 2.10 The centering ring (28.1) has been loose and "floating" during installation of the vacuum interrupter. Check that the movable contact is free to move vertically without binding, and then tighten the hardware which secures the centering ring. Recheck that the movable contact is free to move vertically without binding.
47
Overhaul
2.11 Attach insulating coupler (48.0) and lever (48.6) together, using pin (48.5). Apply retaining clips. Correct pin has ends that have been generously chamfered. 2.12 Open and close circuit breaker several times and then check to see that all bolted joints and devices are tight. 3. C hecking the contact stroke 4. fter eye bolt is tightened to proper A torque, repeat all measurement procedures, making certain they are in agreement with values indicated in step 3.6. omplete all other maintenance C procedures. Completely reassembled circuit breaker should pass the highpotential test before it is ready for service.
5.
3.1 O pen the circuit breaker. 3.2 F ree insulating coupler (48.0) by removing pin (48.5). The vacuum interrupter contacts must now close automatically as a consequence of atmospheric pressure. 3.3 O bserve the terminal clamp (29.2) through the openings on each side of the pole bottom (40.0). Using vernier calipers, measure the distance from the bottom surface of the terminal clamp to the bottom edge of the cutout opening. Measure carefully and record your result. 3.4 C onnect the insulating coupler (48.0) using pin (48.5) and the retaining clips provided. 3.5 R epeat the measurement described in step 3.3 again with care to maximize accuracy. Record your result. 3.6 D etermine difference between the measurements made under steps 3.3 and 3.5. Your results should be per Table 7. 3.7 I f you fail to achieve the listed results, carefully repeat the entire procedure making certain of your measurements. 3.8 L oosen eye bolt locking nut on insulating coupler (48.0), and retain position of the eye. Make adjustments in one-half turn increments. After adjustment is completed, tighten eye bolt locking nut to 26-34 ft-lb. (35-45 Nm).
Hydraulic shock absorber The mechanism is equipped with a hydraulic shock-absorber that functions when the circuit breaker opens (refer to item 61.8 in Figure 6). The shock absorber should require no adjustment. However, at maintenance checks, the shock absorber should be examined for evidence of leaking. If evidence of fluid leakage is found, the shock absorber must be replaced to prevent damage to the vacuum interrupter bellows.
48
Continuous current A
1,200, 2,000 1,200, 2,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000 1,200, 2,000, 3,000 1,200, 2,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000
Stroke2 mm
7-9 7-9 8.5-9.5 8.5-9.5 7-9 8.5-9.5 7-9 8.5-9.5 18-22
MVA
250 350 500 500 750 1,000 1,500
Continuous current A
1,200, 2,000 1,200, 2,000 1,200, 2,000, 3,000 1,200, 2,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000 1,200, 2,000 1,200, 2,000 1,200, 2,000 1,200, 2,000 1,200, 2,000, 3,000 1,200, 2,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000 1,200, 2,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000 1,200, 2,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000
Stroke2 mm
7-9 7-9 8.5-9.5 7-9 8.5-9.5 8.5-9.5 7-9 7-9 7-9 7-9 7-9 8.5-9.5 7-9 8.5-9.5 10-11 15-16 15-16 8.5-9.5 8.5-9.5 15-16 15-16 18-22 18-22 18-22 18-22
kA
31.5 40 50 40 20 25 31.5 40 50 63 20 25 31.5 40 20 25 20 25 31.5 40
49
Problem
Circuit breaker fails to close.
Symptoms
Closing spring will not automatically charge.
Closing coil or solenoid (52SRC) fails to energize. No sound of circuit breaker closing.
1. S econdary control circuit de-energized or control circuit fuses blown. Correct as indicated. 2. N o closing signal to secondary disconnect pin A2. Check for continuity and correct protective relay logic. 3. S econdary disconnect contacts 13 or 15 are not engaging. Check and correct as required. 4. F ailure of anti-pump relay (52Y) contacts 21 to 22, 31 to 32 or 13 to 14. Check and replace as required. 5. F ailure of close coil (solenoid) (52SRC). Check and replace as required. 6. A uxiliary switch NC contacts 41 to 42 are open when circuit breaker contacts are open. Check linkage and switch. Replace or adjust as necessary.
Closing coil energizes. Sound of circuit breaker closing is heard, but circuit breaker contacts do not close.
1. M echanical failure of operating mechanism. Check and contact the factory or Siemens field service at +1 (800) 3476659 or +1 (919) 365-2200 outside the U.S.
50
Problem
Nuisance or false close
Symptoms
Electrical problem
Mechanical problem
1. M echanical failure of operating mechanism. Check and contact the factory or Siemens field service at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S. 1. S econdary control power is deenergized or control power fuses are blown. Correct as indicated. 2. D amage to wiring, terminals or connectors. Check and repair as necessary. 3. N o tripping signal to secondary disconnect contact C2. Check for continuity and correct protective relay logic. 4. S econdary multi-pin plug contacts C1 or D2 are not engaging. Check and replace if required. 5. F ailure of trip coil (52T). Check and replace if necessary. 6. A uxiliary switch 52a NO contacts 23 to 24 or 33 to 34 are open when circuit breaker is closed. Check linkage and switch. Replace or adjust as necessary.
Tripping coil or solenoid (52T) does not energize. There is no tripping sound.
Tripping coil (52T) energizes. No tripping sound is heard, and circuit breaker contacts do not open. In other words, they remain closed. Tripping coil (52T) energizes. Tripping sound is heard, but circuit breaker contacts do not open.
1. F ailure of tripping spring or its mechanical linkage. Check and replace if required. 1. M echanical failure of operating mechanism. Check and contact the factory or Siemens field service at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S. 2. O ne or more of the vacuum interrupters are held closed. Check and replace as necessary.
51
Problem
Nuisance or false trip
Symptoms
Electrical problem
Mechanical problem
1. M echanical failure of operating mechanism. Check and contact the factory or Siemens field service at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S.
52
Appendix
Table 9: Circuit breaker control data
Close coil
Trip coil
Range Trip
14-28 28-56 70-140 140-280 104-127 208-254
Charging Seconds
---10 10 10 10 10
A1
5.7 11.4 2.1 2.1 2.0 2.0
A1
15/---11.4/303 4.8/7.43 4.2/9.63 ----2 ----2
A
---8 4 2 6 3
urrent at nominal voltage C apacitor trip C Value preceding slash (/) is the current for
the standard trip coil with standard rating interrupting time. Value following (/) is current for optional trip coil with three-cycle interrupting time.
4.
48 Vdc
10/301 10
125 Vdc
9.6 6
250 Vdc
4.8 3
10 10
10 6
53
Appendix
These ratings are in accordance Table 11: Type 3AH vacuum circuit breaker ratings (new "constant kA" ratings basis) with: A NSI/IEEE C37.04-1999 Standard Rating Structure for AC High-Voltage Circuit Breakers A NSI/IEEE C37.06-2009 AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis - Preferred Ratings and Related Required Capabilities for Voltages Above 1,000 Volts A NSI/IEEE C37.09-1999 Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis A NSI/IEEE C37.010-1999 Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis.
Footnotes:
1.
Continuous current7
Short-circuit (I)3,4
Power frequency kV rms 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 19 19 19 19 36 36 36 36 36 36 36 50 50 50 50 60 60 80 80 80 80
Lightning impulse (BIL) kV crest 60 60 60 60 95 95 95 95 95 95 95 110 110 110 110 150 150 150/2006 150/2006 150/2006 150/2006
A rms
kA rms sym
5-3AH-31.5 5-3AH-40 5-3AH-50 5-3AH-63 7-3AH-40 15-3AH-20 15-3AH-25 15-3AH-31.5 15-3AH-40 15-3AH-50 15-3AH-63 15.5-3AH-20 15.5-3AH-25 15.5-3AH-31.5 15.5-3AH-40 27-3AH-20 27-3AH-25 38-3AH-20 38-3AH-25 38-3AH-31.5 38-3AH-40
4.76 4.76 4.76 4.76 8.25 15.0 15.0 15.0 15.0 15.0 15.0 15.5 15.5 15.5 15.5 27.6 27.6 38.0 38.0 38.0 38.0
1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000 1,200, 2,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000 1,200, 2,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000 1,200, 2,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000
2.
3.
4.
5.
6.
7.
54
Appendix
Interrupting time5
% dc component
ms/cycles
Peak (2.6 x I) kA peak 82 104 130 164 104 52 65 82 104 130 164 52 65 82 104 52 65 52 65 82 104 5-3AH-31.5 5-3AH-40 5-3AH-50 5-3AH-63 7-3AH-40 15-3AH-20 15-3AH-25 15-3AH-31.5 15-3AH-40 15-3AH-50 15-3AH-63 15.5-3AH-20 15.5-3AH-25 15.5-3AH-31.5 15.5-3AH-40 27-3AH-20 27-3AH-25 38-3AH-20 38-3AH-25 38-3AH-31.5 38-3AH-40
55
83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5 83/5
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47
Appendix
Table 12:Type 3AH vacuum circuit breaker ratings (historic "constant MVA" ratings basis)
These ratings are in accordance with: A NSI/IEEE C37.04-1979 Standard Rating Structure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis A NSI C37.06-1987 AC HighVoltage Circuit Breakers Rated on a Symmetrical Current Basis - Preferred Ratings and Related Required Capabilities A NSI/IEEE C37.09-1979 Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis A NSI/IEEE C37.010-1979 Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis.
Nominal Nominal Maximum voltage threedesign class phase voltage MVA (V)1 class7
Continuous current11
kV
MVA
kV rms
A rms
----
5-3AH-250
4.16
250
4.76
1,200, 2,000
1.24
19
5-3AH-350
4.16
350
4.76
1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000 1,200, 2,000, 3,000
1.19
19
60
7-3AH-500
7.2
500
8.25
1.25
36
95
15-3AH-500
13.8
500
15.0
1.30
36
95
15-3AH-750
13.8
750
15.0
1.30
36
95
15-3AH-1000
13.8
1000
15.0
1.30
36
95
38-3AH-1500
38.0
1,500
38.0
1,200, 2,000
1.65
80
150
Footnotes:
1.
3.
To obtain the required symmetrical interrupting capability of a circuit breaker at an operating voltage between 1/K times rated maximum design voltage and rated maximum design voltage, the following formula shall be used: Required symmetrical interrupting capability = rated short-circuit current (I) x [(rated maximum design voltage)/(operating voltage)]. For operating voltages below 1/K times maximum design voltage, the required symmetrical interrupting capability of the circuit breaker shall be equal to K times rated short-circuit current.
Maximum design voltage for which the circuit breaker is designed and the upper limit for operation.
2.
K is the ratio of the rated maximum design voltage to the lower limit of the range of operating voltage in which the required symmetrical and asymmetrical interrupting capabilities vary in inverse proportion to the operating voltage.
4.
Within the limitations stated in ANSI/IEEE C37.04-1979, all values apply to polyphase and line-to-line faults. For single phase-to-ground faults, the specific conditions stated in clause 5.10.2.3 of ANSI/IEEE C37.04-1979 apply.
56
Appendix
Shortcircuit (at rated maximum design voltage) (I)3, 4, 8
kA rms sym
Interrupting time9
ms / cycles
Sec
kA rms sym
kA rms
29
83 / 5
3.85
36
36
41
83 / 5
4.0
49
49
78
132
5-3AH-350
33
83 / 5
6.6
41
41
66/7710
111/13010
7-3AH-500
18
83 / 5
11.5
23
23
37/5810
62/9710
15-3AH-500
28
83 / 5
11.5
36
36
58/7710
97/13010
15-3AH-750
37
83 / 5
11.5
48
48
77
130
15-3AH1000 38-3AH1500
21
83/5
23.0
35
35
56
95
5.
Current values in this row are not to be exceeded even for operating voltage below 1/K times rated maximum design voltage. For operating voltages between rated maximum design voltage and 1/K times rated maximum design voltage, follow Footnote 5.
9.
S tandard rating interrupting time is five-cycles (83 ms). Optional rated interrupting time of three-cycles (50 ms) is available (except with 24 Vdc tripping). High close and latch (momentary) rating available for special application. Continuous current may be increased by the use of forced-cooling (fan-cooling) in the switchgear, together with increased bus bar capacity.
10.
6.
Current values in this row are independent of operating voltage up to and including rated maximum voltage.
11.
7.
"Nominal three-phase MVA class" is included for reference only. This information is not listed in ANSI C37.06-1987.
8.
57
Appendix
Table 13: Type 3AH vacuum circuit breaker weight in lbs (kg) (circuit breaker operator only)
2,000 A
264 (120) 268 (122) 363 (165) 268 (122) 257 (117) 257 (117) 264 (120) 268 (122) 363 (165) 278 (126) 298 (131) 313 (142) 324 (147) 291 (132) 302 (137) 375 (170) 375 (170) 385 (175) 397 (180)
3,000 A
---390 (177) 396 (180) 390 (177) ---------390 (177) 396 (180) ------385 (175) 390 (177) ------386 (175) 386 (175) ---408 (185)
4.76 4.76 4.76 8.25 15.0 15.0 15.0 15.0 15.0 15.5 15.5 15.5 15.5 27.6 27.6 38.0 38.0 38.0 38.0
Footnote:
1.
58
Appendix
Table 14: Circuit breaker operating times (type 3AH3 operator)
Spring charging time Close time from energizing close coil at rated control voltage to contact touch (last pole) Up to 15.5 kV Over 15.5 kV up to 27.6 kV Over 27.6 kV up to 38 kV Up to 15.5 kV Over 15.5 kV up to 27.6 kV Over 27.6 kV up to 38 kV Up to 15.5 kV Over 15.5 kV up to 27.6 kV Over 27.6 kV up to 38 kV Up to 15.5 kV Over 15.5 kV up to 27.6 kV Over 27.6 kV up to 38 kV
10 s 55 ms 65 ms 70 ms 56 ms 56 ms 56 ms 43 ms 43 ms 43 ms 38 ms 38 ms 38 ms
5-cycle interrupting time (83 ms) Opening time from energization trip coil at rated 3.5-cycle interrupting time control voltage to contact part (58 ms) (last pole), not including arcing time 3-cycle interrupting time (50 ms)
59
Published by and copyright 2010: Siemens AG Energy Sector Freyeslebenstrasse 1 91058 Erlangen, Germany Siemens Energy, Inc. 7000 Siemens Road Wendell, North Carolina 27591 USA For more information, contact +1 (800) 347-6659 Order No. E50001-F710-A251-X-76US Replaces No. E50001-F710-A251-X-4A00 Printed in USA
All rights reserved. Trademarks mentioned in this document are the property of Siemens AG, its affiliates or their respective owners. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract.