Ccum 21

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

PROTECTION

CCUM 21
Reverse Power Relay

CCUM 21 definite time reverse power relay provides a sensitive and economical means of detecting motoring conditions in diesel alternators and back pressure turbines. Faster clearance time can be obtained for lower values of reverse power than that are possible with inverse definite minimum time delay relays.

Features
High speed directional element. Robust construction of less than 3% rated single phase power. Wide range of definite time settings. Consistent timing. Comprehensive range of auxiliary unit ratings. Drawout case and tropicalised finish.

Technical data
Ratings Current 1A or 5A at 50 Hz. Voltage 110V at 50 Hz. Thermal rating Continuous 2 x rated current at 110% Rated voltage Short time 20 x rated current for 3 seconds. Maximum torque angle 30 when connected as shown in Figure1 (applied voltage lagging applied current. This corresponds to Unity Power Factor in the system). Sensitivity About 1% of rated voltage with 1 to 15 times rated current or 3% of rated voltage with 0.4 to 40 times rated current. Nominal power setting less than 3% of rated single phase power. AC burdens Current circuit : 1VA at rated current. Voltage circuit : 9VA at rated voltage. Operating time 1-10 seconds as standard. Other time ranges: 0.5 - 5s, 2.5 - 25s, 6 - 60s and 12 - 120s.

Application
Type CCUM 21 definite time reverse power relay provides a sensitive and economical means of detecting motoring conditions in diesel alternators and back pressure turbines. Faster clearance time can be obtained for lower values of reverse power than that are possible with inverse definite minimum time delay relays.

Description
Basically relay type CCUM is a high speed induction cup unit (type CCD). The cup contact initiates a static timing unit (type VTT) which provides the output contacts for alarm and trip functions. Typical external and internal connections are shown in Figure 1 Customer Benefits Economial means of detecting motoring conditions. Robust construction. Faster fault clearance. Draw out feature

AREVA T&D

Case 1D vertical draw out case suitable for flush mounting. Finished eggshell black and tropicalised. Suitable trip isolating switches, CT shorting switches, and provision for maintaining the under voltage trip circuits on withdrawal of the relay unit from the case, are provided on the cradle assembly/case.

CCUM 21 relay withdrawn from case

Figure 1: Typical external and internal connections for type CCUM 21 relay Dimensions Width

Case

Height

Depth*

1D

362 mm

170 mm

203 mm

*Add 76 mm for maximum length of terminal studs, alternatively, 29 mm for terminal screws.

Contact ratings Current Make and carry Make and carry continuously for 3 seconds Break

AC

1250VA with maxima of 5A and 660V

7500VA with maxima of 30A and 660V

1250VA with maxima of 5A and 660V

DC

1250W with maxima of 5A and 660V

7500W with maxima of 30A and 660V

100W (resistive) 50W (inductive) with maxima of 5A and 660V

2>3

Auxiliary supply 30, 110, 220V dc Standard. 220, 250V 50 Hz ac can be given. Operates satisfactorily between 75 - 120% of rated volts (dc) and 80 - 115% of rated volts (ac). Auxiliary burden Approx. 1.26, 4.46, 9.1 watts for 30, 110, 220 volts dc respectively. Approx. 2.3VA for ac auxiliary supply.

Contacts 2 pairs (S/R) in any combination of normally open and normally closed. Operation indicator Hand reset mechanical operation indicator provided on timer unit. Insulation The relay meets the requirements of IS 3231, IEC-255-5 series C-2 KV for 1 minute. Information required with order 1. 2. 3. 4. Current rating. Operating time range. Contact combination. Auxiliary supply.

AREVA T&D Pallavaram Works 19/1, G.S.T. Road, Pallavaram, Chennai - 600 043 Tel: 91-44-2264 8000 Fax: 91-44-2264 0040
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature. This brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advise on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

AREVA T&D Worldwide Contact Centre:

http://www.areva-td.com/contactcentre/
Tel.: +44 (0) 1785 250 070

www.areva-td.com

MiCOM is a registered trademark of AREVA.All trade names or trademarks mentioned herein whether registered or not, are the property of their owners.

AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA

You might also like