2-A Simplified Three Phase PWM Rectifier With Fixed Frequency Modulation
2-A Simplified Three Phase PWM Rectifier With Fixed Frequency Modulation
2-A Simplified Three Phase PWM Rectifier With Fixed Frequency Modulation
Figure 1. Three- Phase PWM Rectifier Feeding an R-L load
II. PROPOSED CONTROLLER
A novel current control strategy is proposed for a three-
phase voltage source boost PWM rectifier to accomplish the
constant and reduced switching frequency for all the legs
with unity input power factor; thus allowing the user to
directly set the switching frequency of the switches of all the
legs. This simplified control scheme doesnt need additional
computation, circuitry or modulation.
A three phase PWM rectifier feeding an R-L load is
shown in Fig. 1. The dc voltage V
c
is measured and is
compared with the reference voltage V
ref
, which is fed to a PI
controller (G) to obtain the magnitude of the reference
source currents. Synchronization is done for getting the
correct phase information.
Fig. 2 shows the block diagram of the proposed current
controller. The current error signals are generated for the legs
a and b by comparing the source currents with their
respective reference currents. Then the hysteresis controller
determines the appropriate switching signals A1, A2, B1 and B2
to track the source currents within a specified hysteresis band.
Tracking of leg-c is avoided by providing a switching pulse
of fixed user-defined frequency with 50% duty cycle and its
complement to C1 and C2. These switching generate and
control the zero vector states and thus a reduced and constant
switching frequency is obtained for all the legs.
The zero vector (uncontrollable) states occur when all
the top/bottom switches attain the same status i.e. the
condition when all top switches A1, B1 and C1 are ON is
called as zero vector 1 (ZS1) and bottom switches A2, B2
and C
2
are ON is taken as uncontrollable 0 (ZS0). Under such
conditions, the dc link capacitor gets effectively
disconnected from the circuit. Thus, there is no control over
the current synthesis during such periods. But the constant
switching frequency method is intended to bring out the
latent potential of the zero vector states. During every
switching cycle the zero vector states ZS1 and ZS0 are
forced upon the converter to maintain reduced and constant
switching frequency. The duty cycles are allowed to vary
over the switching cycles to obtain constant switching
frequency. Thus the user can indirectly control the duration
and occurrence of these zero vector states.
A1
A2 THREE
B1 PHASE
B2
PWM
C1
RECTIFIER
C2
+
-
isaref
isa
+
-
isbref
isb
User
Defined
Pulse
Figure 2. Block Diagram of the Proposed Controller
Volume 5
85
III. SWITCHING PERFORMANCE PARAMETERS
The performance of the current controller is assessed
using some performance indices defined below.
1) Total average switching frequency
The total average switching frequency, f
av_total
is defined
as
_
, ,
av total
k
k a b c
N
T
f
_
(1)
where Nk is the number of switching cycles in leg-k
during one cycle period T of the system voltage.
2) Switching frequency Deviation Index
The switching frequency deviation index (DI) for any
leg-k is defined as
2
_ _
2
_
( )
( )
k inst k av
k
k k av
DI
f f
N f
-
-
_
for k=a, b, c (2)
where f
k_inst
and f
k_av
are the instantaneous and average
switching frequencies and N
k
is the number of switching
cycles in the leg -k during one power cycle. DI indicates the
constancy in switching frequency and a very low value of DI
is desirable.
3) Percentage Total Harmonic Distortion
The percentage total harmonic distortion indicates the
quality of source current and a value of less than 5% is
desirable.
IV. SIMULATION RESULTS
The simulation is carried out on a three-phase PWM
rectifier feeding an R-L load using PSCAD 4.2.1. The
performance of proposed controller is compared with
conventional hysteresis controller. In a conventional
hysteresis controller, all the three legs of the rectifier are
tracked in hysteresis current tracking mode. Table I shows
the system parameters chosen for simulation. An ac grid
voltage of 100V is provided as input with a source
impedance of 6+j2.826 O . An R-L load of 800+j31.4 O
with an output capacitance of 100
F
is given at the DC
side and a PI controller of proportional and integral gain of
K
p
=0.54 and K
i
=1 is used to obtain the correct magnitude of
reference current. A square pulse of 2.5 kHz is given as
switching signal for the third leg and a fixed bandwidth of
h=8% is provided for other two legs.
TABLE I. SYSTEM PARAMETERS
AC Grid Voltage
100V
Source Impedance
6+j2.826 O
Load parameters
R-L load : 800+ j31.4 O
DC link reference
voltage
430V
PI Controller
Kp= 0.54, Ki=1
Hysteresis Band
8%
Switching frequency to
leg-c
2.5 kHz (For proposed control)
Fig. 3 shows the simulated waveforms of source currents
for the proposed current control. While analysing the
simulation results, the new approach has very low harmonic
distortion. Fig. 4 (a) and (b) shows the instantaneous and
average switching frequency for leg-a, leg-b and leg-c using
conventional hysteresis controller and proposed constant
switching frequency method respectively. In the
conventional hysteresis controller the instantaneous
switching frequency deviates from the average value to a
large extent. In the proposed controller, switching frequency
of all the three legs are constant and is equal to user-defined
value of 2.5 kHz .
0.420 0.425 0.430 0.435 0.440
.
.
.
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
Isa Isb Isc
C
u
r
r
e
n
t
(
A
)
Time (s)
Figure 3. Source currents - Proposed Control
Volume 5
86
0.4950 0.5000 0.5050 0.5100 0.5150 0.5200
0.0
2.5k
5.0k
7.5k
10.0
fa_ins fa_av
0.0
2.5k
5.0k
7.5k
10.0
fb_ins fb_av
0.0
2.5k
5.0k
7.5k
10.0
fc_ins fc_av
F
r
e
q
u
e
n
c
y
(
k
H
z
)
Time (s)
0.3950 0.4000 0.4050 0.4100 0.4150 0.4200
0.0
2.5k
fa_ins fa_av
0.0
2.5k
fb_ins fb_av
0.0
2.5k
fc_ins fc_av
F
r
e
q
u
e
n
c
y
(
k
H
z
)
Time (s)
(a) (b)
Figure 4. Instantaneous and Average Switching Frequency (a) Conventional Hysteresis (b) Proposed Controller
A closer view of switching pulses of upper switches A1,
B1 and C1 of the three-phase converter is presented in Fig. 5.
At time t=0.106507s the converter is trapped into zero vector
state ZS1. But due to the user defined square pulse at third
leg, the converter is able to break ZS1 state at t=0.1066 s.
One by one all the other two legs will attain a status 0, so
that converter is again trapped into ZS0 at time t=0.106723 s.
But that state is again broken at t=0.1068 s. Thus, a control
over the uncontrollable state is obtained.
Switching pulses
0.1062 0.1064 0.1066 0.1068
0.0
1.0
2.0
A1
0.0
1.0
2.0
B1
0.0
1.0
2.0
C1
Time ( s )
Figure 5. Switching signals-a Snapshot
The ac phase voltage and current waveforms in Fig. 6
indicate the unity input power factor operation of proposed
scheme. Fig. 7 shows that the output dc voltage is regulated
and it follows the reference voltage command of 430V.
0.300 0.310 0.320 0.330 0.340
-100
-75
-50
-25
0
25
50
75
100
Isa Ea
V
o
l
t
a
g
e
(
V
)
/
C
u
r
r
e
n
t
(
A
)
Time (s)
Figure 6. AC phase Voltage and Current Waveforms
0.00 0.20 0.40 0.60 0.80
0
100
200
300
400
500
Edc
V
o
l
t
a
g
e
(
V
)
Time (s)
Figure 7. DC Output Voltage
Volume 5
87
TABLE II. PERFORMANCE INDICES
Average Switching Frequency (kHz)
_ av total f
(kHz)
Deviation Index (DI) %THD
Phase a Phase b Phase c isa isb isc
Phase a Phase b Phase c
Conventional Hysteresis
3.023
2.975
2.987
8.985
1.11
1.12
1.16
3.02
2.77
2.97
Proposed Control
2.5
2.5
2.5
7.5
0.0094
0.0090
0.0
0.3628
0.3847
0.728
Table II verifies the better performance of proposed
strategy compared to the conventional hysteresis control.
The switching frequency of all the three legs is varying
between 0.254 kHz and 7.142 kHz in conventional fixed
band hysteresis control. But in the proposed scheme, by
giving a fixed square pulse of 2.5 kHz, the other two legs
follow the same switching frequency. So, a total of 7.5
kHz is obtained as _ av total f , i.e. a reduction of about 1.485
kHz is obtained in the proposed method, which is an added
advantage while concerning the switching losses. The
parameter, switching frequency deviation index (DI),
which is an indication of constancy in switching frequency,
is obtained as a very low value for the simplified scheme
compared to hysteresis method. A very low value
of %THD is obtained for this constant switching frequency
scheme, compared to the conventional control, which
indicates the good quality of source current of PWM
rectifier.
Thus, the simulated waveforms verify the better
performance of the proposed scheme i.e. the constant and
reduced switching frequency is achieved without any
additional circuitry or complexity.
V. CONCLUSIONS
A simplified fixed frequency modulation for a three-
phase PWM rectifier is described in this paper. The
performance of the proposed controller is compared with
conventional hysteresis controller and is found to be very
beneficial. It overcomes the drawbacks of hysteresis
controller while retaining its merits as such, without any
additional computation or complexity. The existing
constant switching frequency schemes are quite
complicated in operation and hardware. But in this
approach, constant and reduced switching frequency is
achieved by controlling the happening and duration of
zero vector states indirectly. The power factor of nearly
unity and low harmonic distortion are the main attraction
of this scheme. The simulation studies validate the
efficacy of the proposed scheme over the conventional
controller.
REFERENCES
[1] Boon-Teck Ooi, Juan W. Dixon and Asok B. Kulkarni,
An integrated AC drive system using a controlled
current
PWM rectifier/inverter link, IEEE Trans. Power Electronics,
vol. 3, no. 1, jan 1994.
[2] M. A. Rahman, T. S. Radwan, A. M. Osheiba, and A. E.
Lashine, Analysis of current controller for voltage source
inverter, IEEE Trans. Industrial Electronics, vol. 44, no. 4,
pp. 477-485, Aug. 1997.
[3] D. M. Brod and D. W. Novotny, Current control of VSI-
PWM inverters, IEEE Trans. on Industrial Appications, Vol.
1A-21, No. 4, pp. 562-570, May/June 1985
[4] J. Holtz, Pulse width Modulation A survey, IEEE
Transactions on. Industrial Electronics, vol. 39, no. 5, pp.
410-420, Dec. 1992.
[5] Juan W. Dixon and Boon-Teck Ooi, Indirect Current
Control of a Unity Power Factor Sinusoidal Current Boost
Type Rectifier, IEEE Trans. Industrial Electronics, vol. 35,
no. 4, pp. 508-515, Nov. 1988.
[6] Zhang, R. , Prasad, V. H., Boroyevich, D., and Lee, F. C.,
Three-dimensional space vector modulation for four leg
voltage-source converters, IEEE Trans. Power Electronics,
vol. 17, no. 3, pp. 314-326, May 2002.
[7] Marian P. Kazmierkowski, Maciej A. Dzieniakowski, and
Waldemar Sulkowski, Novel Space Vector Based Current
Controllers for PWM-Inverters, IEEE Trans. Power
Electronics, vol. 6, no. 1, Jan 1991.
[8] Bong-Hwan Kwon, Tae-Woo Kim, and Jang-Hyoun Youm,
A Novel SVM-Based Hysteresis Current Controller,
IEEE Trans. Power Eletronics, vol. 13, no. 2, March 1998.
[9] L. Malesani and P. Tenti, A novel hysteresis control method
for current-controlled voltage-source PWM inverters
with constant modulation frequency, IEEE Trans. Industrial.
Appications, vol. 26, Jan. 1990.
[10] S. Buso, L. Malesani, and P. Mattavelli, Comparison of
current control techniques for active power filter applications,
IEEE Trans. Industrial Electronics, vol. 45, no. 5, pp. 722-
729, Oct. 1998.
[11] M. P. Kazmierkowski and L. Malesani, Current control
techniques for three-phase voltage-source PWM converters:
a survey, IEEE Trans. Industrial Electronics, vol. 45, no. 5,
pp. 691-703, Oct. 1998
[12] V. George, Mahesh K. Mishra and S. Sridharan, A novel
constant frequency strategy for a three-leg DSTATCOM,
in Proc. 21st Canadian Conference on Electrical and
Computer Engineering, Niagara Falls, Canada, May, 2008, pp.
681-684.
[13] V. George and M.K. Mishra, User-defined constant
switching frequency current control strategy for a four-leg
inverter, IET Power Electron., 2009, Vol. 2, Iss. 4,
pp. 335345.
Volume 5