Specifications Manual: Tcs-Net Modbus
Specifications Manual: Tcs-Net Modbus
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
Model name:
TCB-IFMB640TLE
Contents
1 System Overview....................................................................................................................... 2 2 RS 485 Communication Parameters ......................................................................................... 3 3 Applied Function Codes............................................................................................................. 3 4 Exception Response.................................................................................................................. 4 5 Counters and Registers ............................................................................................................. 4 6 Sequence................................................................................................................................... 5 7 Address Assignment Table........................................................................................................ 6 8 Appendix.................................................................................................................................. 15
Specifications Manual
System Overview
This manual describes Modbus* protocol implementation specifications of TCB-IFMB640TLE. TCB-IFMB640TLE is equipped with the Modbus Slave function. Specifications that are not detailed in this manual conform to the following MODBUS specifications. MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b MODBUS over Serial Line Specification and Implementation Guide V1.01 http://www.modbus-ida.org/ This implementation specification specifies the operation of Modbus that works on the RS485 serial line, where a slave device sends a response to a request from the master device. Multiple slave devices are connected to the RS485 bus. Modbus uses the Modbus RTU mode with the frame format shown below.
START >=3.5 characters SLAVE ADDRESS 8 bits FUNCTION 8 bits DATA CRC END >= 3.5 characters N*8 bits (N = 252 max.) 16 bits
Each slave device is connected to the TCC-LINK main bus. The internal data and operation of indoor units and TCB-IFCG1TLE units (general purpose interface) to which central addresses 1 to 64 are assigned are controlled by the master device. Up to 15 slave devices may be connected to the master device. A broadcast message will be sent when the slave address 0x00 is specified in a request, and all slave devices will receive the request but send no response including exception response. The figure below shows an example of the connection of the master device, slave devices, and air conditioners.
Terminator A Terminator A B
TCB-IFMB640TLE
Modbus-Master
B
Modbus-I/F Slave 1
U1 U2 TCC-LINK Bus
INDOOR/OUTDOOR TCB-IFCG1TLE
RS-485 Bus
TCB-IFMB640TLE
A
Modbus-I/F Slave 2
B U1 U2 TCC-LINK Bus
INDOOR/OUTDOOR TCB-IFCG1TLE
TCB-IFMB640TLE
A
Modbus-I/F Slave N
B U1 U2 TCC-LINK Bus
INDOOR/OUTDOOR TCB-IFCG1TLE
N = Max. 15
2 (EN)
Specifications Manual
RS 485 communication parameters are shown below. Character length = 11 bits, Data = 8 bits, Parity Check = even, Start bit =1 bit low, Stop bit = 1bit high Communication: 9600/19200/38400 bps (default: 19200 bps) Selected manually. Bit transmission order: LSB first (b0, b1.). Bit data is transmitted sequentially from the LSB. Byte transmission order: Big Endian. 0x1234 -> 0x12 then 0x34. Byte data is transmitted in the big endian order. Half duplex, 2 wires. 120 termination. A: Non-inverted input, B: Inverted input After receiving a packet, a response is permitted after at least 3.5 characters. Connecter: 2 terminals
3
0x01 0x02 0x03 0x04 0x05 0x06 0x08 0x0B 0x0C 0x0F 0x10
The relationship between the start address specified in a request from the master device and the value shown by Modbus-address for registers in the address assignment table is as follows: For Coil Start address = (Value of Modbus-address for registers) - 1 For Discrete input Start address = (Value of Modbus-address for registers) - 10001 For Input register Start address = (Value of Modbus-address for registers) - 30001 For Holding register Start address = (Value of Modbus-address for registers) - 40001
3 (EN)
Specifications Manual
4
0x01 0x02
Exception Response
Except for Broadcast, the master device issues a request expecting a normal response from a slave device. Slave units return a normal response when no error is detected, but return no response when an error occurs during the parity check or CRC check. Slave units must return an exception response when they receive a request which has been sent correctly but contains an error that applies to any of the following exception codes.
Exception code Name Illegal function A request of illegal function that is not supported by this specification is received Illegal data address An illegal address that does not exist in section 7 of this manual. Address Assignment table or a data request size larger than 249 octets is specified. Illegal data value Illegal data in any of the following cases: 1) When data other than that defined in section 7 of this manual Address Assignment table is specified. 2) When Broadcast (slave address = 0) is specified with a function code other than 0x05, 0x06, 0x0F, 0x10 3) When an address is specified for two or more devices Slave device failure Slave device internal processing is not correct (When any error occurs during booting or reading the RAM). ACK A slave device returns response ACK when it received a request while it is acquiring response data during the slave device initial data acquisition process. Slave device busy When a slave device is busy and cannot return response data, this code is returned. When a masters request is about an indoor unit which does not respond to the request. (However, the masters request is sent to the indoor unit.)
0x03
0x04 0x05
0x06 0x07
TCB-IFMB640TLE is equipped with the following counters and registers that are cleared by a power-on reset, restart process, or a counter reset command.
Register/Counter Coils (R/W) Discrete input (R) Input register (R) Holding register (R/W) Event counter Message counter Diagnostics register
Bus Communication Error Count Exception Error Count Slave Message Count No Response Count Busy Count Bus Character Overrun Count
4 (EN)
Specifications Manual
Sequence
The master device sends a request sequentially to each slave device, and gets response data from each slave device. A slave device returns a response to a request from the master device within one second (see the diagram below). When a slave device receives a data read request, the slave device returns the data stored in the register. It is recommended that the master device collects specific information such as air conditioner models, addresses, unique numbers, and operation setting range when the master device accesses the air conditioning system for the first time. When writing to air conditioners, the master device must read the operation range for, operation mode, fan speed and setting temperature from each air conditioner and write values within the operation range. Pay attention to the sequence of simultaneous setting for writing to air conditioners because it requires time for processing on the slave device side. Furthermore, because no response or exception response with respect to the writing for broadcast message is sent from slave devices, it is recommended that data written to slave devices be checked on the master device side as required. It is recommended to confirm whether a masters request is reflected by reading the read register after appropriate time once a communication is completed, because indoor units may not be able to receive a normal request from the mater due to TCC-LINK communication condition. In addition, it is also recommended that data be requested at appropriate intervals so that the alarm data that is output from air conditioners is properly reflected in the discrete input register.
Master
Indoor #1 request Indoor #1 response Indoor #2 request Indoor #2 response
Slave 1
Slave 2
Slave 3
Slave N
..
Indoor #64 request Indoor #64 response Indoor #1 request Indoor #1 response
5 (EN)
Specifications Manual
Total 42368 octets (9728*2/8 + 9984*2*2). The data of the address assignment table is cleared during initialization.
Modbusdescription Coills (R/W)
17-24
1 octet
25-32
Louver setting
1 octet
33-40
1 octet
41-48
Relay 1ch output for TCB-IFCG1TLE Relay 2ch output for TCB-IFCG1TLE Relay 3ch output for TCB-IFCG1TLE Relay 4ch output for TCB-IFCG1TLE Reserved
1 octet
49-152 2 153-160
104bit 1 octet
161-168
1 octet
21
0x00= unfix,0x 01= heat,0x 02= cool,0x 03= dry 0x 04= fan ,0x05 auto (address=161 LSB ,address= 168MSB) 0x00=Invalid,0x01=Fan Sop,0x02=Auto,0x03=High,0x04=Medium,0x05= Low,0x06=Ultra Low,0x07=unfix (address=169 LSB,address=176MSB) 0x00= invalid ,0x 1 =swing, 0x 2= f1,0x 3 =f2,0x 4= f3, 0x 5= f4 ,0x 6 =f5,0x7=stop (address=177 lsb,address=184MSB) Remote controller on/off prohibit setting (address=185) TCB-IFCG1TLE bit output (See manual of TCB-IFCG1TLE)
169-176
1 octet
22
177-184
Louver setting
1 octet
23
1 octet
24 25 26-38
6 (EN)
Specifications Manual
Modbusdescription
Data name On/Off setting Filter sign reset setting Reserved Operation mode setting Fan speed setting Louver setting Remote controller on/ off prohibit setting
Explanation
(152*n 143)(152*n 136) (152*n 135)(152*n 128) (152*n 127)(152*n 120) (152*n 119)(152*n 112) (152*n 111)(152*n 104) (152*n 103)152*n 64 9577-9584
19*n 17 19*n 16 19*n 15 19*n 14 19*n 13 TCB-IFCG1TLE bit output See manual of TCBIFCG1TLE
Relay output for TCB- 1 octet IFCG1TLE Reserved On/Off setting Filter sign reset setting Reserved
104 bits 19*n 1219*n 1 octet 1198 1= On,0 =Off1 (address=9577) 1= reset,others=no action (address=9578) 1 octet 1199 0x00=unfix,0x 01= heat,0x 02= cool,0x 03= dry 0x 04= fan,0x05 auto (address=9585 LSB,address= 9592MSB) 0x00=Invalid,0x01=Fan Sop,0x02=Auto,0x03=High,0x04=Medium,0x05= Low,0x06=Ultra Low,0x07=unfix (address=9593 LSB,address=9600MSB) 0x00= invalid ,0x 1 =swing, 0x 2= f1,0x 3 =f2,0x 4= f3, 0x 5= f4 ,0x 6 =f5,0x7=stop (address=9601 LSB,address=9608MSB) Remote controller on/off prohibit setting (address=9609) Remote controller mode prohibit setting (address=9610) Remote controller setpoint prohibit setting (address=9611) Remote controller louver prohibit setting (address=9612) Remote controller fan speed prohibit setting (address=9613) 1=prohibit 0=permit TCB-IFCG1TLE bit output (See manual of TCBIFCG1TLE)
9585-9592
9593-9600
1 octet
1200
9601-9608
Louver setting
1 octet
1201
9609-9616
1 octet
1202
9617-9624 9625-9728
1203
7 (EN)
Specifications Manual
Data name
10001-10004 On/Off setting status Filter sign status Alarm Status Reserved 10005-10008 Reserved
0x00= invalid,0x 01= heat,0x 02= cool,0x 03= dry 0x 04= fan,0x05 auto heat ,0x06=auto cool,0x07=unfix (address=9 LSB,address 16=MSB) 0x00=Invalid,0x01=Fan Sop,0x02=Auto,0x03=High,0x04=Medium,0x05= Low,0x06=Ultra Low,0x07=unfix (address=10017 LSB,address=10024MSB) 0x00= invalid ,0x 1 =swing, 0x 2= f1,0x 3 =f2,0x 4= f3, 0x 5= f4 ,0x 6 =f5,0x7=stop (address=10025 LSB,address=10032MSB) Remote controller on/off prohibit setting (address=10033) Remote controller mode prohibit setting (address=10034) Remote controller setpoint prohibit setting (address=10035) Remote controller louver prohibit setting (address=10036) Remote controller fan speed prohibit setting (address=10037) 1=prohibit 0=permit
1 octet
1 octet
1 octet
10041-10048 Reserved 10049-10056 Reserved 10057-10064 On/Off input for TCBIFCG1TLE Alarm input for TCBIFCG1TLE Din2 input for TCBIFCG1TLE Din3 input for TCBIFCG1TLE Local Prohi. input for TCB-IFCG1TLE Din1 input for TCBIFCG1TLE Reserved 10065-10152 Reserved
88 bits
9-19
8 (EN)
Specifications Manual
Modbusdescription
Data name
10153-10156 On/Off setting status Filter sign status Alarm Status Reserved 10157-10160 Reserved
21
0x00= invalid,0x 01= heat,0x 02= cool,0x 03= dry 0x 04= fan,0x05 auto heat ,0x06=auto cool,0x07=unfix (address=10161 LSB ,address=10168MSB) 0x00=Invalid,0x01=Fan Sop,0x02=Auto,0x03=High,0x04=Medium,0x05= Low,0x06=Ultra Low,0x07=unfix (address=10169 LSB,address=10176MSB) 0x00= invalid ,0x 1 =swing, 0x 2= f1,0x 3 =f2,0x 4= f3, 0x 5= f4 ,0x 6 =f5,0x7=stop (address=10177LSB,address=10184MSB) Remote controller on/off prohibit setting (address=10185) Remote controller mode prohibit setting (address=10186) Remote controller setpoint prohibit setting (address=10187) Remote controller louver prohibit setting (address=10188) Remote controller fan speed prohibit setting (address=10189) 1=prohibit 0=permit
1 octet
22
1 octet
23
1 octet
24
10193-10200 Reserved 10201-10208 Reserved 10209-10216 On/Off input for TCBIFCG1TLE 10217-10304 Reserved n 152*n+9849 On/Off setting status/ -152*n+9856 etc
25 26 27 28-38 19*n 18 19*n 17 19*n 16 19*n 15 19*n 14 TCB-IFCG1TLE bit input See manual of TCBIFCG1TLE
152*n+9857 Operation mode status 1 octet -152*n+9864 152*n+9865 Fan speed set status -152*n+9872 152*n+9873 Louver setting status -152*n+9880 152*n+9881 Remote controller on/ -152*n+9888 off prohibit setting status 152*n+9889 Reserved -152*n+9896 152*n+9897 Reserved -152*n+9904 152*n+9905 On/Off input for TCB-152*n+9912 IFCG1TLE/ETC 152*n+9913 Reserved 152*n+10000 1 octet 1 octet 1 octet
19*n 13 19*n 12 19*n 11 TCB-IFCG1TLE bit input See manual of TCBIFCG1TLE 19*n 10-19*n
9 (EN)
Specifications Manual
Modbusdescription
Data name
19577-19580 On/Off setting status Filter sign status Alarm Status Reserved 19581-19584 Reserved
1199
0x00= invalid,0x 01= heat,0x 02= cool,0x 03= dry 0x 04= fan,0x05 auto heat ,0x06=auto cool,0x07=unfix (address=19585 LSB ,address=19592MSB) 0x00=Invalid,0x01=Fan Sop,0x02=Auto,0x03=High,0x04=Medium,0x05= Low,0x06=Ultra Low,0x07=unfix (address=19593 LSB,address=19600MSB) 0x00= invalid ,0x 1 =swing, 0x 2= f1,0x 3 =f2,0x 4= f3, 0x 5= f4 ,0x 6 =f5,0x7=stop (address=19601LSB,address=19608MSB) Remote controller on/off prohibit setting (address=19609) Remote controller mode prohibit setting (address=19610) Remote controller setpoint prohibit setting (address=19611) Remote controller louver prohibit setting (address=19612) Remote controller fan speed prohibit setting (address=19613) 1=prohibit 0=permit
1 octet
1200
1 octet
1201
1 octet
1202
19617-19624 Reserved 19625-19632 S-code Status 19633-19640 On/Off input for TCBIFCG1TLE/ETC 19641-19728 Reserved
1203 1204 1205 12061216 TCB-IFCG1TLE bit input (See manual of TCBIFCG1TLE)
10 (EN)
Specifications Manual
Modbusdescription
Data name
Length
Explanation
Room temperature
2 octets
unit:C SEEEEMMM MMMMMMMM Temperature = (-1)S (0.01 M) 2(E) s: sign (s = 1: -, s = 0: +), M: -2048 to +2047 Range:-671088.64-----670760.96 unit: C Same as Room temperature 30003 upper header indoor unit: 00 when no alarm occurs 30003 lower follower indoor unit 1: 00 when no alarm occurs 30006 upper follower indoor unit 6: 00 when no alarm occurs 30006 lower follower indoor unit 7: 00 when no alarm occurs 16 characters in 16 ASCII codes 16 characters in 16 ASCII codes Unit ability Octet expression Octet expression 0x00** 6-channel analog input for TCB-IFCG1TLE (See manual of TCB-IFCG1TLE) address=30025 CH1, address=30026 CH2 etc. see Note RS FM Operation mode and air volume can be set CT CB Temperature setting upper and lower limits in cool mode HT HB Temperature setting upper and lower limits in heat mode DT DB Temperature setting upper and lower limits in dry mode FT FB Temperature setting upper and lower limits in auto mode
30002 30003-30006
Model name Peculiar number Ability Indoor Type Analog input for TCB-IFCG1TLE OperationMode/ Fan Cool temp range Heat temp range Dry temp range Auto temp range Reserved Room temperature
Setting temperature 2 octets status 8 octets 16 octets 16 octets 2 octets 2 octets 2 octets*6CH 2 octets 2 octets 2 octets 2 octets 2 octets 126*2 octets 6-channel analog input for TCB-IFCG1TLE (See manual of TCB-IFCG1TLE) RS FM Operation mode and air volume can be set CT CB Temperature setting upper and lower limits in cool mode HT HB Temperature setting upper and lower limits in heat mode DT DB Temperature setting upper and lower limits in dry mode FT FB Temperature setting upper and lower limits in auto mode
29847+156*n Alarm code -29850+156*n 29851+156*n Model name -29858+156*n 29859+156*n Peculiar number -29864+156*n 29865+156*n 29868+156*n Ability Indoor Type
29869+156*n- Analog input for 29874+156*n TCB-IFCG1TLE 29875+156*n 29876+156*n 29877+156*n 29878+156*n 29879+156*n OperationMode/ Fan Cool temp range Heat temp range Dry temp range Auto temp range
11 (EN)
Specifications Manual
Modbusdescription
Indoor- Modbusnumber address for registers 64 39829 39830 39831-39834 39835-39842 39843-39850 39851 39852 39853-39858 39859 39860 39861 39862 39863 39864-39984 39985-39992
Data name
Length
Explanation
Room temperature
2 octets
See Modbus address 30001-30024 See Modbus address 30001-30024 See Modbus address 30001-30024 See Modbus address 30001-30024 See Modbus address 30001-30024 See Modbus address 30001-30024 See Modbus address 30001-30024 6-channel analog input for TCB-IFCG1TLE See manual of TCB-IFCG1TLE RS FM Operation mode and air volume can be set CT CB Temperature setting upper and lower limits in cool mode HT HB Temperature setting upper and lower limits in heat mode DT DB Temperature setting upper and lower limits in dry mode FT FB Temperature setting upper and lower limits in auto mode TCB-IFCG1TLE is expressed in ASCII codes followed by the version number. Same as Room temperature Valid range: 0 to 92, unit: 1, fractions rounded off Octet expression unit: hour ex) 255hours=0xFF Unit: hour. Monitor on/off of the discrete input register to check the on/off state of all air conditioners every 15 minutes. When the register state is on, add 15 minutes. The register data is retained even during power-off. 4-channel analog output for TCB-IFCG1TLE (See manual of TCB-IFCG1TLE) see Note 2 See Modbus address 40001-40156 See Modbus address 40001-40156 See Modbus address 40001-40156 See Modbus address 40001-40156 See Modbus address 40001-40156 See Modbus address 40001-40156 See Modbus address 40001-40156 See Modbus address 40001-40156 See Modbus address 40001-40156 See Modbus address 40001-40156 See Modbus address 40001-40156 See Modbus address 40001-40156 See Modbus address 40001-40156
Setting temperature 2 octets status Alarm code Model name Peculiar number Ability Indoor Type Analog input for TCB-IFCG1TLE OperationMode/ Fan Cool temp range Heat temp range Dry temp range Auto temp range Reserved Software version Temperature setting value Accumulated operation time 8 octets 16 octets 16 octets 2 octets 2 octets 2 octets*6CH 2 octets 2 octets 2 octets 2 octets 2 octets 126*2 octets 16 octets 2 octets 2 octets
40001 40002
Analog output for TCB-IFCG1TLE Reserved Temperature setting value Accumulated operation time Analog output for TCB-IFCG1TLE Reserved Temperature setting value Accumulated operation time
2 octets*4CH 150*2 octets 2 octets 2 octets 2 octets*4CH 150*2 octets 2 octets 2 octets 2 octets*4CH 150*2 octets 2 octets 2 octets 2 octets*4CH 150*2 octets
39847+156*n- Analog output for 39850+156*n TCB-IFCG1TLE 39851+156*n- Reserved 40000+156*n 64 49829 49830 49831-49834 49835-49984 Temperature setting value Accumulated operation time Analog output for TCB-IFCG1TLE Reserved
12 (EN)
Specifications Manual
Note 1
Analog In (2 channels, thermistor) reading Received TCC-LINK value is retained in this register with two bytes. The received 2-byte data is a twos complement and is converted to as an absolute measurement temperature by dividing it by 100. Example) Received value 0xFE90 -> x0169 (converted to twos complement) -> 361 -> converted to 3.61 (K) (divided by 100) The Celsius temperature is obtained by subtracting 273.15 from 3.61. Analog In (4CH 0-10VDC) Received TCC-LINK value is retained in this register with two bytes. The true value is a twos complement, and the value obtained by dividing the true value by 1000 becomes the board input value. Example) Received value 0xD8F1 -> converted to 0x270F (twos complement) -> 9999 -> converted to 9.999V (divided by 1000)
Note 2
TCB-IFCG1TLE Analog Out 4-channel writing The master device writes a 2-byte twos complement that is 1000 times of the transmit value. The TCB-IFCG1TLE board value is obtained by dividing a twos complement of 2-byte received value by 3000. A level in accordance with the value is output from the MPU treating 3.333 as 256 levels. The MPU output value is multiplied by 3 in the external circuit, and the TCB-IFCG1TLE board output value equals the transmit value. Example 1) A value 9.999V calculated by the master device is sent -> -> 9999 (1000 times) -> 0x270F---> 0x D8F1 (twos complement) This value is written. Calculation at the receiver (TCB-IFCG1TLE board) 0xD8F1- -> 0x270F (twos complement) -> 9999 -> 3.333V (divided by 3000)- -> 256 levels = 0xFF (3.333V) is DA output. A value 3.333*3 = 9.999V is output from Analog Out on the TCB-IFCG1TLE board. Example 2) A value 3.000V calculated by the master device is sent -> 3000 (1000 times) -> 0x0BB8-- -> 0xF448 (twos complement) This value is written to the register. Calculation at the receiver (TCB-IFCG1TLE board) 0xF448 -> 0x0BB8 (twos complement) -> 3000 -> 1V (divided by 3000) - -> 77 levels = 0x4D (1.00V) is DA output. A value 1.00*3 = 3.00V is output from Analog Out on the TCB-IFCG1TLE board.
Note 3
Unused bits can be read and written. No data can be written to reserved areas. If a reserved area is read, 00 is always returned.
Note 4
The meaning of RS/FM (operation mode, fan speed), CT/CB (temperature setting upper and lower limits in cool mode), HT/HB (temperature setting upper and lower limits in heat mode), DT/DB (temperature setting upper and lower limits in dry mode), and FT/FB (temperature setting upper and lower limits in auto mode) in the Input register (R) is shown below. The master device must read the following values from each air conditioner in advance, and must set values within this range when specifying operation data.
Bits of RS
b7, b6 b5 b4 b3 b2 b1 LSB
Meaning
00 All operation modes enabled 01 Cooling/drying disabled 10 Heating disabled 11 Fan only enabled 1: Auto mode enabled, 0: Auto mode disabled 1: Ventilation enabled, 0: Ventilation disabled 1: Heating mode enabled, 0: Heating mode disabled 1: Drying mode enabled, 0: Drying mode disabled 1: Cooling mode enabled, 0: Cooling mode disabled 1: Fan mode enabled, 0: Fan mode disabled
13 (EN)
Specifications Manual
Bits of FM
b3 b2 b1 b0
Meaning
Temperature setting upper-limit value in cool mode Temperature setting lower-limit value in cool mode Temperature setting upper-limit value in heat mode Temperature setting lower-limit value in heat mode Temperature setting upper-limit value in dry mode Temperature setting lower-limit value in dry mode Temperature setting upper-limit value in auto mode Temperature setting lower-limit value in auto mode
The upper-limit and lower-limit values in the table above are converted to Celsius temperatures using the following formula. Celsius temperature (C) = -35 + (decimal read value / 2)
14 (EN)
Specifications Manual
8
Code
0x25, 0x26 Ox41 0x42 0x43 0x44 0x46 0x47 0x48 0x49 0x4a 0x4c 0x4f 0x50 0x52 0x53 0x54 0x57 0x59 0x5a 0x5c 0x5f 0x61 0x62 0x63 0x64 0x65 0x66 0x67 0x68 0x6a 0x6c 0x6d 0x6F 0x70 0x77 0x78 0x7d 0x7f 0x81 0x82 0x83 0x84 0x86 0x87 0x88 0x8e
Appendix
Description
TCC-LINK central control device transmit error Indoor-remote controller communication error Remote controller transmit error Indoor-remote controller communication error Indoor-outdoor communication error Decrease in the number of indoor units Indoor-outdoor communication circuit error Indoor address duplication Master remote controller duplication Communication error in indoor PCB Automatic address start error No indoor unit during automatic addressing Too many indoor units connected or over capacity Header-follower indoor units communication error Error in the number of header outdoor units Connection to other system refrigerant line during automatic addressing Outdoor-outdoor communication error Follower outdoor setup address duplication Decrease in the number of outdoor units Follower outdoor error IPDU communication error Indoor coil TC1 sensor error Indoor coil TC2 sensor error Indoor coil TC1 sensor error TD1 sensor error TD2 sensor error TE1 sensor error TL sensor error TO sensor error Indoor suction temperature TA sensor error TS1 sensor error TH sensor error Outdoor temperature sensor incorrect wiring (TE, TL) Outdoor pressure sensor incorrect wiring (Pd, Ps) Ps sensor error Pd sensor error Other indoor errors Outdoor EEPROM error Compressor breakdown Compressor error (lock) Current detector circuit error Compressor 1 case thermostat operation Low-pressure protective operation Low oil level detection protection Oil level detection temperature sensor error Compressor 2 case thermostat operation Detected by outdoor unit Detected by indoor unit Detected by indoor unit Detected by remote controller
Alarm Codes
Note
15 (EN)
Specifications Manual
Code
0x90 0xc3 0xc4 0xc5 0xc6 0xc7 0xc8 0xc9 0xca 0xd4 0xdc 0xdd 0xde 0xdf 0xe1 0xe3 0xe4 0xe5 0xe7 0xea 0xec 0xed 0xef 0xf1 0xf3 0xf4 0xf6 0xfa 0xfd 0xff 0x100 0x103 0x104 0x105 0x106 0x107 0x108 0x109
Description
Oil level detection circuit error Indoor header address duplication Outdoor line address duplication Priority indoor unit duplication (displayed on unit with priority) Priority indoor unit duplication (displayed on unit with priority) Group wire on individual indoor No address setting of indoor group No setting of indoor capacity No setting of outdoor capacity Central control address duplication Too many outdoor units connected IPDU error External interlock error in indoor unit IC error Indoor fan moter error Discharge temperature TD1 error High-pressure switch operation error Missing phase detected, phase sequence error Heatsink TH overhead error Indoor water overflow error Indoor DC fan motor error Outdoor liquid back detection error Gas leak detected Discharge temperature TD2 error 4-way valve error High-pressure protective operation Outdoor fan IPDU error G-TR short-circuit protection error Compressor position detector circuit error Other indoor unit errors Intelligent Server communication error Group follower indoor unit error BMS-IFWH communication error BMS-IOKIT communication error BMS-IFWH communication error BMS-IFDD communication error Communication error Communication error
Note
16 (EN)
Specifications Manual
17 (EN)
DE88909601