Abstract of Is 1255
Abstract of Is 1255
Abstract of Is 1255
1) Route Indicator
Power cable route indicators should be provided at an interval not exceeding 200 M and also at turning points of the power cable route wherever practicable
2) Electrolytic corrosion:
Where the possibility of electrolytic corrosion exists, for example, adjacent to dc traction system, the potential gradient along the pipe-line and the cable sheath should be specified.
3) Neutral
The neutral point is earthed in such a manner that during a line-to-earth fault the highest rms voltage to earth of a sound phase(s) expressed as a percentage of the highest line-to-line voltage, does not exceed 80 percent, irrespective of the fault location,
4) Earthing
The neutral point is not earthed but a device is installed which automatically and instantly cuts out any part of the system which becomes accidentally earthed, In case of ac systems only, the neutral point is earthed through an arc suppression coil with arrangement for isolation within one hour for the non-radial field cables and within 8 hours for radial field cables, of occurrence of the fault provided that the total of such periods in a year does not exceed 125 hours.
5) Tensile Strength
Maximum Permissible Tensile Strength for Cables: PVC and XLPE insulated armored power cables P = 9 D2 ,P=Pulling Strength(N),D=Outer Diameter of Cable(mm) Maximum Permissible Tensile Strength for Cables: PVC and XLPE insulated unarmored power cables P = 5 D2 Maximum Permissible Tensile Strength for Cables: Paper insulated armored power cables P = 5 D3
6) Cable Pulling
1. For Cables Pulled by Pulling Eye : 2. Expected Pulling Force When Pulling Cables by Winch : If the cables are pulled by gripping the conductor directly with pulling eye, the maximum permissible tensile stress depends on the material of the conductor and on their cross-section as given below: For aluminum conductors 30 N/mm2 and For copper conductors 50 N/mm2 The following values of pulling force are expected = (approximately percentage of cable weight): In trenches without large bends 15-20 percent In trenches with 1 or 2 bends of 90 each 20-40 percent In trenches with 3 bends of 90 each (assuming the use of easy-running support and corner rollers) 50-60 percent In ducts with bends totaling 360 Up to 100 percent
High voltage cables, 3.3 kV to 11 kV rating =0.9 m High voltage cables, 22 kV, 33 kV rating= 1.05 m Low voltage and control cables = 0.75 m Cables at road crossings = 1.00 m
8) Cables at railway
Cables at railway level crossings (measured from bottom of sleepers to the top of pipe)=1.00m
9) Cable Clearance
Clearances The desired minimum clearances are Power cable to power cable = Clearance not necessary; however, larger the clearance, better would be current carrying capacity. Power cable to control cables = 0.2 m Power cable to communication cable = 0.3 m Power cable to gas/water main = 0.3m Inductive influence on sensitive control cable on account of nearby power cables should be checked The power cable should not be laid above the telecommunication cable, to avoid danger to life of the person, digging to attend to the fault in the Telecommunication cable.
10) Crossing
Cables Laid Across Roads, Railway Tracks and Water Pipe Lines: Steel, cast iron, plastics, cement or earthenware ducts, or cable ducting blocks should be used where cables cross roads and railway tracks. Spare ducts for future extensions should be provided. Spare duct runs should be sealed off. Buried ducts or ducting blocks should project into footpath or up to the edge of road, where there is no footpath, to permit smooth entry of cable without undue bending
at such depths as may be specified by the railway authorities but not less than 1 m measured from the bottom of sleepers to the top of the pipe. On long run ducts, it is desirable to apply lubrication to the lead or serving/outer sheath as it enters the duct. Petroleum jelly or graphite powder or a combination of both is effective for this purpose and through lubrication will reduce the pulling tension by about 40 percent.
19) Identification/Marking
Type of Cable Legend: Improved fire performance or Category C1 FR
Cables in constrained areas, Does not propagate fire even when installed in groups in vertical ducts), Improved fire performance for Category C2 FRLSH (Cables in constrained areas with limited human activity and/or presence of sophisticated systems) Aluminum conductor= A, PVC insulation=Y, Steel round wire armor= W, Steel strip armor= F, Steel double round wire armor= WW, Steel double strip armor =FF, PVC outer sheath= Y
This method involves digging a trench in the ground and laying cable(s) on a bedding of minimum 75 mm riddled soil or sand at the bottom of the trench, and covering it with additional riddled soil or sand of minimum 75 mm and protecting it by means of tiles, bricks Depth The desired minimum depth of laying from ground surface to the top of cable is as follows: High voltage cables, 3.3 kV to 11 kV rating =0.9 m High voltage cables, 22 kV, 33 kV rating= 1.05 m Low voltage and control cables = 0.75 m Cables at road crossings = 1.00 m Cables at railway level crossings (measured from bottom of sleepers to the top of pipe)=1.00m
On long run ducts, it is desirable to apply lubrication to the lead or serving/outer sheath as it enters the duct. Petroleum jelly or graphite powder or a combination of both is effective for this purpose and through lubrication will reduce the pulling tension by about 40 percent.