Abb - The Motor Guide
Abb - The Motor Guide
2.
3.
Standards
3.1 3.2 3.3 3.4 3.5 General Introduction Direction of rotation Cooling Degrees of protection: IP code/IK code Standard voltage ranges - Code letters for voltage ranges - Motors for other voltages 3.6 Tolerances 3.7 Mounting arrangements - International standards, IM mounting - Examples of common mounting arrangements 3.8 Dimensions and power standards 35 35 36 39 40 40 41 42 43 43 43 44
4.
Electrical design
4.1 Insulation 4.2 Ambient temperatures and high altitudes - Permitted output in high ambient temperatures or at high altitudes 4.3 Starting motors - D.O.L - Y/-starting 4.3.1 Soft starters 4.3.2 Starting time
v
49 50 50 50 50 51 52 53
Contents
- Permitted starting time - Permitted frequency of starting and reversing 4.3.3 - Starting characteristics 4.3.4 - Examples of starting performance Duty types - Duty types from S1 to S9 Uprating Efficiency Power factor 4.7.1 Phase compensation 4.7.2 Power factor values Connection diagrams 53 54 56 58 60 60 65 66 67 67 69 70
4.8
5.
Mechanical design
5.1 Frame constructions 73 5.2 Terminal boxes 74 - Co-ordination of terminal boxes and cable entries 76 5.3 Bearings 77 - Bearing life 77 - Bearing size 77 - Bearing design for aluminum motors - Bearing design for steel and cast iron motors 78 - Vibration test photo 79 5.4 Balancing 79 5.5 Surface treatment 81
6.
Noise
6.1 Noise reduction 6.2 Noise components 6.2.1 - Fan 6.2.2 - Magnetic noise 6.3 Airborne and structure borne noise 6.3.1 - Airborne noise 6.3.2 - Structure borne noise 6.3.3 - Low noise motors 6.4 Sound pressure level and sound power level 6.5 Weighting filters 6.6 Octave bands - Octave band analysis 6.7 Converter duty 6.8 Additional sound sources 85 85 86 86 86 86 87 87 87 88 88 89 90 91
vi
Contents
6.8.1 - Perception of difference in sound level 6.9 Sound pressure levels 91 92
7.
8.
The SI system
8.1 Quantities and units - Example 8.2 Conversion factors 109 110 112
9.
Selecting a motor
9.1 Motor type - Type of enclosure 9.2 Loading (kW) 9.3 Speed - Motor speeds table 9.4 Mounting 9.5 Power supply 9.6 Operating environment 9.7 Ordering check list - Check lists 115 115 115 115 116 116 116 116 117 117
vii
viii
ABB Profile
1. ABB Profile
Improving the way people work together offers the greatest efficiency gains. To harness this potential, we have redirected the way ABB thinks - from board room to factory floor. We call this Customer Focus - which stands for first finding out what you need, then examining and if necessary changing the way we work in order to achieve it. New skills
11
1. ABB Profile
have been acquired, along with improved motivation and greater individual responsibility. Customer Focus has dramatically improved our own efficiency, which means our customers can gain the benefits of more efficient new technology more quickly.
Technology transfer
The combination of global capabilities and individual autonomous local operations gives ABB an unmatched edge in creating more efficient technologies around the world. Independently, and through joint ventures, we manufacture many of our products in the countries in which they are sold; we hire the very best local talent; retrain existing work forces, and closely co-operate with local governments to help increase exports and foreign earnings.
Innovative Technology and Leadership
ABBs dedication to quality includes the commitment to supply its customers with the most advanced, energy efficient and reliable products and services. Our commitment to research and development plays an important role in this regard, reflected in an annual R&D budget of 7.6 per cent of turnover. Some 90 per cent of our total R&D budget funds immediate practical market applications. This massive investment funds cross border research programs which achieve new levels of productivity and speed up the creation of next generation products in our 50 business areas.
12
1. ABB Profile
ABB Motors is the worlds leading manufacturer of low voltage induction motors, with over one hundred years experience, and a presence in more than 140 countries worldwide. We offer a full range of industrial rotating machines, both AC and DC, LV and HV to meet the needs of most applications, with virtually any power rating. ABB Motors comprehensive understanding of customer applications enables us to solve customer specific problems, or supply custom designed motors for any project - no matter how complex or demanding. Our products are hallmarked by efficiency, robustness and reliability, offering the best value available on the market. Backed by the ABB commitment to deliver unrivalled customer service and back up, ABB Motors provides customers with the means to significantly improve their competitive advantage. This best value is further enhanced by ABB Motors worldwide customer service network which guarantees fast delivery, rapid response, local back up, and after sales support. ABB Motors has manufacturing facilities in Denmark, Finland, Italy, Spain, Sweden, India and Mexico, plus a joint venture in China. Each holds comprehensive motors and parts stocks, reinforced by Central Stock Europe, in Germany, Central Stock Asia, Singapore, and numerous distribution sites.
13
1. ABB Profile
STANDARD MOTORS
Aluminum motors
56 63 71 80 90 100 112 132 160 180 200 225 250
Steel motors
280
315
355
400
280
315
355
400
280
315
355
400
EEx n motors
63 71 80 90 100 112 132 160 180 200 225 250
280
315
355
400
280
315
355
400
14
1. ABB Profile
250
280
315
355
400
INTEGRAL MOTORS
80
90
100
112
132
BRAKE MOTORS
71 80 90 100 112 132 160
MARINE MOTORS
Aluminum motors
63 71 80 90 100 112 132 160 180 200 225 250
Steel motors
280
315
355
400
280
315
355
400
250
280
315
355
400
15
1. ABB Profile
250
280
315
355
400
112
132
160
180
200
225
250
280
315
355
400
200
225
250
280
315
355
400
STANDARD MOTORS
According to NEMA standards
48
140
180
210
250
280
320
360
400
440
500
580
16
1. ABB Profile
ABB Motors European production units are all certified according to ISO 9001 quality standard. All ABB motors supplied are inspected and tested to ensure they are free from defects and have the desired design and performance characteristics.
Routine testing
This inspection is carried out on every motor. It involves checking that the motor possesses the necessary electrical strength and that its electrical and mechanical performance is satisfactory.
Type inspection
Type inspection is performed for one or more motors, to demonstrate that the characteristics and functions of the design are in accordance with the specifications of the manufacturer. Type inspection covers the inspection and testing of:
s s s s s
electrical and mechanical operation electrical and mechanical strength temperature rise and efficiency overload capacity other special characteristics of the motor
17
1. ABB Profile
Subject to agreement at the time of ordering, purchasers may select a certain number of motors from a specific order for more detailed inspection and testing, similar in content to type inspection. The remaining motors undergo routine testing.
Special motor versions
Motors to be used onboard merchant vessels or in potentially explosive areas must undergo additional inspection and testing as laid down in the requirements of the relevant classification society or in applicable national or international standards.
Test reports
Type test reports providing typical performance values for purchased motors, together with a copy of the inspection and testing report will be issued to customers on request.
18
1. ABB Profile
A selection of certificates of approval from various authorities worldwide can be downloaded from the ABB Motors web site: www.abb.com/motors.
The ABB Motors web site (www.abb.com/motors) includes our Customer Technical Information Database, a complete library of practical technical information relating to the ABB Motors range. To view information, simply click on Technical Information Database on the Product Page of the web site. Technical documents can also be downloaded directly in a choice of formats.
The following can be accessed from the database:
s Accessories - detailed information on available motor options s CAD outline drawings which can be copied into practically any AutoCad system s Certificates of Approval - a selection of actual certificates from various authorities worldwide s Declarations of Conformity - including voltage directives, CE markings etc. s Machine instructions - available in seven languages s Maintenance - specific information, often not included in catalogues, such as special rules on how to store motors for long periods
19
1. ABB Profile
s Motor dimension prints - over 1,300 motor dimension prints, including frame size and frame length for both standard and hazardous area motors for each motor type s Spare parts. The ABB Motors web site is regularly updated and continuously developed.
CD-ROM
Also s s s s
available on CD-ROM are: Complete motor catalogs CAD outline drawings Dimension drawings Motor Selection Program
The Motor Selection Program is not available on our web site. However, the CD-ROM can be obtained at ABB Motors nearest sales office.
20
1. ABB Profile
ABB Motors established Central Stock Europe (CSE) in 1988. The concept of a central stock system is unique in the electric motors market. The rapid and efficient service it provides has since become a powerful marketing and sales argument for ABB Motors. To further improve the CSE service, ABB Motors opened a new, fully automated warehouse in nearby Menden, Germany, in June 1997. The new premises provide 1,500 m2 additional storage space and 7,000 new pallet locations for the 1,500 stock articles and 90,000 stocked items. Robotized warehousing has cut processing times, enabling later cut-offs for same day dispatch. Central Stock Europe is open 24 hours a day, seven days a week, therefore allowing rapid deliveries in break down situations. CSE is also investing in a new order handling system to improve the entire process. A single phone call or fax to any local ABB sales office now accesses one of the most efficient on-line sales support and access networks for stock enquiries and order processing.
fast
- standard delivery services - online sales support - 98% on time deliveries - 98% stock availability - zero faults - multi-stock - multi-article - total supply chain optimization by using EDI
reliable
flexible
cost-efficent
21
2.1 General
At the World Summit held in Kyoto, Japan, in December 1997, 55 nations of the world agreed to implement measures to reduce emissions to stabilise the global environment. The 38 industrialised nations agreed to reduce their 1990 level greenhouse emissions by an average of 5% between 2008 and 2012. Further, the European Union made a commitment to reduce its emissions by 8%, the US by 7% and Japan by 6%.
Effiency Classes - EU/CEMEP agreement in Oct 98
4-pole
98 96 94 92 90 88 86 84 82 80 78 76 74 72
1,1 1,5 2,2 3 4 5,5 7,5 11 15 18,5 22 30 37 45 55 75 90
Output kW
In October 1998, the European Union and CEMEP (The European Committee of Manufacturers of Electrical Machines and Power Electronics) agreed to introduce three efficiency classes for electric motors. This agreement forms part of the European Commissions aims to improve energy efficiency and reduce CO 2 emissions. The burning of fossil fuels to generate electricity, primarily consumed by households and industry, is a major source of greenhouse gas emissions. Industry will, therefore, have a major part to play in reducing harmful emissions. For instance by increasing the efficiency of their production processes, and installing energy efficient devices, industrial processes will consume less electricity. Which, in turn, will reduce the amount of electricity which must be generated to meet demand.
25
Motors account for around 65 per cent of the electric energy consumed in industrial applications. Energy saving is dependent on the kW rating of the motor, the loading and the hours run. As such, higher efficiency motors can play a significant part in reducing CO2 emissions. ABB Motors M2000 range is designed to meet changing world attitudes towards energy efficiency and motor performance. The all round operational performance of these motors goes a long way towards fulfilling the commitments of world governments to the Kyoto Summit. Industries can also help by recycling raw materials such as plastic and aluminium. This will save the electricity needed to produce these materials from their raw state (oil and aluminum ore respectively).
2.2.1 Motors for EU motor efficiency levels
ABB is one of only a handful of leading motor manufacturers in Europe, to have a motor range to meet or exceed the minimum efficiencies stated in the highest level of the EU agreement for LV motors. These efficiency levels apply to 4-pole, three phase squirrel cage induction motors, rated for 400 V, 50 Hz, with S1 duty class and with the output 1.1-90 kW, which account for the largest volume on the market. CEMEP and the European Commission are formulating an agreement for 2-pole motors, which account for the second largest production volume. This agreement is expected to be announced by April 1999.
2.2.2 Motors according to EPAct requirements
The recently amended American Energy Policy and Conservation Act, generally referred to as EPAct, requires electric motors in the 0.7 - 150 kW (1 - 200 hp) range, manufactured in or imported to the United States or Canada, to meet the efficiency levels demanded by law. ABB Motors wide product range includes motors that fulfil these requirements.
26
Reducing energy costs is one way companies can cut their overheads to remain competitive. Significant savings can be made by installing an energy efficient motor. This is particularly the case when considering either new installations or equipment packages, replacing oversized and underloaded motors, making major modifications to facilities or processes, or instead of repairing or rewinding a failed motor. High efficiency motors offer savings through reduced energy costs, less downtime and a lower stock inventory. Even small rises in efficiency will make a substantial saving in the overall cost of a motor, taking into account both the operating and capital cost. For example, in the UK, an 11 kW motor costs, typically, under GBP 500 to buy, yet over GBP 50,000 to run over a 10 year operating life. The purchase price is therefore around 1 per cent of the motors total life cycle cost. The table below compares the capital cost of various motor sizes with their running costs by showing approximately how long it takes to consume their own capital cost in energy cost.
Capital cost versus running cost (GBP) Rating Approx. cap cost Typical efficiency Input kW Daily running cost Days to consume capital cost 5.5 kW 285 85 % 6.47 7.76 18.5 kW 680 90 % 20.56 24.67 90 kW 3,700 92 % 97.83 117.40 250 kW 10,500 94 % 265.96 319.15
37
28
32
33
All ABB motors are energy efficient as standard, available off the shelf in all standard frame sizes. There is also a range of High Effiency Motors available. They are suitable for all applications, including hazardous areas, and variable speed drive.
27
An energy efficient motor produces the same output power (torque) but uses less electrical input power (kW) than a standard efficiency motor. This higher efficiency is achieved by using higher quality and thinner laminations in the stator to reduce core loss, more copper in the slots to reduce I 2R loss. Energy efficient motors also have reduced fan and stray losses. There are three main motor efficiency testing standards, IEC 34-2 (EU), IEEE 112-1991 (USA), and JEC 37 (Japan). The main difference is that IEEE 112 measures the total losses by a direct method, thus giving the lowest values. IEC 34-2 is an indirect method which assumes the additional losses to be 0.5 per cent, which is lower than real losses for small motors. JEC 37 is also an indirect method which assumes the additional losses to be zero, thus giving the highest values.
28
Life Cycle Assessment can show designers how to obtain environmental benefits in their products. The table below compares two standard 11 kW electric motors of different design. Motor A is manufactured by ABB Motors, and Motor X by a competitor. The ABB motor requires more copper and iron to manufacture than motor B, but this makes it more efficient in operation. This means that it uses less electricity than motor X over its lifetime. Operating 8,000 hours per year for 15 years, the more efficient ABB motor will use 140,681 kWh, and the less efficient motor X, 177,978 kWh. With an efficiency of 91.1 per cent, an ABB motor will lose 8.9 per cent of the 140,681 kWh. Motor X, with an efficiency of 89 per cent, will lose 11 per cent of the 177,978 kWh. The table shows the environmental aspects of these two motors based on their losses, manufacture and 96 per cent recycling. Evaluated according to the EPS scheme, motor A has a 21 per cent lower environmental impact.
Environmental aspects over full life cycle Efficiency Use of resources electricity generation average European mix Coal kg Gas kg Oil kg Steel and other materials (kg) Emissions (kg) percentage CO2 Total EPS1) indices 16,370 2,070 3,240 32 64,278 98 8,260 ELU2) 99.4 % from operation
1
ABB Motor 11 kW 91 %
Motor X 11 kW 89 %
) The Environmental Priority Strategies in Design. The EPS method includes five safeguard objects: ) Environmental Load Limit, ELU, is used to estimate the input of the five safeguard objects of EPS.
Human health, biological diversity, biological production, resources and aesthetic values.
2
29
With its deep local roots, global technological know-how, and commitment to technology transfer, ABB is making a significant contribution to achieving sustainable development worldwide. The ABB Environment Management Program is an important part of our response to promoting sustainable development. ABB is a signatory to the International Chamber of Commerce (ICC) Business Charter for Sustainable Development and committed to fulfilling the requirements of this charter. As a global supplier of energy solutions, ABB is responsible for activities that directly or indirectly impact the environment. Our environmental objective is to limit, or, if possible, eliminate the impact our business has on the global environment, by reducing emissions, cutting waste and improving the utilization of resources. This far-reaching objective touches every aspect of our business.
30
ISO 14001 is the international standard for environmental management systems. Set by a sub committee of the World Business Council for Sustainable Development, the overall aim of ISO 14001 is to support environmental protection and prevent pollution in balance with socioeconomic needs. The standard requires that organizations establish and maintain environmental management systems, and sets targets for environmental work. In addition to complying with all relevant environmental legislation, companies must commit to continuous improvement and prevention of pollution. ISO 14001 also enables the public to appraise an organizations environmental performance. ABB has already made significant progress in applying ISO 14001 to sites around the world. By the end of 1998, around 400 manufacturing and service sites have implemented ISO 14001.
31
Standards
3. Standards
ABB motors are of the totally enclosed, three phase squirrel cage type, built to comply with international IEC standards, CENELEC and relevant VDEregulations, and DIN-standards. Motors conforming to other national and international specifications are also available on request. All ABB Motors European production units are certified to ISO 9001 international quality standard and conform to all applicable EU Directives. ABB Motors strongly supports the drive to harmonize European standards and actively contributes to various working groups within both IEC and CENELEC.
International standards: EN 60034-1,2 5, 6, 7, 9 NEMA MG 1 1993 IEC Electrical IEC 34-1 IEC 34-2 IEC 34-8 IEC 34-12
Mechanical IEC 72 IEC 34-5 IEC 34-6 IEC 34-7 IEC 34-9 IEC 34-14
Motor cooling is independent of the direction of rotation, with the exception of certain larger 2-pole motors. When the mains supply is connected to the stator terminals marked U,V and W, of a three phase motor, and the mains phase sequence is L1, L2, L3, the motor will rotate clockwise, as viewed from the D-end. the direction of rotation can be reversed by interchanging any two of the three conductors connected to the starter switch or motor.
35
3. Standards
3.3 Cooling
International Cooling Circuit arrangement 0: Free circulation (open circuit) 4: Frame surface cooled Primary coolant A for air (omitted for simplified designation) Method of movement of primary coolant 0: Free convection 1: Self-circulation 6: Machine-mounted independent component Secondary coolant A for air (omitted for simplified designation) W for water Method of movement of secondary coolant 0: Free convection 1: Self-circulation 6: Machine-mounted independent component 8: Relative displacement
Note :
Motors without fan can deliver same output power provided installation are according to IC 418.
36
3. Standards
3.3 Cooling
The air flow and the air speed between ribs of frame must meet minimum the figures given below as to shaft height.
Shaft height 63 71
80
90
100
112
132
160
180
200
225
250
280
315
355
400
Air speed and Air flow : Pole number Air speed m/s 2 2 4 1 8 0.5 2 2.5 4 1.5 6 1.0 8 0.75 2 3.5 4 2.5 6 1.5 8 1.2 2 4.5 4 3.0 6 2.0 8 1.6 2 7.5 4 4.5 6 3 8 2.5 2 11 4 7 6 7 8 7 2 12 4 9 6 8 8 8 2 11 4 8 6 6 8 3 2 11 4 8 6 6 8 4 2 10 4 8 6 5 8 5 2 10 4 10 6 9 8 7 2 10 4 12 6 9 8 6 2 7.6 4 7.1 6 8.5 8 6.5 2 6.8 4 8.8 6 7.5 8 5.5 2 11 4 17 6 11.5 8 8.5 2 10 4 15 6 10.5 8 8
Air flow m3/s 0.16 0.07 0.03 0.21 0.10 0.07 0.06 0.31 0.19 0.12 0.09 0.36 0.28 0.17 0.14 0.69 0.42 0.25 0.19 0.015 0.010 0.010 0.010 0.25 0.20 0.15 0.15 0.35 0.25 0.20 0.10 0.45 0.30 0.25 0.15 0.45 0.35 0.25 0.25 0.50 0.55 0.45 0.35 0.55 0.65 0.45 0.30 0.35 0.34 0.30 0.35 0.46 0.47 0.40 0.30 0.75 1.4 1.0 0.7 0.9 1.5 1 0.7
37
3. Standards
3.3 Cooling
IC 411
Standard motors
IC 416
Standard motors (Normally bigger frame sizes only equipped with auxiliary fan).
IC 418
Fan application motors without a cooling fan, cooled by the airstream of the driven machine
IC 01
IC 31 W
38
3. Standards
Classification of degrees of protection provided by enclosures of rotating machines are refers to: - Standard IEC 34-5 or EN 60529 for IP code - Standard EN 50102 for IK code
IP protection:
Protection of persons against getting in contact with (or approaching) live parts and against contact with moving parts inside the enclosure. Also protection of the machine against ingress of solid foreign objects. Protection of machines against the harmful effects due to the ingress of water
IP 5 5
Characteristic letter Degree of protection to persons and to parts of the motors inside the enclosure 2: Motors protected against solid objects greater than 12 mm 4: Motors protected against solid objects greater than 1 mm 5: Dust-protected motors Degree of protection provided by the enclosure with respect to harmful effects due to ingress of water 3: Motors protected against spraying water 4: Motors protected against splashing water 5: Motors protected against water jets 6: Motors protected against heavy seas
IK code :
Classification of degrees of protection provided by enclosure for motors against external mechanical impacts.
IK 05
International mechanical protection Characteristic group Relation between IK code and impact energy: IK code IK 00 IK 01 IK 02 IK 03 IK 04 Impact * energy Joule 0.15 0.2 0.35 0.5
IK 05 0.7
IK 06 1
IK 07 2
IK 08 5
ABB Motors Standard
IK 09 10
IK 10 20
3. Standards
ABB Motors can supply the global market. To be able to meet your delivery requirements ABB Motors products are designed to operate over wide voltage ranges. The codes S and D cover the world voltages. Other voltage ranges available on request.
ABB Motors are available in these voltage ranges.
Direct start or, with -connection, also Y/-start Motor size 63-100 112-132 160-400 S______________________________ 50 Hz 60 Hz 220-240 V 380-420 VY 440-480 VY 220-240 V 380-420 VY 440-480 VY 220-240 V 440-480 VY 380-420 VY 440-480 VY E 50 Hz 500 V 500 V 500 V F 50 Hz 500 VY 500 VY 500 VY D_______________________________ 50 Hz 60 Hz 380-420 V 440-480 V 660-690 VY 380-420 V 440-480 V 660-690 VY 380-420 Y 440-480 V 660-690 VY -
60 Hz 575 V
60 Hz 575 VY
To obtain a poster about world voltages, please contact your nearest ABB Motors sales office.
40
3. Standards
Motors wound for a given voltage at 50 Hz can also be used for other voltages. Efficiency, power factor and speed remain approximately the same. Guaranteed values available on request.
Motor wound for Connected to (50 Hz) 230 V 220 V 230 V 400 V 380 V 415 V 500 V 500 V 550 V 690 V 660 V 690 V
% of values at 400 V, 50 Hz Output IN IS/IN TS/TN Tmax/TN 100 182 90 90 90 100 174 100 100 100 100 105 90 90 90 100 98 106 106 106 100 80 100 100 100 100 75 119 119 119 100 61 90 90 90 100 58 100 100 100
41
3. Standards
3.6 Tolerances
Efficiency by summation losses PN (kW) 50 PN (kW) >50 -15% (1- ) -10 % (1- ) Moment of Inertia PN (kW) 50 PN (kW) >50 10% 10% Slip PN (kW) <1 PN (kW) 1 30% 20% Efficiency by inputoutput test -15% (1- ) -15% (1-) Noise level +3 dB(A) +3 dB(A) Power factor Locked rotor current +20% + 20% Locked rotor torque -15% +25% -15% +25% Pull-up torque -15% -15% -
Tolerances are in accordance with IEC 34-1 and based on test procedure in accordance with IEC 34-2.
42
3. Standards
Designation for international mounting Type of construction, foot-mounted motor with two bearing end shields Mounting arrangement, horizontal mounting with feet downwards etc. External shaft extension, one cylindrical shaft extension etc.
Code I Code II
Flange-mounted motor, large flange with clearance fixing holes.
IM B5 IM 3001
IM V1 IM 3011
IM V3 IM 3031
*) IM 3051
*) IM 3061
*) IM 3071
Code I Code II
Flange-mounted motor, small flange with tapped fixing holes.
IM B14 IM 3601
IM V18 IM 3611
IM V19 IM 3631
*) IM 3651
*) IM 3661
*) IM 3671
43
3. Standards
Below is a typical dimension drawing which is available in catalogs, CD-ROM and on the web site.
44
3. Standards
K = L =
M = N = P =
S =
45
3. Standards
46
CENELEC harminisation document, HD 231, lays down data for rated output and mounting, i.e. shaft height, fixing dimensions and shaft extension dimensions, for various degrees of protection and sizes. It covers totally enclosed squirrel cage motors at 50 Hz, in frame sizes 56 to 315 M.
Electrical design
4. Electrical design
4.1 Insulation
ABB Motors use class F insulation systems, which, with temperature rise B, is the most common requirement among industry today.
Class F insulation system
s Max ambient temperature 40 C s Max permissible temperature rise 105 K s Hotspot temperature margin + 10 K
Class B rise
s Max ambient temperature 40 C s Max permissible temperature rise 80 K s Hotspot temperature margin + 10 K
Insulation system temperature class
49
4. Electrical design
1000 100
1500 96
2000 92
2500 88
3000 84
3500 80
4000 76
It is important to remember that the term starting current refers to the steady-state rms value. This is the value measured when, after a few cycles, the transient phenomena have died out. The transient current, the peak value, may be about 2.5 times the steady-state starting current, but decays rapidly. The starting torque of the motor behaves in a similar way, and this should be borne in mind if the moment of inertia of the driven machine is high, since the stresses on the shaft and coupling can be very great.
50
4. Electrical design
Y/-starting
If it is necessary to restrict the starting current of a motor due to supply limitations, the Y/ method can be employed. This method, where for instance, a motor wound 400 V is started with the winding Y connected, will reduce the starting current to about 30 per cent of the value for direct starting, and the starting torque will be reduced to about 27 per cent of the D.O.L value. However, before using this method, one must first determine whether the reduced motor torque is sufficient to accelerate the load over the whole speed range. Please contact your nearest sales office for the Mot Size calculation program.
D.O.L starting
Y/ starting
Example taken from the MotSize calculation program showing D.O.L. starting curves (1. starting torque at Un, 2. starting torque at 80 per cent Un, 3 torque load) for a cast iron motor.
Example taken from the MotSize calculation program showing D.O.L. starting curves (1. starting torque at Un, 2. starting torque at 80 per cent Un, 3 torque load) for an aluminum motor.
51
4. Electrical design
A soft starter limits the starting current while providing a smooth start. The magnitude of the starting current is directly dependent on the static torque requirement during a start, and on the mass of the load to be accelerated. By continually adapting the motor voltage to the actual requirement automatically, a soft starter will generally save energy, particularly when the motor runs with a light load. In the ABB soft starter, the main circuit is controlled by semiconductors instead of mechanical contacts. Each phase is provided with two antiparallel connected thyristors which allows current to be switched at any point within both positive and negative half cycles. The lead time is controlled by the firing angle of the thyristor which, in turn, is controlled by the built in printed circuit board.
52
4. Electrical design
Starting time is a function of load torque, inertia and motor torque. As the starting current is always very much higher than the rated current, an excessively long starting period will cause a harmful temperature rise in the motor. The high current also leads to electromechanical stresses.
53
4. Electrical design
PN = rated output of motor in continuous duty J + J'L m=x. M JM x = number of starts per hour J M = moment of inertia of motor in kgm2 J' L = moment of inertia of load in kgm2, recalculated for the motor shaft, i.e. multiplied by (load speed/motor speed)2. The moment of inertia J (kgm2) is equal to 1/4 GD2 in kpm2. m o= highest permitted number of starts per hour for motor at no load, as stated in the table at right.
54
4. Electrical design
55
4. Electrical design
Catalogues usually state a maximum starting time as a function of motor size and speed. However, there is now a standardized requirement in IEC 34-12 which specifies the permitted moment of inertia of the driven machine instead of the starting time. For small motors, the thermal stress is greatest in the stator winding, whilst for larger motors it is greatest in the rotor winding. If the torque curves for the motor and the load are known, the starting time can be calculated by integrating the following equation:
TM - TL = (JM + JL) x d
dt where TM= motor torque, Nm TL = load torque, Nm JM = moment of inertia of motor, kgm2 JL = moment of inertia of load, kgm2 = motor angular velocity In case of gearing TL and JL will be replaced by T'L and J'L correspondingly. If the starting torque TS and maximum torque Tmax of the motor are known, together with the nature of the load, the starting time can be approximately calculated with the following equation:
tst = (JM +JL) x K1 Tacc
where tst = starting time, s Tacc = acceleration torque, K1 Nm K1 = as per table below
Speed constant nm K1 nm K1
8 750 78 900 94
10 600 62 720 75
Frequency Hz 50 60
56
4. Electrical design
If there is gearing between the motor and the driven machine, the load torque must be recalculated to the motor speed, with the aid of the following formula:
T'L = TL x nL nM
(n )
M
nL
57
4. Electrical design
4-pole motor, 160 kW, 1475 r/min Torque of motor: TN = 1040 Nm Ts = 1.7 x 1040 = 1768 Nm Tmax = 2.8 x 1040 = 2912 Nm Moment of inertia of motor: JM = 2.5 kgm2 The load is geared down in a ratio of 1:2 Torque of load: n TL = 1600 Nm at nL = M r/min
nM r/min 2
2
J'L = 80 x
(1 2) = 20 kgm
at nM r/min
Total moment of inertia: JM + J'L at nM r/min 2.5 + 20 = 22.5 kgm2 Example 1: TL = 1600 Nm T'L = 800 Nm Constant during acceleration Tacc = 0.45 x (TS + Tmax) - T'L Tacc = 0.45 x (1768 + 2912) - 800 = 1306 Nm tst = (JM + J'L) x K1 Tacc
58
4. Electrical design
Example 2: TL = 1600 Nm T'L = 800 Nm Linear increase during acceleration Tacc = 0.45 x (TS + Tmax) - 1 x T'L 2 Tacc = 0.45 x (1768 + 2912) - 1 x 800 = 1706 Nm 2 tst = (JM + J'L) x K1 Tacc
tst = 22.5 x 157 = 2.1 s 1706 Example 3: TL = 1600 Nm T'L = 800 Nm Square-law increase during acceleration Tacc = 0.45 x (TS + Tmax) - 1 T'L 3 Tacc = 0.45 x (1768 + 2912) - 1 x 800 = 1839 Nm 3 tst = (JM + J'L) x K1 Tacc
tst = 22.5 x 157 = 1.9 s 1839 Example 4: TL = 0 Tacc = 0.45 x (TS + Tmax) Tacc = 0.45 x (1768 + 2912) = 2106 Nm tst = (JM + J'L) x K1 Tacc
59
4. Electrical design
The duty types are indicated by the symbols S1...S9 according to IEC 34-1 and VDE 0530 Part 1. The outputs given in the catalogs are based on continuous running duty, S1, with rated output. In the absence of any indication of the rated duty type, continuous running duty is assumed when considering motor operation.
Operation at constant load of sufficient duration for thermal equilibrium to be reached. Designation S1.
S2 Short-time duty
Operation at constant load during a given time, less than that required to reach thermal equilibrium, followed by a rest and de-energized period of sufficient duration to allow motor temperature to return to the ambient, or cooling temperature. The values 10, 30, 60 and 90 minutes are recommended for the rated duration of the duty cycle. Designation e.g. S2 60 min.
Explanation to figures: P = output power D = acceleration N = operation under rated condition
F V R PN
= = = =
60
4. Electrical design
S3 Intermittent duty
A sequence of identical duty cycles, each including a period of operation at constant load and a rest and de-energized period. The duty cycle is too short for thermal equilibrium to be reached. The starting current does not significantly affect the temperature rise. Recommended values for the cyclic duration factor are 15, 25, 40 and 60 per cent. The duration of one duty cycle is 10 min. Designation e.g. S3 25%.
N x 100% Cyclic duration factor = N+R
A sequence of identical duty cycles, each cycle including a significant period of starting, a period of operation at constant load, and a rest and de-energized period. The cycle time is too short for thermal equilibrium to be reached. In this duty type, the motor is brought to rest by the load or by mechanical braking which does not thermally load the motor.
61
4. Electrical design
The following parameters are required to fully define the duty type: the cyclic duration factor, the number of duty cycles per hour (c/h), the moment of inertia of the load JL and the moment of inertia of the motor JM. Designation e.g. S4 25 % 120 c/h JL = 0.2 kgm2 JM = 0.1 kgm2.
D+N Cyclic duration factor = x 100% D+N+R
A sequence of identical duty cycles, each cycle consisting of a significant starting period, a period of operation at constant load, a period of rapid electric braking and a rest and de-energized period. The duty cycles are too short for thermal equilibrium to be reached. The following parameters are required to fully define the duty type: the cyclic duration factor; the number of duty cycles per hour (c/h), the moment of inertia of the load JL and the moment of inertia of the motor JM. Designation e.g. S5 40 % 120 c/h JL = 2.6 kgm2 JM = 1.3 kgm2.
D+N+F x 100% Cyclic duration factor = D+N+F+R
62
4. Electrical design
A sequence of identical duty cycles, each cycle consisting of a period at constant load and a period of operation at no-load. The duty cycles are too short for thermal equilibrium to be reached. Recommended values for the cyclic duration factor are 15, 25, 40 and 60 per cent. The duration of the duty cycle is 10 min. Designation e.g. S6 40%. Cyclic duration factor =
N N+V
x 100%
A sequence of identical duty cycles, each cycle consisting of a starting period, a period of operation at constant load, and a period of braking. The braking method is electrical braking e.g. counter-current braking. The duty cycles are too short for thermal equilibrium to be reached. The following parameters are required to fully define the duty type: the number of duty cycles per hour c/h, the moment of inertia of the load JL and the moment of inertia of the motor JM. Designation e.g. S7 500 c/h JL = 0.08 kgm2 JM =0.08 kgm2.
63
4. Electrical design
A sequence of identical duty cycles, each cycle consisting of a starting period, a period of operation at constant load corresponding to a predetermined speed, followed by one or more periods of operation at other constant loads corresponding to different speeds. There is no rest and de-energized period. The duty cycles are too short for thermal equilibrium to be reached. This duty type is used for example by pole changing motors. The following parameters are required to fully define the duty type: the number of duty cycles per hour c/h, the moment of inertia of the load JL, the moment of inertia of the motor JM, and the load, speed and cyclic duration factor for each speed of operation. Designation e.g. S8 30 c/h JL = 63.8 kgm2 JM 2.2. kgm2.
64
4. Electrical design
A duty in which, generally, load and speed are varying non-periodically within the permissible operating range. This duty includes frequently applied overloads that may greatly exceed the full loads. For this duty type, suitable full load values should be taken as the basis of the overload concept.
4.5 Uprating
Because of the lower temperature rise in the motor in short-time or intermittent duty, it is usually possible to take a higher output from the motor in these types of duty than in continuous duty, S1. The tables below show some examples of this.
Short-time duty, S2 Poles Permitted output as % of rated output in S1 continuous duty for motor size: 63-100 112-250 280-400 105 110 100 125 130 110 130 130 115
Permitted output as % of rated output in S1 continuous duty for motor size: 63-100 112-250 280-400 115 140 140 110 130 135 110 120 125 105 110 115 145 145 140 130 130 125 110 110 108 107 107 105 140 140 140 130 130 130 120 120 120 110 110 110
15%
2 4 6, 8 2 4 6, 8 2 4 6, 8 2 4 6, 8
25%
40%
60%
65
4. Electrical design
4.6 Efficiency
The efficiency values for the rated output are listed in technical data tables in our product catalogs. The table below illustrates typical values for part load. For instance, a motor with an efficiency value 90 has a 3/4 load value of 90, a 1/2 load value of 89 and a 1/4 value of 85. ABB can supply guaranteed part load values on request.
66
4. Electrical design
A motor consumes both active power, which it converts into mechanical work, and also reactive power, which is needed for magnetization but does not perform any work. The active and reactive power, represented in the diagram (below) by P and Q, together give the apparent power S. The ratio between the active power, measured in kW, and the apparent power, measured in kVA, is known as the power factor. The angle between P and S is usually designated . The power factor is equal to cos. The power factor is usually between 0.7 and 0.9. It is lower for small motors and higher for large motors.
The power factor is determined by measuring the input power, voltage and current at rated output. The power factor stated is subject to a tolerance of (1-cos)/6
If there are many motors in an installation, a lot of reactive power will be consumed and therefore the power factor will be lower. For this reason, power suppliers sometimes require the power factor of an installation to be raised. This is done by connecting capacitors to the supply which absorb reactive power and thus raise the power factor.
4.7.1 Phase compensation
With phase compensation, the capacitors are usually connected in parallel with the motor, or group of motors. However, in some cases, overcompensation can cause an induction motor to self-excite and run as a generator. Therefore, to avoid complications, it is normal practice not to compensate for more than the no-load current of the motor. The capacitors must not be connected in parallel with single phases of the winding; such an arrangement may make the motor difficult or impossible to start with star starting.
67
4. Electrical design
If a two-speed motor with separate windings has phase compensation on both windings, the capacitors should not remain in circuit on the unused winding. Under certain circumstances, such capacitors can cause increased heating of the winding and possibly also vibration.
The following formula is used to calculate the size (per phase) of a capacitor for a mains frequency of 50 Hz:
Q C = 3.2 . 106 .
where
U2
= effiency of motor
68
4. Electrical design
The power factor values for the rated output are listed in technical data tables in our product catalogs. The table below illustrates typical values. ABB can supply guaranteed values on request. As the following example illustrates, a motor with a power factor 0.85 has 3/4 load value of 0.81, 1/2 load value 0.72 and 1/4 value 0.54.
69
4. Electrical design
-connection
Connection of two-speed motors
Y connection
Two-speed motors are normally connected as illustrated below; direction of rotation as given on page 35. Motors of normal design have six terminals and one earth terminal in the terminal box. Motors with two separate windings are normally - connected. They can also be Y/Y, Y/ or /Y connected. Motors with one winding, Dahlander-connection, are connected /YY when designed for constant torque drives. For fan drive, the connection is Y/YY. A connection diagram is supplied with every motor. When starting a motor using Y connection, one must always refer to the connection diagram supplied by the starter manufacturer.
70
Mechanical design
5. Mechanical design
5 Mechanical design
Modern totally enclosed squirrel cage motors are available in a choice of aluminum, steel and cast iron frames and open drip proof motors in steel frames for different application areas.
Motor Frame Construction STANDARD Aluminum Frame Steel Frame Cast Iron Frame HAZARDOUS AREA on) EEx e, Ex N (al. & cast ir iron) on) EEx d, EEx de (cast ir iron) OPEN DRIP PROOF (steel frame) MARINE SINGLE PHASE (aluminum) BRAKE MOTORS 56 63 71 80 90 100 112 132 160 180 200 250 280 315 355 400
73
5. Mechanical design
Terminal boxes are mounted either on the top of the motor, or on either side of the motor.
Motor size and frame material 63-180 aluminum motors 200-250 aluminum motors 71cast iron motors 80-250 cast iron motors 280-400 cast iron motors 280-400 steel motors Standard Standard Standard Standard Standard Standard Standard Option Option Standard Standard Option Option Standard Terminal box Right side
On top
Left side
Non-standard design of terminal boxes, eg size, degree of protection, are available as options. The terminal box of aluminum motors in sizes 63 to 180 are provided with knockout openings. The sizes 200-250 have a terminal box with two gland plates. The terminal boxes of cast iron motors in sizes 71 to 250 are equipped with blank cover plates for connection flanges. In motor sizes 280 to 400 the terminal box is equipped with cable glands. Cable glands for all other motors available as option. The terminal box of aluminum motors allow cable entry from both sides. The terminal box of cast iron motors in sizes 71 to 250 can be rotated 4x90 and in sizes 280 to 400 2x180, to allow cable entry from either side of the motor. Degree of protection of standard terminal box is IP 55.
74
5. Mechanical design
To ensure suitable terminations are supplied for the motor, please specify cable type, quantity and size when ordering.
75
5. Mechanical design
Terminal bolt size M4 M4 M5 M5 M6 M6 M10 M10 M10 M12 M12 M12 M12 M12 M12
Coordination of terminal box and cable entry of aluminum motors Max. connection Cu-cable area 2.5 mm2 2.5 mm2 10 mm2 35 mm
2
Opening Knockout openings Knockout openings Knockout openings Knockout openings Gland plate
70 mm2
76
5. Mechanical design
5.3 Bearings
Motors are normally fitted with single row deep groove ball bearings. The complete bearing designation is stated on the rating plate of most motor types. If the bearing in the D-end of the motor is replaced with a roller bearing NU- or NJ-, higher radial forces can be handled. Roller bearings are especially suitable for belt drive applications. When there are high axial forces, angular-contact ball bearings should be used. This version is available on request. When ordering a motor with angular-contact bearings, the method of mounting and direction and magnitude of the axial force must be specified. Please see the respective product catalog for more specific details about bearings.
Bearing life
The normal life L10 of a bearing is defined, according to ISO, as the number of operating hours achieved or exceeded by 90 per cent of identical bearings in a large test series under certain specific conditions. 50 per cent of the bearings achieve at least five times this figure.
Bearing size
Reliability is the main criteria for bearing size design, taking into account the most common types of application, load of the motor and motor size. ABB uses 63 series bearings which are of robust design for longer life and higher loadability. 62 series bearings have lower noise levels, higher maximum speeds, and lower losses.
77
5. Mechanical design
5.3 Bearings
Bearing design for aluminum motors Motor size DE NDE 63 71 80 90 100 112 132 160 180 200 225 250 62-2Z series 62-2Z series 62-2Z series 63-2Z series 63-2Z series 62-2Z series 62-2Z series 62-2Z series 62-2Z series 63 series 63 series 63 series 62-2Z series 62-2Z series 62-2Z series 62-2Z series 62-2Z series 62-2Z series 62-2Z series 62-2Z series 62-2Z series 63 series 63 series 63 series
Bearing design for steel and cast iron motors Motor size DE NDE 71 80 90 100 112 132 160 180 200 225 250 280, 2 pole 280, 4-12 pole 315, 2 pole 315, 4-12 pole 355, 2 pole 355, 4-12 pole 400, 2 pole 400, 4-12 pole 62-2RS series 62-2RS series 62-2RS series 62-2RS series 62-2RS series 62-2RS series 63-Z series 63-Z series 63-Z series 63-Z series 63-Z series 6316/C4 6316/C3 6316/C4 6319/C3 6319M/C4 6322/C3 6319M/C4 6322/C3 62-2RS series 62-2RS series 62-2RSseries 62-2RS series 62-2RS series 62-2RS series 63-Z series 63-Z series 63-Zseries 63-Z series 63-Z series 6316/C4 6316/C3 6316/C4 6316/C3 6319M/C4 6319-C3 6319M/C4 6319-C3
Roller bearing option no no no no no no yes yes yes yes yes yes yes yes yes
Locked at D D D D D D D D D D D D D D D
78
5. Mechanical design
5.4 Balancing
Vibration is expressed in mm/s, rms, measured under no load with the motor on elastic mountings. The requirements apply across the measuring range 10 to 1,000 Hz.
79
5. Mechanical design
5.4 Balancing
The rotor is dynamically balanced with a half sized key in the shaft extension. For vibration, standard motors satisfy IEC 34-14, grade N. Grade R and S are also available on request.
Quality grade
Speed r/min
Maximum vibration velocity in mm/s, at shaft height 56 - 400 56 - 132 mm/s 1.8 0.71 1.12 0.45 0.71 160 - 225 mm/s 2.8 1.12 1.8 0.71 1.12 250 - 400 mm/s 4.5 1.8 2.8 1.12 1.8
> 600 < 3600 > 600 < 1800 > 1800 < 3600 > 600 < 1800 > 1800 < 3600
80
5. Mechanical design
Special attention is paid to the finish of ABB motors. Screws, steel, aluminum alloy and cast iron parts are treated by the appropriate method for each material. This ensures reliable anti-corrosion protection under the most severe environmental conditions. The finish coat is blue, Munsel color code 8B 4.5/3.25. It is also designated NCS 4822B05G. The standard finish is moisture and tropic proof in accordance with DIN 50016. It is suitable for outdoor installations, including chemical works.
Surface treatment of steel and cast iron motors Motor size 71-132 Surface treatment Two-component polyurethane paint > 60 m 160-400 Two-component epoxy paint > 70 m Paint specification Colour definition: Munsell blue 8B, 4.5/3.25/NCS 4822 B05G Colour definition: Munsell blue 8B, 4.5/3.25/NCS 4822 B05G
Surface treatment of aluminum motors Motor size 63-100 Surface treatment One-component polyester paint > 30 m 112-150 Polyester powder paint > 60 m Paint specification Colour definition: Munsell blue 8B, 4.5/3.25/NCS 4822 B05G Colour definition: Munsell blue 8B, 4.5/3.25/NCS 4822 B05G
81
Noise
6 Noise
Noise is subject to strict regulations today, with maximum permitted levels. Accordingly, we make noise reduction a major design criterion in the development of our motors.
6.2 Noise components
The principal noise components in a motor are the fan and the magnetic circuit. At high speeds and high outputs, the noise of the fan dominates. At low speeds, the magnetic circuit dominates. In slip-ring motors, the brushes and slip-rings also add noise.
85
6 Noise
6.2.1 Fan
Fan noise can be reduced by an optimized fan design. Similarly, increasing the overall efficiency of the motor enables the fan diameter to be reduced. However, the fan must be large enough to generate sufficient air flow to ensure adequate cooling of the motor. The noise level of larger motors can be reduced by fitting a silencer. On larger 2 pole motors, an unidirectional fan which rotates in one direction only and so generates less noise, can be used. ABB can advise you on the best solution for your specific application.
6.2.2 Magnetic noise
Noise can be propagated in two ways. Airborne noise caused by the fan is propagated by air. Structure borne noise is caused by the bearings, and by magnetic noise vibrating through the motor frame, foundation, walls and any pipework.
6.3.1 Airborne noise
Depending on the application, airborne noise can be reduced by fitting a silencer, a unidirectional fan or by installing a water cooled motor. For instance, choosing an air-water cooled version has a far lower noise level at high outputs and is far cheaper than a totally enclosed air-air cooled version. A totally enclosed version with separate cooling air supply and exhaust usually has the same noise level as a water cooled version, and costs even less. And as larger motors are often installed in separate rooms, the noise level is of secondary importance.
86
6 Noise
An effective method of eliminating structure borne noise is to mount accurately dimensioned vibration dampers. Choosing vibration dampers arbitrarily, could, however, worsen the noise problem.
6.3.3 Low noise motors
Most manufacturers offer low noise versions of large motors and motors for high speeds. However to achieve low noise, the motor design is modified in ways which may impair cooling. In certain cases, a larger motor may be necessary to deliver the required output, and so increase the cost. The cost of a low noise motor should therefore be weighed against the cost of other noise reducing measures that can be applied to the plant.
6.4 Sound pressure level and sound power level
Sound is pressure waves sent out by an object through the medium (usually air) in which it is immersed. The sound pressure is measured in dB during a noise test. The difference between the sound pressure detectable by the human ear, and the human pain threshold is 1:10,000,000. As the difference in pressure is so great and we experience a 10 dB difference as a doubling of the sound level, a logarithmic scale is employed where:
sound pressure level Lp = 10 log (P/P0)2 dB P0 = 2* 10 - 5 (Pa) minimum detectable noise P = measured pressure (Pa)
87
6 Noise
The sound pressure is measured in a test room to eliminate reflected noise and external sources. A microphone is variously placed 1 meter from the motor to measure sound from different directions. As the noise level varies in different directions due to the influence of the sources, a tolerance of 3 dB (A) is applicable for the average sound pressure level. The measured sound level (Lp) can be converted into power radiated from the sound source, to determine the sound power level (Lw). The formula for this is: Lw = Lp + Ls (Ls is calculated from the measuring surface, acc to DIN).
6.5 Weighting filters
Amplifiers and various filters are used when measuring the composite sound. The dB figures measured in this way have (A), (B), or (C) added after them, depending on which filter is used. Normally only the dB (A) figure is given. This corresponds most closely with the perception of the ear. The filters pass the entire frequency range, but attenuate or amplify certain parts of it. The filter characteristics correspond to stylized 40-, 70- and 100-phon curves for pure tones. Information on sound pressure level is meaningful only if the distance from the sound source is stated. For example, 80 dB(A) at a distance of one meter from a point sound source corresponds to 70 dB(A) at three meters.
6.6 Octave bands
The mean sound pressure level is measured with a broad band filter covering the entire frequency band. Measurement is also done with a
88
6 Noise
narrow band filter to define the noise level per octave band (frequency band), as the perception of the human ear is dependent on the octave band.
Octave band analysis
To get an idea of the character of the composite sound, it has proven practical to divide up the frequency range into octave bands with a ratio of 1:2 between the band limit frequencies. The frequency range is usually referred to by the mid-frequency of the band. The measured dB figures for all octave bands, the octave band levels, are generally shown in the form of an octave band diagram. A system of noise rating curves, known as NR curves, has been developed under ISO to express the subjective degree of disturbance of different noises. These curves are intended to be used when assessing the risk of damage to hearing. Similar systems are also available. NR curve numbers signify the degree of noise. For the octave band with a mid-frequency of 1,000 Hz, the number is equal to the sound pressure level in dB. The NR curve that touches the noise curve of the motor in question determines the motors noise rating. The table below illustrates the use of noise rating. It shows how long a person can remain in a noisy environment without suffering permanent hearing damage.
NR 85 90 95 105 120
Time per day > 5 hours = 5 hours = 2 hours < 20 minutes < 5 minutes
89
6 Noise
At converter duty, the motor noise produced in certain octave bands can change considerably, depending on the switching frequency of the converter. The converter does not produce a sinusoidal voltage. However, as ABB Direct Torque Control converters do not have a fixed switching frequency, the noise level is much lower than would be the case if a fixed switching frequency converter were used with the same motor.
90
6 Noise
A difference of 1 dB in sound level is barely detectable, whereas a 10 dB difference is perceived as a doubling or halving of the sound level. The table (position) illustrates the sound pressure level when several sources of sound are present. For example, diagram A shows that the sound pressure level will be 3 dB higher if the sound level of two identical sources are added together. Diagram B shows how the sound level pressure changes when the sound sources have different pressure levels. However, before logarithmic values can be added or subtracted, they must be converted into absolute numbers. An easier way of adding or subtracting sound sources is to use the diagrams below.
Adding several equal sound sources. Adding together two such sources increases the total level by 3 dB; adding together four increases it by 6 dB, and so on.
Adding two different levels. When the difference between the two sound pressure levels is greater than 10 dB, the lower level contributes so little to the total sound pressure level it may be disregarded.
91
6 Noise
dB(A) 48 55 58 63 68 63 69 69 69 72 74 75 77 80 83 85
dB(A) 37 45 48 50 54 56 60 62 62 63 66 67 68 71 80 85
dB(A) 36 43 44 49 54 61 59 59 63 63 63 66 68 75 80
dB(A) 32 39 44 43 46 52 56 59 59 60 63 63 65 66 75 80
Sound pressure level at 50 Hz net duty Cast iron motors 2 poles frame size 71 80 90 100 112 132 160 180 200 225 250 280 315 355 400 4 poles frame size 71 80 90 100 112 132 160 180 200 225 250 280 315 355 400 6 poles frame size 71 80 90 100 112 132 160 180 200 225 250 280 315 355 400 8 poles frame size 71 80 90 100 112 132 160 180 200 225 250 280 315 355 400
dB(A) 57 58 61 65 68 73 70 72 74 74 75 77 80 83 85
dB(A) 45 46 52 53 56 60 66 66 66 68 68 68 70 80 85
dB(A) 47 48 48 51 54 59 66 68 73 67 68 66 68 75 80
dB(A) 73 65 71 73 68 65 62 75 80
92
Please note every motor must be installed and maintained in accordance with the Machine Instructions booklet which is included with the motor on delivery. The installation and maintenance instructions in this chapter are for guideline purposes only. 1. Please inspect equipment for transit damage on delivery, and if found, inform the forwarding agent immediately. 2. Check all rating plate data, especially the voltage and winding connection (Y or ). 3. Remove transit locking, if fitted, and turn shaft by hand to check for free rotation.
7.2 Insulation resistance check
Before commissioning the motor, or when winding dampness is suspected, measure the insulation resistance. Resistance, measured at 25 C, must be greater than the reference value where
Ri > 20 X U + 2P M ohm (measured with 500 V DC Megger) 1000
Windings should be discharged immediately after measuring to avoid risk of electric shock. The insulation resistance reference value is halved for each 20 C rise in ambient temperature. If the reference resistance value is not attained, the winding is too damp, and must be oven dried at 90 C for 12-16 hours, followed by 105 C for 6-8 hours. NB Drain hole plugs, if fitted must always be removed before oven drying. If the dampness is caused by sea water, the winding should be rewound.
95
This is a guide only. Frame material and surface treatment effect the tightening torque.
7.4 Usage
Operating conditions
Motors are designed for use in industrial drive applications. Normal ambient temperature range -25 C to + 40 C. Maximum altitude 1,000 m above sea level.
Safety
All motors must be installed and operated by qualified personnel familiar with all relevant safety requirements. Safety, and accident prevention equipment required by local health and safety regulations must always be provided at the mounting and operating site.
WARNING
Small motors with supply current directly switched by thermally sensitive switches can start automatically.
Accident prevention
Never stand on a motor. To prevent burns, the outer casing must never be touched during operation. Special instructions may also apply to certain special motor applications (e.g. frequency converter supply). Always use lifting lugs to lift the motor.
96
7.5 Handling
Storage
s Motors should always be stored in a dry, vibration free and dust free environment. s Unprotected machined surfaces (shaft-ends and flanges) should be treated with an anti-corrosive. s It is recommended that shafts are periodically rotated by hand to prevent grease migration. s Anti condensation heaters, if fitted, should preferably be energized. The characteristics of electrolytic capacitors, if fitted to single-phase motors, will require reforming if stored over 12 months.
Please contact ABB Motors for details.
Transportation
Machines fitted with cylindrical-roller and/or angular-contact bearings must be secured with locking devices during transit.
Machine weights
The total weight of machines with the same frame size can vary depending on output, mounting arrangement and add-on special details. More accurate weight data can be found on the rating plate of each motor.
97
7.6 Foundations
Customers are responsible for preparing the foundation for the motor. The foundation must be smooth, level and, if possible, vibration free. A concrete foundation is therefore recommended. If a metal foundation is used, this should be treated with an anti-corrosive. The foundation must be stable enough to withstand the forces that can arise in the event of a three-phase short-circuit. Short-circuit torque is primarily a damped sinusoidal oscillation, and can thus have both positive and negative values. The stress on the foundation can be calculated with the aid of the data tables in the motor catalog and the formula below.
F = 0.5 x g x m + 4 x Tmax A
where F = stress per side, N g = gravitational acceleration, 9.81 ms2 m = weight of motor, kg Tmax = maximum torque, Nm A = lateral distance between the holes in the motor feet, m. The dimension is taken from the dimension drawing and is expressed in meters. The foundation should be dimensioned to afford a sufficiently large resonance gap between the natural frequency of the installation and any interference frequencies.
7.6.1 Foundation studs
The motor should be secured with foundation studs or a base plate. Motors for belt drives should be mounted on slide rails. The foundation studs are bolted to the feet of the motor once the locating pins have been inserted in the holes reamed for the purpose. The studs must be fitted to the right feet with a 1-2 mm shim between the stud and the feet; see the markings on the studs and on the stator feet. Place the motor on the foundation and align the coupling. With a
98
spirit level check that the shaft is horizontal. The height of the stator frame can be adjusted with either setting screws or shims. When you are quite sure alignment is correct, grout the blocks.
7.7 Coupling alignment
Motors must always be aligned accurately. This is particularly important in the case of directly coupled motors. Incorrect alignment can lead to bearing failure, vibration, and even shaft fracture. In the event of bearing failure or if vibration is detected, the alignment should be checked immediately. The best way of achieving proper alignment is to mount a pair of dial gauges as shown (page 100). Each gauge is on a coupling half, and they indicate the difference between the coupling halves both axially and radially. Slowly rotating the shafts while observing the gauge readings, gives an indication of the adjustments that need to be made. The coupling halves must be loosely bolted together so that they can easily follow each other when they are turned. To determine whether the shafts are parallel, measure with a feeler gauge the distance x between the outer edges of the coupling halves at a point on the periphery: see page 100. Then turn both halves together through 90, without changing the relative positions of the shafts, and measure again at exactly the same point. Measure the distance again after 180 and 270 rotation. For typical coupling sizes, the difference between the highest and lowest readings must not exceed 0.05 mm. To check that the shaft centres are directly opposite each other, place a steel rule parallel with the shafts on the turned periphery of one coupling half and then measure the clearance between the periphery of the other half and the rule in four positions as a parallelism check. The difference between the highest and lowest readings must not exceed 0.05 mm.
99
When aligning a motor with a machine whose frame reaches a different temperature to the motor in normal service, allowance must be made for the difference in shaft height resulting from different thermal expansion. For the motor, the increase in height is about 0.03 % from ambient temperature to operating temperature at full output. Mounting instructions from manufacturers of pumps, gear units etc. often state the vertical and lateral displacement of the shaft at operating temperature. It is important to bear in mind this information to avoid vibration and other problems in service.
100
Care must be taken when fitting pulleys and coupling halves to prevent damage to bearings. They must never be forced into place or levered out. A coupling half or pulley that is a push fit on the shaft can be pushed on by hand for about half the length of the shaft extension. A special tool or fully-threaded bolt, a nut and two flat pieces of metal, are then used to push it fully home against the shoulder of the shaft.
Mounting a pulley with a fully-threaded bolt, a nut and two flat pieces of metal.
101
Motors for belt drives should be mounted on slide rails as shown in figure 2. The slide rails should be placed horizontally on the same level. Then position the motor and slide rails on the foundation and align them such that the middle of the motor pulley coincides with the middle of the pulley on the driven machine. Check the motor shaft is parallel with the drive shaft, and tension the belt in accordance with supplier instructions. Do not exceed the maximum belt forces (i.e. radial bearing loads) stated in the product catalog. The slide rail nearest the belt must be positioned such that the tensioning screw is between the motor and the driven machine. The screw in the other slide rail must be on the other side. See figure. After alignment, grout in the slide rail fixing bolts.
WARNING
Do not over-tension the belts. Excessive belt tension can damage bearings and cause shaft fracture.
With belt drive the shafts must be parallel and the pulleys must be in line.
102
Always take special care with bearings. Bearings should be fitted by heating or purpose made tools, and removed with pullers. When a bearing is to be mounted on a shaft, cold or hot mounting may be used. Cold mounting is only suitable for small bearings and bearings that do not have to be pressed far on to the shaft. For hot mounting and where the bearing is an interference fit on the shaft, the bearing is first heated in an oil bath or with a special heater. It is then pressed onto the shaft with a mounting sleeve that fits the inner ring of the bearing. Grease-filled bearings, which usually have sealing plates or shield plates, should not be heated.
103
7.10 Lubrication
ABB Motors policy is to have reliability as a vital issue in bearing design as well as in bearing lubrication systems. That is why we, as standard, follow the L1-principle (meaning that 99 per cent of the motors are sure to make the interval time). The lubrication intervals can also be calculated according to L10-policy which means that 90 per cent of the motors are sure to make the interval time. L 10-values, which are normally doubled compared to L1-values, are available from ABB Motors at request.
7.10.1 Motors with permanently greased bearings
Motors up to frame size 180 are normally fitted with permanently greased bearings of type Z or 2Z.
Guidelines for bearing lifetime:
s 4 pole motors, 20,000 - 40,000 duty hours1) s 2 and 2/4 pole motors, 10,000 - 20,000 duty hours1) s The shorter intervals apply to larger motors.
1
Lubricate the motor when operational. If a grease outlet plug is fitted, temporarily remove when lubricating, or permanently with auto lubrication. If the motor is fitted with a lubrication plate, use values given, else use the values accoding to L1 -principle, following on the next page:
104
7.10 Lubrication
L1-principle
The following lubrication table follows the L1- principle, which is the ABB standard for all motors.
Frame size Amount of grease g 3600 r/min 3000 r/min 1800 r/min 1500 r/min 1000 r/min 500-900 r/min
26 30 40 46 60 67 90 120 120
105
7.10 Lubrication
The tables are prepared for horizontally mounted motors. Halve table values for vertically mounted motors. If the motor is fitted with a lubrication information plate, values in that plate should be followed. More detailed information can be found in the Machine Instructions from ABB Motors.
106
The SI system
8. The SI system
This section explains some of those units in the SI (Systeme International dUnits) system of units that are used in conjuction with electric motors and their application. A distinction is made between quantity, quantity value, unit, measurement number and between the name and symbol of a unit. These distinctions are explained by the following example:
Example:
Name power watt Symbol P W
Quantity Unit
P = 5.4 W, i.e. the power is 5.4 watts Measurement number = 5.4 Symbol for unit = W Name of unit = watt Symbol for quantity = P Name of quantity = power Value of quantity = 5.4 watts
109
8. The SI system
I A V t
f v a g
Energy
Active Watt second Watt hour Reactive Apparent W Ws Wh Wq Ws J 1 J = 1 Ws = 1 Nm
Var second Var hour Volt-ampere second Volt-ampere hour Watt Var Volt-ampere
Power
Active Reactive Apparent
1
P Q, Pq S, Ps
W var VA
110
8. The SI system
Remarks
Mechanical
Mass Density Force Moment of force Moment of inertia Pressure
1 Pa = 1 N/m2 1 N/m2 = 0.102 kp/m2 = 10-5 bar 1 bar = 105 N/m2 Old name: absolute temperature 0 C = 273.15 K The intervall 1 K is identical to the interval 1 C
Heat
Thermodynamic temperature Celsius temperature Temperature difference Thermal energy T, , t T,
Q V U I C X R Z
Electricity
Electric potential Electric voltage Electric current Capacitance Reactance Resistance Impedance
Prefixes for multiples: Multiples of SI units are indicated by the following prefixes. The use of prefixes in brackets should be restricted. 103 (102) (101) (10-1) (10-2) 10-3 10-6 10-9 10-12 10-15 10-18 kilo (hecto) (deca) (deci) (centi) milli micro nano pico femto atto k (h) (da) (d) (c) m n p f a
111
8. The SI system
The units normally used for technical applications are SI units. However, other units may be encountered in descriptions, drawings, etc., especially where the inch system is involved. Note that the US gallon and the UK gallon are not the same. To avoid confusion it is advisable to put US or UK after the unit.
Length 1 nm = 1.852 km 1 mile = 1.609344 km 1 yd = 0.9144 m 1 ft = 0.3048 m 1 in = 25.4 mm Velocity 1 knot = 1.852 km/h 1 m/s = 3.6 km/h 1 mile/h = 1.61 km/h Area 1 acre = 0.405 ha 1 ft2 = 0.0929 m2 1 in2 = 6.45 cm2 Volume 1ft3 = 0.0283 m3 1 in3 = 16.4 cm3 1 gallon (UK) = 4.55 l 1 gallon (US) =3.79 l 1 pint = 0.568 l 1 km = 0.540 nm 1 km = 0.621 mile 1 m = 1.09 yd 1 m = 3.28 ft 1 mm = 0.039 in 1 atm = 101.325 kPa 1 lbf/in2 = 6.89 kPa Energy 1 kpm = 9.80665 J 1 cal = 4.1868 J 1 kWh = 3.6 MJ 1 kPa = 0.00987 atm 1 kPa = 0.145 lbf/in2
Power 1 hp = 0.736 kW 1 kW = 1.36 hp 1 hp (UK, US) = 0.746 kW 1 kW = 1.34 hp (UK, US) 1 kcal/h = 1.16 W 1 W = 0.860 kcal/h Temperature 0 C = C = 0 F = F =
1 m3 = 36.3 ft3 1 cm3 = 0.0610 in3 1 l = 0.220 gallon (UK) 1 l = 0.264 gallon (US) 1 l = 1.76 pint
Flow 1 m3/h = 0.278 x 10-3 m3/s 1 m3/s = 3600 m3/h 1 cfm = 0.472 x 10-3 m3/s 1 m3/s = 2120 cfm Mass 1 lb = 0.454 kg 1 oz = 28.3 g Force 1 kp = 9.80665 N 1 lbf = 4.45 N Pressure 1 mm vp = 9.81 Pa 1 kp/cm2 = 98.0665 kPa 1 kp/cm2 = 0.980665 bar
1 kg = 2.20 lb 1 g = 0.0352 oz
Comparison table for temperatures F C 0 -17.8 10 -12.2 20 -6.7 30 -1.1 32 0 40 4.4 50 9.9 60 15.5 70 21.0 80 23.6 90 32.1 100 37.8
112
Selecting a motor
9. Selecting a motor
The two fundamental variables to consider when selecting a motor are: s The electricity supply to which the motor will be connected s The type of enclosure or housing
Type of enclosure
There are two basic enclosure options available: drip proof in steel or totally enclosed, in aluminum, steel and cast iron. The totally enclosed fan cooled (TEFC) motor is the predominant standard for industrial applications today. The versatile TEFC is fully enclosed within the motor frame, with cooling air directed over it by an externally mounted fan.
List ABB motors: Standard three phase motors IEC and NEMA Hazardous area motors Marine motors Open drip proof motors Single phase motors Brake motors Integral motors Windmill generators Water cooled motors Roller table motors Fan application motors Smoke venting motors High speed motors Traction motors Reluctance motors
Loading is determined by the equipment to be driven, and the torque available at the shaft. Electric motors have standard outputs per frame size.
9.3 Speed
The induction motor is a fixed single speed machine. Its speed is dependent on the frequency of the electricity supply and the stator winding design.
115
9. Selecting a motor
9.3 Speed
No load speed is slightly lower than synchronous speed due to the no load losses in the machine. Full load speed is typically a further 3-4 per cent lower than no load speed.
Synchronous Speed r/min = Frequency X 120 Number of poles (Stator winding)
Motor speeds Number of poles 2 4 6 8 10 12 16 50 Hz speed r/min Synchronous Typical full load 3.000 2.900 1.500 1.440 1.000 960 750 720 600 580 500 480 375 360 60 Hz speed r/min Synchronous Typical full load 3.600 3.450 1.800 1.740 1.200 1.150 900 850 720 700 600 580 450 430
9.4 Mounting
The environment in which the motor is to operate is an important factor to consider when ordering, as the ambient temperature, humidity and altitude can all affect performance.
116
9. Selecting a motor
Check List
Safe area TEFC Motor Fixed Speed Supply Volts Rating Speed Duty Drive Insulation/Temp rise Torque type Environmental conditions IP kW r/min
Ph Direct / Quadratic
Pole
Hz
Mounting IM
Ambient
Belt
o o
Constant
Relative Humidity
Check List
Safe area TEFC Motor Variable Speed Supply Volts Ph Rating Speed Duty Drive Insulation/Temp rise Torque type Environmental conditions IP VSD Type of controller Speed Range Abs Power (kW) Output Filters (du/dt) Max cable length (Metres) kW r/min
o o
Direct / Quadratic
Pole
Hz
Mounting IM
Ambient
o o o
Belt
Constant
Max Max
Relative Humidity
o
DTC
117
Fitted
o
PWM
Min Min
Not fitted
10
10.1 General
Squirrel cage induction motors offer excellent availability, reliability and efficiency. However, they have two weaknesses; starting performance and smooth speed control over a wide range. A motor with a frequency converter - variable speed drive (VSD) - solves both these problems. A variable speed drive motor can be started softly with low starting current, and the speed can be controlled and adjusted to suit the application demand without steps over a wide range. Manufacturers are increasingly recognizing the tremendous advantages VSD delivers. Today VSDs account for about 10 per cent of motor drives and this is expected to rise to 25 per cent in the year 2005. The principal advantages of VSD: s Optimal speed and control accuracy to deliver major energy savings (typically 50 per cent). s Lower maintenance s Higher production quality and greater productivity.
121
10.2 Converters
Converters are power electronic devices which convert input AC power at fixed voltage and frequency into output electric power with variable voltage and frequency. Direct or indirect converters are used, depending on the solution employed.
10.2.1 Direct converters
Direct converters such as cyclo-converters and matrix converters change the input directly to output with no intermediate links. Cyclo-converters are used in high power applications (MW range) and at low frequencies.
10.2.2 Indirect converters
Indirect converters are either current source, or voltage source converters. In a current-source converter (CSC), the intermediate link acts as a dccurrent source and the output consists of controlled current pulses at continuously variable frequency which are fed to different phases of the three-phase system. This enables stepless speed control of the motor. In a voltage-source converter (VSC), the dc link acts as a dc-voltage network and the output is a voltage pulse, or voltage pulse sequence.
10.3 Pulse Width Modulation (PWM)
ABB variable speed drives use Pulse Width Modulated (PWM) with variable swiching frequency voltage source converters as these best meet the majority of requirements. In a PWM drive, the rectifier converts the input line power which has a nominally fixed voltage and frequency to fixed voltage dc power. This fixed voltage dc power is then filtered to reduce the ripple voltage resulting from the rectification of the ac line. The inverter then changes the fixed voltage dc power to ac output power with adjustable voltage and frequency.
122
Frequency converter
Motor
+
V1 V3 V5
U, 3 ~
C
V2 V4 V6
Rectifier
DC- circuit
Inverter unit
A complete dimensioning program for drives and motors are availiable on a CD. Below here is a brief information about motor and converter selection.
Motor selection
The motor selected should have a specified load torque totally below the guideline for the converter to be used. However, if operation will not be continuous in all speed range duty points, the load curve may exceed the guideline. In which case, special dimensioning is required. Further, the maximum torque must be at least 40 per cent higher than the load torque at any frequency, and the maximum permissible speed of the motor must not be exceeded.
Motor design
Converters with different working principles, modulation patterns and switching frequencies give different performances for the same motor.
123
As performance and behavior is also dependent on the motor design and construction, motors of the same size and output power but of different design, may behave quite differently with the same converter.
Converter selection
The converter should be selected according to the nominal power P N of the motor. The rated current of the converter must also be that of the motor selected.
124
Both theoretical calculations and laboratory tests show that the continuous maximum load (torque) of a converter driven motor is mainly dependent on the modulation pattern and switching frequency of the converter. The tables below offer guidelines for motor selection.
Motor Loadability with ACS600. Standard aluminum and cast iron motors
These guidelines present the maximum continuous load torque of a motor as a function of frequency (speed) to give the same temperature rise as with rated sinusoidal voltage supply at nominal frequency and full rated load. The temperature rise is normally class B. If the ABB catalogue indicates that class F temperature rise is utilized on sinusoidal supply, according to the guidelines, the converter drive also utilizes class F temperature rise. For general applications, the following motors from the ABB range (IP 55) can be used with frequency converters: s Standard aluminum motors s Standard cast iron motors s Standard flameproof motors type EEx de, EEx d. For pump and fan applications, standard steel motors (IP 55) and open drip proof motors (IP 23) can be used.
125
Slip ring motors are not recommended for converter applications. Please note that in critical conditions, frequency converter application may require a special rotor design in frame sizes 355 and 400. Torque is reduced due to extra heating from harmonics and a decrease in cooling according to frequency range. Loadability can therefore be improved by more effective cooling, filtering the converter output voltage and by special rotor design
s More effective cooling
More effective cooling is achieved by mounting a separate constant speed cooling fan, which is especially beneficial at low speeds. Selecting a fan motor speed and fan design to deliver a higher cooling effect than that of the standard motor at nominal speed, will give an improved cooling effect over the entire speed range. Liquid cooling (water cooled motors) is another very effective cooling method. In very demanding cases, the bearing end shields must also be cooled.
s Filtering
Filtering the converter output voltage reduces the harmonic content of the motor voltage and current and so causes less additional losses in the motor. This minimizes the need for derating. The full power of the drive and the speed range must be taken into account when dimensioning filters (additional reactances). Filters also reduce electromagnetic noise, EMC and voltage peak problems. However they do limit the maximum torque of the motor.
s Special rotor design
A motor with a rotor cage and rotor bars specifically designed for converter drive performs better in a converter drive but less well in normal network application.
126
In a PWM converter, the output voltage (or current) is a voltage (current) pulse or pattern of pulses. Depending on the type of power components and the design of power circuit, a considerable overshoot is developed at the voltage pulse leading edge. The insulation level must, therefore, always be checked using the following simple rules: s If the nominal voltage of the supply network is up to 500 V, no insulation strengthening is required for standard ABB induction motors s If the network voltage is 525-690 V, reinforced motor insulation is recommended If the rated voltage is 500-575 V, the need for reinforced insulation will depend on the drive, especially the converter type and size, the motor size, and the cable length between the motor and converter terminals.
10.7 Earthing
In a converter drive special attention must be paid to the earthing arrangements to ensure: s Proper action of all protective devices and relays for general safety s Minimum or acceptable level of electromagnetic interference s Acceptable level of bearing voltages to avoid bearing currents and bearing failures.
127
In a frequency converter drive the actual speed of the motor may deviate considerably from its rated speed. For higher speed operation, the maximum permissible speed of the motor type - or critical speed of the entire equipment must not be exceeded.
The maximum permissible speeds for basic motors are as follows: Frame size 63-100 112-200 225-280 315, 2-pole 315, other pole numbers 355, 400 2-pole 355, 400 other pole numbers Speed r/min 6000 4500 3600 3600 3000 3600 2500
When high speed operation exceeds the nominal speed of the motor, the maximum torque and bearing construction should also be checked.
10.8.1 Maximum torque
In the field weakening area, the voltage of the motor is constant, but the motor flux and the capability to produce torque reduces rapidly when the frequency is increased. At the highest speed point (or at any other duty point in the field weakening area), the maximum (breakdown) torque must be not less than 40 per cent higher than the load torque. If filters or additional reactances are used between the converter and the motor, the voltage drop of the fundamental voltage with full load current must be taken into account.
10.8.2 Bearing construction
There is a limit to the speed at which rolling bearings can be operated. Bearing type and size, internal design, load, lubrication and cooling conditions, plus cage design, accuracy and internal clearance, all influence the permissible maximum speed.
128
10.8.3 Lubrication
In general, the limit is set by the operating temperature with respect to the lubricant and bearing component. Changing the bearings enables higher speeds. However, if this is done, the lubrication should also be upgraded.
10.8.3 Lubrication
The sheer strength of the lubricant is determined by its base oil viscosity and thickener, which, in turn, determines the permissible operating speed for the particular bearing. The maximum speed can be increased by using high speed greases or oil lubrication. Very accurate lubrication with small quantities also reduces the bearing friction and heat generation.
10.8.4 Fan noise
Fan noise increases with the speed of the motor and generally becomes dominant at 50 Hz for 2- and 4-pole motors. If the motor speed further increases, the noise level will also be higher. The noise level increase can be calculated approximately using the following formula:
Lsp = 60 x log n2 n1 dB (A)
where Lsp = increase of the sound pressure level when the speed is changed from n1 to n2. Fan noise is typically white noise, i.e. containing all frequencies within the audible frequency range. Fan noise can be reduced by either: s Replacing the fan (and fan cover) with a reduced outer diameter fan s Using a unidirectional fan s Fitting a silencer
129
10.9 Balancing
The balancing accuracy and mechanical strength of all rotating parts should be checked if the standard motor speed limit is to be exceeded. All other parts mounted on the motor shaft, such as coupling halves and pulleys must also be carefully balanced.
10.10 Critical speeds
The first critical speed of a standard motor must never be exceeded, and a safety margin of 25 per cent allowed.
10.11 Shaft seals
All rubbing shaft seals (V-rings, oil seals, sealed bearings RS, etc.) have a recommended maximum speed limit. If this is below the proposed high speed operation, non-rubbing labyrinth seals should be used.
10.12 Low speed operation
10.12.1 Lubrication
At very low speeds, the motors ventilation fan loses its cooling capacity. If the operational temperature of the motor bearings is 80 C, (check by measuring the surface temperature of the bearing endshields), shorter relubrication intervals or special grease (Extreme Pressure (EP) grease or high temperature lubricant) should be used. The relubrication interval should be halved for each 15 C increase in the bearing temperature above + 70 C.
10.12.2 Cooling capacity
The air flow and cooling capacity depends on the fan speed. A separate constant speed fan can be used to increase cooling capacity and motor loadability at low speeds. As the internal cooling is not affected by an outer separate fan, a small reduction in loadability is still necessary at very low speeds.
130
The harmonic components of the frequency converter voltage increase the magnetic noise level of the motor. The frequency range of these magnetic force waves can cause structural resonance in the motor, especially steel frame ones. Magnetic noise can be reduced by: s Increasing the switching frequency, giving higher order harmonics and lower amplitudes, less sensitive to the human ear s Filtering the harmonic components at the converter output filter or in additional reactances s Motor silencer s Separate cooling system with white fan noise which masks the magnetic noise.
131