For Biomass 2 LR
For Biomass 2 LR
For Biomass 2 LR
Introducing automatically fed systems Biomass combustion Fuel handling Supplying the boiler Automatic feed burner types Buffer vessels and boiler controls System design
Biomass boilers
Low temperature hot water biomass boilers, those operating at up to 95 C, can be classified by various methods based on fuel type or on the physical characteristics of the boilers. The classification that follows is based on fuel type. The critical difference between stoves and boilers is that stoves provide radiant room heating while boilers only produce hot water, either for heating or domestic hot water (DHW). Although some stoves will allow the incorporation of a boiler and radiators, stoves are usually much simpler devices than boilers. Figure 1(a) and (b) shows two examples of medium scale boilers that can be used in different commercial settings.
Figure 1b
Figure 1a
features. This guide deals with larger pellet systems (from 50 kW up to several MW). For further detailed information on pellet stoves and small pellet boilers (up to around 50 kW) see Biomass heating: a guide to small log and wood pellet systems.
Figure 1 (a) and (b) Medium scale commercial boilers (Forestry Commission).
Log boilers
These appliances run on logs and other larger pieces of wood, including joinery offcuts. Log boilers do not have automatic feed systems and are only suitable for installation where a certain amount of physical labour is available and there is space for a managed wood store. Log boilers are batch fired devices and simple to operate but they do require a large water storage cylinder (also known as a thermal store, accumulator or buffer tank) to capture the heat produced, except in extremely simple small stoves with an integral water-jacket. Log boilers up to 50 kW are covered in detail in Biomass heating: a guide to small log and wood pellet systems.
1
All moisture contents quoted in this publication are on a wet basis, that is
Biomass combustion
While several different types of biomass boilers are described in this guide, their principle of operation is the same. In many respects the technology used to burn wood is similar to that used in coal boilers which are still in use in some parts of the UK. Fuel is fed to the grate mechanically where it undergoes combustion to produce energy. Figure 2 outlines the main stages and the temperature ranges associated with them; however it is a simplification and several stages can occur simultaneously. Separate control of primary air (from beneath the grate) and secondary air (into the gas oxidation zone) is required to maintain the lower grate temperature for stage 2 while ensuring that a sufficiently high temperature and turbulence exist to oxidise the wood gases completely at stage 4. Careful control of the excess O2 content (often monitored by a lambda sensor) and gas oxidation zone combustion temperature at stage 4 is required to minimise the formation of soot, CO and NOx and maximise thermal efficiency. However, as complete oxidation of the wood gases usually requires 4 a slightly higher combustion Combustion temperature than in fossil of gases 800-1600 C fuelled boilers, the quantity of NOx produced by biomass boilers per unit of heat generated is usually greater than that from gas fuelled boilers. If wet fuel is not dried sufficiently by the boiler (because the fuel moisture content is outside the fuel tolerance range of the boiler) incomplete gasification and oxidation will occur and black smoke will be produced. In addition, the tars released at stage 2 will gradually coat the heat exchanger surfaces resulting in reduced heat exchange efficiency and the eventual failure of the boiler. Tar accumulation is also one reason why many manufacturers recommend minimum running periods for their boilers to ensure that combustion chambers and heat exchangers reach full working temperature to drive off the heavy volatiles deposited during the heat-up phase. The energy used to evaporate the moisture is not available to the appliance user. If the fuel is too dry for the boiler, grate (stage 2) and oxidation zone (stage 4) temperatures can be too high, resulting in the formation of slag and a higher concentration of NO2. This latter issue can be addressed by installing flue gas recirculation to primary air. This allows dry fuel to be used in a boiler designed to burn wet fuel by maintaining the primary gas flow rate while reducing its O2 content, thus reducing the gasification rates (stage 3) on the grate.
1
Warming and drying < 150 C
2
Pyrolysis 150-500 C
3
Gasification 500-800 C
When there is no longer a demand for heat from a biomass boiler, the boiler continues to produce heat for some time (unlike a liquid or gas fuelled boiler which ceases producing heat immediately). Fuel on the grate will need to be burned off and, depending on the type of boiler, the fuel in the feed system may need to be emptied onto the grate and burned as well. The refractory lining of the boiler will also need to release heat to prevent steam being generated in the boiler. The time taken for a boiler to stop producing hot water will vary between 15 minutes and 2 hours, and the heat produced during this period must be absorbed or dissipated. The usual practice is to store the heat in a large water-filled buffer vessel, sized to the specific boiler output and thermal mass. The buffer vessel acts as a store to absorb part of the boiler output when the system load is below the minimum operating output of the boiler. This stored heat is then used at the start of the heating period each day when the buffer will discharge in a controlled manner to satisfy part or all of the initial peak heat demand while the biomass boiler heats up.
Fuel handling
Fuel storage and extraction
Automatic feed boilers burning wood pellets or wood chips can also be classified by type, and range in size from 10 kW to the very largest boilers. Before describing these main types of boilers it is important to understand the variations in fuel supply systems, starting with the fuel store and ending with the delivery of fuel into the boiler. Fuel can be stored in a range of ways, including silos, hoppers, containerised stores, flexible fabric silos, and in sheds above fuel extractor systems in large installations. Figures 4, 5 and 6 show combinations of fuel silos and fuel extractor mechanisms.
Wood chips are often stored in a silo with a sloping floor, and extracted using an outfeed mechanism known as an agitator which prevents bridging within the stack and ensures a continual feed of fuel. This usually comprises two sweeping arms which push wood chip onto the extract auger, shown in Figure 5. Alternatively, wood chips with a moisture content less than 35% can be stored in a hopper bottom incorporating a fuel extractor mechanism. Both chips and pellets can be delivered by tipping into a silo, for example where this is constructed underground or where ramped access is provided. Articulated containers can deliver up to 25 tonnes of wood chip at a time and may either be delivered using a walking floor or pneumatically.
Fuel silos
Wood pellets are usually stored in a hopper bottom store. Providing the angle of the floor is greater than 40pellets will flow down into the extractor auger. They can be filled by pneumatic delivery where one of the two hoses (Figure 4) receives the pellets and the other provides pressure relief and recovers the dust produced to the delivery vehicle. While these silos can be fitted with auger outfeed equipment, pellets can also be extracted by a vacuum pump to the boilers dosing silo. This also requires a pressure relief hose.
Figure 4 Pellet store showing pneumatic delivery coupling (Ashwell Engineering Ltd).
Pneumatic delivery of wood pellets is now routine, and some wood chip delivery companies are offering blown fuel delivery (Figure 6), allowing less accessible stores to be reached. For wood chips blown delivery is slow compared to tipping, and this will add to the cost of fuel delivery.
Storage sheds
Large or very large-scale fuel storage is best achieved by using storage sheds. Deliveries are either received from articulated vehicles or material is chipped directly into the storage area. Fuel handling in large stores requires the use of mechanical handling equipment, such as a front end loader or a mechanical grab, with walking floor arrangements or conveyor systems to move the material to the main boiler unit. Wood chips can also be stored in large sheds and moved to a smaller boiler feed hopper as required.
Figure 7 Wood chip delivery using a removable container system (Forestry Commission).
Walking floors
An alternative method of fuel extraction from a silo is by walking floor. These floors can be designed to take the weight of a delivery vehicle where chips or pellets are tipped directly onto the floor (Figure 9). Lighter weight versions are available where fuel is loaded onto the floor by mechanical shovel. Fuel is extracted from the walking floor by either a cross-feed auger (Figure 10) or a hydraulically operated ram-stoker system.
Figure 9 Chip store using a walking floor (Ashwell Engineering Ltd).
Flexible silos
For smaller wood pellet installations a range of prefabricated sectional and collapsible silos manufactured from plastics, steel or fabric (Figure 8) are available. These are designed for installation in difficult to access and confined spaces, and can be assembled in situ in basements or loft spaces.
Figure 8 Flexible bag type chip store (Organic Energy (UK) Ltd).
Wood pellets
The safety risk with wood pellets relates to the dust produced during delivery by pneumatic conveying. When pellets are blown into a silo a proportion break up and produce the sawdust from which they were manufactured. If the dust concentration is not controlled it is possible for an explosive mixture of dust in air to be created which could explode if an ignition source is present. Minimising dust build up and ensuring no ignition sources are present will prevent this, and can be done by the combination of design, maintenance and operation. Buying quality pellets with a low dust content and good mechanical durability is also important. Abrasion and impact during delivery of pellets can generate fine dust. This can be prevented by using smooth metal delivery pipes, with any bends of large radius, and a yielding impact baffle opposite the point of exit from the delivery tube to ensure that pellets are not shattered on impact with the opposite wall of the store. It is also important that, during delivery, tanker drivers avoid excessive pressure and there is some mechanism for dust collection. This will vary between different pellet store designs and size. The store should be regularly checked for build up of dust and periodically cleaned out. To ensure that no possible ignition source is present there should be no electrical fittings within the store, or if they are required, that they meet the appropriate Explosives Atmospheres (ATEX) specification. Delivery pipes must also be securely bonded to earth to avoid build up of static charge. Another risk is from the potential for wood pellets to outgas CO in storage. This gas is both toxic and flammable. In particular nobody should enter an enclosed pellet store until it has been thoroughly ventilated, and only under the supervision of another person, outside the store. Other safety mechanisms include zoning to classify potentially hazardous areas, ensuring dust is effectively contained within the store and cannot escape into other areas (such as the boiler room), a fireproof partition between the fuel store and boiler room, and in extreme cases inclusion of an explosion relief panel. For information on DSEAR (The Dangerous Substances and Explosive Atmospheres Regulations 2002) and ATEX (Explosive Atmospheres Directives 99/92/EC (ATEX 137) and 94/9/EC (ATEX 100)) and guidance on safe storage practice see Sources of further information (page 20).
Wood chips
Unless wood chips are reasonably dry, typically less than 30% moisture content, they may degrade in storage. Microbial activity can lead to piles of wood chips generating heat as they decompose. The loss of calorific value via decomposition has been measured at 1% per month. Under the right conditions fungal spores will develop in the chip pile and these spores will be released when the pile is disturbed; if inhaled they can cause an incurable disease commonly known as farmers lung. To avoid the formation of spores moist or wet wood chip should be stored for as short a period as possible, and should be used within 1 month of being chipped. In very large piles of wood chips it is possible for the heat released from microbial action to lead to an increase in temperature in the heart of the pile, sufficient to give rise to spontaneous ignition, causing a fire. The potential for this to occur will depend on a number of factors, including the moisture content of the chips, ambient conditions and the store design; advice on the maximum safe size for piles of chips varies between countries and sources, with figures quoted from 8 m to 15 m. In any case, chips in longterm storage should be turned regularly to prevent microbial activity and aid drying.
Figure 11 Fuel feed safety devices: rotary valve and mains water drench valve (RBAN).
Rotary valve
Fuel from the extractor auger is dropped onto the top of a rotary valve which meters fuel onto the boiler feed auger below. The segmented design of the rotary valve enables it to provide a positive seal between the two augers every time it rotates, physically preventing the fire from travelling to the fuel silo. The inclined stoker also provides a degree of burn-back protection. A burn-back flap valve may be used as an alternative to a rotary valve.
Advantages
Auger feeds
Disadvantages
Can be configured into a series of augers to allow fuel to Will only accept fuels of a consistent quality and not be moved between levels and around corners. exceeding certain dimensions. Only the larger augers would be able to accept wood chips with a dimension of Generally cheaper than hydraulic feeds. up to 100 mm (P100 grade). Do not work well with large and thick shards of timber which can cause augers to jam, but can incorporate a sliver breaker. In very cold weather wet wood chip can freeze in the extract augers, causing the boiler to shut down. Can handle very large pieces of wood, breaking all but the most oversized pieces. Generally contain splitting knives to break up very large pieces of wood. Can handle frozen wood chip. More reliable than auger feeds and very difficult to jam. Generally more expensive than auger feeds. Very expensive to achieve significant changes of level. Usually need to be on the same plane and in line with the boiler fuel inlet. There is a possible fire risk with a fine mist hydraulic fluid leak onto an ignition source. Use of fire resistant hydraulic fluid is advised.
Hydraulic feeds
Bi-metallic strip
Some manufacturers install a bi-metallic strip within the feed auger casing immediately outside the combustion chamber. This strip is set to operate if the temperature in the auger housing exceeds about 90 C, and sends a disrupt signal to the boiler control system to stop the extractor auger, rotary valve and feed auger from operating.
10
Figure 12 Diagram of a boiler using a stoker burner combustion system (after R. Landen).
Stoker burner boilers can burn wood pellets and wood chips up to 30% moisture content (MC). These boilers usually have moderate levels of refractory lining and are not of the high water content (HWC) type in order to produce a fast response to heating load demands. On small stoker burner boilers there may be only one combustion fan as shown in Figure 12, which means that it is very difficult to separate the primary air supply to the grate from that in the final combustion zone above the grate. As a result the potential for overheating and subsequent slag formation on the grate is very high, and some boiler manufacturers have included a water cooling circuit within the grate as a preventative measure.
Underfed stoker boilers can burn wood pellets and wood chips up to 30% MC. Some may be designed specifically for use only with pellets, in which case very little refractory lining may be installed. For wood chips up to 30% MC a moderate level of refractory lining will be installed, and the boiler is usually limited in the size of wood chip it can accept. Again, they are designed for a reasonably fast response to heating load demands. Underfed stoker boilers are always auger fed and do not have a HWC capability. It is not possible to install a flap valve beneath the grate. Most underfed stoker boilers have separate primary and secondary air fans to provide an independent combustion control on the grate and in the final gas combustion zone.
11
Figure 14 Diagram of a boiler using a moving or stepped grate combustion system (after R. Landen).
Moving grate boilers are designed to burn wood chip with a MC of between 30% and 50%. The boiler can be either auger or ram stoker fed. Moving grate boilers are also suitable for burning dry wood chip and some will also burn pellets, but this usually requires the addition of flue gas recirculation to limit the combustion temperature above the grate. A side entry moving grate boiler will also take the larger sizes of wood chip. A high level of refractory lining will be used together with a combustion chamber that is physically larger than those found in other boiler types. Moving grate boilers can also be of the HWC type. The minimum buffer vessel size required for a moving grate boiler burning wood pellets will be between that required for a high MC moving grate boiler and that for an underfed stoker boiler designed to burn pellets. As with underfed stoker boilers, moving grate boilers have separate primary and secondary combustion fans, and on the largest boilers tertiary fans to ensure the complete combustion of all wood gases.
Boiler maintenance
Biomass boilers have greater maintenance requirements than fossil fuelled boilers. The boiler manufacturers representative or boiler installer will usually carry out an annual maintenance which will include a full internal and external inspection of the boiler, the replacement of worn components (particularly grate components on moving grate boilers), lubrication and cleaning. The main maintenance interventions required by the user at regular intervals are a weekly visual inspection, emptying of the ash bin, greasing of induced draught fan bearings and manual brushing of the flueways. If automatic flue cleaning is installed a significant reduction in boiler downtime and in maintenance time is possible, reducing manual flue cleaning from a weekly to a 6-monthly exercise. The cleaning system comprises a series of compressed air jets or nozzles installed on the ends of the flueways which are pulsed in succession at regular intervals to blow soot from the boiler. This happens automatically while the boiler is operation. The system requires a small compressed air supply in the boiler house.
12
13
The boiler is usually fitted with a constant speed pump (pump 1) whereas the connection to the load circuits must have a variable speed pump or variable speed drive (VSD; pump 2) installed if the system is configured for thermal storage operation as opposed to a simple buffer vessel. Figure 15 shows thermal storage operation. If the system is configured for a buffer vessel, and not a thermal store, a fixed speed pump is normally used for pump 2. When charging, the heat produced by the boiler is greater than the heat demand from the load circuit and the flow rate through pump 2 is less than that of pump 1. When discharging, the output from the boiler is insufficient to meet the load, and the speed of pump 2 is greater than that of pump 1. The speed of pump 2 is often determined by setting a constant temperature difference across the load circuit, allowing the pump flow to be varied to meet the power demanded by the load.
T1
T2
VSD
Figure 16 Boiler/buffer control system based on two temperature sensors (after D. Palmer).
14
Figure 17 shows a typical winter load profile for a building occupied between 08:00 and 18:00 with a representative pattern of operation of a biomass system with a buffer vessel superimposed. The biomass boiler is sized at 50% of the peak load on the design winter day2 with a buffer vessel capacity ratio of 34 l/kW at a temperature drop across the buffer of 25 C. When the heat demand occurs at 06:00 pump 2 will switch on and begin to discharge the buffer vessel. The biomass boiler will only fire once the buffer vessel has fully discharged (the cold interface having reached the upper temperature sensor). While it is heating up, shown as a one-hour period in Figure 17, the auxiliary boiler has to fire to provide much of the heat during the pre-heat period. When the biomass boiler eventually comes on-line the load is shared between the biomass boiler and the auxiliary boiler. In this example 85% of the energy is being provided by the biomass boiler. In order to prevent the auxiliary boiler from supplying the full load at any point during the day, either an improved control system or a much larger buffer vessel is required. These options are explored below. The problem described above can be alleviated by moving the boiler start sensor further down the tank or programming the boiler to run immediately a heat demand is received, although this may not be possible on simple systems.
Figure 18 Progressive buffer vessel control system using multiple sensors (after D. Palmer).
Clearly it is important that the energy storage in the buffer vessel is matched to the time it takes for the boiler to start up, and this will usually determine the buffer vessel capacity required. Some of the boilers using this system are sufficiently sophisticated to have little or no need for a buffer vessel to protect the boiler or improve its efficiency, the buffer vessel being required to meet as great a proportion of the annual heat energy demand as possible.
Figure 17 Typical winter load profile for a building occupied during the daytime (after D. Palmer).
2
The design winter day is the one used to represent the worst case winter temperature profile expected for a given location.
15
System design
Recommended connection methods and design considerations Flash steam
There are a number of principal considerations when connecting a biomass system to an existing or planned heating system. Most heating systems are designed to operate at 82 C flow, 71 C return, to avoid producing steam in the heating system in the event of a sudden system depressurisation or system overheating. This is a major safety consideration. Steam, known as flash steam, will form in a system pressurised to more than 1 bar if the system depressurises rapidly3. The operating pressure will be well over 1 bar even in systems pressurised by a gravity header tank. By holding the design operating temperature down to 82 C, a flash margin of 18 C is provided so that flash steam cannot be produced. However, to maximise the thermal storage capacity of a buffer tank it is better to operate the biomass system at up to 95 C and where possible to design the heating circuits to return at a temperature lower than 71 C.
components (valve and pump 1) are shown in all the figures in this section on system design.
Hydraulic stability
Another consideration is the hydraulic stability of the overall system. By far the best way of connecting a biomass boiler is via a low loss header, as shown in Figures 19 and 20. Current practice is to design new boiler installations using a low loss header. The use of a variable speed drive pump, necessary to allow water to be drawn from both the buffer vessel and the boiler simultaneously, means that hydraulic instability would occur if the boiler and buffer were to be connected to split headers. Split headers are separate flow and return headers with all of the pumps on one or other of the headers. Split headers result in variable flows through the boilers as load circuit pumps switch on and off (which are commonly found in existing boiler houses). Instability, or poor performance from the biomass boiler, may also occur if the boiler is sized as a base load boiler or at a low percentage of the peak load. A low loss header is strongly recommended and, if this is not possible, the biomass boiler should be connected via a plate heat exchanger as discussed in System optimisation (page 17).
Corrosion prevention
To prevent corrosion within the boiler, the minimum return temperature when burning drier fuels (20% MC and below) should be 60 C, but a return temperature of 65 C is required when burning fuels with 50% MC. This is achieved in the majority of systems by using a three port back-end protection valve and boiler circulating pump, and these
Figure 19 Direct connection method using a low loss header (after D. Palmer).
16
Where a large buffer vessel or thermal store is employed this can itself act as a low loss header, simplifying the design of systems. The actual configuration required will depend on the whether existing fossil fuel boilers are to be connected as part of a biomass system and how these are connected to both the biomass system and the load circuits. Figure 20 is an example of a system incorporating both fossil fuel and biomass boilers.
System optimisation
A biomass boiler can be connected directly to a system operating at 82 C flow providing the temperature in the buffer vessel does not exceed this temperature by more than a few degrees. With a typical mean circuit return temperature greater than 60 C, the temperature difference across the buffer vessel is only 20 C. Since the energy storage capacity of a buffer is directly proportional to the temperature difference across it, a low temperature difference means a larger buffer vessel is needed to store the required heat. If only variable temperature (external temperature compensated) load circuits are present, the associated control system will allow the buffer vessel to operate at a higher temperature together with low return temperatures to optimise the energy storage capacity. This means that it is not uncommon to operate biomass boilers at a temperature of up to 95 C, and sometimes as high as 110 C on larger boilers. Unfortunately, if a boiler and buffer vessel operating at above 85 C are directly connected to a system operating at 82 C, the system pressure may need to be increased to accommodate the higher operating temperature (to prevent flash steam formation).
Depending on the nature of the lower temperature heating system it may not be possible to increase pressure sufficiently to provide an adequate flash margin. In this case it may be necessary to isolate the biomass boiler from the heating system and auxiliary boiler by using a plate heat exchanger, to allow an increase in the system pressure accordingly. While some manufacturers design their boilers to operate at 90 C or 95 C, a more expensive boiler and equipment designed to operate at a higher pressure (including the buffer vessel) may be required; this will always be the case with operation at 110 C. When connecting to an existing heating system, if it is not possible to reconfigure the system to a low loss header system as shown in Figures 19 and 20, the simplest way to ensure the existing system remains hydraulically balanced is to replace one of the existing boilers with a plate heat exchanger. Providing the pressure loss on the secondary of the plate heat exchanger at full load is equal to that of the boiler it replaces, the existing heating system should continue to operate as before without the need for a circuit rebalancing exercise.
Figure 20 Example of an installation design using a low loss header and incorporating biomass and fossil fuel boilers (after D. Palmer).
DHW calorifier
Existing circuit 1
Existing circuit 3
Biomass boiler
Thermal store
DHW calorifier
Existing circuit 1
Pump 1
Existing circuit 2
Existing circuit 3
17
Figure 21 Case study: wood chip and auxiliary boiler installation designed to drive a district heating system (courtesy Queen Margaret University, Edinburgh and Buccleuch Bioenergy Ltd).
18
A flue gas oxygen sensor (Lambda sensor) to monitor the oxygen content in the flue and, via a control system, to ensure sufficient excess oxygen is supplied for complete combustion by regulating secondary and tertiary air fans. This is not always used. In order to avoid the production of black smoke from a biomass boiler chimney the following conditions must be met: The boiler must operate within its turndown band, e.g. a 300 kW boiler with a 3:1 turndown ratio must not operate if the load falls below 100 kW. Either the boiler must switch off, or it must enter a slumber mode, or it must operate with a buffer vessel in parallel to accept the excess energy produced. The moisture content of the fuel must be within the range the boiler can accept. In particular, fuel with a moisture content that is greater than the boiler can accept will invariably produce black smoke.
Abatement technologies
Table 2 details the available emissions abatement technologies and their properties. Many of these technologies require significant maintenance, have high operating costs and require the disposal of waste. Further detail on emissions from biomass combustion can be found in Biomass heating: a guide to feasibility studies.
Technology
Cyclone grit arrestor Bag filter
Advantages
Will take out most particulates down to about 20 micron.
Disadvantages
Will not take out a significant proportion of PM10 and smaller. Will not take out any gas including NOx.
Will take out most particulates down to about 1 micron Regular filter cleaning required. (0.001mm) diameter. Will take out almost all PM10 and A cyclone in series is advisable to reduce the load on the PM2.5 particulates. bag filter from larger particulates. Will not take out any gas including NOx. Pressure losses through the filter can be very large if fine particles are to be filtered out. This requires a large induced draught fan. Unlikely to be commercially viable if flue gas temperatures exceed 200 oC. Will take out almost all particulates down to ultrafine particles, i.e. smaller than PM2.5. Will take out almost all particulates down to ultrafine particles, i.e. smaller than PM2.5. Will dissolve gases including CO2 and (less effectively) NO2. Enables a high degree of heat recovery from the boiler flue gases. Able to remove most particulates from high temperature flue gas. Long life expectancy. Must be used in series with a cyclone. Will not take out any gas including NOx. Must be used in series with a cyclone. Weak acid produced as gases dissolve; requires neutralisation and the removal of salts from the scrubber water. Significantly reduces flue gas buoyancy. Will not remove any gas including NOx. Must be used in series with a cyclone. High cost.
Ceramic filter
19
Crown copyright 2011 Written, co-ordinated and produced by David Palmer, Ian Tubby, Geoff Hogan and Will Rolls, and peer reviewed by members of the Renewable Energy Association. Information on flue design and specification kindly supplied by HETAS. For further information please contact: www.biomassenergycentre.org.uk email: [email protected] Editing: Jenny Claridge Designed and printed by Colourgraphic Arts, Bordon, Hampshire. Published by the Biomass Energy Centre, Farnham, Surrey. www.biomassenergycentre.org.uk
20