14 7 4 Nmac

Download as pdf or txt
Download as pdf or txt
You are on page 1of 30
At a glance
Powered by AI
The document outlines New Mexico's earthen building materials code, including definitions of terms, allowable wall heights, and figures explaining construction concepts.

Earthen materials covered under the code include adobe, rammed earth, compressed earth block, and terrón.

Allowable wall heights are provided in Table 1 and vary based on wall thickness and maximum seismic design spectral response acceleration.

TITLE 14 HOUSING AND CONSTRUCTION

CHAPTER 7 BUILDING CODES GENERAL


PART 4 2006 NEW MEXICO EARTHEN BUILDING MATERIALS CODE

14.7.4.1 ISSUING AGENCY: Construction Industries Division of the Regulation and Licensing
Department.
[14.7.4.1 NMAC - Rp, 14.7.4.1 NMAC, 1-1-08]

14.7.4.2 SCOPE: This rule applies to all earthen building materials contracting work performed in New
Mexico on or after January 1, 2008, that is subject to the jurisdiction of CID, unless performed pursuant to a permit
for which an application was received by CID before that date.
[14.7.4.2 NMAC - Rp, 14.7.4.2 NMAC, 1-1-08]

14.7.4.3 STATUTORY AUTHORITY: NMSA 1978 Section 60-13-9 and 60-13-44.


[14.7.4.3 NMAC - Rp, 14.7.4.3 NMAC, 1-1-08]

14.7.4.4 DURATION: Permanent.


[14.7.4.4 NMAC - Rp, 14.7.4.4 NMAC, 1-1-08]

14.7.4.5 EFFECTIVE DATE: January 1, 2008, unless a later date is cited at the end of a section.
[14.7.4.5 NMAC - Rp, 14.7.4.1 NMAC, 1-1-08]

14.7.4.6 OBJECTIVE: The purpose of this rule is to establish minimum standards for earthen building
materials construction in New Mexico.
[14.7.4.6 NMAC - Rp, 14.7.4.1 NMAC, 1-1-08]

14.7.4.7 DEFINITIONS:
A. Amended soil means improving an unqualified soil to a qualified state with the addition of other
soils or amendments.
B. Amendments means additive elements to soil, such as lime, portland cement, fly ash, etc. which
are “dry-mixed” into the main soil body as a percentage of total weight to achieve stabilization.
C. Buttress means a projecting structure providing lateral support to a wall. The buttress shall be
incorporated into the foundation and wall system. (Refer to figure 1 of the earthen building figures supplement).
D. CEB means compressed earth block.
E. Keyway means a groove on the vertical rammed earth wall surface for interlocking purposes.
Refer to figure 3 of the earthen building figures supplement).
F. Lift means a course of rammed earth, placed within the forms, and then compacted.
G. Nailer means any material rammed into the wall that serves as an attachment device. Refer to
figure 4 of the earthen building figures supplement).
H. Optimum moisture means sufficient water (generally no more than ten (10) percent) mixed into
the soil to attain sufficient compaction.
I. psi means pounds per square inch.
J. Qualified soil means any soil, or mixture of soils, that attains 300 psi compression strength and
attains 50 psi. modulus of rupture.
K. Rammed earth means qualified soil that is mechanically or manually consolidated to full
compaction.
L. Round-cap nails means fasteners that include nails or screws in combination with caps of at least
three-fourths (3/4) inches diameter or three-fourths ( ¾) inch square.
M. Stabilization, stabilized means qualified soils that pass the wet strength test under ASTM D1633-
00 or contain a minimum of six (6) percent portland cement by weight. Stabilization is achieved through the use of
amendments.
N. Wet strength compression test means an approved testing laboratory process in which a fully
cured rammed earth cylinder is completely submerged in water a minimum of four hours according to ASTM
D1633-00, then subjected to a compression test.
[14.7.4.7 NMAC - Rp, 14.7.4.7 NMAC, 1-1-08]

14.7.4 NMAC 1
14.7.4.8 EARTHEN BUILDING MATERIALS:
A. General. The provisions of this rule, 14.7.4 NMAC, shall control the design and construction of
one- and two-family dwellings in which earthen building materials form the bearing wall system.
B. Allowable wall heights for earthen structures. All earthen structures whether adobe, burned
adobe, compressed earth block, rammed earth or terrón, shall conform to table 1. For purposes of using table 1,
height is defined as the distance from the top of the slab or top of stem wall to the underside of the bond beam.

Table 1 ALLOWABLE WALL HEIGHTS FOR EARTHEN STRUCTURES


Maximum Sds Wall Maximum Maximum Sds Wall Thickness Maximum
Thickness Height Height
10 120” 10 120”
12 128 12 128
14 144 14 144
.25 16 144 .3 16 144
18 144 18 144
24 144 24 144
10 120” 10 120”
12 128 12 128
14 144 14 144
.35 16 144 .4 16 144
18 144 18 144
24 144 24 144
10 104” 10 96”
12 128 12 112
14 144 14 136
.45 16 144 .5 16 144
18 144 18 144
24 144 24 144
This table is based on two story maximum, one and two family residential with seismic soil site class D1.
[14.7.4.8 NMAC - Rp, 14.7.4.8 NMAC, 1-1-08]

14.7.4.9 ADOBE CONSTRUCTION:


A. General. Adobe shall not be used in any building more than (2) stories in height. The maximum
height of every wall of adobe block without lateral support is specified in 14.7.4.8 NMAC, table 1. The height of
the wall is defined as the distance from the top of the slab or top of stem wall to the underside of the bond beam.
The maximum height of exterior walls, which are laterally supported with those supports located no more than
twenty-four (24) feet apart, are as defined in 14.7.4.8 NMAC, table 1. The bottom story of a two-story is allowed a
minimum thickness of fourteen (14) inches with the upper story allowed a thickness of ten (10) inches providing the
structure meets the provisions of 14.7.4.8 NMAC, table 1.
B. Fireplaces. Adobe or masonry fireplaces and chimneys in adobe structures shall comply with
14.7.3.18 NMAC. They shall be integrated into adjacent adobe walls during construction or secured to them by
suitable steel ladder reinforcement or reinforcing rods.
C. Count Rumford fireplaces. Count Rumford fireplaces are allowed as provided in 14.7.3.18
NMAC.
D. Soil. Soil for use in adobe blocks should have a mixture of coarse sand, sand, silt and clay,
naturally occurring, or amended with sand or straw, that will make a sun-dried brick without serious warping or
cracking. The best way to determine the fitness of a soil is to make sample blocks and allow them to cure in the
open, protected from moisture. Then test as specified by Subsections C and D of 14.7.4.11 NMAC. The soil shall
not contain more than two (2) percent soluble salts.
E. Passive solar structures. Passive solar structures incorporating the use of solar mass walls
(trombes), direct gain arrays or sunspaces (greenhouses) as defined by the passive solar heating worksheet, dated
June, 2004 and prepared by the state of New Mexico energy, minerals and natural resources department, are
allowed.
[14.7.4.9 NMAC - Rp, 14.7.4.9 NMAC, 1-1-08]

14.7.4 NMAC 2
14.7.4.10 CLASSES OF ADOBE:
A. Stabilized adobe. The term “stabilized” is defined to mean water-resistant adobe made of soil to
which certain admixtures are added in the manufacturing process in order to limit water absorption into the adobe.
Exterior walls constructed of stabilized mortar and adobe requires no additional protection. Cement stucco or other
waterproof coating is not required. The test required is that a dried four (4) inch cube cut from a sample unit shall
not gain more than 2.5% in weight when placed upon a constantly water-saturated porous surface for seven (7) days.
An adobe unit that meets this specification shall be considered “stabilized.”
B. Unstabilized adobe. Unstabilized or “natural” adobes are adobes that do not meet the water
absorption specifications indicated in Subsection A of 14.7.4.10 NMAC above. Use of unstabilized adobes is
prohibited within four (4) inches of the finished floor grade. Stabilized adobe or waterproof masonry units and
mortar may be used for the first four (4) inches above floor grade.
C. Terrón. The term “Terrón” shall refer to a cut sod brick. Their use is permitted if units are dry
and the wall design is in conformance with this code.
D. Burned adobe. The term “burned adobe” shall refer to mud adobe bricks that have been cured by
low-temperature kiln firing. This type of adobe is not generally dense enough to be “frostproof” and may deteriorate
with seasonal freeze-thaw cycles. Its use for exterior locations is discouraged in climate zones with daily freeze-
thaw cycles.
[14.7.4.10 NMAC - Rp, 14.7.4.10 NMAC, 1-1-08]

14.7.4.11 PROPERTIES, SAMPLING AND TESTING:


A. General. Each of the tests prescribed in this section shall be applied to sample units selected at
random at a ratio of five (5) units per twenty-five thousand (25,000) bricks to be used or at the discretion of the
building official.
B. Shrinkage cracks. Shrinkage cracks are allowed, providing that these cracks do not jeopardize
the structural integrity of the blocks.
C. Compressive strength.
(1) Cured units shall have an average minimum compressive strength of three hundred (300) pounds
per square inch when tested. One (1) sample out of five (5) may have a compressive strength of not less than two
hundred fifty (250) psi.
(2) The adobe block shall be tested in the flat position. The length of the test unit must be a
minimum of twice the width. The surfaces must be smooth. The test unit shall be subjected to a uniform
compressive load that is gradually increased at a rate of five hundred (500) psi./minute until failure occurs. A true
platen should be used in the testing machine, along with swivel head to accommodate nonparallel bearing surfaces.
The compressive strength is defined as P/A, where P= load and A = area of compression surface.
D. Modulus of rupture. Cured units shall average fifty (50) psi in modulus of rupture when tested
according to the following procedures. A cured unit shall be laid over two-inch (2”) diameter cylindrical supports
two (2) inches from each end and extending across the full width of the unit. A cylinder two (2) inches in diameter
shall be laid midway between and parallel to the supports. Load shall be applied to the cylinder at a rate of five
hundred (500) psi/minute until rupture occurs. The modulus of rupture is equal to: 3PL/2bt2 (P=rupture load in
pounds, L=span between supports, b=width of block, t=thickness of block) .
E. Mortar. The use of earth mortar is allowed if the earth mortar material is of the same type as the
adobe blocks. Conventional lime/sand/cement mortars of types M, S, and N are also allowed. Mortar “bedding”
joints shall be fully grouted, with partially open “head” joints allowable if the surface is to be plastered. All joints
shall be lapped at least twenty-five (25) percent of the visible block length.
F. Use. No adobe shall be laid in the wall until fully cured.
G. Foundations. Adobes may not be used for foundations or basement walls. All adobe walls,
except as noted, shall have a continuous footing at least eight (8) inches thick and not less than two (2) inches wider
on each side that supports the foundation stem walls above. All foundation stem walls that support adobe units shall
extend to an elevation not less than six (6) inches above the finish grade. Foundation stem walls shall be at least as
thick as the adobe walls they support. Where perimeter insulation is used, a variance is allowed for the stem wall
width to be two (2) inches narrower than the width of the adobe wall it supports. Alternative foundation systems
must be approved by the building official.
H. Bond beams. All bearing walls shall be topped with a continuous bond beam (except patio walls
less than six (6) feet high above stem). All bond beam construction shall be in accordance with accepted
engineering practices.

14.7.4 NMAC 3
I. Concrete bond beam. Concrete bond beams shall be a minimum of six (6) inches high by ten
(10) inches wide for walls up to fourteen (14) inches thick. Where adobe walls are wider than one course, two-
thirds (2/3) of each visible course top shall be covered by the concrete bond beam. All concrete bond beams shall be
reinforced with a minimum of two (2) no. 4 reinforcing rods at each floor and ceiling plate line.
J. Wood bond beam. Wood bond beams shall be a minimum of six (6) inches deep by ten (10)
inches wide for walls up to fourteen (14) inches thick. Where adobe walls are wider than one course, two-thirds
(2/3) of each visible course top shall be covered by a wood bond beam and the roof load shall be distributed over
both bond beams. Wood bond beams may be solid in the six-inch (6”) dimension, or may be built up by applying
layers of lumber. Ends of wood bond beams are to be lapped a minimum of the width of the wall and fully nailed.
No wood layer shall be less than one (1) inch nominal thickness. The building official shall approve all wooden
bond beams for walls wider than fourteen (14) inches.
K. Lintels. Lintels of wood or concrete are allowed. When an engineer’s drawing and seal is not
provided, all lintels shall conform to table 2 or 3 below. The required bearing of any lintel shall not be reduced by a
splayed or angled window or door opening.
L. Wood lintels. When an engineer’s drawing and seal is not provided for lintels, all wood lintels
shall conform to table 2 and have a fiber stress rating of at least 850 psi.

Table 2 ADOBE WALL WOOD LINTEL SCHEDULE


MINIMUM FIBER STRESS 850 psi
Wall Max. Span Size Bearing length on Load
Width earth wall Capacity
4'-0” 10” x 6” 12” 860 PLF
6'-0” 10” x 8” 12” 1020 PLF
10” 8'-0” 10” x 10” 18” 1150 PLF
10'-0” 10” x 12” 24” 1000 PLF
12'-0” 10” x 14” 24” 1000 PLF
4'-0” 10” x 6” 12” 860 PLF
6'-0” 10” x 8” 12” 1020 PLF
12” 8'-0” 10” x 10” 18” 1150 PLF
10'-0” 10” x 12” 24” 1000 PLF
12'-0” 10” x 14” 24” 1000 PLF
4'-0” 12” x 6” 12” 950 PLF
6'-0” 12” x 8” 12” 1150 PLF
14” 8'-0” 12” x 10” 18” 1300 PLF
10'-0” 12” x 12” 24” 1300 PLF
12'-0” 12” x 14” 24” 1200 PLF

M. Concrete lintels. When an engineer’s drawing and seal is not provided for lintels, all concrete
lintels shall conform to table 3 and have a minimum strength of 3000 psi.

Table 3 ADOBE WALL CONCRETE LINTEL SCHEDULE MIN. 3000 psi


Maximum Minimum depth* Reinforcing Maximum Capacity per Bearing length on
Span linear foot earth wall
Less than 6’ - 0” 8” 2-#4 1500 lbs. 12”
6' - 0" to 10'- 0” 12” 3-#5 1500 lbs. 18”
11' - 0" to 16'- 0” 16” 3-#6 1500 lbs. 24”
* SIZE Wall width X depth of lintel

N. Anchorage. Roof and floor structures will be suitably anchored to bond beams. Wood joists,
vigas or beams shall be attached to the wood or concrete bond beams with adequate metal fasteners. Door and
window bucks shall be secured to the adobe wall with adequate metal fasteners. “Gringo blocks” or wood nailers,
placed in the adobe walls as they are laid up, are allowed. Wood and metal partitions may be secured to nailing
blocks laid up in the adobe wall or by other approved methods.
O. Plastering. Unstabilized exterior adobe walls can be protected with portland cement plaster with
a minimum thickness of seven-eighths (7/8) inch, if adequate roof, parapet, canal and window flashing is provided.

14.7.4 NMAC 4
If portland cement plaster is used, it must be reinforced with metal wire mesh, minimum seventeen (17) gauge by
one-and-a-half (1 1/2) inch openings, securely attached to the exterior adobe wall surface by nails or staples with a
minimum penetration of one-and-a-half (1 1/2) inch. Such mesh fasteners shall have a maximum spacing sixteen
(16) inches from each other. Any wood surfaces to be covered with stucco or plaster must be protected from
moisture with asphalt felt, reinforced with expanded metal lath. Protective coatings other than plaster are allowed.
Interior gypsum or mud plasters may be applied directly to the wall, provided that adobe head joints have been left
partially open. Expanded metal lath shall be used around window and door openings. If desired, exterior adobe
walls may be protected with mud plaster. Alternative plastering systems shall be submitted for approval by the
building official.
P. Wall insulation. When rigid insulation board is used, round-cap nails shall attach it to the adobe
wall. Cap nails shall have a maximum spacing of sixteen (16) inches from each other. Additionally, cap nails shall
secure the rigid insulation boards around their perimeter edges, with nails spaced no less than twelve (12) inches
apart. All cap nails shall penetrate a minimum of two (2) inches into the adobe wall when securing rigid insulation
board up to two (2) inches in thickness, and three (3) inches when securing insulation board greater than two (2)
inches in thickness.
[14.7.4.11 NMAC - Rp, 14.7.4.11 NMAC, 1-1-08]

14.7.4.12 RAMMED EARTH CONSTRUCTION:


A. General. The following provisions shall apply.
(1) Rammed earth shall not be used in any building more than (2) stories in height. The height of
every wall of rammed earth without lateral support is specified in 14.7.4.8 NMAC table 1. The height of the wall is
defined as the distance from the top of the slab or top of stem wall to the underside of the bond beam.
(2) Exterior rammed earth walls shall be a minimum of eighteen (18) inches in thickness. Exception:
Exterior walls that are also designed as solar mass walls (trombes) as defined by the passive solar heating worksheet,
dated June 2004 and prepared by the state of New Mexico energy, minerals and natural resources department, are
allowed and shall be minimum thickness of ten (10) inches, not to exceed twelve (12) inches. They shall be fully
attached to or integrated with any adjacent structural wall and topped with a bond beam that fully attaches them to
the bond beam of any adjacent structural wall as described in 14.7.4.17 NMAC.
(3) Interior rammed earth walls shall be a minimum of twelve (12) inches in thickness.
(4) Unstabilized rammed earth walls must be covered to prevent infiltration of moisture from the top
of the wall at the end of each workday and prior to wet weather conditions, whether the walls are contained within
forms or not.
(5) Fully stabilized rammed earth walls may be left unprotected from the elements.
(6) In no case shall a rammed earth wall be reduced in thickness with back to back channels or
nailers. Channels or nailers rammed on both sides of a running wall shall not be opposite each other to avoid an
hourglass configuration in the wall section. Channels or nailers on both sides of a running wall shall be separated
from each other vertically at a distance no less than the rammed earth wall thickness. (Refer to figure 4 of the
earthen building figures supplement).
(7) An architect or engineer registered in the state of New Mexico shall design and seal structural
portions of two-story residential rammed earth construction documents.
(8) The general construction of the building shall comply with all provisions of the 2006 New
Mexico Residential Building Code (NMRBC), unless otherwise provided for in this rule.
(9) Passive solar structures incorporating the use of solar mass walls (trombes), direct gain arrays or
sunspaces (greenhouses) as defined by the passive solar heating worksheet, dated June 2004 and prepared by the
state of New Mexico energy, minerals and natural resources department, are allowed.
B. Fireplaces. Adobe or masonry fireplaces and chimneys in rammed earth structures shall comply
with 14.7.3.18 NMAC. They shall be integrated into adjacent rammed earth walls during construction or secured to
them by suitable steel ladder reinforcement or reinforcing rods.
C. Count Rumford fireplaces. Count Rumford fireplaces are allowed as provided in 14.7.3.18
NMAC.
D. Stop work. The building inspector shall have the authority to issue a “stop work” order if the
provisions of this section are not complied with.
E. Lateral support. Lateral support shall occur at intervals not to exceed twenty-four (24) feet.
Rammed earth walls eighteen (18) inches to less than twenty-four (24) inches thick shall be laterally supported with
any one or combination of the following: A rammed earth wall of bond beam height that intersects the running wall
with at least sixty (60) degrees of support (refer to a figure 5 of the earthen building figures supplement); an adobe

14.7.4 NMAC 5
wall of bond beam height and at least ten (10) inches in width that intersects with and attaches to the running wall
with at least sixty (60) degrees of support (refer to figure 5 of the earthen building figures supplement); a minimum
twenty 20 gauge steel frame or wood frame wall of full height that intersects with and attaches to the running wall
with ninety (90) degrees of support, that is properly cross-braced or sheathed (refer to figure 6 of the earthen
building figures supplement); a buttress configuration that intersects the running wall at ninety (90) degrees, of
adobe or rammed earth. The buttress base must project a minimum of three (3) feet (or thirty-three (33) percent of
the wall height) from the running wall and support at least seventy-five (75) percent of the total wall height (refer to
figure 7 of the earthen building figures supplement). The thickness of a rammed earth buttress shall be at least
eighteen (18) inches. The thickness of an adobe buttress shall be a minimum fourteen (14) inches. Rammed earth
walls greater than twenty-four (24) inches in thickness are self-buttressing and do not require lateral support
provided their design adheres to 14.7.4.8 NMAC table 1 and the other applicable provisions of this rule.
F. Openings. Door and window openings shall be designed such that the opening shall not be any
closer to an outside corner of the structure as follows.
(1) In rammed earth walls eighteen (18) inches to less than twenty-four (24) inches thick, openings
shall not be located within three (3) feet of any corner of the structure. (Refer to figure 8 of the earthen building
figures supplement). Exception: Openings may be located within three (3) feet of any corner provided a buttress
extending at least three (3) feet from the structure supports the corner. A continuous footing below and a continuous
bond beam above, shall be provided across such openings.
(2) Rammed earth walls greater than twenty-four (24) inches thick are self-buttressing, with no
special consideration for placement of openings within the area of the wall.
G. Piers. Rammed earth piers supporting openings shall measure no less than three (3) square feet in
area and no dimension shall be less than eighteen (18) inches. (Refer to figures 9-A and 9-B of the earthen building
figures supplement).
[14.7.4.12 NMAC - Rp, 14.7.4.12 NMAC, 1-1-08]

14.7.4.13 FOUNDATIONS:
A. General. Foundation construction shall comply with applicable provisions of the 2003 New
Mexico Residential Building Code, and the following: a minimum of three (3) continuous #4 reinforcing rods are
required in minimum 2500 psi. concrete footings supporting rammed earth walls. Stem walls shall be the full width
of the wall supported above or wider to receive forming systems. Footings shall be a minimum of ten (10) inches in
depth.
B. Perimeter insulation. For the purposes of placement of perimeter insulation, rammed earth walls
may overhang the bearing surface up to the thickness of the perimeter insulation, but in no case greater than two (2)
inches.
C. Keyway. A key way shall be provided where the rammed earth wall meets the foundation system.
The keyway shall be established at the top of the stem a minimum of two (2) inches deep by six (6) inches wide
formed at the time of the pour, and shall run continuously around the structure to include any intersecting rammed
earth wall sections. The rammed earth wall shall be fully rammed into this keyway (refer to figure 2 of the earthen
building figures supplement). Exception: Placement of vertical reinforcing rods extending a minimum twelve (12)
inches into the rammed earth wall. The vertical rods shall be minimum #4, imbedded into the concrete and spaced
forty-eighty (48) inches on center, maximum.
D. Concrete grade beam. Rubble filled foundation trench designs with a reinforced concrete grade
beam above are allowed to support rammed earth wall construction. An architect or engineer registered in the state
of New Mexico shall certify the grade beam/rubble-filled trench design portion.
[14.7.4.13 NMAC - Rp, 14.7.4.13 NMAC, 1-1-08]

14.7.4.14 RAMMED EARTH SOIL SPECIFICATIONS:


A. General. The soil shall not contain rock more than one-and-a-half (1 1/2) inch in diameter. The
soil shall not contain clay lumps more than one-half (1/2) inch in diameter. The soil shall be free of all organic
matter. The soil shall not contain more than two (2) percent soluble salts.
B. Soil compressive strength. Prior to the start of construction, fully-cured rammed earth soil
samples shall be tested at an approved testing laboratory for compressive strength. The ultimate compressive
strength of all rammed earth soil, stabilized or non-stabilized, shall be a minimum three-hundred (300) psi. The
compressive strength report shall be submitted with the permit application. This report may be waived if the builder
provides certification of compliance. The certification must be dated within one year of the date on the application

14.7.4 NMAC 6
for the building permit. Samples tested shall be representative of soil to be used on the project for which the permit
application is submitted.
C. Stabilized rammed earth soil. The following shall apply to stabilization of rammed earth soil:
Asphalt emulsion may not be used for stabilization of rammed earth soil. Thorough mixing of additives to the soil
may be achieved by any method that assures a complete blending to a uniform color and texture. Stabilized soil is
suitable soil that contains six (6) percent or more portland cement by weight or that passes ASTM D1633-00.
Samples tested shall be representative of soil to be used on the project for which the permit application is submitted.
The compressive strength report shall be submitted with the permit application. Laboratory testing shall indicate
rammed earth samples attained a minimum of two-hundred (200) psi. after seven (7) days. If a different soil is
provided at any time during construction, it must meet the minimum requirements outlined above, prior to use in the
structure.
D. Unstabilized rammed earth soil. Unstabilized rammed earth soil is that containing less than six
(6) percent portland cement by weight or that fails to pass ASTM D1633-00. The exterior of such walls shall be
protected with approved stucco systems or other method approved by the building official. Refer to 14.7.4.19
NMAC for weather-resistive barrier requirements.
E. Amended soil. The following guidelines shall apply when amending soils to attain a qualified
soil. Soil shall not contain rock greater than one-and-a-half (1 1/2) inch in diameter. Soil shall not contain clay
lumps greater than one-half (1/2) inch diameter. Soil shall be free of organic matter. Soil shall not contain more
than two (2) percent soluble salts. Soils to be mixed shall be sufficiently dry to blend completely to one uniform
color and texture. The amended soil shall be tested prior to use as per Subsection B of 14.7.4.14 NMAC.
F. Forming systems. The forming system shall be adequate to contain the material under
compaction. It shall be properly plumbed and braced to withstand the soil pressures as well as construction activity
on and around it.
G. Placement of material, compaction and curing.
(1) No amount of portland cement stabilized soil will be mixed that will not be placed in the wall
system within sixty (60) minutes of its preparation.
(2) Lifts of prepared soil shall be placed in the forms in relatively even layers not to exceed 8 inches
in depth. Each lift shall then be rammed to full compaction.
(3) Optimum moisture content as determined to meet minimum compressive strength shall be
maintained for stabilized and unstabilized walls.
(4) Work will progress, lift-by-lift, until the work approaches bond beam height.
(5) Forms may be stripped immediately after ramming is completed for a section of wall, providing
ramming of adjacent sections does not affect the structural integrity of completed walls.
(6) Portland cement stabilized walls not in forms shall be lightly spray-cured with water at least five
(5) spaced times during daylight hours. This procedure shall continue for at least three (3) days starting from the
time that the wall is exposed to the elements. Exception: Rammed earth walls left in forms three (3) or more days
shall not require water-spray curing.
H. Placement of attachment materials.
(1) Nailers: Nailers incorporated into the rammed earth wall shall be installed as follows (Refer to
figure 4 of the earthen building figures supplement); The rammed earth wall shall not be reduced in thickness with
back-to-back nailers. To avoid an hourglass configuration in the wall section, nailers on either side of a running
wall shall not be opposite each other. Nailers on either side of a running wall shall be separated from each other
vertically a distance not less than the rammed earth wall thickness. Nailers shall be placed onto the wall such that
the narrow dimension of the nailer is exposed on the race of the wall prior to ramming. Nailers shall be cured and
sealed against moisture penetration prior to installation in forms. The nailers shall not extend the full depth of the
wall. Box wood nailers are not allowed. (Refer to figure 11 of the earthen building figures supplement). The nailer
shall be no more than two (2) inches by four (4) inches by its length.
(2) Channels: Channels may be incorporated into the rammed earth wall as follows (Refer to figure
2 of the earthen building figures supplement); To avoid an hourglass configuration in the wall section, channels on
either side of a running wall shall not be opposite each other. (Refer to figure 4 of the earthen building figures
supplement). Channels shall be no more than two (2) inches by four (4) inches by their length in dimension.
Vertical channels shall not be placed closer than twelve (12) inches to a rammed earth wall finished edge or corner.
[14.7.4.14 NMAC - Rp, 14.7.4.14 NMAC, 1-1-08]

14.7.4.15 NICHOS OR OTHER SHAPED VOIDS:

14.7.4 NMAC 7
A. General. The depth of voids shall not exceed 8 inches. The width of the void shall be as defined
in Subsections B and C of 14.7.4.15 NMAC below.
B. Voids in stabilized rammed earth walls. Voids shall not exceed two (2) feet in width. Voids
greater than two (2) feet in width require a lintel or half-circle arched opening. Refer to 14.7.4.18 NMAC for lintel
requirements.
C. Voids in unstabilized rammed earth walls. Voids shall not exceed one (1) foot in width. Voids
greater than one (1) foot in width require a lintel or half-circle arched opening of stabilized rammed earth material.
Refer to 14.7.4.18 NMAC for lintel requirements.
[14.7.4.15 NMAC - Rp, 14.7.4.15 NMAC, 1-1-08]

14.7.4.16 ATTACHMENTS AND CONNECTIONS:


A. General. Attachment and connection methods of alternate wall construction to rammed earth
walls are described as follows. The building official may approve other attachment and connection methods. In no
case shall two wall types be butted to each other without consideration for attachment or connection.
B. Attachment of a rammed earth wall to a rammed earth wall. A keyway, at least six (6) inches
wide by three (3) inches deep shall be formed vertically at the center of the wall section from stem top to underside
of bond beam. The connecting wall shall be rammed into the keyway. (Refer to figure 3 of the earthen building
figures supplement).
C. Attachment of a load-bearing adobe wall to a rammed earth wall. Where adobe is deployed
as an interior wall that will be incorporated into the rammed earth wall for lateral support, the adobe shall measure a
minimum of ten (10) inches in thickness. Steel ladder reinforcement shall be rammed into the wall at the
intersection with the adobe wall. The reinforcement may be bent against the forms during the ramming process.
After ramming is complete and forms removed, the reinforcement shall be incorporated into the adjoining adobe
coursing, every four (4) courses minimum. (Refer to figure 12 of the earthen building figures supplement). As an
alternative, a keyway, not to exceed the depth of the adobe wall, nor one-third (1/3) the depth of the rammed earth
wall, shall be formed into the rammed earth wall. The adobe shall be incorporated into the keyway. (Refer to figure
13 of the earthen building figures supplement).
D. Attachment of a loadbearing wood or steel frame wall to a rammed earth wall. A half-inch
(1/2) minimum diameter anchor bolt with four (4) inch hook, set in a linear vertical pattern, a maximum of twenty-
four (24) inches on-center. The anchor bolt shall be embedded at least twelve (12) inches into the earth wall with
the threaded end protruding sufficiently to pass through and attach the adjoining vertical wall stud. The washer and
nut shall be tightened just prior to sheathing the frame wall. As an alternative, eighteen (18) gauge by two (2) inch
minimum galvanized strap tie, grouted into the concrete bond beam (or secured to the wood bond beam or wood top
plate), securely nailed to the top plate of the frame wall. The remainder of the vertical stud shall be attached to the
rammed earth wall with thirty-D (30D) nails or screws embedded a minimum of three (3) inches into the adjacent
wall at eight (8) inches on center vertically. (Refer to figure 14 of the earthen building figures supplement).
E. Attachment of a door or window unit to a rammed earth wall. The unit shall be attached to
nailers within the opening or nailed or screwed directly into the rammed earth wall. The nail or screw shall
penetrate at least three (3) inches into the rammed earth wall. Heavier units may utilize stronger attachments, such
as anchor bolts, T-bolts, steel pins, etc., embedded into the rammed earth wall.
F. Attachment of rigid insulation to a rammed earth wall. When rigid insulation board is used,
round-cap nails shall attach it to the rammed earth wall. Cap nails shall have a maximum spacing of sixteen (16)
inches from each other. Additionally, cap nails shall secure the rigid insulation boards around their perimeter edges,
with nails spaced no less than twelve (12) inches apart. All cap nails shall penetrate a minimum of two (2) inches
into the rammed earth wall when securing rigid insulation board up to two (2) inches in thickness, and three (3)
inches when securing insulation board greater than two (2) inches in thickness.
G. Attachment of cabinetry to a rammed earth wall. Deck screws shall penetrate a minimum of
three (3) inches through cabinetry and into a nailer, eight (8) inches on center maximum, or; deck screws with a least
three (3) inch minimum penetration through cabinetry and into the rammed earth wall. Screws shall be placed
horizontally, eight (8) inches on center maximum, on the top and bottom of cabinetry. As an alternative, all-thread
rods or other attachment devices, suitable for attachment of cabinetry through the rammed earth wall.
H. Attachment of concrete bond beam to a rammed earth wall. Number four (4) reinforcing bar
shall be driven into the uncured wall top. The reinforcing bar shall be set at a maximum twenty degree (20o) angle
along both edges of the wall, staggered no more than twenty-four (24) inches on-center and no closer than four (4)
inches from the exterior faces of the wall. The reinforcing bar shall extend a minimum of twelve (12) inches into

14.7.4 NMAC 8
the rammed earth wall and four (4) inches into the concrete bond beam. (Refer to figure 16 of the earthen building
figures supplement).
I. Attachment of wood bond beam to a rammed earth wall. One-half (1/2) inch anchor bolts with
four (4) inch base hooks shall be rammed into the wall. The bolts shall be staggered a maximum of forty-eight (48)
inches on-center along both edges of the wall, staggered no closer than six (6) inches from the exterior faces of the
wall. The bolt shall extend a minimum of eighteen (18) inches into the rammed earth wall.
[14.7.4.16 NMAC - Rp, 14.7.4.16 NMAC, 1-1-08]

14.7.4.17 BOND BEAMS:


A. General. The bond beam shall be secured to the rammed earth wall. Refer to Subsections H and I
of 14.7.4.16 NMAC above. Bond beams may be of wood or concrete construction. Bond beams shall measure six
(6) inches nominal depth and extend the full width of the wall. Exception: The bond beam width may be reduced as
follows: Two (2) inches maximum in an eighteen (18) to less than twenty-four (24) inch thick rammed earth wall,
or three (3) inches maximum in a rammed earth wall twenty-four (24) inches or greater in thickness. Bond beams
must be continuous, running the full perimeter of the structure. Interior rammed earth or adobe walls shall be
incorporated into the bond beam. Varying height bond beams shall extend into the adjoining rammed earth wall
one-half (1/2) the thickness of the adjoining rammed earth wall. The concrete bond beam may secure anchoring and
strapping devices.
B. Wood bond beam construction. In addition to the general requirements of Subsection A of
14.7.4.17 NMAC, wood bond beams may be constructed as approved by the building official. Light wood bond
beam construction may be utilized as shown in figure 10 of the earthen building figures supplement.
C. Concrete bond beam construction. In addition to the general requirements of Subsection A of
14.7.4.17 NMAC, concrete bond beams shall be constructed of minimum twenty-five hundred (2500) psi. concrete
and shall contain steel reinforcement as follows: For eighteen (18) to less than twenty-four (24) inch thick rammed
earth wall construction, a minimum of two (2) continuous number four (4) reinforcing rods shall be used. For walls
equal to or greater than twenty-four (24) inches in thickness, a minimum of two (2) continuous number five (5)
reinforcing rods shall be used. Provide two (2) inch minimum reinforcement concrete cover over all horizontal
reinforcing rods. Concrete bond beams may be used to secure anchoring and strapping devices.
D. Concrete bond beam cold joints. Concrete bond beam cold joints are limited to corners of
perpendicular intersections with other structural, full-height walls. Cold joints shall be tied into the adjoining bond
beam with three (3) number four (4) reinforcing rods. The reinforcement shall extend a minimum of twenty-four
(24) inches into both portions of the concrete bond beam.
[14.7.4.17 NMAC - Rp, 14.7.4.17 NMAC, 1-1-08]

14.7.4.18 LINTELS OVER OPENINGS:


A. General. All openings require a lintel or semi-circular arch over the opening. All lintels, whether
of wood or concrete shall bear a minimum of twelve (12) inches into the length of the wall. Exception: Nichos and
other shaped voids as defined in 14.7.4.15 NMAC.
B. Bearing limitations. Lintels shall bear a minimum of twelve (12) inches beyond coved, splayed
or rounded bearing portions of openings that are less than the full width of the wall. (Refer to figure 15 of the
earthen building figures supplement).
C. Lintels over openings in stabilized rammed earth walls. Openings less than twenty-four (24)
inches in width shall not require a lintel or semi-circular arched opening. Openings greater than twenty-four (24)
inches in width require lintels as defined in table 4.

Table 4 Concrete Lintels Over Openings in Rammed Earth Walls [1]


Wall Lintel span Lintel depth Reinforcement [2] Reinforcement Uniform
width Concrete Cover [3] Load
24” 6” 3- #4 @ 4”o.c.
36” 6” 3- #4 @ 4”o.c.
48” 6” 3- #4 @ 4”o.c. 3” minimum
18” 60” 6” 3- #4 @ 4”o.c. concrete cover on all 1000 PLF
72” 8” 3- #5 @ 4”o.c. sides
84” 8” 3- #5 @ 4”o.c.
96” 8” 3- #5 @ 4”o.c.

14.7.4 NMAC 9
24” 6” 3- #4 @ 4”o.c.
36” 6” 3- #4 @ 4”o.c.
48” 6” 3- #4 @ 4”o.c. 4” minimum
20” 60” 6” 3- #4 @ 4”o.c. concrete cover on all 1350 PLF
72” 8” 3- #5 @ 4”o.c. sides
84” 8” 3- #5 @ 4”o.c.
96” 10” 3- #5 @ 4”o.c.
24” 6” 3- #4 @ 5”o.c.
36” 6” 3- #4 @ 5”o.c.
48” 6” 3- #4 @ 5”o.c. 3 1/2” minimum
22” 60” 6” 3- #4 @ 5”o.c. concrete cover on all 1700 PLF
72” 8” 3- #5 @ 5”o.c. sides
84” 10” 3- #5 @ 5”o.c.
96” 10” 3- #5 @ 5”o.c.
24” 6” 3- #4 @ 6”o.c.
36” 6” 3- #4 @ 6”o.c.
48” 6” 3- #4 @ 6”o.c. 3” minimum
24” 60” 6” 3- #4 @ 6”o.c. concrete cover on all 2000 PLF
72” 8” 3- #5 @ 6”o.c. sides
84” 10” 3- #5 @ 6”o.c.
96” 12” 3- #5 @ 6”o.c.

[14.7.4.18 NMAC - Rp, 14.7.4.18 NMAC, 1-1-08]


[1. 3000 psi minimum concrete at approximately 28 days. 2. Grade 40 steel reinforcement minimum. 3. Steel
reinforcement at mid-depth of lintel.]

14.7.4.19 WEATHER RESISTIVE BARRIERS:


A. General. Stabilized rammed earth walls do not require a weather-resistive barrier or an approved
exterior finish. Unstabilized rammed earth walls require a weather-resistive barrier and approved exterior finish.
When a vapor barrier is installed over the rammed earth wall, it shall not be installed on both sides of a rammed
earth wall system. Exception: On the top and sides of a parapet wall.
B. Moisture barrier locations. A moisture barrier shall protect rammed earth walls adjacent to bath
and shower enclosures. A moisture barrier shall protect rammed earth walls at window sills, the top of the parapet,
or other exterior wall portions exposed to the elements. A moisture barrier installed over an exposed parapet top of
a rammed earth wall shall lap a minimum of six (6) inches down both sides of the parapet top.
[14.7.4.19 NMAC - Rp, 14.7.4.19 NMAC, 1-1-08]

14.7.4.20 LATH AND PLASTER:


A. General. When non-cementious plasters are applied directly to the rammed earth wall surface, the
surface shall be scored or sandblasted prior to the application of the plaster. Rammed earth walls must cure to a
depth of four (4) inches minimum prior to application of an approved exterior finish.
B. Lath. Where rammed earth walls have a plaster finish, metal lath shall be installed around interior
and exterior wall openings and over dissimilar materials.
C. Exterior plaster. In unstabilized rammed earth walls, stucco netting shall be installed and
cementious plaster shall have a minimum seven-eighths (7/8) inch finished thickness, unless an elastomeric “color
coat” is used, then it shall have a minimum base coat of five-eighths (5/8) inch. Applications shall follow the
material manufacturers’ specifications.
[14.7.4.20 NMAC - Rp, 14.7.4.20 NMAC, 1-1-08]

14.7.4.21 PLUMBING:
A. General. Code compliant plumbing systems may be rammed into the wall system, either
vertically or horizontally, provided that such plumbing material is of sufficient strength to withstand the ramming
pressures without any rupture or collapse.

14.7.4 NMAC 10
B. Plumbing system installation. Installations shall not reduce the width of the rammed earth wall
by more than one-third (1/3). Prior to ramming, a minimum five (5) inch earth cover is provided over any horizontal
pipe.
[14.7.4.21 NMAC - Rp, 14.7.4.21 NMAC, 1-1-08]

14.7.4.22 ELECTRICAL:
A. Electrical system installation. Electrical wiring shall pass through a channel or conduit.
Approved rigid or flexible electrical conduit shall withstand ramming pressures without damage or collapse.
Electrical wiring within a channel shall be covered a minimum of one and one-fourth (1 1/4) inches. Prior to
ramming, a minimum five (5) inch earth cover shall be provided over any horizontal pipe.
B. UF cable installation. UF cable may not be rammed within the rammed earth wall. Exception:
UF cable installed within an approved conduit or channel. In a channel installation, UF cable must be covered a
minimum of one-and-one-fourth (1 1/4) inches with plaster, adobe or similar finish.
C. Electrical box installation. Plastic electrical boxes shall not be rammed within the rammed earth
wall. Exception: Plastic electrical boxes installed in a channel installation.
[14.7.4.22 NMAC - Rp, 14.7.4.22 NMAC, 1-1-08]

14.7.4.23 COMPRESSED EARTH BLOCK CONSTRUCTION (CEB):


A. General. Compressed earth block shall not be used in any building more than (2) stories in
height. The height of every wall of compressed earth block without lateral support shall be defined in Subsection B
of 14.7.4.8 NMAC, table 1. The height of the wall is defined as the distance from the top of the slab or top of stem
wall to the underside of the bond beam. Heights for exterior walls, which are laterally supported with those supports
located no more than twenty-four (24) feet apart, are defined in Subsection B of 14.7.4.8 NMAC, table 1. The
bottom story of a two-story is allowed a minimum thickness of fourteen (14) inches with the upper story allowed a
thickness of ten (10) inches, providing the structure meets the provisions of Subsection B of 14.7.4.8 NMAC, table
1. Passive solar structures incorporating the use of solar mass walls (trombes), direct gain arrays or sunspaces
(greenhouses) as defined by the passive solar heating worksheet, dated June 2004 and prepared by the state of New
Mexico energy, minerals and natural resources department, are allowed.
B. Fireplaces. Adobe or masonry fireplaces and chimneys in compressed earth block structures shall
comply with 14.7.3.18 NMAC. They shall be integrated into adjacent compressed earth block walls during
construction or secured to them by suitable steel ladder reinforcement or reinforcing rods.
C. Count Rumford fireplaces. Count Rumford fireplaces are allowed as designated in 14.7.3.18
NMAC.
D. Stop work. The building inspector shall have the authority to issue a “stop work” order if the
provisions of this section are not complied with.
E. Stabilized compressed earth blocks. The term “stabilized” is defined to mean a block with
certain admixtures that retains minimum strength requirements as specified in Subsection J of 14.7.4.23 NMAC
after saturation in water. Saturation is defined as a minimum four (4) hours of submersion in water as defined in
ASTM D1633-00.
F. Unstabilized compressed earth blocks. Unstabilized blocks are defined as not meeting the
minimum strength requirements as defined in Subsection J of 14.7.4.23 NMAC after saturation in water. Use of
unstabilized compressed earth blocks is prohibited within four (4) inches of the finished floor grade. Stabilized
compressed earth blocks, poured concrete, or waterproof masonry units and mortar may be used for the first four (4)
inches above floor grade.
G. Materials. The material must be a mineral soil with the aggregate content not exceeding one (1)
inch in diameter. The material shall not contain more than two (2) percent soluble salts.
H. Testing. Each of the tests prescribed in this section shall be applied to sample units selected at
random of five (5) units per building project prior to construction. Test may be waived if block manufacturer
provides certification of compliance. The certification must be dated within one year of the date on the application
for the building permit.
I. Shrinkage cracks. Shrinkage cracks are allowed, providing that these cracks do not jeopardize
the structural integrity of the blocks.
J. Compressive strength. Cured units shall have a minimum compressive strength of three hundred
(300) pounds per square inch when tested. The compressed earth block shall be tested in the flat position. The
length of the test unit must be a minimum of twice the width. The surfaces must be smooth. The test unit shall be
subjected to a uniform compressive load that is gradually increased at a rate of five hundred (500) psi/minute until

14.7.4 NMAC 11
failure occurs. A true platen should be used in the testing machine, along with swivel head to accommodate
nonparallel bearing surfaces. The compressive strength is defined as P/A, where P = load and A - area of
compression surface.
K. Modulus of rupture. Units shall have a minimum compressive strength of fifty (50) pounds per
square inch in modulus of rupture when tested according to the following procedures: A cured unit shall be laid
over two-inch (2”) diameter cylindrical supports two (2) inches from each end and extending across the full width of
the unit. A cylinder two (2) inches in diameter shall be laid midway between and parallel to the supports. Load
shall be applied to the cylinder at a rate of five hundred (500) psi/minute until rupture occurs. The modulus of
rupture is equal to: 3PL/2bt2 (P= rupture load in pounds, L= span between supports, b= width of block, t= thickness
of block).
[14.7.4.23 NMAC - Rp, 14.7.4.23 NMAC, 1-1-08]

14.7.4.24 MORTAR:
A. General. The use of earth mortar is allowed if the earth mortar material is compatible with the
compressed earth blocks. Conventional lime/sand/cement mortars of Types M, S, and N are also allowed. Mortar
“bedding” joints shall be fully grouted. Head joint mortar is not required provided that the blocks are initially laid in
contact. Partially open “head” joints are allowed if the surface is to be plastered. All joints shall be lapped at least
twenty-five (25) percent of the visible block length.
B. Slip mortars. Liquid mud slip mortar is allowed, providing it is made of a compatible soil that is
screened to eliminate aggregate larger than one-eighth (1/8) inch in diameter. Water may be substituted for slip or
other mortars, providing adequate adhesion is demonstrated.
C. Stacking. “Dry stacking” of compressed earth blocks is allowed providing that adequate adhesion
is demonstrated, the wall is to be stuccoed or plastered and the wall is not less than ten (10) inches in thickness.
D. Use. Compressed earth block may be cured prior to use or laid directly from the press into the
wall in an uncured state.
E. Foundations. Compressed earth blocks may not be used for foundations or basement walls.
F. Footings. All compressed earth block walls shall have a continuous footing at least ten (10)
inches thick. The footing width must be a minimum of thirty-three (33) percent greater than the wall width, but not
less than two (2) inches on each side. The stem wall must be centered on the footing.
G. Stem walls. All stem walls that support CEB units shall extend to an elevation not less than eight
(8) inches above the exterior finish grade. Stem walls shall be as thick as the exterior wall. Where perimeter
insulation is used, a variance is allowed for the stem wall width to be two (2) inches smaller than the width of the
CEB wall it supports.
H. Concrete grade beam. Rubble-filled foundation trench designs with a reinforced concrete grade
beam above are allowed to support CEB construction. An architect or engineer registered in the state of New
Mexico shall certify the grade beam/rubble-filled trench design portion. Other alternative foundation systems must
be approved by the building official.
[14.7.4.24 NMAC - Rp, 14.7.4.24 NMAC, 1-1-08]

14.7.4.25 BOND BEAMS:


A. General. All bearing walls shall be topped with a continuous bond beam (except patio walls less
than six (6) feet high above stem). All bond beam construction shall be in accordance with accepted engineering
practices.
B. Concrete bond beam. Concrete bond beams shall be a minimum of six (6) inches high by ten
(10) inches wide for walls up to fourteen (14) inches thick. Where CEB walls are wider than one course, two-thirds
(2/3) of each visible course top shall be covered by the concrete bond beam. All concrete bond beams shall be
reinforced with a minimum of two (2) no. 4 reinforcing rods at each floor and ceiling plate line.
C. Wood bond beam. Wood bond beams shall be a minimum of six (6) inches deep by ten (10)
inches wide for walls up to fourteen (14) inches thick. Where CEB walls are wider than one course, two-thirds (2/3)
of each visible course top shall be covered by a wood bond beam and the roof load shall be distributed over both
bond beams. Wood bond beams may be solid in the six inch (6”) dimension, or may be built up by applying layers
of lumber. Ends of wood bond beams are to be lapped in minimum of the width of the wall and fully nailed.
Galvanized metal straps or perforated metal straps, 18 gauge minimum and twelve (12) inches long, may be used to
join the ends of wood bond beam members. Full nailing of straps is required. No wood layer shall be less than one
(1) inch nominal thickness. The building official shall approve all wooden bond beams for walls wider than
fourteen (14) inches.

14.7.4 NMAC 12
[14.7.4.25 NMAC - Rp, 14.7.4.25 NMAC, 1-1-08]

14.7.4.26 LINTELS:
A. General. Lintels of wood or concrete are allowed. The bearing length of any lintel shall not be
reduced by an angled or splayed window or door opening. Other lintel designs are accepted providing that
engineering is submitted for review by the building official.
B. Wood lintels. When an engineer’s drawing and seal is not provided for lintels, all wood lintels
shall conform to table 5 and have a fiber stress rating of at least 850 psi.

Table 5 CEB WALL WOOD LINTEL SCHEDULE


MINIMUM FIBER STRESS 850 PSI
Wall Max. Span Size Bearing length on Load
Width earth wall Capacity
4'-0” 10” x 6” 12” 860 PLF
6'-0” 10” x 8” 12” 1020 PLF
10” 8'-0” 10” x 10” 18” 1150 PLF
10'-0” 10” x 12” 24” 1000 PLF
12'-0” 10” x 14” 24” 1000 PLF
4'-0” 10” x 6” 12” 860 PLF
6'-0” 10” x 8” 12” 1020 PLF
12” 8'-0” 10” x 10” 18” 1150 PLF
10'-0” 10” x 12” 24” 1000 PLF
12'-0” 10” x 14” 24” 1000 PLF
4'-0” 12” x 6” 12” 950 PLF
6'-0” 12” x 8” 12” 1150 PLF
14” 8'-0” 12” x 10” 18” 1300 PLF
10'-0” 12” x 12” 24” 1300 PLF
12'-0” 12” x 14” 24” 1200 PLF

C. Concrete lintels. When an engineer’s drawing and seal is not provided for lintels, all concrete
lintels shall conform to table 6 and have a minimum strength of 3000 psi.

Table 6 CEB WALL CONCRETE LINTEL SCHEDULE MIN. 3000 psi

Maximum Span Minimum depth* Reinforcing


Maximum Capacity per Bearing length on
linear foot earth wall
Less than 6' - 0" 8” 2-#4 1500 lbs. 12”
6' - 0" to 10'- 0" 12” 3-#5 1500 lbs. 18”
11' - 0" to 16'- 0" 16” 3-#6 1500 lbs. 24”
* SIZE Wall width X depth of lintel
[14.7.4.26 NMAC - Rp, 14.7.4.26 NMAC, 1-1-08]

14.7.4.27 ATTACHMENTS AND CONNECTIONS: When rigid insulation board is used, round-cap
nails shall attach it to the CEB wall. Cap nails shall have a maximum spacing of sixteen (16) inches from each
other. Additionally, cap nails shall secure the rigid insulation boards around their perimeter edges, with nails spaced
no less than twelve (12) inches apart. All cap nails shall penetrate a minimum of two (2) inches into the CEB wall
when securing rigid insulation board up to two (2) inches in thickness, and three (3) inches when securing insulation
board greater than two (2) inches in thickness.
[14.7.4.27 NMAC - Rp, 14.7.4.27 NMAC, 1-1-08]

14.7.4 NMAC 13
14.7.4.28 FIGURE 1 - BUTTRESS

Figure 1 – Buttress:

[14.7.4.28 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 14
14.7.4.29 FIGURE 2 - CHANNEL

[14.7.4.29 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 15
14.7.4.30 FIGURE 3 - KEYWAY

[14.7.4.30 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 16
14.7.4.31 FIGURE 4 - NAILER:

[14.7.4.31 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 17
14.7.4.32 FIGURE 5 - LATERAL SUPPORT

[14.7.4.32 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 18
14.7.4.33 FIGURE 6 - LATERAL SUPPORT

[14.7.4.33 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 19
14.7.4.34 FIGURE 7 - LATERAL SUPPORT:

[14.7.4.34 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 20
14.7.4.35 FIGURE 8 - OPENINGS:

[14.7.4.35 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 21
14.7.4.36 FIGURE 9 - A PIERS:

[14.7.4.36 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 22
14.7.4.37 FIGURE 9 - B PIERS:

[14.7.4.37 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 23
14.7.4.38 FIGURE 10 - WOOD BOND BEAM CONSTRUCTION:

[14.7.4.38 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 24
14.7.4.39 FIGURE 11 - PLACEMENT OF ATTACHED MATERIALS:

[14.7.4.39 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 25
14.7.4.40 FIGURE 12 - ATTACHMENT OF AN ADOBE WALL TO A RAMMED EARTH WALL:

[14.7.4.40 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 26
14.7.4.41 FIGURE 13 - ATTACHMENT OF AN ADOBE WALL TO A RAMMED EARTH WALL:

[14.7.4.41 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4.42 FIGURE 14 - ATTACHMENT OF A LOAD BEARING WOOD OR STEEL FRAME


WALL TO A RAMMED EARTH WALL:

[14.7.4.42 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 27
14.7.4.43 FIGURE 15 - BEARING LIMITATIONS:

[14.7.4.43 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 28
14.7.4.44 FIGURE 16 - ATTACHMENT OF A CONCRETE BOND BEAM TO A RAMMED
EARTH WALL:

[14.7.4.44 NMAC - Rp, 14.11.11.8 NMAC, 1-1-08]


[This figure was not included in the first version of 14.7.4 NMAC (filed 10-18-04).]

14.7.4 NMAC 29
HISTORY OF 14.7.4 NMAC:
Pre-NMAC History: None.

History of Repealed Material:


14.11.11 NMAC, Standard for Rammed Earth Construction (filed 10-31-01) repealed 11-19-04.
14.7.4 NMAC, 2003 New Mexico Earthen Building Materials Code (filed 10-18-04) repealed 1-1-08.

Other History:
14.11.11 NMAC, Standard for Rammed Earth Construction (filed 10-31-01) renumbered and replaced by 14.7.4
NMAC, 2003 New Mexico Earthen Building Materials Code (which did not include figures previously filed in
14.11.11 NMAC), effective 11-19-04.
14.7.4 NMAC, 2003 New Mexico Earthen Building Materials Code (filed 10-18-04) was replaced by 14.7.4 NMAC,
2006 New Mexico Earthen Building Materials Code (which includes figures previously filed in 14.11.11 NMAC),
effective 1-1-08.

14.7.4 NMAC 30

You might also like