14 7 4 Nmac
14 7 4 Nmac
14 7 4 Nmac
14.7.4.1 ISSUING AGENCY: Construction Industries Division of the Regulation and Licensing
Department.
[14.7.4.1 NMAC - Rp, 14.7.4.1 NMAC, 1-1-08]
14.7.4.2 SCOPE: This rule applies to all earthen building materials contracting work performed in New
Mexico on or after January 1, 2008, that is subject to the jurisdiction of CID, unless performed pursuant to a permit
for which an application was received by CID before that date.
[14.7.4.2 NMAC - Rp, 14.7.4.2 NMAC, 1-1-08]
14.7.4.5 EFFECTIVE DATE: January 1, 2008, unless a later date is cited at the end of a section.
[14.7.4.5 NMAC - Rp, 14.7.4.1 NMAC, 1-1-08]
14.7.4.6 OBJECTIVE: The purpose of this rule is to establish minimum standards for earthen building
materials construction in New Mexico.
[14.7.4.6 NMAC - Rp, 14.7.4.1 NMAC, 1-1-08]
14.7.4.7 DEFINITIONS:
A. Amended soil means improving an unqualified soil to a qualified state with the addition of other
soils or amendments.
B. Amendments means additive elements to soil, such as lime, portland cement, fly ash, etc. which
are “dry-mixed” into the main soil body as a percentage of total weight to achieve stabilization.
C. Buttress means a projecting structure providing lateral support to a wall. The buttress shall be
incorporated into the foundation and wall system. (Refer to figure 1 of the earthen building figures supplement).
D. CEB means compressed earth block.
E. Keyway means a groove on the vertical rammed earth wall surface for interlocking purposes.
Refer to figure 3 of the earthen building figures supplement).
F. Lift means a course of rammed earth, placed within the forms, and then compacted.
G. Nailer means any material rammed into the wall that serves as an attachment device. Refer to
figure 4 of the earthen building figures supplement).
H. Optimum moisture means sufficient water (generally no more than ten (10) percent) mixed into
the soil to attain sufficient compaction.
I. psi means pounds per square inch.
J. Qualified soil means any soil, or mixture of soils, that attains 300 psi compression strength and
attains 50 psi. modulus of rupture.
K. Rammed earth means qualified soil that is mechanically or manually consolidated to full
compaction.
L. Round-cap nails means fasteners that include nails or screws in combination with caps of at least
three-fourths (3/4) inches diameter or three-fourths ( ¾) inch square.
M. Stabilization, stabilized means qualified soils that pass the wet strength test under ASTM D1633-
00 or contain a minimum of six (6) percent portland cement by weight. Stabilization is achieved through the use of
amendments.
N. Wet strength compression test means an approved testing laboratory process in which a fully
cured rammed earth cylinder is completely submerged in water a minimum of four hours according to ASTM
D1633-00, then subjected to a compression test.
[14.7.4.7 NMAC - Rp, 14.7.4.7 NMAC, 1-1-08]
14.7.4 NMAC 1
14.7.4.8 EARTHEN BUILDING MATERIALS:
A. General. The provisions of this rule, 14.7.4 NMAC, shall control the design and construction of
one- and two-family dwellings in which earthen building materials form the bearing wall system.
B. Allowable wall heights for earthen structures. All earthen structures whether adobe, burned
adobe, compressed earth block, rammed earth or terrón, shall conform to table 1. For purposes of using table 1,
height is defined as the distance from the top of the slab or top of stem wall to the underside of the bond beam.
14.7.4 NMAC 2
14.7.4.10 CLASSES OF ADOBE:
A. Stabilized adobe. The term “stabilized” is defined to mean water-resistant adobe made of soil to
which certain admixtures are added in the manufacturing process in order to limit water absorption into the adobe.
Exterior walls constructed of stabilized mortar and adobe requires no additional protection. Cement stucco or other
waterproof coating is not required. The test required is that a dried four (4) inch cube cut from a sample unit shall
not gain more than 2.5% in weight when placed upon a constantly water-saturated porous surface for seven (7) days.
An adobe unit that meets this specification shall be considered “stabilized.”
B. Unstabilized adobe. Unstabilized or “natural” adobes are adobes that do not meet the water
absorption specifications indicated in Subsection A of 14.7.4.10 NMAC above. Use of unstabilized adobes is
prohibited within four (4) inches of the finished floor grade. Stabilized adobe or waterproof masonry units and
mortar may be used for the first four (4) inches above floor grade.
C. Terrón. The term “Terrón” shall refer to a cut sod brick. Their use is permitted if units are dry
and the wall design is in conformance with this code.
D. Burned adobe. The term “burned adobe” shall refer to mud adobe bricks that have been cured by
low-temperature kiln firing. This type of adobe is not generally dense enough to be “frostproof” and may deteriorate
with seasonal freeze-thaw cycles. Its use for exterior locations is discouraged in climate zones with daily freeze-
thaw cycles.
[14.7.4.10 NMAC - Rp, 14.7.4.10 NMAC, 1-1-08]
14.7.4 NMAC 3
I. Concrete bond beam. Concrete bond beams shall be a minimum of six (6) inches high by ten
(10) inches wide for walls up to fourteen (14) inches thick. Where adobe walls are wider than one course, two-
thirds (2/3) of each visible course top shall be covered by the concrete bond beam. All concrete bond beams shall be
reinforced with a minimum of two (2) no. 4 reinforcing rods at each floor and ceiling plate line.
J. Wood bond beam. Wood bond beams shall be a minimum of six (6) inches deep by ten (10)
inches wide for walls up to fourteen (14) inches thick. Where adobe walls are wider than one course, two-thirds
(2/3) of each visible course top shall be covered by a wood bond beam and the roof load shall be distributed over
both bond beams. Wood bond beams may be solid in the six-inch (6”) dimension, or may be built up by applying
layers of lumber. Ends of wood bond beams are to be lapped a minimum of the width of the wall and fully nailed.
No wood layer shall be less than one (1) inch nominal thickness. The building official shall approve all wooden
bond beams for walls wider than fourteen (14) inches.
K. Lintels. Lintels of wood or concrete are allowed. When an engineer’s drawing and seal is not
provided, all lintels shall conform to table 2 or 3 below. The required bearing of any lintel shall not be reduced by a
splayed or angled window or door opening.
L. Wood lintels. When an engineer’s drawing and seal is not provided for lintels, all wood lintels
shall conform to table 2 and have a fiber stress rating of at least 850 psi.
M. Concrete lintels. When an engineer’s drawing and seal is not provided for lintels, all concrete
lintels shall conform to table 3 and have a minimum strength of 3000 psi.
N. Anchorage. Roof and floor structures will be suitably anchored to bond beams. Wood joists,
vigas or beams shall be attached to the wood or concrete bond beams with adequate metal fasteners. Door and
window bucks shall be secured to the adobe wall with adequate metal fasteners. “Gringo blocks” or wood nailers,
placed in the adobe walls as they are laid up, are allowed. Wood and metal partitions may be secured to nailing
blocks laid up in the adobe wall or by other approved methods.
O. Plastering. Unstabilized exterior adobe walls can be protected with portland cement plaster with
a minimum thickness of seven-eighths (7/8) inch, if adequate roof, parapet, canal and window flashing is provided.
14.7.4 NMAC 4
If portland cement plaster is used, it must be reinforced with metal wire mesh, minimum seventeen (17) gauge by
one-and-a-half (1 1/2) inch openings, securely attached to the exterior adobe wall surface by nails or staples with a
minimum penetration of one-and-a-half (1 1/2) inch. Such mesh fasteners shall have a maximum spacing sixteen
(16) inches from each other. Any wood surfaces to be covered with stucco or plaster must be protected from
moisture with asphalt felt, reinforced with expanded metal lath. Protective coatings other than plaster are allowed.
Interior gypsum or mud plasters may be applied directly to the wall, provided that adobe head joints have been left
partially open. Expanded metal lath shall be used around window and door openings. If desired, exterior adobe
walls may be protected with mud plaster. Alternative plastering systems shall be submitted for approval by the
building official.
P. Wall insulation. When rigid insulation board is used, round-cap nails shall attach it to the adobe
wall. Cap nails shall have a maximum spacing of sixteen (16) inches from each other. Additionally, cap nails shall
secure the rigid insulation boards around their perimeter edges, with nails spaced no less than twelve (12) inches
apart. All cap nails shall penetrate a minimum of two (2) inches into the adobe wall when securing rigid insulation
board up to two (2) inches in thickness, and three (3) inches when securing insulation board greater than two (2)
inches in thickness.
[14.7.4.11 NMAC - Rp, 14.7.4.11 NMAC, 1-1-08]
14.7.4 NMAC 5
wall of bond beam height and at least ten (10) inches in width that intersects with and attaches to the running wall
with at least sixty (60) degrees of support (refer to figure 5 of the earthen building figures supplement); a minimum
twenty 20 gauge steel frame or wood frame wall of full height that intersects with and attaches to the running wall
with ninety (90) degrees of support, that is properly cross-braced or sheathed (refer to figure 6 of the earthen
building figures supplement); a buttress configuration that intersects the running wall at ninety (90) degrees, of
adobe or rammed earth. The buttress base must project a minimum of three (3) feet (or thirty-three (33) percent of
the wall height) from the running wall and support at least seventy-five (75) percent of the total wall height (refer to
figure 7 of the earthen building figures supplement). The thickness of a rammed earth buttress shall be at least
eighteen (18) inches. The thickness of an adobe buttress shall be a minimum fourteen (14) inches. Rammed earth
walls greater than twenty-four (24) inches in thickness are self-buttressing and do not require lateral support
provided their design adheres to 14.7.4.8 NMAC table 1 and the other applicable provisions of this rule.
F. Openings. Door and window openings shall be designed such that the opening shall not be any
closer to an outside corner of the structure as follows.
(1) In rammed earth walls eighteen (18) inches to less than twenty-four (24) inches thick, openings
shall not be located within three (3) feet of any corner of the structure. (Refer to figure 8 of the earthen building
figures supplement). Exception: Openings may be located within three (3) feet of any corner provided a buttress
extending at least three (3) feet from the structure supports the corner. A continuous footing below and a continuous
bond beam above, shall be provided across such openings.
(2) Rammed earth walls greater than twenty-four (24) inches thick are self-buttressing, with no
special consideration for placement of openings within the area of the wall.
G. Piers. Rammed earth piers supporting openings shall measure no less than three (3) square feet in
area and no dimension shall be less than eighteen (18) inches. (Refer to figures 9-A and 9-B of the earthen building
figures supplement).
[14.7.4.12 NMAC - Rp, 14.7.4.12 NMAC, 1-1-08]
14.7.4.13 FOUNDATIONS:
A. General. Foundation construction shall comply with applicable provisions of the 2003 New
Mexico Residential Building Code, and the following: a minimum of three (3) continuous #4 reinforcing rods are
required in minimum 2500 psi. concrete footings supporting rammed earth walls. Stem walls shall be the full width
of the wall supported above or wider to receive forming systems. Footings shall be a minimum of ten (10) inches in
depth.
B. Perimeter insulation. For the purposes of placement of perimeter insulation, rammed earth walls
may overhang the bearing surface up to the thickness of the perimeter insulation, but in no case greater than two (2)
inches.
C. Keyway. A key way shall be provided where the rammed earth wall meets the foundation system.
The keyway shall be established at the top of the stem a minimum of two (2) inches deep by six (6) inches wide
formed at the time of the pour, and shall run continuously around the structure to include any intersecting rammed
earth wall sections. The rammed earth wall shall be fully rammed into this keyway (refer to figure 2 of the earthen
building figures supplement). Exception: Placement of vertical reinforcing rods extending a minimum twelve (12)
inches into the rammed earth wall. The vertical rods shall be minimum #4, imbedded into the concrete and spaced
forty-eighty (48) inches on center, maximum.
D. Concrete grade beam. Rubble filled foundation trench designs with a reinforced concrete grade
beam above are allowed to support rammed earth wall construction. An architect or engineer registered in the state
of New Mexico shall certify the grade beam/rubble-filled trench design portion.
[14.7.4.13 NMAC - Rp, 14.7.4.13 NMAC, 1-1-08]
14.7.4 NMAC 6
for the building permit. Samples tested shall be representative of soil to be used on the project for which the permit
application is submitted.
C. Stabilized rammed earth soil. The following shall apply to stabilization of rammed earth soil:
Asphalt emulsion may not be used for stabilization of rammed earth soil. Thorough mixing of additives to the soil
may be achieved by any method that assures a complete blending to a uniform color and texture. Stabilized soil is
suitable soil that contains six (6) percent or more portland cement by weight or that passes ASTM D1633-00.
Samples tested shall be representative of soil to be used on the project for which the permit application is submitted.
The compressive strength report shall be submitted with the permit application. Laboratory testing shall indicate
rammed earth samples attained a minimum of two-hundred (200) psi. after seven (7) days. If a different soil is
provided at any time during construction, it must meet the minimum requirements outlined above, prior to use in the
structure.
D. Unstabilized rammed earth soil. Unstabilized rammed earth soil is that containing less than six
(6) percent portland cement by weight or that fails to pass ASTM D1633-00. The exterior of such walls shall be
protected with approved stucco systems or other method approved by the building official. Refer to 14.7.4.19
NMAC for weather-resistive barrier requirements.
E. Amended soil. The following guidelines shall apply when amending soils to attain a qualified
soil. Soil shall not contain rock greater than one-and-a-half (1 1/2) inch in diameter. Soil shall not contain clay
lumps greater than one-half (1/2) inch diameter. Soil shall be free of organic matter. Soil shall not contain more
than two (2) percent soluble salts. Soils to be mixed shall be sufficiently dry to blend completely to one uniform
color and texture. The amended soil shall be tested prior to use as per Subsection B of 14.7.4.14 NMAC.
F. Forming systems. The forming system shall be adequate to contain the material under
compaction. It shall be properly plumbed and braced to withstand the soil pressures as well as construction activity
on and around it.
G. Placement of material, compaction and curing.
(1) No amount of portland cement stabilized soil will be mixed that will not be placed in the wall
system within sixty (60) minutes of its preparation.
(2) Lifts of prepared soil shall be placed in the forms in relatively even layers not to exceed 8 inches
in depth. Each lift shall then be rammed to full compaction.
(3) Optimum moisture content as determined to meet minimum compressive strength shall be
maintained for stabilized and unstabilized walls.
(4) Work will progress, lift-by-lift, until the work approaches bond beam height.
(5) Forms may be stripped immediately after ramming is completed for a section of wall, providing
ramming of adjacent sections does not affect the structural integrity of completed walls.
(6) Portland cement stabilized walls not in forms shall be lightly spray-cured with water at least five
(5) spaced times during daylight hours. This procedure shall continue for at least three (3) days starting from the
time that the wall is exposed to the elements. Exception: Rammed earth walls left in forms three (3) or more days
shall not require water-spray curing.
H. Placement of attachment materials.
(1) Nailers: Nailers incorporated into the rammed earth wall shall be installed as follows (Refer to
figure 4 of the earthen building figures supplement); The rammed earth wall shall not be reduced in thickness with
back-to-back nailers. To avoid an hourglass configuration in the wall section, nailers on either side of a running
wall shall not be opposite each other. Nailers on either side of a running wall shall be separated from each other
vertically a distance not less than the rammed earth wall thickness. Nailers shall be placed onto the wall such that
the narrow dimension of the nailer is exposed on the race of the wall prior to ramming. Nailers shall be cured and
sealed against moisture penetration prior to installation in forms. The nailers shall not extend the full depth of the
wall. Box wood nailers are not allowed. (Refer to figure 11 of the earthen building figures supplement). The nailer
shall be no more than two (2) inches by four (4) inches by its length.
(2) Channels: Channels may be incorporated into the rammed earth wall as follows (Refer to figure
2 of the earthen building figures supplement); To avoid an hourglass configuration in the wall section, channels on
either side of a running wall shall not be opposite each other. (Refer to figure 4 of the earthen building figures
supplement). Channels shall be no more than two (2) inches by four (4) inches by their length in dimension.
Vertical channels shall not be placed closer than twelve (12) inches to a rammed earth wall finished edge or corner.
[14.7.4.14 NMAC - Rp, 14.7.4.14 NMAC, 1-1-08]
14.7.4 NMAC 7
A. General. The depth of voids shall not exceed 8 inches. The width of the void shall be as defined
in Subsections B and C of 14.7.4.15 NMAC below.
B. Voids in stabilized rammed earth walls. Voids shall not exceed two (2) feet in width. Voids
greater than two (2) feet in width require a lintel or half-circle arched opening. Refer to 14.7.4.18 NMAC for lintel
requirements.
C. Voids in unstabilized rammed earth walls. Voids shall not exceed one (1) foot in width. Voids
greater than one (1) foot in width require a lintel or half-circle arched opening of stabilized rammed earth material.
Refer to 14.7.4.18 NMAC for lintel requirements.
[14.7.4.15 NMAC - Rp, 14.7.4.15 NMAC, 1-1-08]
14.7.4 NMAC 8
the rammed earth wall and four (4) inches into the concrete bond beam. (Refer to figure 16 of the earthen building
figures supplement).
I. Attachment of wood bond beam to a rammed earth wall. One-half (1/2) inch anchor bolts with
four (4) inch base hooks shall be rammed into the wall. The bolts shall be staggered a maximum of forty-eight (48)
inches on-center along both edges of the wall, staggered no closer than six (6) inches from the exterior faces of the
wall. The bolt shall extend a minimum of eighteen (18) inches into the rammed earth wall.
[14.7.4.16 NMAC - Rp, 14.7.4.16 NMAC, 1-1-08]
14.7.4 NMAC 9
24” 6” 3- #4 @ 4”o.c.
36” 6” 3- #4 @ 4”o.c.
48” 6” 3- #4 @ 4”o.c. 4” minimum
20” 60” 6” 3- #4 @ 4”o.c. concrete cover on all 1350 PLF
72” 8” 3- #5 @ 4”o.c. sides
84” 8” 3- #5 @ 4”o.c.
96” 10” 3- #5 @ 4”o.c.
24” 6” 3- #4 @ 5”o.c.
36” 6” 3- #4 @ 5”o.c.
48” 6” 3- #4 @ 5”o.c. 3 1/2” minimum
22” 60” 6” 3- #4 @ 5”o.c. concrete cover on all 1700 PLF
72” 8” 3- #5 @ 5”o.c. sides
84” 10” 3- #5 @ 5”o.c.
96” 10” 3- #5 @ 5”o.c.
24” 6” 3- #4 @ 6”o.c.
36” 6” 3- #4 @ 6”o.c.
48” 6” 3- #4 @ 6”o.c. 3” minimum
24” 60” 6” 3- #4 @ 6”o.c. concrete cover on all 2000 PLF
72” 8” 3- #5 @ 6”o.c. sides
84” 10” 3- #5 @ 6”o.c.
96” 12” 3- #5 @ 6”o.c.
14.7.4.21 PLUMBING:
A. General. Code compliant plumbing systems may be rammed into the wall system, either
vertically or horizontally, provided that such plumbing material is of sufficient strength to withstand the ramming
pressures without any rupture or collapse.
14.7.4 NMAC 10
B. Plumbing system installation. Installations shall not reduce the width of the rammed earth wall
by more than one-third (1/3). Prior to ramming, a minimum five (5) inch earth cover is provided over any horizontal
pipe.
[14.7.4.21 NMAC - Rp, 14.7.4.21 NMAC, 1-1-08]
14.7.4.22 ELECTRICAL:
A. Electrical system installation. Electrical wiring shall pass through a channel or conduit.
Approved rigid or flexible electrical conduit shall withstand ramming pressures without damage or collapse.
Electrical wiring within a channel shall be covered a minimum of one and one-fourth (1 1/4) inches. Prior to
ramming, a minimum five (5) inch earth cover shall be provided over any horizontal pipe.
B. UF cable installation. UF cable may not be rammed within the rammed earth wall. Exception:
UF cable installed within an approved conduit or channel. In a channel installation, UF cable must be covered a
minimum of one-and-one-fourth (1 1/4) inches with plaster, adobe or similar finish.
C. Electrical box installation. Plastic electrical boxes shall not be rammed within the rammed earth
wall. Exception: Plastic electrical boxes installed in a channel installation.
[14.7.4.22 NMAC - Rp, 14.7.4.22 NMAC, 1-1-08]
14.7.4 NMAC 11
failure occurs. A true platen should be used in the testing machine, along with swivel head to accommodate
nonparallel bearing surfaces. The compressive strength is defined as P/A, where P = load and A - area of
compression surface.
K. Modulus of rupture. Units shall have a minimum compressive strength of fifty (50) pounds per
square inch in modulus of rupture when tested according to the following procedures: A cured unit shall be laid
over two-inch (2”) diameter cylindrical supports two (2) inches from each end and extending across the full width of
the unit. A cylinder two (2) inches in diameter shall be laid midway between and parallel to the supports. Load
shall be applied to the cylinder at a rate of five hundred (500) psi/minute until rupture occurs. The modulus of
rupture is equal to: 3PL/2bt2 (P= rupture load in pounds, L= span between supports, b= width of block, t= thickness
of block).
[14.7.4.23 NMAC - Rp, 14.7.4.23 NMAC, 1-1-08]
14.7.4.24 MORTAR:
A. General. The use of earth mortar is allowed if the earth mortar material is compatible with the
compressed earth blocks. Conventional lime/sand/cement mortars of Types M, S, and N are also allowed. Mortar
“bedding” joints shall be fully grouted. Head joint mortar is not required provided that the blocks are initially laid in
contact. Partially open “head” joints are allowed if the surface is to be plastered. All joints shall be lapped at least
twenty-five (25) percent of the visible block length.
B. Slip mortars. Liquid mud slip mortar is allowed, providing it is made of a compatible soil that is
screened to eliminate aggregate larger than one-eighth (1/8) inch in diameter. Water may be substituted for slip or
other mortars, providing adequate adhesion is demonstrated.
C. Stacking. “Dry stacking” of compressed earth blocks is allowed providing that adequate adhesion
is demonstrated, the wall is to be stuccoed or plastered and the wall is not less than ten (10) inches in thickness.
D. Use. Compressed earth block may be cured prior to use or laid directly from the press into the
wall in an uncured state.
E. Foundations. Compressed earth blocks may not be used for foundations or basement walls.
F. Footings. All compressed earth block walls shall have a continuous footing at least ten (10)
inches thick. The footing width must be a minimum of thirty-three (33) percent greater than the wall width, but not
less than two (2) inches on each side. The stem wall must be centered on the footing.
G. Stem walls. All stem walls that support CEB units shall extend to an elevation not less than eight
(8) inches above the exterior finish grade. Stem walls shall be as thick as the exterior wall. Where perimeter
insulation is used, a variance is allowed for the stem wall width to be two (2) inches smaller than the width of the
CEB wall it supports.
H. Concrete grade beam. Rubble-filled foundation trench designs with a reinforced concrete grade
beam above are allowed to support CEB construction. An architect or engineer registered in the state of New
Mexico shall certify the grade beam/rubble-filled trench design portion. Other alternative foundation systems must
be approved by the building official.
[14.7.4.24 NMAC - Rp, 14.7.4.24 NMAC, 1-1-08]
14.7.4 NMAC 12
[14.7.4.25 NMAC - Rp, 14.7.4.25 NMAC, 1-1-08]
14.7.4.26 LINTELS:
A. General. Lintels of wood or concrete are allowed. The bearing length of any lintel shall not be
reduced by an angled or splayed window or door opening. Other lintel designs are accepted providing that
engineering is submitted for review by the building official.
B. Wood lintels. When an engineer’s drawing and seal is not provided for lintels, all wood lintels
shall conform to table 5 and have a fiber stress rating of at least 850 psi.
C. Concrete lintels. When an engineer’s drawing and seal is not provided for lintels, all concrete
lintels shall conform to table 6 and have a minimum strength of 3000 psi.
14.7.4.27 ATTACHMENTS AND CONNECTIONS: When rigid insulation board is used, round-cap
nails shall attach it to the CEB wall. Cap nails shall have a maximum spacing of sixteen (16) inches from each
other. Additionally, cap nails shall secure the rigid insulation boards around their perimeter edges, with nails spaced
no less than twelve (12) inches apart. All cap nails shall penetrate a minimum of two (2) inches into the CEB wall
when securing rigid insulation board up to two (2) inches in thickness, and three (3) inches when securing insulation
board greater than two (2) inches in thickness.
[14.7.4.27 NMAC - Rp, 14.7.4.27 NMAC, 1-1-08]
14.7.4 NMAC 13
14.7.4.28 FIGURE 1 - BUTTRESS
Figure 1 – Buttress:
14.7.4 NMAC 14
14.7.4.29 FIGURE 2 - CHANNEL
14.7.4 NMAC 15
14.7.4.30 FIGURE 3 - KEYWAY
14.7.4 NMAC 16
14.7.4.31 FIGURE 4 - NAILER:
14.7.4 NMAC 17
14.7.4.32 FIGURE 5 - LATERAL SUPPORT
14.7.4 NMAC 18
14.7.4.33 FIGURE 6 - LATERAL SUPPORT
14.7.4 NMAC 19
14.7.4.34 FIGURE 7 - LATERAL SUPPORT:
14.7.4 NMAC 20
14.7.4.35 FIGURE 8 - OPENINGS:
14.7.4 NMAC 21
14.7.4.36 FIGURE 9 - A PIERS:
14.7.4 NMAC 22
14.7.4.37 FIGURE 9 - B PIERS:
14.7.4 NMAC 23
14.7.4.38 FIGURE 10 - WOOD BOND BEAM CONSTRUCTION:
14.7.4 NMAC 24
14.7.4.39 FIGURE 11 - PLACEMENT OF ATTACHED MATERIALS:
14.7.4 NMAC 25
14.7.4.40 FIGURE 12 - ATTACHMENT OF AN ADOBE WALL TO A RAMMED EARTH WALL:
14.7.4 NMAC 26
14.7.4.41 FIGURE 13 - ATTACHMENT OF AN ADOBE WALL TO A RAMMED EARTH WALL:
14.7.4 NMAC 27
14.7.4.43 FIGURE 15 - BEARING LIMITATIONS:
14.7.4 NMAC 28
14.7.4.44 FIGURE 16 - ATTACHMENT OF A CONCRETE BOND BEAM TO A RAMMED
EARTH WALL:
14.7.4 NMAC 29
HISTORY OF 14.7.4 NMAC:
Pre-NMAC History: None.
Other History:
14.11.11 NMAC, Standard for Rammed Earth Construction (filed 10-31-01) renumbered and replaced by 14.7.4
NMAC, 2003 New Mexico Earthen Building Materials Code (which did not include figures previously filed in
14.11.11 NMAC), effective 11-19-04.
14.7.4 NMAC, 2003 New Mexico Earthen Building Materials Code (filed 10-18-04) was replaced by 14.7.4 NMAC,
2006 New Mexico Earthen Building Materials Code (which includes figures previously filed in 14.11.11 NMAC),
effective 1-1-08.
14.7.4 NMAC 30