CURRENT TRANSFORMERS type IMZ 10

Catalogue card A29/16/00/E

APPLICATION
The cast resin insulated, singlephase, supporting current transformers type IMZ 10 are intended for supplying measuring instruments and protective circuits of electrical power devices with maximum operating voltage of the power network up to 12 kV and frequency 50 Hz. The range of rated primary currents: 5 1500 A and 2 15 2 600 A. Version with one, two or three cores.

CHARACTERISTICS
small overall dimensions, the width of transformer, which enables the installation with distance between phases t =150 mm, all of mounting dimensions enable the interchangeability of transformers of this type with other transformers manufactured by wellknown firms, the reliability of operation.

OPERATING CONDITIONS
The current transformers type IMZ 10 are designed for operation in indoor equipment, in temperate and tropical climate conditions, and in aggressive environmental conditions. Thanks to the increased impulse test voltage strength and to the increased rated thermal strength the current transformers type IMZ 10 are able to operate at altitudes up to 2600 m above sea level. Longduration thermal current and limits of deviations of transformers in class of accuracy 0,5 corre spond to extended current range for 120% Ipn. The lowest permissible temperature during transportation and storage amounts to 218 K (55oC). The current transformers type IMZ 10 are designed for operation at temperatures from 268 K (5oC) to 313 K (+40oC).

DESIGN AND PRINCIPLE OF OPERATION


The cast resin insulated current transformers type IMZ 10 are singlephase, low power transformers, operating in quasi shortcircuit conditions, transforming the primary current flowing through the high voltage circuit to the secondary current at low potential with the accuracy according to their class. The basic structural components of the current transformers are: primary winding, secondary winding or windings, magnetic core and steel base. The primary winding is cast in epoxyresin mixture. The resinous casting constitutes the main insulation of the transformer. The secondary windings, wound on the insulating spools, are placed together with the magnetic cores in the window of the resinous casting. The steel base is screwed down to the resinous casting. There is the terminal box in the base, in which there are installed the terminal plates with the leads of secondary windings connected to them. The grounding of no matter which of the terminals of secondary winding is made by screwing in a bolt, which is present in a small foil bag placed in the terminal box. We deliver, on Customers request, the cover for current transformers with two and three cores, which enables the sealing of the terminals of measuring windings only.

COMPLIANCE WITH STANDARDS


PNIEC 185 IEC 185 GOST 7746 89 VDE 0414/12.70

THE EXAMPLE OF ORDER


The current transformer type IMZ 10, 2 100/5/5 A/A/A, Ith = 200 Ipn I core:10 VA, class 0,5; FS 10 II core: 5 VA, 10 P 10

WARRANTY
The factory warranty is twenty four months since the day of putting the apparatus into operation, but not longer than thirty six months since the date of purchase.

TECHNICAL DATA
Rated voltage

Type

Maximum permissible voltage of transformer

Rated test votage of insulation power lightning frequency

Rated frequency

Maximum shorttime current thermal dynamic (1 sec.)

Rated shorttime dynamic current

kV IMZ 10 10

kV 12

kV 28

kV 75

Hz 50

kA 60

kA 150

kA
2,5 Ith

The approximate mass of current transformer type IMZ 10 amounts to 24 kg.


ABB Power Distribution

Parameters related to primary circuit


The not switchable current transformers
Rated primary current I pn A 1 2 5 10 15 20 25 30 40 50 60 75 80 100 120 125 150 200 250 300 400 500 600 750 800 1000 1200 1500 Rated shorttime thermal current (1 sec.) Ith 100Ipn kA 0,1 0,2 0,5 1 1,5 2 2,5 3 4 5 6 7,5 8 10 12 15 20 25 30 40 40 40 40 60 60 60 60 200I pn kA 0,2 0,4 1 2 3 4 5 6 8 10 12 15 20 24 30 40 40 60 60 60 37,5 40 40 40 60 40 300I pn kA 0,3 0,6 1,5 3 6 7,5 9 12 15 18 22,5 24 30 500Ipn kA 0,5 1 2,5 7,5 10 12,5 15 20 25 30 37,5 40

The switchable current transformers


Rated primary current I pn A 2x1 2x2 2x5 2x10 2x15 2x20 2x25 2x30 2x40 2x50 2x60 2x75 2x100 2x120 2x125 2x150 2x200 2x250 2x300 2x400 2x500 2x600 Rated shorttime thermal current (1 sec.) Ith 100I pn kA 0,10,2 0,20,4 0,51 12 1,53 24 2,55 36 48 510 612 7,515 1020 1224 1530 2040 2540 3040 4040 4040 4040 200Ipn kA 0,20,4 0,40,8 12 24 36 48 510 612 1020 1224 1530 2040 300Ipn kA 0,30,6 0,61,2 1,53 36 612 7,515 918 1224 1530 22,540 3040 37,540 3040 4040 4040 4040 4040 500Ipn kA 0,51 12 2,55 7,515 1020 12,525 1530 2550 37,540

Rated secondary current Isn = 5 [A]

Parameters of secondary windings

Range of production Rated shorttime thermal current (1 sec.) Ith 100I pn 200Ipn 300I pn 500I pn

Version

The first windings 1S1 1S2 (S1 S2) 10VA cl.0,5 FS10 15VA cl.0,5 FS10 30VA cl.0,5 FS10 45VA cl.0,5 FS10 10VA 10P10 15VA 10P10 20VA 10P10 30VA 10P10 45VA 10P10 10VA cl.0,5 FS10 10VA cl.0,5 FS10 10VA cl.0,5 FS10

The second windings 2S1 2S2

The third windings 3S1 3S2

Parameters of secondary windings


version not recommended version recommended impossible to make * except Ipn = 800; 2400 [A] ** except Ipn = 1; 5; 25; 50; 800; 1000; 21; 25; 225; 250; 2250; 2400; 2500 [A]

1 core

5VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 20VA 10P10 30VA 10P10 30VA 10P10 45VA 10P10 5VA 10P10 5VA 10P10 10VA 10P10 15VA 10P10 5VA 10P10 10VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 5VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 5VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 15VA 10P10

2 cores

15VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 30VA cl.0,5 FS10 30VA cl.0,5 FS10 5VA cl.0,5 FS10 10VA cl.0,5 FS10 10VA cl.0,5 FS10

Minimum installation distances for current transformers type IMZ 10 in consideration of test voltage

* **

3 cores

10VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 30VA cl.0,5 FS10

* * ** **

ABB Power Distribution

DIMENSIONAL DRAWING

Manufacturer reserves for itself the right to train the changes resulting from the technological progress.

Publication 04.2000

CURRENT TRANSFORMERS type IMZ 15


Catalogue card A34/06/00/E

APPLICATION
The castresin insulated single phase, supporting current transformers type IMZ 15 are intended for supplying mea suring instruments and protective circuits of electrical power devices with the maximum permissible voltage of the power network up to 17,5 kV and frequency 50 Hz. The range of rated primary currents: 5 1500 A and 2 15 2 600 A.

CHARACTERISTICS
small overall dimensions, the width of the transformer enables its installation with the distance between phases t = 150 mm, all of mounting dimensions enable the interchangeability of these transformers with the transformers of such kind manufactured by other wellknown firms, producers of current transformers, very low level of partial discharges ensures the durability of insulation and the reliability of operation.

OPERATING CONDITIONS
The current transformers type IMZ 15 are designed for operation in indoor equipment, in temperate and tropical climate conditions, and in aggressive environmental conditions. Thanks to the increased impulse test voltage strength and to the increased rated thermal strength the current transformers type IMZ 15 can operate at altitudes up to 2600 m above sea level. The longduration thermal current and the limits of errors of the transformers in class of accuracy 0,5 correspond to the extended current range for 120% Ipn. The current transformers type IMZ 15 are designed for operation at temperatures from 268 K (5oC) to 313 K (+40oC). The lowest permissible temperature during transportation and storage is 218 K (55 oC).

DESIGN AND PRINCIPLE OF OPERATION


The castresin insulated current transformers type IMZ 15 are the singlephase, low power transformers working in conditions close to the shortcircuit state, transforming the primary current flowing trough the high voltage circuit into the secondary current of low potential with the accuracy according to their class. The basic structural components of the current transformers are: the primary winding, the secondary winding or windings, the magnetic core and the steel base. The primary winding is cast in epoxy resin mixture. The resinous casting makes the main insulation of the transformer. The secondary windings, wound on the insulating spools are placed together with the magnetic cores in the window of the resinous casting. The steel base is screwed down to the resinous casting. There is the terminal box in the base, in which there are installed the terminal plates with the leads of secondary windings connected to them.

COMPLIANCE WITH STANDARDS


PNIEC 185 + A1:1994 IEC 185 DIN/VDE 0414 Teil 1/01.94 GOST 774689

THE EXAMPLE OF ORDER:


The current transformer type IMZ 15; 2 10/5/5 A/A/A; Ith = 200 Ipn I core: 10 VA; class 0,5; FS10 II core: 5 VA; 10P10

WARRANTY
The factory grants 24 months of warranty since the day of putting the apparatus into operation, but no longer than 36 months since the date of sale.

ADDITIONAL INFORMATION
The secondary terminals of measuring windings of the currnet transformers type IMZ 15 can be sealed separately.

TECHNICAL DATA
Maximum permissible voltage of transformer
Rated test votage of insulation power lightning frequency

Rated frequency

Type

Maximum shorttime current thermal dynamic (1 sec.)

Rated shorttime dynamic current

kV IMZ 15 17,5

kV 38

kV 95

Hz 50

kA 60

kA 150

kA
2,5 Ith

The approximate mass of current transformer type IMZ15 amounts to 24 kg.

ABB Power Distribution

PARAMETERS RELATED TO PRIMARY CIRCUIT


The not switchable current transformers Rated primary Rated shorttime thermal current (1 sec.) Ith current Ipn 100Ipn 200Ipn 300Ipn A 5 10 15 20 30 50 75 100 150 200 300 400 600 800 1000 1200 1500 kA 0,5 1 1,5 2 3 5 7,5 10 15 20 30 40 40 60 60 60 60 kA 1 2 3 4 6 10 15 20 30 40 40 kA 1,5 3 6 15 30 40 The switchable current transformers Rated primary Rated shorttime thermal current (1 sec.) Ith current Ipn 100Ipn 200Ipn 300Ipn A 215 250 275 2100 2150 2200 2300 2400 2600 kA 1,53 510 7,515 1020 1530 2040 3040 4040 4040 kA 36 1020 1530 2040 3040 3040 kA 1530

Version

Parameters of secondary windings The first The second The third windings windings windings 1S1 1S2 2S1 2S2 3S1 3S2 (S1 S2)
Rated secondary current Isn = 5 A

Range of production Rated shorttime thermal current (1 sec.) I th 100Ipn 200Ipn 300Ipn

15VA cl. 0,5 FS10 30VA cl. 0,5 FS10 30 VA 10P10 45VA 10P10 10VA cl. 0,5 FS10 10VA cl. 0,5 FS10 15VA cl. 0,5 FS10 15VA cl. 0,5 FS10 5VA 10P10 10VA cl. 0,5 FS10 30VA 10P10 15VA 10P10 15VA 10P10

1 core

2 cores 3 cores

Range of catalogue production except Ipn = 1; 5; 25; 50; 800; 1000; 21; 25; 250; 2250; 2400; 2500 A Note: There is a possibility making the transformer with parameters relating to current circuit and with parameters of secondary windings the same like in the transformers IMZ10.

Minimum installation distances for the current transformers type IMZ 15

The current circuit for the transformers type IMZ 15 (for type tests)

ABB Power Distribution

Notes:
1. 2. 3. 4. 5. 6. 7. 8. Steel base. Insulating housing. Plastic cover. Standardised machine elements: FeZn 12 m. For switchable transformers only. Union pieces: brass for version N3, CuNi 10 m for version T3 (for Ith>30/60 kA: Cu for version N3, CuNi 10 m for version T3). Fasteners: CuNi 10 m. For version N3 mandrels M8 and standardised machine elements M8: Fe(Cu 3 m + Sn 10 m). For version T3 mandrels M8:Fe(Cu 10 m + Ni 5 m + Cr 0.3 m). spring washers: as for version N3. remaining standardised machine elements brassNi 10 m. For version N3 bolt M12 and standardised machine elements M12: Fe(Cu 3 m + Sn 10 m). For version T3 bolt M12 and standardised machine elements M12: Fe(Cu 10 m + Ni 5 m + Cr 0.3 m). spring washers: as for version N3. remaining standardised machine elements brass(CuNi 5 m). Primary terminals: brass for version N3, brassNi 10 m for version T3 (for cooper terminals: Cu for version N3, CuNi 10 m for version T3). Secondary terminals: brassNi 10 m. Standardised machine elements M6: spring washer: Fe(Cu 3 m+Sn 10 m). Remaining standardised machine elements: brassNi 10 m).

9.

11.

Publication 04.2000

10.

CURRENT TRANSFORMERS type IMZ 20


Catalogue card A29/26/00/E

APPLICATION
The cast resin insulated, singlephase, supporting current transformers type IMZ 20 are intended for supplying measuring instruments and protective circuits of electrical power devices with maximum operating voltage of the power network up to 24 kV and frequency 50 Hz. The range of rated primary currents: 5 1500 A and 2 15 2 600 A. Version with one, two or three cores.

CHARACTERISTICS
small overall dimensions, all of mounting dimensions enable the interchangeability of transformers of this type with other transformers manufactured by wellknown firms, the reliability of operation.

OPERATING CONDITIONS
The current transformers type IMZ 20 are designed for operation in indoor equipment, in temperate and tropical climate conditions, and in aggressive environmental conditions. Thanks to the increased impulse test voltage strength and to the increased rated thermal strength the current transformers type IMZ 20 are able to operate at altitudes up to 2600 m above sea level. Longduration thermal current and limits of deviations of transformers in class of accuracy 0,5 correspond to extended current range for 120% Ipn. The lowest permissible temperature during transportation and storage amounts to 218 K (55oC). The current transformers type IMZ 20 are designed for operation at tempera tures from 268 K (5oC) to 313 K (+40oC).

DESIGN AND PRINCIPLE OF OPERATION


The cast resin insulated current transformers type IMZ 20 are singlephase, low power transformers, operating in quasi shortcircuit conditions, transforming the primary current flowing through the high voltage circuit to the second ary current at low potential with the accuracy according to their class. The basic structural components of the current transformers are: primary winding, secondary winding or windings, magnetic core and steel base. The primary winding is cast in epoxyresin mixture. The resinous casting constitutes the main insulation of the transformer. The secondary windings, wound on the insulating spools, are placed together with the magnetic cores in the window of the resinous casting. The steel base is screwed down to the resinous casting. There is the terminal box in the base, in which there are installed the terminal plates with the leads of secondary windings connected to them. The grounding of no matter which of the terminals of secondary winding is made by screwing in a bolt, which is present in a small foil bag placed in the terminal box. We deliver, on Customers request, the cover for current transformers with two and three cores, which enables the sealing of the terminals of measuring windings only.

COMPLIANCE WITH STANDARDS


PNIEC 185 IEC185 VDE 0414/12.70

THE EXAMPLE OF ORDER


The current transformer type IMZ 20, 2100/5/5 A/A/A, Ith= 200 I pn I core:10 VA, class 0,5; FS 10 II core: 5 VA, 10 P 10

WARRANTY
The factory warranty is twenty four months since the day of putting the apparatus into operation, but not longer than thirty six months since the date of purchase.

TECHNICAL DATA
Rated voltage

Type

Maximum permissible voltage of transformer

Rated test votage of insulation power lightning frequency

Rated frequency

Maximum shorttime current thermal dynamic (1 sec.)

Rated shorttime dynamic current

kV IMZ 20 20

kV 24

kV 50

kV 125

Hz 50

kA 60

kA 150

kA
2,5 Ith

The approximate mass of current transformer type IMZ 20 amounts to 33 kg.

ABB Power Distribution

Parameters related to primary circuit


The not switchable current transformers
Rated primary current Ipn A 1 2 5 10 15 20 25 30 40 50 60 75 80 100 120 125 150 200 250 300 400 500 600 750 800 1000 1200 1500 Rated shorttime thermal current (1 sec.) Ith 100Ipn kA 0,1 0,2 0,5 1 1,5 2 2,5 3 4 5 6 7,5 8 10 12 15 20 25 30 40 40 40 40 60 60 60 60 200Ipn kA 0,2 0,4 1 2 3 4 5 6 8 10 12 15 20 24 30 40 40 60 60 60 37,5 40 40 40 60 40 300Ipn kA 0,3 0,6 1,5 3 6 7,5 9 12 15 18 22,5 24 30 500Ipn kA 0,5 1 2,5 7,5 10 12,5 15 20 25 30 37,5 40

The switchable current transformers


Rated primary current Ipn A 21 22 25 210 215 220 225 230 240 250 260 275 2100 2120 2125 2150 2200 2250 2300 2400 2500 2600 Rated shorttime thermal current (1 sec.) Ith 100Ipn kA 0,10,2 0,20,4 0,51 12 1,53 24 2,55 36 48 510 612 7,515 1020 1224 1530 2040 2540 3040 4040 4040 4040 200Ipn kA 0,20,4 0,40,8 12 24 36 48 510 612 1020 1224 1530 2040 300Ipn kA 0,30,6 0,61,2 1,53 36 612 7,515 918 1224 1530 22,540 3040 37,540 3040 4040 4040 4040 4040 500Ipn kA 0,51 12 2,55 7,515 1020 12,525 1530 2550 37,540

Rated secondary current Isn = 5 A

Parameters of secondary windings The first windings The second windings The third windings 1S1 1S2 2S1 2S2 3S1 3S2 (S1 S2) 10VA cl.0,5 FS10 15VA cl.0,5 FS10 30VA cl.0,5 FS10 45VA cl.0,5 FS10 10VA 10P10 15VA 10P10 20VA 10P10 30VA 10P10 45VA 10P10 10VA cl.0,5 FS10 10VA cl.0,5 FS10 10VA cl.0,5 FS10 5VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 20VA 10P10 30VA 10P10 30VA 10P10 45VA 10P10 5VA 10P10 5VA 10P10 10VA 10P10 15VA 10P10 5VA 10P10 10VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 5VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 5VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 15VA 10P10

Version

Range of production
Rated shorttime thermal current (1 sec.) Ith 100Ipn 200Ipn 300Ipn 500Ipn

Parameters of secondary windings


version not recommended version recommended impossible to make * except Ipn = 800; 2400 A ** except Ipn = 1; 5; 25; 50; 800; 1000; 21; 25; 225; 250; 2250; 2400; 2500 A

2 cores

1 core

15VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 30VA cl.0,5 FS10 30VA cl.0,5 FS10 5VA cl.0,5 FS10 10VA cl.0,5 FS10 10VA cl.0,5 FS10

* **

3 cores

10VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 30VA cl.0,5 FS10

* * ** **

ABB Power Distribution

Publication 04.2000