ABB - IMZ Prospect
ABB - IMZ Prospect
ABB - IMZ Prospect
APPLICATION
The cast resin insulated, singlephase, supporting current transformers type IMZ 10 are intended for supplying measuring instruments and protective circuits of electrical power devices with maximum operating voltage of the power network up to 12 kV and frequency 50 Hz. The range of rated primary currents: 5 1500 A and 2 15 2 600 A. Version with one, two or three cores.
CHARACTERISTICS
small overall dimensions, the width of transformer, which enables the installation with distance between phases t =150 mm, all of mounting dimensions enable the interchangeability of transformers of this type with other transformers manufactured by wellknown firms, the reliability of operation.
OPERATING CONDITIONS
The current transformers type IMZ 10 are designed for operation in indoor equipment, in temperate and tropical climate conditions, and in aggressive environmental conditions. Thanks to the increased impulse test voltage strength and to the increased rated thermal strength the current transformers type IMZ 10 are able to operate at altitudes up to 2600 m above sea level. Longduration thermal current and limits of deviations of transformers in class of accuracy 0,5 corre spond to extended current range for 120% Ipn. The lowest permissible temperature during transportation and storage amounts to 218 K (55oC). The current transformers type IMZ 10 are designed for operation at temperatures from 268 K (5oC) to 313 K (+40oC).
WARRANTY
The factory warranty is twenty four months since the day of putting the apparatus into operation, but not longer than thirty six months since the date of purchase.
TECHNICAL DATA
Rated voltage
Type
Rated frequency
kV IMZ 10 10
kV 12
kV 28
kV 75
Hz 50
kA 60
kA 150
kA
2,5 Ith
Range of production Rated shorttime thermal current (1 sec.) Ith 100I pn 200Ipn 300I pn 500I pn
Version
The first windings 1S1 1S2 (S1 S2) 10VA cl.0,5 FS10 15VA cl.0,5 FS10 30VA cl.0,5 FS10 45VA cl.0,5 FS10 10VA 10P10 15VA 10P10 20VA 10P10 30VA 10P10 45VA 10P10 10VA cl.0,5 FS10 10VA cl.0,5 FS10 10VA cl.0,5 FS10
1 core
5VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 20VA 10P10 30VA 10P10 30VA 10P10 45VA 10P10 5VA 10P10 5VA 10P10 10VA 10P10 15VA 10P10 5VA 10P10 10VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 5VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 5VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 15VA 10P10
2 cores
15VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 30VA cl.0,5 FS10 30VA cl.0,5 FS10 5VA cl.0,5 FS10 10VA cl.0,5 FS10 10VA cl.0,5 FS10
Minimum installation distances for current transformers type IMZ 10 in consideration of test voltage
* **
3 cores
10VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 30VA cl.0,5 FS10
* * ** **
DIMENSIONAL DRAWING
Manufacturer reserves for itself the right to train the changes resulting from the technological progress.
Publication 04.2000
APPLICATION
The castresin insulated single phase, supporting current transformers type IMZ 15 are intended for supplying mea suring instruments and protective circuits of electrical power devices with the maximum permissible voltage of the power network up to 17,5 kV and frequency 50 Hz. The range of rated primary currents: 5 1500 A and 2 15 2 600 A.
CHARACTERISTICS
small overall dimensions, the width of the transformer enables its installation with the distance between phases t = 150 mm, all of mounting dimensions enable the interchangeability of these transformers with the transformers of such kind manufactured by other wellknown firms, producers of current transformers, very low level of partial discharges ensures the durability of insulation and the reliability of operation.
OPERATING CONDITIONS
The current transformers type IMZ 15 are designed for operation in indoor equipment, in temperate and tropical climate conditions, and in aggressive environmental conditions. Thanks to the increased impulse test voltage strength and to the increased rated thermal strength the current transformers type IMZ 15 can operate at altitudes up to 2600 m above sea level. The longduration thermal current and the limits of errors of the transformers in class of accuracy 0,5 correspond to the extended current range for 120% Ipn. The current transformers type IMZ 15 are designed for operation at temperatures from 268 K (5oC) to 313 K (+40oC). The lowest permissible temperature during transportation and storage is 218 K (55 oC).
WARRANTY
The factory grants 24 months of warranty since the day of putting the apparatus into operation, but no longer than 36 months since the date of sale.
ADDITIONAL INFORMATION
The secondary terminals of measuring windings of the currnet transformers type IMZ 15 can be sealed separately.
TECHNICAL DATA
Maximum permissible voltage of transformer
Rated test votage of insulation power lightning frequency
Rated frequency
Type
kV IMZ 15 17,5
kV 38
kV 95
Hz 50
kA 60
kA 150
kA
2,5 Ith
Version
Parameters of secondary windings The first The second The third windings windings windings 1S1 1S2 2S1 2S2 3S1 3S2 (S1 S2)
Rated secondary current Isn = 5 A
Range of production Rated shorttime thermal current (1 sec.) I th 100Ipn 200Ipn 300Ipn
15VA cl. 0,5 FS10 30VA cl. 0,5 FS10 30 VA 10P10 45VA 10P10 10VA cl. 0,5 FS10 10VA cl. 0,5 FS10 15VA cl. 0,5 FS10 15VA cl. 0,5 FS10 5VA 10P10 10VA cl. 0,5 FS10 30VA 10P10 15VA 10P10 15VA 10P10
1 core
2 cores 3 cores
Range of catalogue production except Ipn = 1; 5; 25; 50; 800; 1000; 21; 25; 250; 2250; 2400; 2500 A Note: There is a possibility making the transformer with parameters relating to current circuit and with parameters of secondary windings the same like in the transformers IMZ10.
The current circuit for the transformers type IMZ 15 (for type tests)
Notes:
1. 2. 3. 4. 5. 6. 7. 8. Steel base. Insulating housing. Plastic cover. Standardised machine elements: FeZn 12 m. For switchable transformers only. Union pieces: brass for version N3, CuNi 10 m for version T3 (for Ith>30/60 kA: Cu for version N3, CuNi 10 m for version T3). Fasteners: CuNi 10 m. For version N3 mandrels M8 and standardised machine elements M8: Fe(Cu 3 m + Sn 10 m). For version T3 mandrels M8:Fe(Cu 10 m + Ni 5 m + Cr 0.3 m). spring washers: as for version N3. remaining standardised machine elements brassNi 10 m. For version N3 bolt M12 and standardised machine elements M12: Fe(Cu 3 m + Sn 10 m). For version T3 bolt M12 and standardised machine elements M12: Fe(Cu 10 m + Ni 5 m + Cr 0.3 m). spring washers: as for version N3. remaining standardised machine elements brass(CuNi 5 m). Primary terminals: brass for version N3, brassNi 10 m for version T3 (for cooper terminals: Cu for version N3, CuNi 10 m for version T3). Secondary terminals: brassNi 10 m. Standardised machine elements M6: spring washer: Fe(Cu 3 m+Sn 10 m). Remaining standardised machine elements: brassNi 10 m).
9.
11.
Publication 04.2000
10.
APPLICATION
The cast resin insulated, singlephase, supporting current transformers type IMZ 20 are intended for supplying measuring instruments and protective circuits of electrical power devices with maximum operating voltage of the power network up to 24 kV and frequency 50 Hz. The range of rated primary currents: 5 1500 A and 2 15 2 600 A. Version with one, two or three cores.
CHARACTERISTICS
small overall dimensions, all of mounting dimensions enable the interchangeability of transformers of this type with other transformers manufactured by wellknown firms, the reliability of operation.
OPERATING CONDITIONS
The current transformers type IMZ 20 are designed for operation in indoor equipment, in temperate and tropical climate conditions, and in aggressive environmental conditions. Thanks to the increased impulse test voltage strength and to the increased rated thermal strength the current transformers type IMZ 20 are able to operate at altitudes up to 2600 m above sea level. Longduration thermal current and limits of deviations of transformers in class of accuracy 0,5 correspond to extended current range for 120% Ipn. The lowest permissible temperature during transportation and storage amounts to 218 K (55oC). The current transformers type IMZ 20 are designed for operation at tempera tures from 268 K (5oC) to 313 K (+40oC).
WARRANTY
The factory warranty is twenty four months since the day of putting the apparatus into operation, but not longer than thirty six months since the date of purchase.
TECHNICAL DATA
Rated voltage
Type
Rated frequency
kV IMZ 20 20
kV 24
kV 50
kV 125
Hz 50
kA 60
kA 150
kA
2,5 Ith
Parameters of secondary windings The first windings The second windings The third windings 1S1 1S2 2S1 2S2 3S1 3S2 (S1 S2) 10VA cl.0,5 FS10 15VA cl.0,5 FS10 30VA cl.0,5 FS10 45VA cl.0,5 FS10 10VA 10P10 15VA 10P10 20VA 10P10 30VA 10P10 45VA 10P10 10VA cl.0,5 FS10 10VA cl.0,5 FS10 10VA cl.0,5 FS10 5VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 20VA 10P10 30VA 10P10 30VA 10P10 45VA 10P10 5VA 10P10 5VA 10P10 10VA 10P10 15VA 10P10 5VA 10P10 10VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 5VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 5VA 10P10 10VA 10P10 15VA 10P10 15VA 10P10 15VA 10P10
Version
Range of production
Rated shorttime thermal current (1 sec.) Ith 100Ipn 200Ipn 300Ipn 500Ipn
2 cores
1 core
15VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 30VA cl.0,5 FS10 30VA cl.0,5 FS10 5VA cl.0,5 FS10 10VA cl.0,5 FS10 10VA cl.0,5 FS10
* **
3 cores
10VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 15VA cl.0,5 FS10 30VA cl.0,5 FS10
* * ** **
Publication 04.2000