Transmission Object Terminals: Station Automation & Protection
Transmission Object Terminals: Station Automation & Protection
Transmission Object Terminals: Station Automation & Protection
Station Automation Station Automation includes control, monitoring, and protection for power plant, transmission, distribution, and industry applications. Solutions range from single
Station Automation & Protection
Network Management Network Management enhances operation of interconnected power networks. It provides integrated solutions that optimize energy supply while maximizing reliability on both transmission and distribution networks.
Network Management
Business Management Business Management provides business tools and solutions to help the power utility become more competitive in todays changing energy market place. Systems for energy trading, asset management, and customer information provide essential descision support in a competitive environment.
Business Management
Meter & Load Management Meter and Load Management comprises products and integrated systems for automatic meter reading, home automation, direct load control, and demandside management.
Meter & Load Management
Consulting & Services The range of comprehensive services includes pre-studies, project management, engineering, system configuration, documentation, installation, commissioning, training, upgrading, and maintenance.
Consulting & Services
Communications Communications offers solutions for all communications requirements in the transmission and distribution networks of power utilities and industries.
Communications
Choose Partnership or Independence The universal object terminal offers a full range of solutions. Through a partnership with ABB or through independent efforts, utility engineers can custom-design the protection, control, and monitoring systems needed to match every specific requirement. Such custom-made solutions may include adding: a stand alone fault-locator, a part of a coordinated station automation system, an RTU replacement, or a uniquely configured line terminal with protection, control, and monitoring functions. Through a partnership with ABB, such custommade terminals can be offered as unique products delivered from the factory, pre-configured, and ready to plug in. Choose the Terminal Design State-of-the-art hardware and software architecture is the foundation of the flexibility offered by the object terminal concept. A large library of typetested hardware and software modules can be mixed in a suitable fashion to ensure that a variety of requirements can be met. As an alternative to tailor-made terminals, ABB also offers standard terminals for protection, control, and monitoring of the electrical power system. Choose the System Design With either custom-made or standard terminals, users exercise tremendous flexibility in designing their systems. The object terminal concept offers the opportunity to design systems that meet high availability requirements and low cost investments.
The flexibility of protection, control, and monitoring functions, combined with system-wide back-up features, gives design engineers a unique opportunity to improve availability and reliability. Choose Retrofit Installations Your companys existing installations may be based on available technology and functionality that date back several decades. To ensure network stability, much of this technology must remain, but in an updated form. Also, time and space often pose problems when replacing technology. However, the object terminal concept offers solutions to all of these prospective problems with improved availability. For instance: New equipment may be installed in parallel to existing equipment, thus reducing space requirements. Plug-and-play pre-configured system devices ensure short project lead time. Custom-made designs (based on a large library of tested modules) ensure compatibility with already existing installations. An open communication structure allows for integration of third-party devices for protection, monitoring, and control. Several alternatives are available, e.g., the standardised and open protocols SPA and LON. Another alternative is the international standard IEC 870-5-103. System-oriented tools ensure functional coordination, plausibility checks, and efficient engineering.
Choose Functions from the Software Library Choose among a large number of protection, control, monitoring, and communication features. The application library contains type-tested software modules that are developed for the electrical power system. For the complete application library of functions see Function Overview on pages 10-12. Select the Necessary Hardware Modules The terminals modular structure supports multiprocessor technology and multiple I/O boards with field upgrading capabilities. The terminal can be delivered with a variety of hardware modules, depending on customer requirements. Add a Terminal Case The basic terminal is delivered with a DC/DC converter and a main processing module equipped with a real-time clock that supports the millennium change. The housing can be a one-half, a threequarter, or a full-size 19 rack, 6 U high (247 mm), and 245 mm deep. The modular system, with standardised plug-in boards, allows for easy modifications and repairs, as well as future field upgrading. Configure the Terminal The configuration of the terminal is carried out by means of an IEC 1131-3 PC-based tool, CAP 531, which allows the user to configure the terminal using graphic symbols, and thus makes configuration and documentation very simple and efficient. The configuration can also be made part of a company standard, delivered by ABB as a preconfigured, plug-and-play device.
Protection, Control, and Monitoring The object terminal software library consists of several type-tested function blocks. Each function block is specifically designed to meet stringent requirements for dependability and security. All function blocks can easily be combined into complex functions by using a graphical PC-based tool, CAP 531. A set of standard, logical building blocks, like AND-gates, OR-gates, timers, etc., ensures ease in designing conditional logics. Thus, custom-designed tripping and auto-reclosing logics, as well as control and interlocking logics can be designed by an IEC 1131-3 based human machine interface (HMI). For available functions, see Function Overview, pages 10-12.
trip logic or block of distance protection from fuse failure supervision. can be used as an input signal to another function block. External signals can be used to block or enable a certain function. A monitoring function offers an on-line check of all internal signals in an object terminal. This function offers the user a powerful help tool, providing a window into the terminal, where the user can see the changes in a signal status.
Communication The object terminal supports multiple communication ports: a front PC connection and two rear serial communication ports, one port with either IEC 870-5-103 or ABB SPA-bus and another port with Local Operating Network (LON)-bus communication. Configuration The LON bus is a high speed (1,25 MHz) openCAP 531 is used throughout all stages of a project, system defacto standard. It allows direct communifrom engineering to testing, commissioning, cation between terminals without depending on a documentation, and maintenance. The user can central PC or bus-master. To further improve the remove and add connections between different fault tolerance, the LON bus uses noise-immune function blocks in order to achieve required funcfiberoptics with a passive star coupler; so, a faulty tionality. A number of free logical elements (AND, fibre optic connection will only affect one terminal. OR, Timers, etc.) enables configuration of different Information is available, both as time-tagged requirements for customer-specific solutions. events with 1 millisecond resolution and load and Various function blocks can be combined either fault data, and as complete oscillographic disturas pre-determined or custom-designed schemes. This bance recording. Any function and parameter can be means that an output signal from one function programmed and changed via remote communicablock (e.g. start of breaker failure protection from tion
Communication possibilities.
HMI & Information Handling Each terminal has a built-in, distributed database. This function secures all information locally, ignores disruptions in DC supply, and does not rely on any central memory. The database acts as a buffer for: event signals, which are time-tagged on-line; fault locator values; and other information. Event recording is not limited to internal events: it can also be used to store any status change in any of the binary inputs. Therefore, the terminal can also be used, for example to monitor switchgear equipment. A number of terminals can be looped over a fibre optic bus and connected directly to a station PC and a telephone modem. From any remote location with a telephone modem, it is possible to access any station and any terminal: available information includes everything stored in each terminal, even load and fault data. To verify performance, it is also possible to use the recorded values of current and voltage during a fault for a playback via computerised relay test set and simulator program. Self-supervision One of the major benefits of microprocessor technology is that no additional hardware is
required for self-supervision a function that increases the availability and reliability of the whole system by ensuring that product faults can be detected immediately. Messages from the self-supervision system can be available both locally and remotely, which further simplifies fault-tracing, and cuts down repair time by identifying defective parts. Example: The mean time to repair (MTTR), can be compared with conventional static or electromechanical equipment without supervision. With a test interval of, say, 2 years, the MTTR without supervision is 1 year, since a fault will most likely not be detected until the next test is performed. With supervision, a fault can normally be repaired within 48 hours. This means that the MTTR will be 2 days instead of 365 days a significant improvement. Documentation Vision Each terminal is delivered with delivery-specific and user-adapted documentation that corresponds to the hardware and software content. The documentation consists of a users manual, terminal schemes, configuration drawings, and apparatus lists. It is available in paper form and on CD-ROM.
The REL 500 series The REL 500 series terminals cover all needs for protection, control and monitoring of overhead lines and cables on all voltage levels, from radial feeders to complex line configurations and series compensated lines. MV/HV Line Distance Protection Terminals: REL 501 and REL 511 The REL 501 and REL 511 terminals can be applied to distribution and subtransmission overhead lines and cables in a solidly earthed, as well as in isolated or high impedance networks. The basic protection function is a quadrilateral impedance measurement of full-scheme type for phase-to-phase faults in REL 501 and for phase-tophase and phase-to-earth faults in REL 511. A separate general fault criteria (GFC) with advanced characteristics is used in both terminals as an overall measuring function, increasing total operating security. HV/EHV Line Distance Protection Terminals: REL 521 and REL 531 Both the REL 521 and the REL 531 terminals can be applied to transmission overhead lines and cables in solidly earthed networks; however, the REL 521 places only moderate demands on tripping time, while the REL 531 places very high demands on short tripping time. REL 531 also comes with optional functions for series-compensated networks.
Both terminals have the basic protection function of a quadrilateral impedance measurement of full-scheme type for phase-to-phase and phase-toearth faults. But, the REL 531 also has a complimentary high-speed zone for carrier send and independent trip functions. Individual earth-return-compensated, separatephase selection zone, and scheme communication logics make both terminals optimal for use with parallel lines. Line Differential Protection Terminals: REL 551 and REL 561 The REL 551 and REL 561 terminals can be applied to distribution, subtransmission and transmission overhead lines and cables in solidly earthed, as well as in isolated or high impedance networks. The basic function in both terminals is a current differential protection of master/master type, evaluating each phase current separately at both ends, using both the current amplitude and phase angle (segregated vector comparison) for maximum sensitivity with maintained stability. As an option in REL 561 a full-scheme threezone distance protection function is available as back-up for the communication channel and for the clearing of faults on the remote busbar.
Object Terminal for Railway Systems: REO 517 The REO 517 terminal can be applied to singlephase contact lines or two-phase transmission lines for railway systems, both in directly earthed and impedance earthed systems. The main protection facility is a full-scheme distance protection device featuring three impedance measuring zones with quadrilateral characteristic. A sudden current change function is used to distinguish between load and fault conditions. Breaker Protection Terminal: REB 551 The REB 551 breaker terminal provides breakerrelated functions associated with protection, such as breaker failure protection, autoreclosing, synchronism and energising check, and pole discordance. In 1 1/2-breaker, double-breaker, and ringbus arrangements there are two breakers assigned to trip one end of a line or one side of a transformer, and some breakers may be shared by two power circuits or objects. Control Terminal: REC 561 REC 561 is used for control and supervision of circuits breakers, disconnectors, and earthing switches in any kind of switchgear and busbar arrangement. Functions such as interlocking, autorecloser, and synchrocheck are also included. The terminal is suitable for various configurations from cost-effective solutions with a
high degree of integration, to optimised, highly available configurations. One REC 561 can handle the supervision and control of three HV bays, with a separate synchrocheck of each bay. Transformer Protection Terminal: RET 521 RET 521 is a multi-functional transformer protection terminal suitable for fast and selective protection and control of two- and three-winding transformers, auto-transformers, generator-transformer blocks and shunt reactors. Also, an optional voltage control of parallel transformers is provided. Users can select the transformer size, vector groups, system neutral earthing, and extension of protection functions according to their preferences. The RET 521, has a compact design for protection and control, with internal programmable logic to provide trip or indication for external protections (e.g. Buchholz and over-pressure relays). With the new tapchanger position, the differential protection function can be set to optimum sensitivity covering low-fault currents. Furthermore, to guarantee high sensitivity to unwanted operations, RET 521 has selectable and adaptive current bias characteristics for through-fault stability and advanced in-rush restraint methods. No interposing current transformer is required. The RET 521 is also a major component in the Intelligent Air Insulated Switchgear (I-AIS) concept.
Included
Optional
Not applicable
REO REL REL REL REL REL REL REB REC RET 517 501 511 521 531 551 561 551 561 521 FUNCTIONS Basic
Self-supervision with internal event recorder Real-time clock with external time syncronization Four groups of setting parameters Local Human Machine Interface (HMI) Configurable logic Service value reading
Line Distance
General fault criteria protection, impedance and current-based General fault criteria protection with phase-preference logic, impedance-based 3 zones phase, phase protection 3 zones phase, earth protection Additions for series-compensated network Additional zone 4 and 5 protection High-speed protection Phase selection logic Power-swing detection Power-swing additional logic Scheme communication logic, incl. curr. rev. and WEI logic Scheme communication logic, phase-segregated Automatic switch onto fault logic Local acceleration logic Sudden current change
Line Differential
Line differential protection, phase-segregated Charging current compensation
Transformer
Transformer differential protection, upto 5 restraint groups Restricted earth fault protection Overexcitation protection
Phase Current
Instantaneous phase overcurrent protection Time-delayed-phase overcurrent protection Inverse time-phase overcurrent protection Thermal-phase overload protection Phase-directional check Stub protection Pole-discordance protection Breaker failure protection
* * *
* * *
* * *
* * *
* *
* * *
* * *
10
REO REL REL REL REL REL REL REB REC RET 517 501 511 521 531 551 561 551 561 521 Residual Current (earth fault)
Instantaneous residual overcurrent protection (non-dir.) Time-delayed residual overcurrent protection (non-dir.) Inverse time residual overcurrent protection (non-dir.) Residual directional check and communication logic (dir. element) Wattmetric residual protection (dir. / non-dir.)* 4-step residual overcurrent protection (dir. / non-dir.)
Voltage
Time-delayed under- and overvoltage protection Residual overvoltage protection
Logic
Three-pole tripping logic Single- or two-pole tripping logic Pole discordance logic (contact based) Additional configurable logic Binary signal collection and transfer to remote end Binary signal interbay communication
11
REO REL REL REL REL REL REL REB REC RET 517 501 511 521 531 551 561 551 561 521 Monitoring
Disturbance recorder, 15/40 seconds Event recorder Fault-locator recorder Trip-value recorder Increased measuring accuracy for U, I, P, Q
Metering
1/2 of 19" rack (Maximum 3 I/O modules) 3/4 of 19" rack (Maximum 8 I/O modules) 1/1 of 19" rack (Maximum 13 I/O modules)
Analogue Input Modules
50/60 Hz analogue systems, conventional inputs 16 2/3 Hz analogue systems, conventional inputs 50/60 Hz analogue systems, low-level voltage inputs (10V)* 50/60 Hz analogue systems, optical transducer interface (OITP)*
Power Supply
Power supply module Power supply module, with binary in/out module
In/Out Modules
Binary in/out module, 8 inputs and 12 output relays, 24/36V Binary input module, 16 inputs, 24/36V mA input module, 6 channels Binary output module, 24 output relays.
Remote-End Data Communication Modules
48/60V
110/125V
220/250V
48/60V
10/125V
220/250V
V35/36 co-mode/contra-mode X21 RS530/422 co-mode/contra-mode Fibre optical modem Short-range galvanic modem Short-range optical modem
Optical Station bus Communication Modules (for SMS and/or SCS):
Port IEC 870-5-103 / SPA (SPA only for RET 521) Port LON
UTILITIES Second MMI Language
12
13
14
Printed with an
INDIGO