Chapter 12 - Electric Motor Drive Start-Up Procedures
Chapter 12 - Electric Motor Drive Start-Up Procedures
PowerPoint Presentation
Chapter 12
Electric Motor Drive Start-up Procedures
Initial Checks Secondary Checks Final Checks
Electric motor drive voltage is tested at the line power terminal strip, load power terminal strip, DC bus terminal strip, and the control terminal strips.
A motor and load must be secured in place and correctly aligned, and the shafts must be rotated to detect mechanical problems.
A conductor and motor winding insulation spottest connects a megohmmeter between a load conductor and ground and stresses the insulation with a voltage.
An insulation spot-test identifies a problem as either with the conductors to a motor or the motor windings.
An ESD-safe vacuum with accessories is used to safely remove debris from an electric motor drive.
A DMM set to measure resistance is used to check for grounds in an electric motor drive.
A DMM set to the diode check mode is used to test the diodes in the converter section of an electric motor drive.
A DMM set to the diode check function is used to test the transistors and fly-back diodes in the inverter section of an electric motor drive.
Power supply voltage to an electric motor drive is measured on the line side of the disconnect with a DMM.
The line conductors, grounds, and control wiring must be tight and must terminate at the correct positions on an electric motor drive.
DIP switches or jumpers are used on electric motor drives to select various functions for a specific application.
Overload relays must be sized for the nameplate current of a motor and are available in a variety of configurations.
Power is applied to an electric motor drive after DIP switches, jumpers, wiring, and overload protection are set or configured correctly.
The functionality of an electric motor drive is tested by running the drive without the motor conductors connected.
To compare the measured current reading with the nameplate current rating of a motor, the motor must be operated at a speed of 60 Hz.
The electric motor drive, motor, and driven load test verifies that a 4 mA 20 mA signal from a mixing process provides proper speed reference to the electric motor drive.
The operation of a bypass contactor must be tested before the start-up of an electric motor drive is complete.