Compressor - 3 PDF
Compressor - 3 PDF
Compressor - 3 PDF
Refrigerant-type dryers cool the air to 35 to 40F and then remove the
condensed moisture before the air is reheated and discharged
Deliquescent-type dryers use a hygroscopic desiccant material with a high
affinity for water. The desiccant absorbs water vapor and is dissolved in the
liquid formed. Dew point suppression of 15 to 50F degrees can be expected
when the proper bed level is maintained
Twin tower regenerative-type dryers use a desiccant which adsorbs water
vapor in the air stream. Adsorb means that the moisture adheres to the
desiccant, collecting in the thousands of small pores within each desiccant
bead. The composition of the desiccant is not changed and the moisture can
be driven off in a regeneration process by applying dry purge air, by the
application of heat, or a combination of both. Regenerative desiccant-type
dryers typically are of twin tower construction. One tower dries the air from
the compressor while the desiccant in the other tower is being regenerated,
after the pressure in the tower being regenerated has been reduced to
atmospheric pressure. The purge air requirement can range from 10 to 18% of
the total air flow, depending on the type of dryer. The typical regenerative
desiccant dryer at 100 psig has a pressure dew point rating of -20F to -40F
Air Receiver
Receivers are used to provide compressed air storage
capacity to meet peak demand events and help control
system pressure.
Receivers are especially effective for systems with widely
varying compressed air flow requirements.
Where peaks are intermittent, a large air receiver may allow
a smaller air compressor to be used and can allow the
capacity control system to operate more effectively and
improve system efficiency.
An air receiver after a reciprocating air compressor can
provide dampening of pressure pulsations, radiant cooling,
and collection of condensate.
Demand-side control will optimize the benefit of the air
receiver storage volume by stabilizing system header
pressure and "flattening" the load peaks.
Heat Recovery with Water-Cooled
Compressors
Heat recovery for space heating is not as
common with water-cooled compressors
because an extra stage of heat exchange is
required and the temperature of the available
heat is lower. Since many water-cooled
compressors are quite large, however, heat
recovery for space heating can be an
attractive opportunity. Recovery efficiencies
of 50-60% are typical.
Traps and Drains
Automatic condensate drains or traps are used to prevent the
loss of air through open petcocks and valves.
Drain valves should allow removal of condensate but not
compressed air.
Two types of traps are common: mechanical and electrical.
Mechanical traps link float devices to open valves when
condensate rises to a preset level.
Electric solenoid drain valves operate on a preset time cycle, but
may open even when condensate is not present.
Other electrical devices sense liquid level and open to drain only
when condensate is present. Improperly operating or
maintained traps can create excessive air usage and waste
energy
Air Distribution Systems
The air distribution system links the various components of the
compressed air system to deliver air to the points of use with minimal
pressure loss.
The specific configuration of a distribution system depends on the
needs of the individual plant, but frequently consists of an extended
network of main lines, branch lines, valves, and air hoses.
The length of the network should be kept to a minimum to reduce
pressure drop.
Air distribution piping should be large enough in diameter to minimize
pressure drop.
A loop system is generally recommended, with all piping sloped to
accessible drop legs and drain points.
N = No. of stages
K = Ratio of specific heats (1.35 for air)
Ps = suction pressure in kg/cm2
Pd = Discharge pressure in kg/cm2
Q = Actual air flow (m3/min.)
Actual kW = √ 3 V I × PF as measured
Every 40C rise in inlet air temperature results in a higher energy consumption by 1 % to
achieve equivalent output. Hence, cool air intake leads to a more efficient compression.
p
Air Inlet Filter on Power
Consumption
Pressure Drop Increase in Power
Across air filter Consumption (%)
(mmWC)
0 0
200 1.6
400 3.2
600 4.7
800 7.0
For every 25 mbar pressure lost at the inlet due to choked filters, the
compressor performance is reduced by about 2 percent.
Elevation
Percentage Relative
Barometric Volumetric Efficiency
Altitude
Pressure Compared with Sea Level
Meters
Mbar
At 4 bar At 7 bar
Sea level 1013 100.0 100.0
500 945 98.7 97.7
1000 894 97.0 95.2
1500 840 95.5 92.7
2000 789 93.9 90.0
2500 737 92.1 87.0
It can be seen from the table that an increase of 5.50C in the inlet to the second stage
results in a 2 % increase in the specific energy consumption. Use of cold water
reduces power consumption.
Cooling Water
Requirement
Minimum quantity of
Cooling Water required
Compressor Type
for 2.85 m 3/min. FAD at 7
bar (lpm)
Single-stage 3.8
Two-stage 7.6
Single-stage with after-cooler 15.1
Two-stage with after-cooler 18.9
Power Reduction through
Pressure Reduction
Pressure
Power Reduction (%)
Reduction
Single-
Two-stage Two-
From stage
To (bar) Water- stage Air-
(bar) Water-
cooled cooled
cooled
6.8 6.1 4 4 2.6
6.8 5.5 9 11 6.5
Gauge
Pressure 0.5 mm 1 mm 2 mm 3 mm 5 mm 10 mm 12.5 mm
Bar
0.5 0.06 0.22 0.92 2.1 5.7 22.8 35.5
1.0 0.08 0.33 1.33 3.0 8.4 33.6 52.5
2.5 0.14 0.58 2.33 5.5 14.6 58.6 91.4
5.0 0.25 0.97 3.92 8.8 24.4 97.5 152.0
7.0 0.33 1.31 5.19 11.6 32.5 129.0 202.0
Cost of Air Leakage
Hot air can be used for space heating, industrial drying, preheating
aspirated air for oil burners, or any other application requiring warm
air. As a rule of thumb, approximately 50,000 Btu/hour of energy is
available for each 100 cfm of capacity (at full-load). Air temperatures
of 30 to 40oF above the cooling air inlet temperature can be
obtained. Recovery efficiencies of 80-90% are common
Steps in simple shop-floor
method for leak
quantification
Shut off compressed air operated equipments (or conduct test
when no equipment is using compressed air).
Run the compressor to charge the system to set pressure of
operation
Note the sub-sequent time taken for ‘on load’ and ‘off load’
cycles of the compressors. For accuracy, take ON & OFF times
for 8 – 10 cycles continuously. Then calculate total ‘ON’ Time
(T) and Total ‘OFF’ time (t).
The system leakage is calculated as
System leakage (cmm) = Q × T / (T + t)
Q = Actual free air being supplied during trial, in cubic
meters per minute
T = Time on load in minutes
t = Time unload in minutes
Leak test: example
Compressor capacity (CMM) = 35
Cut in pressure kg/SQCMG = 6.8
Cut out pressure kg/SQCMG = 7.5
On load kW drawn = 188 kW
Unload kW drawn = 54 kW
Average ‘On-load’ time = 1.5 minutes
Average ‘Unload’ time = 10.5 minutes
Comment on leakage quantity and avoidable loss of power due to
air leakages. (1.5) × 35
a) Leakage quantity (CMM)(1.5) =
+ (10.5)
= 4.375 CMM
b) Leakage per day = 6300 CM/day 188 kWh
c) Specific power for compressed air generation= (35 × 60 )CMH
= 0.0895 kwh/m3
d) Power lost due to leakages/day = 563.85 kWh
Capacity Assessment in
Shop-floor
Isolate the compressor along with its individual receiver being taken for test
from main compressed air system by tightly closing the isolation valve or
blanking it, thus closing the receiver outlet.
Open water drain valve and drain out water fully and empty the receiver and the
pipe line. Make sure that water trap line is tightly closed once again to start
the test.
Start the compressor and activate the stop watch.
Note the time taken to attain the normal operational pressure P2 (in the
receiver) from initial pressure P1.
Calculate the capacity as per the formulae given below :
P2 − P1 V
Actual Free air discharge
Q= × NM 3 / Min.
P0 T
Where
P2 = Final pressure after filling (kg/cm2 a)
P1 = Initial pressure (kg/cm2a) after bleeding
P0 = Atmospheric Pressure (kg/cm2 a)
V = Storage volume in m3 which includes receiver,
after cooler, and delivery piping
T = Time take to build up pressure to P2 in minutes
Example
Piston displacement : 16.88 CMM
Theoretical compressor capacity : 14.75 CMM @ 7 kg/SQCMG
Compressor rated rpm 750 : Motor rated rpm :
1445
Receiver Volume : 7.79 CM
Additional hold up volume,
i.e., pipe / water cooler, etc., is : 0.4974 CM
Total volume : 8.322 CM
Initial pressure P1 : 0.5 Kgf / SQCMG
Final pressure P2 : 7.03 Kgf / SQCMG
Atmospheric pressure P0 : 1.026
Kgf/cm2A
( P2 − P1 ) ×
Total Volume
Atm. Pressure × Pumpup time
Compressor output CMM :
(7.03 − 0.5) × 8.322
1.026 × 4.021
= 13.17 CMM
How Air Amplifiers Work
Compressed air flows through the inlet (1) into an annular chamber
(2). It is then throttled through a small ring nozzle (3) at high
velocity. This primary air stream adheres to the coanda profile (4),
which directs it toward the outlet. A low pressure area is created
at the center (5) inducing a high volume flow of surrounding air
into the primary air stream. The combined flow of primary and
surrounding air exhausts from the Air Amplifier in a high volume,
high velocity flow.
HVAC and Refrigeration
System
Ton of refrigeration
1996
R-11, R-12, R-500, HCFC-152A, Production of these refrigerants is stopped. Equipment
CFC-114 using these refrigerants is no longer manufactured.
2010
HCFC-22 Manufacture of equipment using this refrigerant is stopped.
2020
HCFC-22 Production of this refrigerant is stopped.
2020
HCFC-123 Manufacture of equipment using this refrigerant is stopped.
2030
HCFC-123 Production of this refrigerant is stopped.
Introduction
1. Boiling point of the water is a function of pressure. At atmospheric pressure water boils at 100 deg. C.
When maintained at high vacuum, water will boil and subcool itself. The boiling point of the water at
6 mmHg (abs) is 3.7 deg. C.
How do the chillers work ?
2. Lithium Bromide (LiBr) has the property to absorb water due to its chemical affinity. At higher
concentration and lower temperature LiBr absorbs water vapour (refrigerant vapour) very effectively.
How do the chillers work ?
3. As Lithium Bromide becomes dilute it loses its capacity to absorb water vapour. It thus needs to be
reconcentrated using a heat source. Heat source may be Steam or Flue gases or even Hot water.
Vapour absorption chillers: Types
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW
Cold Insulation
Building Envelop
Building Heat Loads
Process Heat Loads Minimisation
Flow optimization and Heat transfer area increase
to accept higher temperature coolant
Avoiding wastages like heat gains, loss of chilled
water, idle flows
Frequent cleaning / de-scaling of all heat
exchangers
At the Refrigeration A/C
Plant Area
Ensure regular maintenance of all A/C plant
components as per manufacturer guidelines.
Ensure adequacy of chilled water and cooling water
flows, avoidance of bypass flows by valving off the
idle equipment.
Minimize part load operations by matching loads and
plant capacity on line, adopting variable speed drives
for varying process load.
Ensure efforts to continuously optimize condenser
and evaporator parameters for minimizing specific
energy consumption and maximizing capacity.
Adopt VAR system where economics permit as a non
CFC solution
Select the right Cooling Medium
Order of preference
Cooling water ChilledWater Brine
Energy Savings in Refrigeration
systems
Hot well
Refrigeration
Refrigeration 12OC
plant
plant Process
Cold well
8OC
m Cp ∆Τ
Refrigeration TR - 100,000 kg/hr x 1 x 4
3000
- 133.33 TR
Provide controls
install thermostat to control peak and base load
As per ASME the specific pressure, i.e, the ratio of the discharge
pressure over the suction pressure is used for defining the fans,
blowers and compressors as highlighted below :
Peak Efficiency
Centrifugal Fans
Range
Airfoil, backwardly curved/inclined 79-83
Modified radial 72-79
Redial 69-75
Pressure blower 58-68
Forwardly curved 60-65
Axial fan
vanaxial 78-85
Tubeaxial 67-72
Propeller 45-50
Axial-flow Fans Centrifugal Fans
Typical Typical
Type Characteristics Type Characteristics
Applications Applications
Prope Low pressure, high Air- Radial High pressure, Various industrial
ller flow, low efficiency, circulation, medium flow, applications, suitable
peak efficiency close ventilation, efficiency close to for dust laden, moist
to point of free air exhaust tube-axial fans, power air/gases
delivery increases continuously
Vane- High pressure, High pressure Backward High pressure, high HVAC, various
axial medium flow, dip in applications curved flow, high efficiency, industrial
pressure-flow curve, including blades power reduces as flow applications, forced
use of guide vanes HVAC increases beyond draft fans, etc.
improves efficiency systems, point of highest
exhausts efficiency
Q1 N 1 SP1 ⎛ N 1 ⎞
2
kW 1 ⎛ N 1 ⎞
3
= =⎜ =⎜
Q2 N 2 ⎟ ⎟
SP 2 ⎝ N 2 ⎠ kW 2 ⎝ N 2 ⎠
Varying the RPM by 10% Varying the RPM by 10% Varying the RPM by 10%
decreases or increases air decreases or increases the decreases or increases the
delivery by 10%. static pressure by 19%. power requirement by
27%.
Where Q – flow, SP – Static Pressure, kW – Power and N – speed (RPM)
Fan static pressure
Fan Static Pressure U SP = SP (Fan outlet) – SP (Fan outlet)
SP (Fan outlet) – Static pressure at fan outlet, inches WC
SP (Fan outlet) – Static pressure at fan inlet, inches WC
U SP = 0.05 – (-10)
= 10.05 in W.C.
Static Pressure Profile of the System
Static pressure drop and rise
across entire system
Fan behaviour
Speed vs Power
% Speed % Power
100 100
90 73
80 51
70 34
60 22
50 13
Flow control
100 Damper
VFC
Power 75
50
VFD
25
Ideal
25 50 75 100
Flow
Impact of speed reduction
Use of VSD: Boiler ID fan case study
Use of VSD: Boiler ID fan case study
(contd.)
Energy audit of fan
• Collect fan and motor specifications with ducting
network
• Measure motor power input
• Measure fan and motor speed
• Measure static pressure at various points in the
duct
• Measure total and static pressure and compute
flow
• Estimate the system efficiency and check fan
operating point
What to Look for in the Field
Overall system efficiency will be determined by the type of fan or blower, its
interaction with the air distribution system, and the method of control.
•Determine whether the right type of fan or blower is used for an application. Is
your fan or blower is providing the best efficiency and performance in a given
application.
•The efficiency of a system depends on the number and type of bends and
restrictions. Sharp bends, especially, increase the resistance the fan or blower
must overcome. Bends and restrictions near the inlet or outlet seriously degrade
capacity and efficiency.
10” 26 kW
8”
10” 14 kW
6”
COUPLING 2% LOSS
PUMPS
24% LOSS
VALVES
9% LOSS
PIPES
11% LOSS
70 m 82%
A
50 m
Full open valve
42 m
System Curves
Head
Meters
Static Operating Points
Head
300 m3/hr 500 m3/hr
3
Flow (m /hr)
Effect of Throttling
Pump Curve at
Const. Speed Pump Efficiency 77%
70 m Partially B 82%
closed valve
A
50 m
Full open valve
42 m
System Curves C
Head
Meters
Static Operating Points
Head
300 m3/hr 500 m3/hr
3
Flow (m /hr)
Centrifugal Pump Performance
Chart
Efficiency Curves
28.6 kW
14.8 kW
Power Requirement for Pump
You can use any of the following formulas to make your calculations:
Power calculations
Flow:
Q1 / Q2 = N1 / N2
Example: 100 / Q2 = 1750/3500
Q2 = 200 GPM
Head Vs speed
Head:
H1/H2 = (D1) x (D1) / (D2) x (D2)
Example: 100 /H2 = 8 x 8 / 6 x 6
H2 = 56.25 Ft
Power(kW):
kW1 / kW2 = (D1) x (D1) x (D1) / (D2) x (D2) x (D2)
Example: 5/kW2 = 8 x 8 x 8 / 6 x 6 x 6
kW2 = 2.1
Pumps in parallel
Cooling Tower Theory
Heat is transferred from water drops to the surrounding air by the
transfer of sensible and latent heat
Drift losses are estimated to be between 0.1 and 0.2% of water supply.
Syllabus
Lighting System: Light source, Choice
of lighting, Luminance requirements,
and Energy conservation avenues
Basic Terms in Lighting System and Features
Lamps:Lamp is equipment, which produces light.
• Incandescent lamps:
Incandescent lamps produce light by means of a filament heated to incandescence by
the flow of electric current through it. The principle parts of an incandescent lamp, also
known as GLS (General Lighting Service) lamp include the filament, the bulb, the fill
gas and the cap.
• Reflector lamps:
Reflector lamps are basically incandescent, provided with a high quality internal mirror,
which follows exactly the parabolic shape of the lamp. The reflector is resistant to
corrosion, thus making the lamp maintenance free and output efficient.
• Gas discharge lamps:
The light from a gas discharge lamp is produced by the excitation of gas contained in
either a tubular or elliptical outer bulb.
The most commonly used discharge lamps are as follows:
Fluorescent tube lamps (FTL)
Compact Fluorescent Lamps (CFL)
Mercury Vapour Lamps
Sodium Vapour Lamps
Metal Halide Lamps
Most commonly used lamps
Lux (lx): This is the illuminance produced by a luminous flux of one lux,
uniformly distributed over a surface area of one square metre. One lux is equal to one
lumen per square meter.
Lens or Diffuser
Switch
Walls
The Requirement Work Surface
Floor
Lighting Quality
• Illumination level.
• Uniformity
• Absence of glare.
• Colour rendering index (CRI).
Luminaire
• Ballast
– A current limiting device, to counter negative
resistance characteristics of any discharge
lamps. In case of fluorescent lamps, it aids the
initial voltage build-up, required for starting
• Ignitors
– These are used for starting high intensity Metal
Halide and Sodium vapour lamps
Illuminance
• Is the quotient of the illuminous flux incident on
an element of the surface at a point of surface
containing the point, by the area of that element.
• The illuminance provided by an installation affects
both the performance of the tasks and the
appearance of the space.
• Lux (lx)
– Is the illuminance produced by a luminous flux of one
lux, uniformly distributed over a surface area of one
square metre.
Luminous Efficacy (lm/W)
20–30–50–75–100–150–200–300–500–750–1000–1500–2000, … Lux
Lighting
Rating in
Device Use / Shifts as I
S. Plant Watts Population
& / II / III shifts /
No. Location Lamp & Numbers
Ballast Day
Ballast
Type
Energy savings in lighting
System
• Make maximum use of natural light (North roof/translucent
sheets/more windows and openings)
• Switch off when not required
• Modify lighting layout to meet the need
• Select light colours for interiors
• Provide timer switches / PV controls
• Provide lighting Transformer to operate at reduced voltage
• Install energy efficient lamps, luminaries and controls
• Clean North roof glass, translucent sheet and luminaries
regularly
Energy Saving in Lighting
• Separate lighting Transformer
– To isolate from power feeder
– To avoid voltage fluctuation problem
– Energy saving at optimum voltage
Diesel
DieselEngine
Engine A.C.
A.C.Generator
Generator Controls
Controls Load
Load
Fuel Control
Accessories
Accessories
Foundation
Example :
Connected Load = 650 kW
Diversity Factor = 1.86
(connected load / demand)
Max. Demand = 650/1.86 = 350 kW
% Loading = 70
Set rating = 350/0.7 = 500 kW
At 0.8 PF, rating = 625 kVA
High Speed Engine or
Slow/Medium Speed Engine
Factor Slow speed engine High speed
engine
Break mean effective pressure - Low High
therefore wear and tear and
consumption of spares
Weight to power ratio- therefore More Less
sturdiness and life
Space High Less
Water
Temperature Flow % Derating %
oC
25 100 0
30 125 3
35 166 5
40 166 8
Power Factor:
− Transient Loading:
On many occasions to contain transient voltage dip arising due to
transient load application, a specially designed generator may
have to be selected.
− Special Loads:
Special loads like rectifier / thyristor loads, welding loads, furnace
loads need an application check. The manufacturer of diesel
engine and AC generator should be consulted for proper
recommendation so that desired utilisation of DG set is achieved
without any problem.
Energy Balance
& Waste Heat Recovery in DG Sets
If the normal load is 60%, the flue gas parameters for waste
heat recovery unit would be 320oC inlet temperature, 180oC
outlet temperature and 27180 kgs/Hour gas flow.
At 90% loading, however, values would be 355oC and
32,400 kgs/Hour, respectively.
Energy Saving Measures for DG
Sets
a) Ensure steady load conditions on the DG set, and provide cold, dust free air
at intake
b) Improve air filtration.
c) Ensure fuel oil storage, handling and preparation as per manufacturers’
guidelines/oil company data.
d) Consider fuel oil additives
e) Calibrate fuel injection pumps frequently.
f) Ensure compliance with maintenance checklist.
g) Ensure steady load conditions, avoiding fluctuations, imbalance in phases,
harmonic loads.
h) For base load operation, consider waste heat recovery system steam
generation or vapour absorption system adoption.
i) consider partial use of biomass gas for generation. Ensure tar removal from
the gas for improving availability of the engine in the long run.
z j) Consider parallel operation among the DG sets for improved loading .
z Carryout regular field trials to monitor DG set performance, and maintenance
planning as per requirements.
Typical Format for DG Set Monitoring
• Occupancy Sensors
• Timed Based Control
• Daylight Linked Control
• Localized Switching