ModCon 75 Instruction Manual - en
ModCon 75 Instruction Manual - en
ModCon 75 Instruction Manual - en
Instruction Manual
"! WARNING
THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR USING OR SERVICING THE PRODUCT. Like any piece of complex equipment, this instrument will perform as designed only if it is used and serviced in accordance with the manufacturers instructions. OTHERWISE, IT COULD FAIL TO PERFORM AS DESIGNED AND PERSONS WHO RELY ON THIS PRODUCT FOR THEIR SAFETY COULD SUSTAIN SEVERE PERSONAL INJURY OR LOSS OF LIFE. The warranties made by Mine Safety Appliances Company with respect to the product are voided if the product is not used and serviced in accordance with the instructions in this manual. Please protect yourself and others by following them. We encourage our customers to write or call regarding this equipment prior to use or for any additional information relative to use or repairs.
In North America, to contact your nearest stocking location, dial toll-free 1-800-MSA-INST To contact MSA International, dial 1-412-967-3354 MINE SAFETY APPLIANCES COMPANY 2010 - All Rights Reserved This manual is available on the internet at www.msanet.com
Manufactured by
(L)-Y Rev 4
10076943
General Warnings
" WARNING 1. The Controller described in this manual must be installed, operated and maintained in strict accordance with its labels, cautions, warnings, instructions, and within the limitations stated. 2. The Controller must be located in non-hazardous areas. 3. Use only genuine MSA replacement parts when performing any maintenance procedures provided in this manual. Failure to do so may seriously impair instrument performance. Repair or alteration of the ModCon75 Controller beyond the scope of these maintenance instructions or by anyone other than authorized MSA service personnel, could cause the product to fail to perform as designed and persons who rely on this product for their safety could sustain serious personal injury or loss of life. 4. If a portion of the system fails, remaining system functions may not operate properly. In this case, do not use the system until proper repairs are made. Failure to follow the above can result in serious personal injury or loss of life.
ii
Table of Contents
Chapter 1, Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-1
Introducing the ModCon75 Controller . . . . . . . . . . . . . .1-1 Figure 1-1. The ModCon75 System . . . . . . . . . . . .1-1 Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2 ModCon75 Controller . . . . . . . . . . . . . . . . . . . . . . . . . .1-2 Operating Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2 I/Os . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3 Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3 RS232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3 Additional Communication Port . . . . . . . . . . . . . . . . . .1-3 Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3 PLC Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-4 HMI Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-4
RS232 Wiring Considerations . . . . . . . . . . . . . . . . . . .2-8 RS485 Wiring Considerations . . . . . . . . . . . . . . . . . . .2-8 Figure 2-8. R-J11 Pin-out . . . . . . . . . . . . . . . . . . . . .2-8 DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9 Figure 2-9. RS485 Terminal Wiring . . . . . . . . . . . . .2-9 Table 2-1. Specifications of RS232 to RS485 Isolated Universal Controller . . . . . . . . . . . .2-10 Figure 2-10. Dip Switch Settings . . . . . . . . . . . . . .2-10 Figure 2-11. Mechanical Dimensions . . . . . . . . . . .2-11
Increasing Contact Life Span . . . . . . . . . . . . . . . . . . . .4-6 Figure 4-3. Relay Outputs . . . . . . . . . . . . . . . . . . . .4-6 Transistor Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-7 Figure 4-4. Increasing Contact Life Span . . . . . . . .4-7 Figure 4-5. Transistor Outputs . . . . . . . . . . . . . . . . .4-8 Table 4-1. Snap-in I/O Module Technical Specifications . . . . . . . . . . . . . . . . .4-9
Figure 6-11. Sensor 1 Preset Screen . . . . . . . . . . .6-9 Figure 6-12. Sensor 2 Preset Screen . . . . . . . . . .6-10 Figure 6-13. Sensor 3 Preset Screen . . . . . . . . . .6-10 Figure 6-14. Displays all Presets before Downloading to the Unit . . . . . . . . . . . . . . . .6-11 Figure 6-15. Verification Screen . . . . . . . . . . . . . .6-12 " WARNING . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-12 F3-Main Data Screen . . . . . . . . . . . . . . . . . . . . . . . . .6-13 Figure 6-16. Main Data Screen . . . . . . . . . . . . . . .6-13 Figure 6-17. All Clear Status Screen . . . . . . . . . . .6-13 F4-Display Setpoints (view only) . . . . . . . . . . . . . . . .6-14 Figure 6-18. Display Only Setpoints . . . . . . . . . . .6-14 F5- Password Editor . . . . . . . . . . . . . . . . . . . . . . . . .6-15 Figure 6-19. Password Editor . . . . . . . . . . . . . . . .6-15 F6- Modbus Alarms . . . . . . . . . . . . . . . . . . . . . . . . . .6-16 Figure 6-20. Modbus Alarms . . . . . . . . . . . . . . . . .6-16 F7- Fault Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-17 Figure 6-21. Fault Status . . . . . . . . . . . . . . . . . . . .6-17 F8- Zone Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-18 Figure 6-22. Zone Editor - Set Relays as Latched or Unlatched . . . . . . . . . . . . . . .6-18 F9- Remote Remote Relay Editor (Optional: Requires Remote Relay Modules) . . . . . .6-19 Optional: Remote Relay units . . . . . . . . . . . . . . . . .6-19 Figure 6-23. Remote Relay Editor . . . . . . . . . . . . .6-19 " WARNING . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-19 F10-Network Settings . . . . . . . . . . . . . . . . . . . . . . . .6-20 Figure 6-24. F10 - Network Settings . . . . . . . . . . .6-20
Appendix A, Port 3 Ethernet Port / OPC Server . . . . . . . .A-1 Appendix B, Register Maps . . . . . . . . . . . . . . . . . . . . . . . . .B-1
" WARNING . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-1 Function Description MI273 through MI297 Signed Integer . . . . . . . . . . . . . . . . . . . . . .B-8 Function Description MI450 through MI474 Signed Integer . . . . . . . . . . . . . . . . . . . . . .B-9 Function Description MI525 through MI599 Signed Integer . . . . . . . . . . . . . . . . . . . . . .B-9
vii
Chapter 1, Overview
Introducing the ModCon75 Controller
The ModCon75 Controller: is a programmable logic controller with an integral operating panel offers Modbus communications and a real-time clock operating panels contain a graphic LCD screen and a keypad: The LCD screen displays: operator instructions alarms real-time variable system information.
1-1
Two types of I/O modules are compatible with ModCon75 Controllers: Snap-in I/O Modules plug directly into the back of a ModCon75 Controller for a self-contained PLC unit with a local I/O configuration (integral to ModCon 75 Controller).
Remote Relay Modules can also be easily integrated to greatly extend the systems external notification capacity. These features combine to offer a cost-effective solution for midsize industrial applications requiring: operator interface the ability to control small to medium processes according to time and ambient conditions.
Technical Description
ModCon75 Controller
Dimensions: 260 x 155 x 72 mm (10.24 x 6.1 x 2.8") Mounting: Panel-mounted via brackets Power Supply: 12 or 24 VDC controller unit 24 VDC for RS232 to RS485 converter Real-time Clock (RTC): Enables time and date controlled functions Battery Back-up: Protects real-time clock (RTC) and all data, including variable data.
Operating Panel Contains a graphic screen and keypad: LCD Screen Displays: Alphanumeric Keypad contains: six softkeys nine function keys.
1-2
NOTE: To label keys, insert keypad slides according to Chapter 7, "Operating Panel Options". I/Os 16 digital pnp or npn inputs available. 10 relay outputs available. NOTE: All I/O technical specifications are provided in Chapter 4. Not all inputs are used in the standard ModCon75 Controller.
Communications
RS232 The controller has two COM ports which may be used to: download programs from a PC establish communications with devices using RS232 protocol.
Additional Communication Port The additional communication channel has been set up with an Ethernet port. NOTE: Information regarding other communication options can be obtained from MSA Customer Service.
Programming
This programming function should only be used by an authorized MSA Service Representative. ModCon75 Controller programs have PLC and HMI applications. Both applications are programmed via a PC using proprietary software.
1-3
PLC Application enables the user to perform automation tasks has an application memory of up to 1000K.
HMI Application The HMI application customizes the operator interface to: assign functions to the keypad keys enable the operator to enter data via the controller keypad create and display text, graphic images, and variable system data on the ModCon75 screen in response to run-time conditions.
An HMI application can typically include up to 255 Displays, each with the ability to display text, graphic images, and variables. Variables allow the user to display system data on the ModCon75 LCD screen: bit, integer, and timer values times and dates I/O status and values text from the variable text display list.
Variables can also use a graphic image or a bar graph to represent a value or range of values. Typically, 12 fonts in a variety of languages may be installed and used in text messages. When the VisiLogic program is complete, the programmer downloads it into the controller.
1-4
Chapter 2, Mounting
Before Installation
Check the contents of the Controller Kit. Standard kits contain (FIGURE 2-1): the controller (includes panel and Snap-in I/O module) the RS232 to RS485 converter a three-pin power supply connector four mounting brackets, each with an inserted screw. an envelope containing a wire with a ring cable shoe other hardware that may be used to earth the controllers power supply a rubber seal already seated in back of the operating panel a communication cable two sets of keypad slides to be used for labeling the keypad keys One set of slides is already installed in the operating panel. this manual.
Do not install in areas with: excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration.
Do not place in water or allow water to leak onto the controller. Do not allow debris to fall inside the unit during installation. Do not touch live wires. Double-check all the wiring before turning ON the power supply. Stay as far as possible from high-voltage cables and power equipment. Allow a minimum of 10 mm of space for ventilation between the top and bottom edges of the controller and the enclosure walls.
Mounting
NOTE: The mounting panel cannot be more than 5 mm thick. To maximize system performance, avoid electromagnetic interference by: mounting the controller on a metal panel earthing the power supply according to FIGURE 2-3.
2. If you are mounting the controller on a metal panel, earth the power supply: a Bore a hole (FIGURE 2-2) that suits the NC6-32 screw supplied with the controller kit. b. Scrape the panel paint away from the contact area to ensure a conductive connection. c. Drive the screw into the hole.
Figure 2-2. ModCon75 Controller Panel Cut-outFront View d. On the screws shank, place the following hardware in this order: washer, ring cable shoe, second washer, spring, and nut; as shown in FIGURE 2-3.
2-3
3. Slide the controller into the cut-out, ensuring that the rubber seal is in place. 4. Push the four mounting brackets into their slots on the sides of the controller as shown in FIGURE 2-1. 5. Tighten the bracket screws against the panel. When properly mounted, the controller is squarely situated in the panel cut-out as shown in FIGURE 2-4.
2-4
Features
Universal converter: must be used with the ModCon75 Controller automatically senses the direction of the data flow, and switches the transmission direction comes in a standard-sized housing, snap-mounts onto a 35 mm DIN rail screw terminal block connections are provided RJ11 connector provides easy plug-in connection for the ModCon75 Controller supports networks containing up to 25 nodes enables full or half-duplex communications uses a stand-alone power supply has LED indicators.
Wiring Connections
Read the following wiring considerations before making connections. Top Connectors Power Supply Terminals Rear connector 24 V Supply voltage 0V Reference supply voltage Earth to ground
RS232 Terminals Front connector TXD RS232 transmit signal RXD RS232 receive signal 0V RS232 0V reference
2-6
Bottom Connectors RS485 Terminals Rear connector TX- RS485 negative transmit signal RX- RS485 negative receive signal T- Negative termination Front connector TX+ RS485 positive transmit signal RX+ RS485 positive receive signal T+ Positive termination
2-7
RS232 Wiring Considerations Since the RJ11 connector and the screw block terminal use the same signal source, only one can be used for establishing RS232 communications. Connect the screw block terminal as follows: M90-19-R4 Device RxD <--------- TxD TxD 0V ---------> RxD ---------- 0V
RS485 Wiring Considerations Use shielded, twisted pair cables. Configure the network as a multidrop bus network. Minimize the stub (drop) length leading from each device to the bus. Ideally, the main cable should be run in and out of the networked device. Positive terminals must be wired to positive Negative terminals must be wired to negative.
2-8
Network termination points must be created by using the two end point devices integrated into your network. Connect the T- terminal to Rx-, and T+ to RX+ in each end point device as shown in FIGURE 2-9.
To support RS485, connect the Tx+ terminal to the Rx+, and the Rx- terminal to the Tx-, as shown in FIGURE 2-9.
Data can be transmitted in either 10- or 11-bit format. Each format includes a start and stop bit. a lowered switch is 'ON' a raised switch is 'OFF'. The DIP switches are shown in FIGURE 2-10.
2-9
Specifications
Table 2-1. Specifications of RS232 to RS485 Isolated Universal Controller
POWER SUPPLY Input Voltage Permissible Range Maximum Input Current RS232 Input voltage Cable Length Interface Connectors RS422/RS485 Input Voltage Cable Type Cable Length Interface Connector GENERAL Isolation Size 24 VDC 20.4 to 28.8 VDC 35 mA @ 24 VDC 20 VDC maximum 15 m maximum (50 feet) RJ11 or screw-type, 2.5 mm, 2 terminal -7 to +12V differential maximum Shielded twisted pair, in compliance with EIA RS485 1200m maximum (4000 feet) Screw-type, 2.5 mm, 2 terminal yes 110.8 (L) x 22.5 (W) x 75 (H) mm [4.38 (L) x 0.89 (W) x 2.96 (H)"]
2-10
Weight Communication Status Indicators Baud Rate Mounting Flame-Resistant ENVIRONMENTAL Storage Temperature Operating Temperature Storage Humidity Operating Humidity
98 g (3.44 oz) Yes 19200 bps Snap-mounts onto 35mm DIN rail (EN50022-35) UL94-VO -20 to 70C 0 to 50C 10 to 95% relative humidity 5 to 95% relative humidity
2-11
Safety Considerations
" WARNING
Do not touch live wires. Standard safety considerations require that metal cabinet panels be earthed to avoid electrocution. Do not connect either the 'Neutral' or 'Line' signal of the 110/220 VAC to the devices 0V pin. In the event of voltage fluctuations or non-conformity to voltage power supply specifications, connect the device to a regulated power supply. A technician or engineer trained in the local and national electrical standards must perform all tasks associated with the electrical wiring of the device. Double-check all wiring before turning ON the power supply. FAILURE TO FOLLOW THE ABOVE CAN RESULT IN SERIOUS PERSONAL INJURY OR LOSS OF LIFE.
1. Strip the wire to a length of 7 0.5 mm (0.2500.300 inches). 2. Unscrew the terminal to its widest position before inserting a wire. 3. Insert the wire completely into the terminal to ensure a proper connection according to FIGURE 3-1. 4. Tighten enough to keep the wire from pulling free.
NOTE: The wire used to earth the power supply must not exceed 8 cm in length. If your conditions do not permit this, do not earth the power supply.
3-2
Snap-in I/O Modules Snap-in I/O Modules provide a ModCon75 Controller with an onboard I/O configuration. The Snap-in I/O Module plugs directly into the back of the ModCon75 Controller, creating a self-contained control unit with a local I/O configuration.
Features 16 isolated digital inputs, including two high-speed counter inputs, type pnp/npn (source/sink) 10 isolated relay outputs Four isolated pnp/npn (source/sink) transistor outputs Three analog inputs (not used in this application). " WARNING
To avoid electric shock, turn OFF power to the unit before installing I/O modules.
1. Pry off the cap with a screwdriver. 2. Line up the ModCon75 Controller circular guidelines with the Snap-in I/O Module guidelines (FIGURE 4-1). 4-1
3. Apply even pressure on all four corners until you hear a distinct 'click'. 4. Check that all sides and corners are correctly aligned. The module is now installed.
4-2
" WARNING
Failure to comply with appropriate safety guidelines can result in severe personal injury or property damage. Always exercise proper caution when working with electrical equipment.
Check the user program before running it. Do not attempt to use this device with parameters that exceed permissible levels. Install an external circuit breaker and take appropriate safety measures against short-circuiting in external wiring. To avoid damaging the system, do not connect or disconnect the device when the power is ON. Ensure that terminal blocks are properly secured in place.
Environmental Considerations
Do not install the unit in areas with: excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks excessive vibration.
Provide proper ventilation by leaving at least 10 mm of space between the top and bottom edges of the device and the enclosure walls. Do not place in water or let water leak onto the unit. Do not allow debris to fall inside the unit during installation.
Wiring
Do not touch live wires. Unused pins should not be connected. Ignoring this directive may damage the device. Do not connect the Neutral or Line signal of the 110/220 VAC to the devices 0 volt pin. Double-check all wiring before turning ON the power supply. 4-3
Wiring Procedures Use crimp terminals for wiring. Use 26-12 AWG wire (0.13 mm23.31 mm2) for all wiring. 1. Strip the wire to a length of 7 0.5mm (0.2500.300 inches). 2. Unscrew the terminal to its widest position before inserting a wire. 3. Insert the wire completely into the terminal to ensure that a proper connection can be made. 4. Tighten enough to keep the wire from pulling free. " CAUTION
To avoid damaging the wire, do not exceed a maximum torque of 0.5 Nm (5 kgfm). Do not use tin, solder, or any other substance on stripped wire that might cause the wire strand to break. Install at maximum distance from high-voltage cables and power equipment.
I/O WiringGeneral Input or output cables should not: be run through the same multi-core cable share the same wire.
Allow for voltage drop and noise interference with input lines used over an extended distance.
Use wire that is properly sized for the load. Digital Inputs Each group of eight inputs: has a common signal can be used as pnp (source) or npn (sink) when appropriately wired as shown in FIGURE 4-2. Inputs I0 through I8 can be used to reset a latched zone relay. Input I11 can be used to reset a latched relay on a remote sensor. Input I12 can be used as a remote reset for the horn relay.
4-4
I0 I1 I2 I3 I4 I5
Unlatch Zone 1 Unlatch Zone 27 Unlatch Zone 3 Unlatch Zone 4 Unlatch Zone 5 Unlatch Zone 6
I6 I7 I8 I11 I12
Unlatch Zone Unlatch Zone 8 Unlatch Zone 9 Remote Sensor Acknowledge External Horn Silence
Digital Outputs
Wiring Power Supplies 1. Connect the "positive" lead to the: "V1" terminal for the relay outputs "V2" terminal for the transistor outputs. 2. In both cases, connect the "negative" lead to the "0V" terminal for each output group. In the event of voltage fluctuations or non-conformity to voltage power supply specifications, connect the device to a regulated power supply. Do not connect the 'Neutral' or 'Line' signal of the 110/220 VAC to the devices 0V pin.
Relay Outputs The relay output 0-volt signal is isolated from the controller 0-volt signal. 4-5
O0 O1 O2 O3 O4
O5 O6 O7 O8 O9
Zone 6 Alarm Zone 7 Alarm Zone 8 Alarm Zone 9 Alarm Horn Relay
Figure 4-3. Relay Outputs Increasing Contact Life Span To increase the life span of the relay output contacts and protect the device from potential damage by reverse EMF, connect: a clamping diode in parallel with each inductive DC load an RC snubber circuit in parallel with each inductive AC load.
4-6
Transistor Outputs Each output can be wired separately as either npn or pnp. The 0-volt signal of the transistor outputs is isolated from the controllers 0-volt signal. The ModCon75 Controller application uses transistor output O11 for FAULT indication. NOTE: The FAULT indication is normally energized and is deactivated when a fault occurs. The ModCon75 Controller application uses O12 for an internal timer which toggles at a rate of 0.5 seconds ON and 0.5 seconds OFF (1 Hz.). This can be used for external monitoring of the controller operational status.
4-7
4-8
4-9
Maximum Current Consumption 90 mA @ 24 VDC NOTE 1. Outputs #1, #2, #3, and #4 share a common signal. All other outputs have individual contacts. TRANSISTOR Number of Outputs 4; each can be individually wired OUTPUTS as pnp (source) or npn (sink) Output Type pnp P-MOSFET (open drain) npn open collector Galvanic Isolation Output Current Yes pnp npn 0.5 Amp max (per output) Total current: 2 A max (per group)
Maximum Frequency ON Voltage Drop Short Circuit Protection Power Supply Operating Voltage Power Supply Nominal Operating Voltage npn (sink) Power Supply Operating Voltage Operating Temperature Storage Temperature Relative Humidity (RH) Dimensions Weight
50 mA max (per output) Total current: 150 mA (per group) Resistive Load 20 Hz Inductive Load 0.5 Hz pnp 0.5 VDC max npn 0.85 VDC max Yes (pnp only) 20.4 to 28.8 VDC 24 VDC 3.5 V to 28.8 VDC (unrelated to Remote Relay Module voltage or Controller voltage) 0 to 50C (32 to 122F) -20 to 60C (-4to 140F) 5% to 95% (non-condensing) 138 W x 23 H x 123 mm D (5.43 W x 0.9 H x 4.84" D) 222 g (7.8 oz)
ENVIRON MENTAL
4-10
Chapter 5, Communications
This chapter contains guidelines for communications connections. All ModCon75 Controllers contain two RS232 ports and an RS485.
RS232
The RS232 serial ports are used for: Downloading programs from a PC by authorized MSA Service Representative Communicating to the RS232 to RS485 converter, which communicates to the Ultima X3 units.
The RS232 interface is via RJ-11 type serial ports located on the side of the controller. NOTE: Turn OFF power before making communications connections. NOTE: Do not connect the controller directly to a telephone or telephone line.
*Standard programming cables do not provide connection points for pins 1 and 6.
5-1
Signals are related to the controllers 0V; this is the same 0V used by the power supply. The RJ-11 type serial port located on the side of the controller must always be used with an appropriate adapter. The RS232 serial port is not isolated.
5-2
6-1
6-2
Figure 6-3. Password Entry (FIGURE 6-4) Use this screen to: initialize a new Ultima X3 sensor or read all units on the network.
F14- Select F14 once the following three steps are completed: 1) all Ultima X3 sensors (up to 25 X3 transmitters with up to three sensors each) are wired to the network and have unique IDs. 2) network IDs are set by the Ultima Controller (P/N 809086) (Valid IDs are 2 - 26). NOTE: ID 0 is the broadcast modbus message; ID 1 is the ModCon75 address. 3) Baud rate = 19200 and Parity = even. This process may take several minutes.
6-3
Populate registry Stop pinging View registry list Keep old setpoints
NOTE: If changes are made to individual X3 units through the use of the Ultima Controller, user must run F14 to repopulate the registry. Populating the registry will change the setpoints in the ModCon75 Controller to match the setpoints and configuration of all sensors on the network.
6-4
NOTE: Verify that the ModCon75 Controller found all Ultima X3 units on the network. If the total number is less than the actual number on the network, check your wiring and make sure that each X3 on the network has its own unique address in the range of 2 through 26.
6-5
Figure 6-6. Allows Users to Set Enabled or Disabled Alarms Cursor flashes at the network ID#:
Enter the Unit ID for the Setpoints and alarm functions to be modified and press enter 8 . The current settings for the selected unit or ID appear. To modify a setting, press the appropriate function key: When all desired changes are made, press F6 to advance to the next settings screen. Repeat this procedure for other sensor option screens (FIGURES 6-7 and 6-8). " WARNING
If the user changes a sensor, the ModCon75 Controller will retain the setpoints of the previous sensor. To upload new setpoints, the user must populate the sensors through the F1 menu option. Improper setpoints can result in exposure to hazardous atmospheres. (see "F1-Add Units to the Network" earlier in this chapter).
6-6
Figure 6-8. Allows users to Set Latching / Non-latching Alarms NOTE: User must wait for the controller to move to the next screen; this will take six seconds. This Latching Function only changes the relay operation of the Ultima X3 unit. For latching an alarm on the ModCon75 Controller, use a Zone relay and program it for latching. A latched relay at the Ultima X3 unit may be cleared at the ModCon75 Controller by pressing the down arrow () key. 6-7
Figure 6-9. Allows Users to Assign Zone Control Relays to Caution, Warning and Alarm Setpoints for Sensors 1, 2, and 3 Press F6 to skip to the next screen or ENTER to change Zone Relays. Numbers correspond to relays on back of unit.
1 2 3 4 5
The Horn relay- Output (O9): is used for remote alarms sounds a horn on any caution, warning, or alarm condition.
Silence of Horn is accomplished by connecting a push-button to (I12) terminals and/or by pressing the +/- button located on the front panel.
6-8
Figure 6-10. Current Set-point values Read from the Selected Ultima X3 Unit Pressing ESC- returns the user to the main menu screen and does not change saved setpoints Pressing ENTER- advances to the screen for changing the Set-point values. The screen will display Current Values for Unit # for Sensor 1 presets
Figure 6-11. Sensor 1 Preset Screen ENTER enables user to change presets. NOTE: Do not use decimal points; the Decimal is fixed; therefore, to enter 19.5: Press ENTER Type 19 and ENTER Type 5 and ENTER. 6-9
Figure 6-12. Sensor 2 Preset Screen F6- Skips to next screen ENTER- Changes presets (see NOTE above)
NOTE: The ModCon75 Controller displays to one decimal point. With certain sensors (ClO2, CO2, etc.), alarm setpoints in the Ultima X3 unit may be represented to two decimal points. In this 6-10
instance, the ModCon75 Controller will round to the nearest single decimal.
F7: Sends all changes to the ModCon75 Controller Sets Controller relays (connections located on back of unit) to activate according to caution, warning or alarm settings set on the Choose Zone event screen Verifies that all values were sent successfully.
NOTE: If user does not press F7, the changes will not be made. Combustible sensors cannot be set to a range of 61-100.
6-11
NOTE: If changes are made to individual X3 units through the use of the Ultima Controller, user must run F14 to populate the registry. Populating the registry will change the setpoints in the ModCon75 Controller to match the setpoints and configuration of all sensors on the network. " WARNING
Failure to follow the above instructions can result in the ModCon75 Controller not properly indicating a sensor alarm/fault condition.
6-12
Figure 6-16. Main Data Screen F1- Scrolls through all units on the Modbus network. F2- Allows one to view a specific unit. F3- Adjusts the scroll time reading each node.
Typical Display shows three sensors on the ModCon 75 Controller. "All Clear" - shows all three sensors are not in alarm. Box in lower-right corner shows ModBus network/sensor status. Current values are shown next to sensor number.
Figure 6-17. All Clear Status Screen ESC-Back to Main screen 6-13
Figure 6-18. Display Only Setpoints Accesses screen showing presets for Sensor 1.
6-14
6-15
6-16
Figure 6-21. Fault Status The ModCon 75 will display the following Ultima X3 sensor faults: + LOC Over-range Quick under-range Under-range Sensor missing Sensor End of Life Calibration fault Power Fail fault Configuration reset All other faults are shown as General Fault
6-17
Figure 6-22. Zone Editor - Set Relays as Latched or Unlatched F6- Skips to next screen When zone relays are set as unlatched, then Zone relays can be set to On-Delay or Off-Delay. On-Delay:relay activates only if alarm exists for the set time. Off-Delay (Typically used for fan control): relay stays energized for the set delay time after the alarm condition clears.
NOTE: Selecting latching disables ON delay, OFF delay, and delay time settings. Times are adjustable from 0 seconds to 15 minutes. After entering time delay, press enter 8 . or data to display. f 6-18
" WARNING
Do not use On-Delay for any safety critical function. Use only for Process control. Failure to follow the above can result in personal injury or loss of life.
Enter 30 if only one remote relay is on the network, 31, for two remote relays, 32 for three remote relays and 33 for four remote relays. To activate or Deactivate remote relays, enter F2 to Enable or Disable. Optional: Remote Relay units A total of four remote relay units may be added to the modbus network (see Appendix C for additional details). Modbus ID numbers of the remote relay modules must be programmed for ID#30, 31, 32 or 33. Input Remote Relay on all remote units is the local silence alarm. Closing this input will silence the local alarm as well as the ModCon75 Alarm. Output O0 is for the local alarm output. Note: If Zone Alarms are programmed as Latch, one can silence the alarm at the remote relay, but the Zone alarm will not be cleared until the unlatch input is initiated at the ModCon75 Controller. Following would be used for remote alarms: 6-19
ID#30
Output O0- Local horn output Output O1- Zone 1 Alarm Output O2-Zone 2 Alarm Input I0- Local area silence
ID#31
Output O0- Local horn output Output O1- Zone 3 Alarm Output O2- Zone 4 Alarm Input I0- Local area silence Output O0- Local horn output Output O1- Zone 5 Alarm Output O2- Zone 6 Alarm Input I0- Local area silence Output O0- Local horn output Output O1- Zone 7 Alarm Output O2- Zone 8 Alarm Input I0- Local area silence
ID#32
ID#33
Example: Program ID# 5 sensor 1 caution alarm to zone 1. Therefore, if Sensor 1 caution alarm occurs, this will trip the ModCon75 Zone 1 output (O0) as well as the remote relay module ID#30, output O1.
Labeling Keys
Most controller keys can be labeled: 1. Before mounting the controller, insert keypad slides into the slots under the cover of the operating panel. Keypad slides are strips of plastic cut to fit under specific groups of keys. Text should be visible through the operating panel covering. A special slide is provided to allow the user to display a picture (e.g., company logo or a system symbol). Slides cannot be inserted under the following keys: directional arrow keys ESC key <i > key.
7-1
The controller is shipped with two sets of slides appropriate for the users controller model: One set of slides is already inserted into the operating panel The other set does not include a picture slide and is packaged separately.
Labeling Slides
Slides can be labeled with a fine-tip permanent marker or professional labeling tool.
Removing a Slide Slides have tabs to allow for easy removal. 1. Grasp the tab with fingers or flat-bladed long-nose pliers. 2. Pull gently and steadily until the slide slowly slips out. Inserting a Slide Gently and steadily slip the slide into the slot.
7-2
ACCESSORIES
8-1
8-2
Subnet Mask = 255.255.255.0 Retrieving gas value for specific sensor: Value is split into two registries; For example, ID#2 sensor #1: MI300 provides value to the left of the decimal point MI325 provides value to the right of the decimal point. (See Appendix B, "Memory Integers"). When using the ethernet server (provided by the third party vendor), the addressing may be off-set by one.
A-1
B-1
290 291 292 293 294 295 296 297 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333
DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID
#19 Fault status #20 Fault status #21 Fault status #22 Fault status #23 Fault status #24 Fault status #25 Fault status #26 Fault status #2 Sensor 1 A #3 Sensor 1 A #4 Sensor 1 A #5 Sensor 1 A #6 Sensor 1 A #7 Sensor 1 A #8 Sensor 1 A #9 Sensor 1 A #10 Sensor 1 A #11 Sensor 1 A #12 Sensor 1 A #13 Sensor 1 A #14 Sensor 1 A #15 Sensor 1 A #16 Sensor 1 A #17 Sensor 1 A #18 Sensor 1 A #19 Sensor 1 A #20 Sensor 1 A #21 Sensor 1 A #22 Sensor 1 A #23 Sensor 1 A #24 Sensor 1 A #25 Sensor 1 A #26 Sensor 1 A #2 Sensor 1 B #3 Sensor 1 B #4 Sensor 1 B #5 Sensor 1 B #6 Sensor 1 B #7 Sensor 1 B #8 Sensor 1 B #9 Sensor 1 B #10 Sensor 1 B
B-2
334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375
DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID
#11 Sensor 1 B #12 Sensor 1 B #13 Sensor 1 B #14 Sensor 1 B #15 Sensor 1 B #16 Sensor 1 B #17 Sensor 1 B #18 Sensor 1 B #19 Sensor 1 B #20 Sensor 1 B #21 Sensor 1 B #22 Sensor 1 B #23 Sensor 1 B #24 Sensor 1 B #25 Sensor 1 B #26 Sensor 1 B #2 Sensor 2 A #3 Sensor 2 A #4 Sensor 2 A #5 Sensor 2 A #6 Sensor 2 A #7 Sensor 2 A #8 Sensor 2 A #9 Sensor 2 A #10 Sensor 2 A #11 Sensor 2 A #12 Sensor 2 A #13 Sensor 2 A #14 Sensor 2 A #15 Sensor 2 A #16 Sensor 2 A #17 Sensor 2 A #18 Sensor 2 A #19 Sensor 2 A #20 Sensor 2 A #21 Sensor 2 A #22 Sensor 2 A #23 Sensor 2 A #24 Sensor 2 A #25 Sensor 2 A #26 Sensor 2A #2 Sensor 2 B
B-3
376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417
DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID
#3 Sensor 2 B #4 Sensor 2 B #5 Sensor 2 B #6 Sensor 2 B #7 Sensor 2 B #8 Sensor 2 B #9 Sensor 2 B #10 Sensor 2 B #11 Sensor 2 B #12 Sensor 2 B #13 Sensor 2 B #14 Sensor 2 B #15 Sensor 2 B #16 Sensor 2 B #17 Sensor 2 B #18 Sensor 2 B #19 Sensor 2 B #20 Sensor 2 B #21 Sensor 2 B #22 Sensor 2 B #23 Sensor 2 B #24 Sensor 2 B #25 Sensor 2 B #26 Sensor 2B #2 Sensor 3 A #3 Sensor 3 A #4 Sensor 3 A #5 Sensor 3 A #6 Sensor 3 A #7 Sensor 3 A #8 Sensor 3 A #9 Sensor 3 A #10 Sensor 3 A #11 Sensor 3 A #12 Sensor 3 A #13 Sensor 3 A #14 Sensor 3 A #15 Sensor 3 A #16 Sensor 3 A #17 Sensor 3 A #18 Sensor 3 A #19 Sensor 3 A
B-4
418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459
DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID DEC ID
#20 Sensor 3 A #21 Sensor 3 A #22 Sensor 3 A #23 Sensor 3 A #24 Sensor 3 A #25 Sensor 3 A #26 Sensor 3A #2 Sensor 3 B #3 Sensor 3 B #4 Sensor 3 B #5 Sensor 3 B
DEC ID #6 Sensor 3 B DEC ID #7 Sensor 3 B DEC ID #8 Sensor 3 B DEC ID #9 Sensor 3 B DEC ID #10 Sensor 3 B DEC ID #11 Sensor 3 B DEC ID #12 Sensor 3 B DEC ID #13 Sensor 3 B DEC ID #14 Sensor 3 B DEC ID #15 Sensor 3 B DEC ID #16 Sensor 3 B DEC ID #17 Sensor 3 B DEC ID #18 Sensor 3 B DEC ID #19 Sensor 3 B DEC ID #20 Sensor 3 B DEC ID #21 Sensor 3 B DEC ID #22 Sensor 3 B DEC ID #23 Sensor 3 B DEC ID #24 Sensor 3 B DEC ID #25 Sensor 3 B DEC ID #26 Sensor 3B DEC Fault status ID# 2 DEC Fault status ID# 3 DEC Fault status ID# 4 DEC Fault status ID# 5 DEC Fault status ID# 6 DEC Fault status ID# 7 DEC Fault status ID# 8 DEC Fault status ID# 9 DEC Fault status ID# 10 DEC Fault status ID# 11
B-5
460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554
DEC Fault status ID# 12 DEC Fault status ID# 13 DEC Fault status ID# 14 DEC Fault status ID# 15 DEC Fault status ID# 16 DEC Fault status ID# 17 DEC Fault status ID# 18 DEC Fault status ID# 19 DEC Fault status ID# 20 DEC Fault status ID# 21 DEC Fault status ID# 22 DEC Fault status ID# 23 DEC Fault status ID# 24 DEC Fault status ID# 25 DEC Fault status ID# 26 DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 1 Current Alarm DEC Sensor 2 Current Alarm DEC Sensor 2 Current Alarm DEC Sensor 2 Current Alarm DEC Sensor 2 Current Alarm DEC Sensor 2 Current Alarm
Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status
ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID#
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 2 3 4 5 6
B-6
555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 594 595 596 597 598 599
DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC
Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor Sensor
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm Current Alarm
Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status
ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID# ID#
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
B-7
Set if True Set if True Set if True Set if True Set if True Set if True Set if True Always 0
Bit 15 - Set NAME LOC Sensor 1 LOC Sensor 2 LOC Sensor 3 Over Range Sensor 1 Over Range Sensor 2 Over Range Sensor 3 Quick Under Range Sensor 1 Quick Under Range Sensor 2 Quick Under Range Sensor 3 Under Range Sensor 1 Under Range Sensor 2 Under Range Sensor 3 Not Used Not Used Not Used Sign BITS 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 FUNCTION DESCRIPTION Set if True Set if True Set if True Set if True Set if True Set if True Set if True Set if True Set if True Set if True Set if True Set if True Not Used Not Used Not Used Always 1
B-8
B-9
NOTE: If Zone Alarms are programmed as Latch, user can silence the alarm at the remote relay, but the Zone alarm will not clear until the unlatch input is initiated at the ModCon75 Controller.
C-1
ISOLATION OUTPUT CURRENT MAX. FREQUENCY CONTACT PROTECTION DISPLAY ILLUMINATION DISPLAY SIZE CHARACTER SIZE KEYPAD NUMBER OF KEYS
C-2
(NOTE 4) INPUT VOLTAGE CABLE TYPE GALVANIC ISOLATION BAUD RATE NODES OTHER DATA CLOCK (RTC) BATTERY BACK-UP WEIGHT OPERATIONAL TEMPERATURE STORAGE TEMPERATURE RELATIVE HUMIDITY (RH) MOUNTING METHOD
Real-time clock functions (date and time) 7 years typical for RTC and system data 310 g (10.9 oz.) 0 to 50C (32 to 12F) -20 to 60C (-4 to 140F) 5% to 95% (non-condensing) DIN-rail mounted (IP20/NEMA 1) Panel mounted (IP65/NEMA 4X)
NOTES: 1) All 10 inputs can be set to pnp (source) or npn (sink) via a single jumper and appropriate wiring 2) All 10 inputs can function in 12 VDC or 24 VDC via single jumper and appropriate wiring 3) npn (sink) inputs use voltage supplied from the controllers power supply 4) RS232/RS485 is is determined by jumper settings and wiring
C-3
NOTE: To avoid electromagnetic interference, mount the controller in a metal panel/cabinet and earth the power supply. Earth the power supply signal to the metal via wire 10 cm or shorter. If conditions do not permit this, do not earth the power supply. Figure C-1. Power Supply, pnp (source) Inputs
MODBUS ID 30 00 Local Horn 01 Zone 1 Alarm 02 Zone 2 Alarm Input 10 Common Local area silence
MODBUS ID 31 00 Local Horn 01 Zone 3 Alarm 02 Zone 4 Alarm Input 10 Common Local area silence
MODBUS ID 32 00 Local Horn 01 Zone 5 Alarm 02 Zone 6 Alarm Input 10 Common Local area silence
MODBUS ID 33 00 Local Horn 01 Zone 7 Alarm 02 Zone 8 Alarm Input 10 Common Local area silence
C-4
Jumper Settings
Tables C-2 through C-5 indicate how to set a specific jumper to change the Controller functionality. To open the controller and access the jumpers, see FIGURES C-3 and C-4. " CAUTION
Incompatible jumper settings and wiring connections may severely damage the controller.
C-5
Figure C-3. Shown Jumper Settings Cause the Controller to Function as Follows:
DIGITAL INPUTS ANALOG INPUT POWER SUPPLY npn, 24 VDC inputs Voltage input 24 VDC
C-6
1. Locate the four slots on the side of the enclosure. 2. Using the blade of a flat-blade screwdriver, gently pry off the back of the controller (FIGURE C-4), exposing the controllers board.
C-7
To download this application tool, go to www.msanorthamerica.com , select Fixed Gas Detection Instruments, then Software Downloads. The DataXport Users Guide is located under Fixed Gas Detection Instruments, Controllers, ModCon 75 Controller under the Literature tab.
D-1