Occupational Safety and Health Admin., Labor 1926.57: 1926.57 Ventilation
Occupational Safety and Health Admin., Labor 1926.57: 1926.57 Ventilation
Occupational Safety and Health Admin., Labor 1926.57: 1926.57 Ventilation
, Labor
TABLE D3MINIMUM ILLUMINATION INTENSITIES IN FOOT-CANDLESContinued
Foot-candles 10 ...................... Area or operation General construction plant and shops (e.g., batch plants, screening plants, mechanical and electrical equipment rooms, carpenter shops, rigging lofts and active storerooms, barracks or living quarters, locker or dressing rooms, mess halls, and indoor toilets and workrooms). First aid stations, infirmaries, and offices.
1926.57
30 ......................
(b) Other areas. For areas or operations not covered above, refer to the American National Standard A11.1 1965, R1970, Practice for Industrial Lighting, for recommended values of illumination. 1926.57 Ventilation. (a) General. Whenever hazardous substances such as dusts, fumes, mists, vapors, or gases exist or are produced in the course of construction work, their concentrations shall not exceed the limits specified in 1926.55(a). When ventilation is used as an engineering control method, the system shall be installed and operated according to the requirements of this section. (b) Local exhaust ventilation. Local exhaust ventilation when used as described in (a) shall be designed to prevent dispersion into the air of dusts, fumes, mists, vapors, and gases in concentrations causing harmful exposure. Such exhaust systems shall be so designed that dusts, fumes, mists, vapors, or gases are not drawn through the work area of employees. (c) Design and operation. Exhaust fans, jets, ducts, hoods, separators, and all necessary appurtenances, including refuse receptacles, shall be so designed, constructed, maintained and operated as to ensure the required protection by maintaining a volume and velocity of exhaust air sufficient to gather dusts, fumes, vapors, or gases from said equipment or process, and to convey them to suitable points of safe disposal, thereby preventing their dispersion in harmful quantities into the atmosphere where employees work. (d) Duration of operations. (1) The exhaust system shall be in operation continually during all operations which it is designed to serve. If the employee remains in the contaminated zone, the
system shall continue to operate after the cessation of said operations, the length of time to depend upon the individual circumstances and effectiveness of the general ventilation system. (2) Since dust capable of causing disability is, according to the best medical opinion, of microscopic size, tending to remain for hours in suspension in still air, it is essential that the exhaust system be continued in operation for a time after the work process or equipment served by the same shall have ceased, in order to ensure the removal of the harmful elements to the required extent. For the same reason, employees wearing respiratory equipment should not remove same immediately until the atmosphere seems clear. (e) Disposal of exhaust materials. The air outlet from every dust separator, and the dusts, fumes, mists, vapors, or gases collected by an exhaust or ventilating system shall discharge to the outside atmosphere. Collecting systems which return air to work area may be used if concentrations which accumulate in the work area air do not result in harmful exposure to employees. Dust and refuse discharged from an exhaust system shall be disposed of in such a manner that it will not result in harmful exposure to employees. (f) Abrasive blasting(1) Definitions applicable to this paragraph(i) Abrasive. A solid substance used in an abrasive blasting operation. (ii) Abrasive-blasting respirator. A respirator constructed so that it covers the wearers head, neck, and shoulders to protect the wearer from rebounding abrasive. (iii) Blast cleaning barrel. A complete enclosure which rotates on an axis, or which has an internal moving tread to tumble the parts, in order to expose various surfaces of the parts to the action of an automatic blast spray. (iv) Blast cleaning room. A complete enclosure in which blasting operations are performed and where the operator works inside of the room to operate the blasting nozzle and direct the flow of the abrasive material. (v) Blasting cabinet. An enclosure where the operator stands outside and operates the blasting nozzle through an opening or openings in the enclosure.
49
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00059
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
(vi) Clean air. Air of such purity that it will not cause harm or discomfort to an individual if it is inhaled for extended periods of time. (vii) Dust collector. A device or combination of devices for separating dust from the air handled by an exhaust ventilation system. (viii) Exhaust ventilation system. A system for removing contaminated air from a space, comprising two or more of the following elements (A) enclosure or hood, (B) duct work, (C) dust collecting equipment, (D) exhauster, and (E) discharge stack. (ix) Particulate-filter respirator. An air purifying respirator, commonly referred to as a dust or a fume respirator, which removes most of the dust or fume from the air passing through the device. (x) Respirable dust. Airborne dust in sizes capable of passing through the upper respiratory system to reach the lower lung passages. (xi) Rotary blast cleaning table. An enclosure where the pieces to be cleaned are positioned on a rotating table and are passed automatically through a series of blast sprays. (xii) Abrasive blasting. The forcible application of an abrasive to a surface by pneumatic pressure, hydraulic pressure, or centrifugal force. (2) Dust hazards from abrasive blasting. (i) Abrasives and the surface coatings on the materials blasted are shattered and pulverized during blasting operations and the dust formed will contain particles of respirable size. The composition and toxicity of the dust from these sources shall be considered in making an evaluation of the potential health hazards. (ii) The concentration of respirable dust or fume in the breathing zone of the abrasive-blasting operator or any other worker shall be kept below the levels specified in 1926.55 or other pertinent sections of this part. (iii) Organic abrasives which are combustible shall be used only in automatic systems. Where flammable or explosive dust mixtures may be present, the construction of the equipment, including the exhaust system and all electric wiring, shall conform to the requirements of American National Standard Installation of Blower and
50
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00060
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
short, intermittent, or occasional dust exposures such as cleanup, dumping of dust collectors, or unloading shipments of sand at a receiving point when it is not feasible to control the dust by enclosure, exhaust ventilation, or other means. The respirators used must be approved by NIOSH under 42 CFR part 84 for protection against the specific type of dust encountered. (iv) A respiratory protection program as defined and described in 1926.103, shall be established wherever it is necessary to use respiratory protective equipment. (v) Operators shall be equipped with heavy canvas or leather gloves and aprons or equivalent protection to protect them from the impact of abrasives. Safety shoes shall be worn to protect against foot injury where heavy pieces of work are handled. (A) Safety shoes shall conform to the requirements of American National Standard for Mens Safety-Toe Footwear, Z41.11967. (B) Equipment for protection of the eyes and face shall be supplied to the operator when the respirator design does not provide such protection and to any other personnel working in the vicinity of abrasive blasting operations. This equipment shall conform to the requirements of 1926.102. (6) Air supply and air compressors. Air for abrasive-blasting respirators must be free of harmful quantities of dusts, mists, or noxious gases, and must meet the requirements for supplied-air quality and use specified in 29 CFR 1910.134(i). (7) Operational procedures and general safety. Dust shall not be permitted to accumulate on the floor or on ledges outside of an abrasive-blasting enclosure, and dust spills shall be cleaned up promptly. Aisles and walkways shall be kept clear of steel shot or similar abrasive which may create a slipping hazard. (8) Scope. This paragraph applies to all operations where an abrasive is forcibly applied to a surface by pneumatic or hydraulic pressure, or by centrifugal force. It does not apply to steam blasting, or steam cleaning, or hydraulic cleaning methods where work is done without the aid of abrasives.
51
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00061
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
(g) Grinding, polishing, and buffing operations(1) Definitions applicable to this paragraph (i) Abrasive cutting-off wheels. Organic-bonded wheels, the thickness of which is not more than one fortyeighth of their diameter for those up to, and including, 20 inches (50.8 cm) in diameter, and not more than one-sixtieth of their diameter for those larger than 20 inches (50.8 cm) in diameter, used for a multitude of operations variously known as cutting, cutting off, grooving, slotting, coping, and jointing, and the like. The wheels may be solid consisting of organic-bonded abrasive material throughout, steel centered consisting of a steel disc with a rim of organic-bonded material moulded around the periphery, or of the inserted tooth type consisting of a steel disc with organic-bonded abrasive teeth or inserts mechanically secured around the periphery. (ii) Belts. All power-driven, flexible, coated bands used for grinding, polishing, or buffing purposes. (iii) Branch pipe. The part of an exhaust system piping that is connected directly to the hood or enclosure. (iv) Cradle. A movable fixture, upon which the part to be ground or polished is placed. (v) Disc wheels. All power-driven rotatable discs faced with abrasive materials, artificial or natural, and used for grinding or polishing on the side of the assembled disc. (vi) Entry loss. The loss in static pressure caused by air flowing into a duct or hood. It is usually expressed in inches of water gauge. (vii) Exhaust system. A system consisting of branch pipes connected to hoods or enclosures, one or more header pipes, an exhaust fan, means for separating solid contaminants from the air flowing in the system, and a discharge stack to outside. (viii) Grinding wheels. All power-driven rotatable grinding or abrasive wheels, except disc wheels as defined in this standard, consisting of abrasive particles held together by artificial or natural bonds and used for peripheral grinding. (ix) Header pipe (main pipe). A pipe into which one or more branch pipes enter and which connects such branch
52
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00062
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
To 9 (22.86) ................................... Over 9 to 16 (22.86 to 40.64) ....... Over 16 to 19 (40.64 to 48.26) ..... Over 19 to 24 (48.26 to 60.96) ..... Over 24 to 30 (60.96 to 76.2) ....... Over 30 to 36 (76.2 to 91.44) .......
(iv) Grinding wheels or discs for horizontal single-spindle disc grinders shall be hooded to collect the dust or dirt generated by the grinding operation and the hoods shall be connected to branch pipes having exhaust volumes as shown in Table D57.3. TABLE D57.3HORIZONTAL SINGLE-SPINDLE DISC GRINDER
Disc diameter, inches (cm) Up to 12 (30.48) .................................................. Over 12 to 19 (30.48 to 48.26) ........................... Over 19 to 30 (48.26 to 76.2) ............................. Over 30 to 36 (76.2 to 91.44) ............................. Exhaust volume (ft.3/min.) 220 390 610 880
To 9 (22.86) ................................... Over 9 to 16 (22.86 to 40.64) ....... Over 16 to 19 (40.64 to 48.26) ..... Over 19 to 24 (48.26 to 60.96) ..... Over 24 to 30 (60.96 to 76.2) ....... Over 30 to 36 (76.2 to 91.44) .......
(v) Grinding wheels or discs for horizontal double-spindle disc grinders shall have a hood enclosing the grinding chamber and the hood shall be connected to one or more branch pipes having exhaust volumes as shown in Table D57.4. TABLE D57.4HORIZONTAL DOUBLE-SPINDLE DISC GRINDER
Disc diameter, inches (cm) Up to 19 (48.26) .................................................. Over 19 to 25 (48.26 to 63.5) ............................. Over 25 to 30 (63.5 to 76.2) ............................... Over 30 to 53 (76.2 to 134.62) ........................... Over 53 to 72 (134.62 to 182.88) ....................... Exhaust volume (ft.3/min.) 610 880 1,200 1,770 6,280
For any wheel wider than wheel diameters shown in Table D57.1, increase the exhaust volume by the ratio of the new width to the width shown.
Example: If wheel width = 412 inches (11.43 cm), then 4.54 610 = 686 (rounded to 690).
(iii) Scratch-brush wheels and all buffing and polishing wheels mounted on floor stands, pedestals, benches, or special-purpose machines shall have not less than the minimum exhaust volume shown in Table D57.2.
(vi) Grinding wheels or discs for vertical single-spindle disc grinders shall be encircled with hoods to remove the dust generated in the operation. The hoods shall be connected to one or more branch pipes having exhaust volumes as shown in Table D57.5.
53
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00063
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
TABLE D57.5VERTICAL SPINDLE DISC GRINDER
One-half or more of disc covered Disc diameter, inches (cm) Number 1 1 2 2 2 Exhaust foot 3/ min. 500 780 1,770 3,140 Disc not covered Number 1 2 2 4 5 Exhaust foot3/ min. 780 1,480 3,530 6,010
Up to 20 (50.8) .......... Over 20 to 30 (50.8 to 76.2) ....................... Over 30 to 53 (76.2 to 134.62) ................... Over 53 to 72 (134.62 to 182.88) ...............
1 Number
of exhaust outlets around periphery of hood, or equal distribution provided by other means.
(vii) Grinding and polishing belts shall be provided with hoods to remove dust and dirt generated in the operations and the hoods shall be connected to branch pipes having exhaust volumes as shown in Table D57.6. TABLE D57.6GRINDING AND POLISHING BELTS
Belts width, inches (cm) Up to 3 (7.62) ...................................................... Over 3 to 5 (7.62 to 12.7) ................................... Over 5 to 7 (12.7 to 17.78) ................................. Over 7 to 9 (17.78 to 22.86) ............................... Over 9 to 11 (22.86 to 27.94) ............................. Over 11 to 13 (27.94 to 33.02) ........................... Exhaust volume (ft.3/min.) 220 300 390 500 610 740
(viii) Cradles and swing-frame grinders. Where cradles are used for handling the parts to be ground, polished, or buffed, requiring large partial enclosures to house the complete operation, a minimum average air velocity of 150 feet per minute shall be maintained over the entire opening of the enclosure. Swing-frame grinders shall also be exhausted in the same manner as provided for cradles. (See fig. D57.3) (ix) Where the work is outside the hood, air volumes must be increased as shown in American Standard Fundamentals Governing the Design and Operation of Local Exhaust Systems, Z9.21960 (section 4, exhaust hoods). (4) Exhaust systems. (i) Exhaust systems for grinding, polishing, and buffing operations should be designed in accordance with American Standard Fundamentals Governing the Design and Operation of Local Exhaust Systems, Z9.21960.
54
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00064
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
The openings for passing the work into the grinding chamber should be kept as small as possible, but must never be less than twice the area of the branch outlets. (ix) Vertical-spindle disc grinders shall be encircled with a hood so constructed that the heavy dust is drawn off a surface of the disc and the lighter dust exhausted through a continuous slot at the top of the hood as shown in figure D57.1. (x) Grinding and polishing belt hoods shall be constructed as close to the operation as possible. The hood should extend almost to the belt, and 1-inch (2.54 cm) wide openings should be provided on either side. Figure D57.8 shows a typical hood for a belt operation.
55
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00065
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
Dia. D Min.
Note
....................................
When one-half or more of the disc can be hooded, use exhaust ducts as shown at the left.
Over 20 (50.8) ........... Over 30 (76.2) ........... Over 53 (134.62) ....... ....................................
2 2 2 2
780 1,770 3,140 780 When no hood can be used over disc, use exhaust ducts as shown at left.
2 2 4 5
4 512 6 7
Entry loss=1.0 slot velocity pressure + 0.5 branch velocity pressure. Minimum slot velocity=2,000 ft/min12-inch (1.27 cm) slot width.
56
EC30OC91.000
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00066
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
Wheel dimension, inches (centimeters) Diameter Width, Max Min= d Max= D 9 (22.86) 16 (40.64) 19 (48.26) 24 (60.96) 30 (76.2) 36 (91.44) 112 (3.81) 2 (5.08) 3 (7.62) 4 (10.16) 5 (12.7) 6 (15.24) 3 4 412 5 6 7 Exhaust outlet, inches (centimeters) E
Volume of air at 4,500 ft/ min 220 390 500 610 880 1,200
9 (22.86) ............................................................................. 16 (40.64) ........................................................................... 19 (48.26) ........................................................................... 24 (60.96) ........................................................................... 30 (76.2) .............................................................................
Entry loss = 0.45 velocity pressure for tapered takeoff 0.65 velocity pressure for straight takeoff.
57
EC30OC91.001
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00067
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
58
EC30OC91.002
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00068
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
9 (22.86) ............................................................................. 16 (40.64) ........................................................................... 19 (48.26) ........................................................................... 24 (60.96) ........................................................................... 30 (76.2) .............................................................................
Entry loss = 0.15 velocity pressure for tapered takeoff; 0.65 velocity pressure for straight takeoff.
59
EC30OC91.003
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00069
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
60
EC30OC91.004
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00070
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
NOTE: If grinding wheels are used for disc grinding purposes, hoods must conform to structural strength and materials as described in 9.1. Entry loss = 0.45 velocity pressure for tapered takeoff.
61
EC30OC91.005
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00071
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
Note
When width W permits, exhaust ducts should be as near heaviest grinding as possible.
1 2 4
7 6 8
62
EC30OC91.006
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00072
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
Minimum duct velocity = 4,500 ft/min branch, 3,500 ft/min main. Entry loss = 0.45 velocity pressure for tapered takeoff; 0.65 velocity pressure for straight takeoff.
(6) Scope. This paragraph (g), prescribes the use of exhaust hood enclosures and systems in removing dust, dirt, fumes, and gases generated through the grinding, polishing, or buffing of ferrous and nonferrous metals. (h) Spray finishing operations(1) Definitions applicable to this paragraph(i) Spray-finishing operations. Spray-finishing operations are employment of methods wherein organic or inorganic materials are utilized in dispersed form for deposit on surfaces to be coated, treated, or cleaned. Such methods of deposit may involve either automatic, manual, or electrostatic deposition but do not include metal spraying or metallizing, dipping, flow coating, roller coating, tumbling, centrifuging, or spray washing and degreasing as conducted in self-contained washing and degreasing machines or systems. (ii) Spray booth. Spray booths are defined and described in 1926.66(a). (See sections 103, 104, and 105 of the Standard for Spray Finishing Using Flam-
mable and Combustible Materials, NFPA No. 331969). (iii) Spray room. A spray room is a room in which spray-finishing operations not conducted in a spray booth are performed separately from other areas. (iv) Minimum maintained velocity. Minimum maintained velocity is the velocity of air movement which must be maintained in order to meet minimum specified requirements for health and safety. (2) Location and application. Spray booths or spray rooms are to be used to enclose or confine all operations. Spray-finishing operations shall be located as provided in sections 201 through 206 of the Standard for Spray Finishing Using Flammable and Combustible Materials, NFPA No. 331969. (3) Design and construction of spray booths. (i) Spray booths shall be designed and constructed in accordance with 1926.66(b) (1) through (4) and (6) through (10) (see sections 301304 and 306310 of the Standard for Spray Finishing Using Flammable and Combustible Materials, NFPA No. 331969), for general construction specifications. For a more detailed discussion of fundamentals relating to this subject, see ANSI Z9.21960 (A) Lights, motors, electrical equipment, and other sources of ignition shall conform to the requirements of 1926.66(b)(10) and (c). (See section 310 and chapter 4 of the Standard for Spray Finishing Using Flammable and Combustible Materials NFPA No. 331969.) (B) In no case shall combustible material be used in the construction of a
63
EC30OC91.007
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00073
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
spray booth and supply or exhaust duct connected to it. (ii) Unobstructed walkways shall not be less than 612 feet (1.976 m) high and shall be maintained clear of obstruction from any work location in the booth to a booth exit or open booth front. In booths where the open front is the only exit, such exits shall be not less than 3 feet (0.912 m) wide. In booths having multiple exits, such exits shall not be less than 2 feet (0.608 m) wide, provided that the maximum distance from the work location to the exit is 25 feet (7.6 m) or less. Where booth exits are provided with doors, such doors shall open outward from the booth. (iii) Baffles, distribution plates, and dry-type overspray collectors shall conform to the requirements of 1926.66(b) (4) and (5). (See sections 304 and 305 of the Standard for Spray Finishing Using Flammable and Combustible Materials, NFPA No. 331969.) (A) Overspray filters shall be installed and maintained in accordance with the requirements of 1926.66(b)(5), (see section 305 of the Standard for Spray Finishing Using Flammable and Combustible Materials, NFPA No. 33 1969), and shall only be in a location easily accessible for inspection, cleaning, or replacement. (B) Where effective means, independent of the overspray filters, are installed which will result in design air distribution across the booth cross section, it is permissible to operate the booth without the filters in place. (iv) (A) For wet or water-wash spray booths, the water-chamber enclosure, within which intimate contact of contaminated air and cleaning water or other cleaning medium is maintained, if made of steel, shall be 18 gage or heavier and adequately protected against corrosion. (B) Chambers may include scrubber spray nozzles, headers, troughs, or other devices. Chambers shall be provided with adequate means for creating and maintaining scrubbing action for removal of particulate matter from the exhaust air stream. (v) Collecting tanks shall be of welded steel construction or other suitable non-combustible material. If pits are used as collecting tanks, they shall be
64
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00074
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
(E) Inspection or clean-out doors shall be provided for every 9 to 12 feet (2.736 to 3.648 m) of running length for ducts up to 12 inches (0.304 m) in diameter, but the distance between cleanout doors may be greater for larger pipes. (See 8.3.21 of American National Standard Z9.11951.) A clean-out door or doors shall be provided for servicing the fan, and where necessary, a drain shall be provided. (F) Where ductwork passes through a combustible roof or wall, the roof or wall shall be protected at the point of penetration by open space or fire-resistive material between the duct and the roof or wall. When ducts pass through firewalls, they shall be provided with automatic fire dampers on both sides of the wall, except that three-eighth-inch steel plates may be used in lieu of automatic fire dampers for ducts not exceeding 18 inches (45.72 cm) in diameter. (G) Ductwork used for ventilating any process covered in this standard shall not be connected to ducts ventilating any other process or any chimney or flue used for conveying any products of combustion. (6) Velocity and air flow requirements. (i) Except where a spray booth has an adequate air replacement system, the velocity of air into all openings of a spray booth shall be not less than that specified in Table D57.7 for the operating conditions specified. An adequate air replacement system is one which introduces replacement air upstream or above the object being sprayed and is so designed that the velocity of air in the booth cross section is not less than that specified in Table D57.7 when measured upstream or above the object being sprayed.
65
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00075
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
(1) Attention is invited to the fact that the effectiveness of the spray booth is dependent upon the relationship of the depth of the booth to its height and width. (2) Crossdrafts can be eliminated through proper design and such design should be sought. Crossdrafts in excess of 100fpm (feet per minute) should not be permitted. (3) Excessive air pressures result in loss of both efficiency and material waste in addition to creating a backlash that may carry overspray and fumes into adjacent work areas. (4) Booths should be designed with velocities shown in the column headed Design. However, booths operating with velocities shown in the column headed Range are in compliance with this standard.
(ii) In addition to the requirements in paragraph (h)(6)(i) of this section the total air volume exhausted through a spray booth shall be such as to dilute solvent vapor to at least 25 percent of the lower explosive limit of the solvent being sprayed. An example of the method of calculating this volume is given below.
Example: To determine the lower explosive limits of the most common solvents used in spray finishing, see Table D57.8. Column 1 gives the number of cubic feet of vapor per gallon of solvent and column 2 gives the lower explosive limit (LEL) in percentage by volume of air. Note that the quantity of solvent will be diminished by the quantity of solids and nonflammables contained in the finish. To determine the volume of air in cubic feet necessary to dilute the vapor from 1 gallon of solvent to 25 percent of the lower explosive limit, apply the following formula:
Solvent
Dilution volume required per gallon of solvent=4 (100LEL) (cubic feet of vapor per gallon) LEL
Using toluene as the solvent. (1) LEL of toluene from Table D57.8, column 2, is 1.4 percent. (2) Cubic feet of vapor per gallon from Table D57.8, column 1, is 30.4 cubic feet per gallon. (3) Dilution volume required =
Benzene ........................................ Butyl Acetate (n) ............................ Butyl Alcohol (n) ............................ Butyl Cellosolve ............................. Cellosolve ...................................... Cellosolve Acetate ......................... Cyclohexanone .............................. 1,1 Dichloroethylene ...................... 1,2 Dichloroethylene ...................... Ethyl Acetate ................................. Ethyl Alcohol .................................. Ethyl Lactate .................................. Methyl Acetate ............................... Methyl Alcohol ............................... Methyl Cellosolve .......................... Methyl Ethyl Ketone ...................... Methyl n-Propyl Ketone ................. Naphtha (VM&P) (76Naphtha) ..... Naphtha (100Flash) Safety SolventStoddard Solvent ............. Propyl Acetate (n) ......................... Propyl Acetate (iso) ....................... Propyl Alcohol (n) .......................... Propyl Alcohol (iso) ....................... Toluene .......................................... Turpentine ..................................... Xylene (o) ......................................
1 At
1.7 1.4 1.1 1.8 1.7 1 1.1 5.9 9.7 2.5 4.3 1 1.5 3.1 7.3 2.5 1.8 1.5 0.9 1.0 2.8 1.1 2.1 2.0 1.4 0.8 1.0
Solvent
Acetone ......................................... Amyl Acetate (iso) ......................... Amyl Alcohol (n) ............................ Amyl Alcohol (iso) .........................
(iii)(A) When an operator is in a booth downstream of the object being sprayed, an air-supplied respirator or other type of respirator approved by NIOSH under 42 CFR part 84 for the material being sprayed should be used by the operator. (B) Where downdraft booths are provided with doors, such doors shall be closed when spray painting. (7) Make-up air. (i) Clean fresh air, free of contamination from adjacent industrial exhaust systems, chimneys, stacks, or vents, shall be supplied to a spray booth or room in quantities equal to the volume of air exhausted through the spray booth. (ii) Where a spray booth or room receives make-up air through self-closing doors, dampers, or louvers, they shall be fully open at all times when the
66
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00076
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
sources of heat may be employed to meet this requirement. (C) No means of heating make-up air shall be located in a spray booth. (D) Where make-up air is heated by coal or oil, the products of combustion shall not be allowed to mix with the make-up air, and the products of combustion shall be conducted outside the building through a flue terminating at a point remote from all points where make-up air enters the building. (E) Where make-up air is heated by gas, and the products of combustion are not mixed with the make-up air but are conducted through an independent flue to a point outside the building remote from all points where make-up air enters the building, it is not necessary to comply with paragraph (h)(7)(iv)(F) of this section. (F) Where make-up air to any manually operated spray booth or room is heated by gas and the products of combustion are allowed to mix with the supply air, the following precautions must be taken: (1) The gas must have a distinctive and strong enough odor to warn workmen in a spray booth or room of its presence if in an unburned state in the make-up air. (2) The maximum rate of gas supply to the make-up air heater burners must not exceed that which would yield in excess of 200 p.p.m. (parts per million) of carbon monoxide or 2,000 p.p.m. of total combustible gases in the mixture if the unburned gas upon the occurrence of flame failure were mixed with all of the make-up air supplied. (3) A fan must be provided to deliver the mixture of heated air and products of combustion from the plenum chamber housing the gas burners to the spray booth or room. (8) Scope. Spray booths or spray rooms are to be used to enclose or confine all spray finishing operations covered by this paragraph (h). This paragraph does not apply to the spraying of the exteriors of buildings, fixed tanks, or similar structures, nor to small portable spraying apparatus not used repeatedly in the same location. (i) Open surface tanks(1) General. (i) This paragraph applies to all operations involving the immersion of materials in liquids, or in the vapors of
67
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00077
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
such liquids, for the purpose of cleaning or altering the surface or adding to or imparting a finish thereto or changing the character of the materials, and their subsequent removal from the liquid or vapor, draining, and drying. These operations include washing, electroplating, anodizing, pickling, quenching, dying, dipping, tanning, dressing, bleaching, degreasing, alkaline cleaning, stripping, rinsing, digesting, and other similar operations. (ii) Except where specific construction specifications are prescribed in this section, hoods, ducts, elbows, fans, blowers, and all other exhaust system parts, components, and supports thereof shall be so constructed as to meet conditions of service and to facilitate maintenance and shall conform in construction to the specifications contained in American National Standard Fundamentals Governing the Design and Operation of Local Exhaust Systems, Z9.21960. (2) Classification of open-surface tank operations. (i) Open-surface tank operations shall be classified into 16 classes, numbered A1 to D4, inclusive. (ii) Determination of class. Class is determined by two factors, hazard potential designated by a letter from A to D, inclusive, and rate of gas, vapor, or mist evolution designated by a number from 1 to 4, inclusive (for example, B.3). (iii) Hazard potential is an index, on a scale of from A to D, inclusive, of the severity of the hazard associated with the substance contained in the tank because of the toxic, flammable, or explosive nature of the vapor, gas, or mist produced therefrom. The toxic hazard is determined from the concentration, measured in parts by volume of a gas or vapor, per million parts by volume of contaminated air (p.p.m.), or in milligrams of mist per cubic meter of air (mg./m.3), below which ill effects are unlikely to occur to the exposed worker. The concentrations shall be those in 1926.55 or other pertinent sections of this part. (iv) The relative fire or explosion hazard is measured in degrees Fahrenheit in terms of the closed-cup flash point of the substance in the tank. Detailed information on the prevention of fire hazards in dip tanks may be found in Dip Tanks Containing Flammable or
(vi) Rate of gas, vapor, or mist evolution is a numerical index, on a scale of from 1 to 4, inclusive, both of the relative capacity of the tank to produce gas, vapor, or mist and of the
68
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00078
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
(D) The extent that the tank gases or produces mist in an arbitrary scale high, medium, low, and nil. (See Table D57.10, Note 2.) Gassing depends upon electrochemical or mechanical processes, the effects of which have to be individually evaluated for each installation (see Table D57.10, Note 3). (vii) Rate of evolution shall be determined from Table D57.10. When evaporation and gassing yield different rates, the lowest numerical value shall be used.
1 In certain classes of equipment, specifically vapor degreasers, an internal condenser or vapor level thermostat is used to prevent the vapor from leaving the tank during normal operation. In such cases, rate of vapor evolution from the tank into the workroom is not dependent upon the factors listed in the table, but rather upon abnormalities of operating procedure, such as carryout of vapors from excessively fast action, dragout of liquid by entrainment in parts, contamination of solvent by water and other materials, or improper heat balance. When operating procedure is excellent, effective rate of evolution may be taken as 4. When operating procedure is average, the effective rate of evolution may be taken as 3. When operation is poor, a rate of 2 or 1 is indicated, depending upon observed conditions. 2 Relative evaporation rate is determined according to the methods described by A. K. Doolittle in Industrial and Engineering Chemistry, vol. 27, p. 1169, (3) where time for 100-percent evaporation is as follows: Fast: 03 hours; Medium: 312 hours; Slow: 1250 hours; Nil: more than 50 hours. 3 Gassing means the formation by chemical or electrochemical action of minute bubbles of gas under the surface of the liquid in the tank and is generally limited to aqueous solutions.
(3) Ventilation. Where ventilation is used to control potential exposures to workers as defined in paragraph (i)(2)(iii) of this section, it shall be adequate to reduce the concentration of the air contaminant to the degree that a hazard to the worker does not exist. Methods of ventilation are discussed in American National Standard Fundamentals Governing the Design and Operation of Local Exhaust Systems, Z9.21960. (4) Control requirements. (i) Control velocities shall conform to Table D 57.11 in all cases where the flow of air past the breathing or working zone of the operator and into the hoods is undisturbed by local environmental conditions, such as open windows, wall fans, unit heaters, or moving machinery.
(ii) All tanks exhausted by means of hoods which (A) Project over the entire tank; (B) Are fixed in position in such a location that the head of the workman, in all his normal operating positions while working at the tank, is in front of all hood openings; and (C) Are completely enclosed on at least two sides, shall be considered to be exhausted through an enclosing hood. (D) The quantity of air in cubic feet per minute necessary to be exhausted through an enclosing hood shall be not less than the product of the control velocity times the net area of all openings in the enclosure through which air can flow into the hood.
69
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00079
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
TABLE D57.11CONTROL VELOCITIES IN FEET PER MINUTE (F.P.M.) FOR UNDISTURBED LOCATIONS
Enclosing hood Class One open side 100 75 65 50 .................. Two open sides 150 100 90 75 .................. Lateral exhaust 1 150 100 75 50 .................. Canopy hood 2 Three open sides Do not use 125 100 75 .................. Four open sides Do not use 175 150 125 ..................
B1 and A2 ........................................................................... A3 2, B1, B2, and C1 ....................................................... A3, C2, and D1 3 ............................................................... B4 2, C3, and D2 3 ............................................................. A4, C4, D3 3, and D4 4 ....................................................
1 See 2 Do
Table D57.12 for computation of ventilation rate. not use canopy hood for Hazard Potential A processes. complete control of hot water is desired, design as next highest class. 4 General room ventilation required.
3 Where
(iii) All tanks exhausted by means of hoods which do not project over the entire tank, and in which the direction of air movement into the hood or hoods is substantially horizontal, shall be considered to be laterally exhausted. The quantity of air in cubic feet per minute necessary to be laterally exhausted per square foot of tank area in order to maintain the required control velocity shall be determined from Table D57.12 for all variations in ratio of tank width (W) to tank length $(L). The total quantity of air in cubic feet per minute required to be exhausted per tank shall be not less than the product of the area of tank surface times the cubic feet per minute per square foot of tank area, determined from Table D57.12.
(A) For lateral exhaust hoods over 42 inches (1.06 m) wide, or where it is desirable to reduce the amount of air removed from the workroom, air supply slots or orifices shall be provided along the side or the center of the tank opposite from the exhaust slots. The design of such systems shall meet the following criteria: (1) The supply air volume plus the entrained air shall not exceed 50 percent of the exhaust volume. (2) The velocity of the supply airstream as it reaches the effective control area of the exhaust slot shall be less than the effective velocity over the exhaust slot area.
TABLE D57.12MINIMUM VENTILATION RATE IN CUBIC FEET OF AIR PER MINUTE PER SQUARE FOOT OF TANK AREA FOR LATERAL EXHAUST
Required minimum control velocity, f.p.m. (from Table D 57.11) C.f.m. per sq. ft. to maintain required minimum velocities at following ratios (tank width (W)/tank length (L)). 1,2 0.00.09 0.10.24 0.250.49 0.50.99 1.02.0
Hood along one side or two parallel sides of tank when one hood is against a wall or baffle. 2 Also for a manifold along tank centerline. 3 50 ............................................................................................ 75 ............................................................................................ 100 .......................................................................................... 150 .......................................................................................... 50 75 100 150 60 90 125 190 75 110 150 225 90 130 175 260 100 150 200 300
Hood along one side or two parallel sides of free standing tank not against wall or baffle. 50 ............................................................................................ 75 ............................................................................................ 100 .......................................................................................... 150 ..........................................................................................
1 It
is not practicable to ventilate across the long dimension of a tank whose ratio W/L exceeds 2.0. It is undesirable to do so when W/L exceeds 1.0. For circular tanks with lateral exhaust along up to 1/2 the circumference, use W/L=1.0; for over one-half the circumference use W/L=0.5. 2 Baffle is a vertical plate the same length as the tank, and with the top of the plate as high as the tank is wide. If the exhaust hood is on the side of a tank against a building wall or close to it, it is perfectly baffled. 3 Use W/2 as tank width in computing when manifold is along centerline, or when hoods are used on two parallel sides of a tank. Tank Width (W) means the effective width over which the hood must pull air to operate (for example, where the hood face is set back from the edge of the tank, this set back must be added in measuring tank width). The surface area of tanks can frequently be reduced and better control obtained (particularly on conveyorized systems) by using covers extending from the upper edges of the slots toward the center of the tank.
70
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00080
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
the liquid in the tank to minimize mist formation, or any combination thereof, may all be used as gas, mist, or vapor control means for open-surface tank operations, provided that they effectively reduce the concentrations of hazardous materials in the vicinity of the worker below the limits set in accordance with paragraph (i)(2) of this section. (7) System design. (i) The equipment for exhausting air shall have sufficient capacity to produce the flow of air required in each of the hoods and openings of the system. (ii) The capacity required in paragraph (i)(7)(i) of this section shall be obtained when the airflow producing equipment is operating against the following pressure losses, the sum of which is the static pressure: (A) Entrance losses into the hood. (B) Resistance to airflow in branch pipe including bends and transformations. (C) Entrance loss into the main pipe. (D) Resistance to airflow in main pipe including bends and transformations. (E) Resistance of mechanical equipment; that is, filters, washers, condensers, absorbers, etc., plus their entrance and exit losses. (F) Resistance in outlet duct and discharge stack. (iii) Two or more operations shall not be connected to the same exhaust system where either one or the combination of the substances removed may constitute a fire, explosion, or chemical reaction hazard in the duct system. Traps or other devices shall be provided to insure that condensate in ducts does not drain back into any tank. (iv) The exhaust system, consisting of hoods, ducts, air mover, and discharge outlet, shall be designed in accordance with American National Standard Fundamentals Governing the Design and Operation of Local Exhaust Systems, Z9.21960, or the manual, Industrial Ventilation, published by the American Conference of Governmental Industrial Hygienists 1970. Airflow and pressure loss data provided by the manufacturer of any air cleaning device shall be included in the design calculations.
71
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00081
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
(8) Operation. (i) The required airflow shall be maintained at all times during which gas, mist, or vapor is emitted from the tank, and at all times the tank, the draining, or the drying area is in operation or use. When the system is first installed, the airflow from each hood shall be measured by means of a pitot traverse in the exhaust duct and corrective action taken if the flow is less than that required. When the proper flow is obtained, the hood static pressure shall be measured and recorded. At intervals of not more than 3 months operation, or after a prolonged shutdown period, the hoods and duct system shall be inspected for evidence of corrosion or damage. In any case where the airflow is found to be less than required, it shall be increased to the required value. (Information on airflow and static pressure measurement and calculations may be found in American National Standard Fundamental Governing the Design and Operation of Local Exhaust Systems, Z9.2 1960, or in the manual, Industrial Ventilation, published by the American Conference of Governmental Industrial Hygienists.) (ii) The exhaust system shall discharge to the outer air in such a manner that the possibility of its effluent entering any building is at a minimum. Recirculation shall only be through a device for contaminant removal which will prevent the creation of a health hazard in the room or area to which the air is recirculated. (iii) A volume of outside air in the range of 90 percent to 110 percent of the exhaust volume shall be provided to each room having exhaust hoods. The outside air supply shall enter the workroom in such a manner as not to be detrimental to any exhaust hood. The airflow of the makeup air system shall be measured on installation. Corrective action shall be taken when the airflow is below that required. The makeup air shall be uncontaminated. (9) Personal protection. (i) All employees working in and around open-surface tank operations must be instructed as to the hazards of their respective jobs, and in the personal protection and first aid procedures applicable to these hazards.
72
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00082
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.57
type of construction and by frequent flushing. They shall be firm, sound, and of the design and construction to minimize the possibility of tripping. (ii) Before cleaning the interior of any tank, the contents shall be drained off, and the cleanout doors shall be opened where provided. All pockets in tanks or pits, where it is possible for hazardous vapors to collect, shall be ventilated and cleared of such vapors. (iii) Tanks which have been drained to permit employees to enter for the purposes of cleaning, inspection, or maintenance may contain atmospheres which are hazardous to life or health, through the presence of flammable or toxic air contaminants, or through the absence of sufficient oxygen. Before employees shall be permitted to enter any such tank, appropriate tests of the atmosphere shall be made to determine if the limits set by paragraph (i)(2)(iii) of this section are exceeded, or if the oxygen concentration is less than 19.5 percent. (iv) If the tests made in accordance with paragraph (i)(11)(iii) of this section indicate that the atmosphere in the tank is unsafe, before any employee is permitted to enter the tank, the tank shall be ventilated until the hazardous atmosphere is removed, and ventilation shall be continued so as to prevent the occurrence of a hazardous atmosphere as long as an employee is in the tank. (v) If, in emergencies, such as rescue work, it is necessary to enter a tank which may contain a hazardous atmosphere, suitable respirators, such as self-contained breathing apparatus; hose mask with blower, if there is a possibility of oxygen deficiency; or a gas mask, selected and operated in accordance with paragraph (i)(9)(vi) of this section, shall be used. If a contaminant in the tank can cause dermatitis, or be absorbed through the skin, the employee entering the tank shall also wear protective clothing. At least one trained standby employee, with suitable respirator, shall be present in the nearest uncontaminated area. The standby employee must be able to communicate with the employee in the tank and be able to haul him out of the tank with a lifeline if necessary.
73
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00083
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150
1926.58
(vi) Maintenance work requiring welding or open flame, where toxic metal fumes such as cadmium, chromium, or lead may be evolved, shall be done only with sufficient local exhaust ventilation to prevent the creation of a health hazard, or be done with respirators selected and used in accordance with paragraph (i)(9)(vi) of this section. Welding, or the use of open flames near any solvent cleaning equipment shall be permitted only after such equipment has first been thoroughly cleared of solvents and vapors. (12) Vapor degreasing tanks. (i) In any vapor degreasing tank equipped with a condenser or vapor level thermostat, the condenser or thermostat shall keep the level of vapors below the top edge of the tank by a distance at least equal to one-half the tank width, or at least 36 inches (0.912 m), whichever is shorter. (ii) Where gas is used as a fuel for heating vapor degreasing tanks, the combustion chamber shall be of tight construction, except for such openings as the exhaust flue, and those that are necessary for supplying air for combustion. Flues shall be of corrosion-resistant construction and shall extend to the outer air. If mechanical exhaust is used on this flue, a draft diverter shall be used. Special precautions must be taken to prevent solvent fumes from entering the combustion air of this or any other heater when chlorinated or fluorinated hydrocarbon solvents (for example, trichloroethylene, Freon) are used. (iii) Heating elements shall be so designed and maintained that their surface temperature will not cause the solvent or mixture to decompose, break down, or be converted into an excessive quantity of vapor. (iv) Tanks or machines of more than 4 square feet (0.368 m2) of vapor area, used for solvent cleaning or vapor degreasing, shall be equipped with suitable cleanout or sludge doors located near the bottom of each tank or still. These doors shall be so designed and gasketed that there will be no leakage of solvent when they are closed. (13) Scope. (i) This paragraph (i) applies to all operations involving the immersion of materials in liquids, or in
1926.58 1926.59
NOTE: The requirements applicable to construction work under this section are identical to those set forth at 1910.1200 of this chapter. [61 FR 31431, June 20, 1996]
1926.60
Methylenedianiline.
(a) Scope and application. (1) This section applies to all construction work as defined in 29 CFR 1910.12(b), in which there is exposure to MDA, including but not limited to the following:
74
VerDate Mar<15>2010
Jkt 223116
PO 00000
Frm 00084
Fmt 8010
Sfmt 8010
Q:\29\29V8.TXT
ofr150
PsN: PC150