Modpoll Modbus Master Simulator

modpoll is a command line based Modbus master simulator and test utility. It is free software. modpoll is using theFieldTalk Modbus driver. Modpoll binaries are available for the following operating system platforms and architectures:

Windows Linux (x86 32-bit) Solaris (SPARC) QNX Neutrino 6 (x86)

Usage
Usage: modpoll [options] serialport|host Arguments: serialport Serial port when using Modbus ASCII or Modbus RTU protocol COM1, COM2 ... on Windows /dev/ttyS0, /dev/ttyS1 ... on Linux /dev/ser1, /dev/ser2 ... on QNX host Host name or dotted ip address when using MODBUS/TCP protocol General options: -m ascii Modbus ASCII protocol -m rtu Modbus RTU protocol (default) -m tcp MODBUS/TCP protocol -m enc Encapsulated Modbus RTU over TCP -a # Slave address (1-255, 1 is default) -r # Start reference (1-65536, 100 is default) -c # Number of values to poll (1-100, 1 is default) -t 0 Discrete output (coil) data type -t 1 Discrete input data type -t 3 16-bit input register data type -t 3:hex 16-bit input register data type with hex display -t 3:int 32-bit integer data type in input register table -t 3:mod 32-bit module 10000 data type in input register table -t 3:float 32-bit float data type in input register table -t 4 16-bit output (holding) register data type (default) -t 4:hex 16-bit output (holding) register data type with hex display -t 4:int 32-bit integer data type in output (holding) register table -t 4:mod 32-bit module 10000 type in output (holding) register table -t 4:float 32-bit float data type in output (holding) register table -i Slave operates on big-endian 32-bit integers -f Slave operates on big-endian 32-bit floats -1 Poll only once, otherwise poll every second -e Use Daniel/Enron single register 32-bit mode -0 First reference is 0 (PDU addressing) instead 1 Options for MODBUS/TCP: -p # TCP port number (502 is default) Options for Modbus ASCII and Modbus RTU: -b # Baudrate (e.g. 9600, 19200, ...) (9600 is default) -d # Databits (7 or 8 for ASCII protocol, 8 for RTU) -s # Stopbits (1 or 2, 1 is default) -p none No parity -p even Even parity (default) -p odd Odd parity -4 # RS-485 mode, RTS on while transmitting and another # ms after -o # Time-out in seconds (0.01 - 10.0, 1.0 s is default)

Usage Examples
To get help on usage run the following command:

modpoll h
To retrieve continuously 10 Modbus holding registers starting from reference 500 of slave ID number 5 with Modbus RTU at 19200 baud, no parity on COM1 run:

modpoll -b 19200 -p none -m rtu -a 3 -r 500 -c 10 COM1


To retrieve once 5 floating point values starting from reference 100 with Modbus/TCP from slave device with IP 10.0.0.100:

modpoll -m tcp -t4:float -r 100 -c 5 -1 10.0.0.100 http://www.modbusdriver.com/modpoll.html